ITEM QTY DESCRIPTION REFERENCE

1 1 RAISED BEAM - (Depends on Span and Loading)


2 1 OVERFLOW
3 1 SKIMMERS
4 POOL WALLS
5 1 COVER PIT
9 10
6 1 COVER PIT DRAIN (Optional)
2 7 1 REMOVABLE COVER (Manually Removable Section)
8 1 AUTO REFILL
9 1 CONDUIT WITH DRAW WIRE - For motor cable Minimum 32mm Dia
10 1 EARTHING ROD (Motor Side)

3 4
POOL SHELL 4
PLAN VIEW
3 4
4 9
A A 2 10
6
3

8
5 NOTES:
FOR CIRCUIT DIAGRAM REFER DRG No.BGTR-E
FOR EARTHING ROD DETAILS SEE DRG No BGTR-4

8 7 POOL SHELL
2 10 1 4 3
ISOMETRIC VIEW
9
6

POOL SHELL
3 SECTION A-A

8
5 6 5

22/06/2021 BELOW GROUND 1 OF 5 B


Ph (03) 8833 3800 TUBULAR DRIVE WITH
Fax (03) 8833 3801 RAISED BEAM

A4
NO SAFETY LEDGE
BGTR-1
PIT 20MM WIDER
A MIN 32MM CONDUIT MUST RISE THE PIT IS TO BE THAN THE POOL
ABOVE MAX. WATER LEVEL AT SOME A MINIMUM 20mm NOTE: ON THE MOTOR SIDE
POINT BETWEEN THE PIT AND THE WIDER ON EACH IF THE PIT WALL IS NOT 20MM WIDER REMCO POOL
CONTROL BOX OR JUNCTION BOX. IT SIDE THAN THE THAN THE POOL ON THE MOTOR SIDE COVER COPING
THEN A CHANNEL 20MM X 20MM WILL COPING
MUST ALSO HAVE A STRONG DRAW POOL WALL
NEED TO BE CHASED AND SEALED
WIRE.THE CONTROL BOX MUST BE
BEFORE INSTALLATION
LOCATED WITHIN 18m OF DRIVE SIDE OF MAX WATER BEAM THICKNESS
SEE DRAWING BGTR-4
PIT SEE BGTR-E FOR MORE DETAIL LEVEL SEE ENGINEERING
SPECIFICATION

D 100MM

30
LETTERBOX

30
OPENING

C
SECTION C-C
SIDE WALL WITH MIN WATER
DIVIDING
STANDARD COPING LEVEL
OVERFLOW WALL

PIT WALL
EARTHING NOT SEEN
ROD
D C
NOTE: PIT 20MM WIDER
DROP FACE COPING CANNOT THAN THE POOL
DROP BELOW THE TOP OF THE ON THE MOTOR SIDE
LETTERBOX OPENING REMCO POOL
COVER DROP FACE
COPING
PIT DETAIL
PLAN VIEW COPING
MAX WATER BEAM THICKNESS
LEVEL SEE ENGINEERING
SPECIFICATION
100MM

30
LETTERBOX
B B

30
OPENING

AUTO-REFILL SECTION C-C DIVIDING


MIN WATER WALL
SIDE WALL WITH
LEVEL
DROP FACE COPING PIT WALL
NOT SEEN

22/06/2021 BELOW GROUND 2 OF 5 B


Ph (03) 8833 3800 TUBULAR DRIVE WITH
Fax (03) 8833 3801 RAISED BEAM

A4
NO SAFETY LEDGE
BGTR-2
COVER PIT SIZES
LENGTH OF POOL C: D:
UP TO 5 Metres 900 600
UP TO 9 Metres 1000 700
UP TO 15 Metres 1100 800
UP TO 20 Metres 1200 900
UP TO 25 Metres 1300 1000
UP TO 30 Metres 1400 1100
350MM MINIMUM
32mm MIN CONDUIT PIT OPENING IS MANUALLY
CENTRALLY LOCATED CENTRALLY LOCATED REMOVABLE
ON PIT WALL ABOVE (RUNS ENTIRE LENGTH COVERS BEAM THICKNESS
WATER LINE OF PIT) HERE DETERMINED BY SPAN
SEE ENGINEER FOR
SPECIFICATIONS
SKIMMER
BOX
OVERFLOW
WATER LEVEL

TRAUMA
SWITCH EARTHING
ROD 45°
CHAMFER
ON PIT WALL

C ISOMETRIC VIEW

NOTES:
THE PIT MUST HAVE -REFER TO TABLE FOR NUMERIC DIMENSIONS
SQUARE CORNERS TUBULAR -ALL MEASUREMENTS ARE IN MM
ON ALL SIDES AS ANY DRIVE -ALL SIZES ARE FINISHED SIZES AFTER RENDERING
RADIUS WILL REDUCE D IN AXLE
PIT SIZE -FOR SPECS ON EXTRA CABLING
SEE ELECTRICAL DWG BGTR - E
SECTION B - B
22/06/2021 BELOW GROUND 3 OF 5 B
Ph (03) 8833 3800 TUBULAR DRIVE WITH
Fax (03) 8833 3801 RAISED BEAM

