Front-Panel Operations 8.

15
Two-Line Display Front Panel

remain, the relay re-illuminates the corresponding target LEDs. The TARGET
RESET pushbutton also removes the trip automatic message displayed on the
LCD menu screens if the trip conditions have cleared.

Figure 8.26 Target Reset Pushbutton

Lamp Test
The TARGET RESET pushbutton also provides a front-panel lamp test. Pressing
and holding TARGET RESET illuminates all the front-panel LEDs, and these
LEDs remain illuminated for as long as TARGET RESET is pressed. The target
LEDs return to a normal operational state after release of the TARGET RESET
pushbutton.

Other Target Reset Options


Use the ASCII command TAR R to reset the target LEDs; see Table 7.12 for
more information. Programming specific conditions in the SELOGIC control
equation RSTTRGT is another method for resetting target LEDs. Access
RSTTRGT in Global Settings (SET G Command), Data Reset on page 4.187
for further information.

Front-Panel Operator Control Pushbuttons


The base SEL-751 features eight operator-controlled pushbuttons, each with
two programmable tricolor pushbutton LEDs, for local control as shown in
Figure 8.27.

Pushbutton LED PB5A_LED PB1A_LED


Operator Control Pushbutton PB05 AUX1 PB01 AUX
Pushbutton LED PB5B_LED PB1B_LED

PB6A_LED PB2A_LED
PB06 AUX2 PB02
PB6B_LED PB2B_LED
Factory Default
Slide-In Labels
PB7A_LED PB3A_LED BLOCK CLOSE

PB07 AUX3 PB03


BREAKER CLOSED
PB7B_LED PB3B_LED

PB8A_LED PB4A_LED
PB08 AUX4 PB04
PB8B_LED PB4B_LED BREAKER OPEN

Figure 8.27 Operator Control Pushbuttons and LEDs

Pressing any one of these eight pushbuttons asserts the corresponding PBn
NOTE: If the relay part number
specifies the Spanish language (n = 01 through 08) Relay Word bit, and the corresponding PBn_PUL Relay
option, all of the front-panel Word bit. The PBn Relay Word bit remains asserted as long as the pushbutton
pushbuttons and LED labels will be in
Spanish.
is pressed, but the PBn_PUL Relay Word bit asserts only for the initial
processing interval, even if the button is still being pressed. Releasing the

Date Code 20170814 Instruction Manual SEL-751 Relay