A4
NO SAFETY LEDGE
BGTR-3
SHADED AREA IS WHERE
32MM D EARTHING ROD IS TO BE 50
CONDUIT LOCATED ON THE MOTOR min
SIDE OF PIT
COPING COPING
LETTERBOX

110
RAISED RAISED OPENING RAISED BEAM
BACK FRONT
BEAM BEAM
COPING

EARTHING LETTERBOX OPENING

50
SKIMMER ROD FIXED SAFETY LEDGE
TO POOL TOP OF DIVIDING WALL
STEEL
PRIOR TO 20MM X 20 MM
CONCRETING CHASED AND
SEALED GROOVE EARTHING ROD M10 THREADED
ONLY IF WALL
ROD FIXED TO POOL STEEL
PRIOR TO CONCRETING.
CANNOT BE SET
CONTACT REMCO FOR THIS KIT
BACK 20MM
WHICH INCLUDES REBAR CLIP
AND M10 ALL THREAD

D
NOTE: 20MM X 20MM GROOVE
EARTHING POINT NEEDS TO BE CHASED AND SEALED
MADE FROM A HIGH CORROSION ONLY IF PIT WALL CANNOT BE
RESISTANT MATERIAL THAT CAN BE SET BACK 20MM
EASILY ATTACHED TO A STAINLESS
STEEL MULTI STRAND CABLE
PROVIDED BY REMCO

SECTION B-B SECTION D-D


WITH NO HARDWARE EARTHING PIT MOTOR SIDE WALL
AND CHASING DETAILS

22/06/2021 BELOW GROUND TUBULAR DRIVE 4 OF 5 B


Ph (03) 8833 3800 WITH RAISED BEAM
Fax (03) 8833 3801 NO SAFETY LEDGE

A4
EARTHING AND CHASING DETAILS
BGTR-4
CONTROL BOX A

SIZES TRANSFORMER- N
POWER SUPPLY E
150NM AND 250NM MOTORS
KEY SWITCH
240mm X 230mm X 120mm
MAXIMUM CURRENT OUTPUT 3x1.0mm²
0.75AMPS @240VOLTS
CONTROL BOX DETAILS
400NM AND 600NM MOTORS
MOTOR
240MM X 340MM X 140MM

CLOSE

OPEN
STOP
N.O. C N.C. SUPPLY
MAXIMUM CURRENT OUTPUT
1.5AMPS @240VOLTS 24v FROM
14 13 12 11 10 9 8 7 6 5 4 3 2 1
POWER
SUPPLY
KEY
SWITCH 10 AMP 240V
CONTROL

BLACK
GREEN

BLACK
WHITE
AC SUPPLY ON

BLUE
COMMON

BLUE
BOX

RED
CLOSE
A SURGE

OPEN
STOP
1m LEAD
PROTECTED WITH PLUG

(WIRE SIZE DEPENDENT


VOLTAGE KEY SWITCH
10 AMP CIRCUIT
FREE
ON LENGTH OF RUN
GPO
2 x MOTOR WIRES
5 x 1.0mm² WIRES

CONTACTS
- SEE NOTES)
see MANUAL TUBULAR
POOL EQUIPMENT ROOM MOTOR
M

COMMON
CLOSE
MOTOR CABLE RUN - 18 M MAX

OPEN
MOTOR MAXIMUM DISTANCE 18 METERS CLOSE

WITHOUT JUNCTION BOX OPEN

(STD OPTION) STOP FUNCTION OPTIONAL


JUNCTION
BOX COMMON
JUNCTION BOX WITH EXTENSION N.B.
OPTION
CABLES REQUIRED FOR DISTANCES WHEN MULTIPLE ACTIVATION
OVER 15 METERS FROM MOTOR DEVICES ARE INSTALLED.
TO CONTROL BOX. WIRE UP IN PARALLEL WITH
SEE NOTE BELOW REMCO KEY SWITCH. TRAUMA SWITCH WIRED
IN PARRALEL WITH
MUST BE NORMALLY OPEN OPEN ACTIVATION
VOLTAGE FREE CONTACTS.
WITH A MINIMUM OF TWO CONTACTS.
NOTES:
· All tubular motors are supplied with a 20m long cable
POOL · The Remco control box should be located within 18m of the motor
in a dry place and out of direct sunlight Should the Transformer/Processor Unit have to
be located further away, a junction box can be used to connect extension cables
· Where extension cables are required please refer to below for the wire size and
quantity that must be used from the junction box to the Transformer/Processor Unit
· If a junction box is used it needs to be as close to the motor as possible(no more than 5m is recommended).

Extension cable requirements are as follows: Up to 20m Extension 2 x 4mm2 wires plus 5 x 1mm2 wires
EQUIPMENT LAYOUT Up to 30m Extension 2 x 6mm2 wires plus 5 x 1mm2 wires

22/06/2021 BELOW GROUND TUBULAR DRIVE 5 OF 5 B


Ph (03) 8833 3800 WITH RAISED BEAM
Fax (03) 8833 3801 NO SAFETY LEDGE

A4
CIRCUIT DIAGRAM AND WIRE SIZES
BGTR-E