Professional Documents
Culture Documents
1HSB425416-30 en rev0
LTB 72.5-170D1/B
2-column frame
BLK 222
3-pole operation
PRODUCT MANUAL
PRODUCT DESCRIPTION
- Circuit-Breaker 1
PRODUCT DESCRIPTION
- Operating Mechanism 2
ASSEMBLY INSTRUCTIONS
3
CHECKLIST
4
OPERATING AND MAINTENANCE
INSTRUCTIONS 5
LUBRICANTS
6
MAINTENANCE INSTRUCTIONS
- Operating Mechanism 7
OVERHAUL INSTRUCTIONS
- Circuit-Breaker 8
SPARE PARTS
- Circuit-Breaker 9
ABB Power Technology Products AB
S-771 80 LUDVIKA
SPARE PARTS
- Operating Mechanism 10
11
SF6 Circuit-Breaker LTB 72.5-170D1/B
with operating mechanism
BLK 222
3-pole operation
Product Description
1HSB425455-30 en rev1
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of
this document.
The document, or parts thereof, may not be reproduced or copied without prior permission from
ABB Power Technology Products AB. It may not either be imparted to third party or otherwise be
used without authorisation. Infringement hereof will be subject to action in accordance with applica-
ble laws.
Date: 2002-05-03
Product Description
TABLE OF CONTENTS
1. Description.......................................................................... 1
1.1 Design of the circuit-breaker.......................................................... 1
1.2 Circuit-breaker gas system ............................................................. 2
1.3 Operating mechanism..................................................................... 4
1.4 Standards ........................................................................................ 4
1HSB425455-30 en rev1 i
Product Description Description
1. Description
High-voltage circuit-breaker LTB 72.5-170D1/B, with operating mechanism type
BLK 222.
5 Frames,
two column frame see dimension drawing 3
three column frame
5
Från
4
B30259
5
1HSB425455-30 en rev1 1
Description Product Description
2 1HSB425455-30 en rev1
Product Description Description
B30033
1HSB425455-30 en rev1 3
Description Product Description
1.4 Standards
The circuit-breakers comply with the requirements according to IEC Publication
60056 and in most cases also ANSI C37 and are restrike-free when breaking a
capacitive load.
4 1HSB425455-30 en rev1
ABB Power Technology Products AB 1HSB425455-30 en rev1
Head Office 0502
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 782 320
SF6 Circuit-Breaker Operating mechanism
type BLK 222
Product Description
1HSB535432-100 en rev4
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to third party or otherwise be used wit-
hout authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-03-21
Product Description
LIST OF CONTENTS
1. Description.......................................................................... 1
1.1 Delivery.......................................................................................... 2
1.2 Unpacking ...................................................................................... 2
1.3 Storage............................................................................................ 3
3. Operations......................................................................... 11
3.1 Remote/local operations............................................................... 11
3.2 Close operation............................................................................. 11
3.3 Open operation ............................................................................. 12
3.4 Rapid reconnection....................................................................... 12
4. Component parts.............................................................. 13
4.1 Drive mechanism.......................................................................... 13
4.2 Catch gear..................................................................................... 13
4.3 Dashpot ........................................................................................ 14
4.4 Limit switch with auxiliary contact.............................................. 14
4.5 Heater element ............................................................................. 15
1HSB535432-100 en rev4 i
Product Description
FIGURES
ii 1HSB535432-100 en rev4
Product Description Description
1. Description
The operating mechanism BLK 222 is intended for operating circuit-breakers with
integrated opening springs. Under no circumstances may the operating mechanism
be operated without first being mounted and adjusted for a circuit-breaker.
The operating mechanism consists of an closing spring with associated motor
charging device that automatically charge the closing spring after each closing
operation. A closing interlock holds the tensioned closing spring prepared for the
Closing of the circuit-breaker and the re-tensioning of the opening springs. A
opening interlock holds a closed circuit-breaker prepared for immediate Opening.
The component parts of the operating mechanism are integrated in a cabinet which
also accommodates an operating panel and operating equipment. The cabinet’s
cover can be removed and the operating panel opened to facilitate service and
overhauling.
The standard operating cycle is O - 0.3 s - CO - 3 min - CO (IEC) or CO - 15s - CO
(ANSI). The time between closing operations should not be less than 1 minute
during the testing of the circuit-breaker and relay systems involving more than 3
closing operations.
2 1
5
3
Item
1 Drive unit
2 Operating mechanism
3 Operating panel
4 Closing spring
5 Heater element
1HSB535432-100 en rev4 1
Description Product Description
1.1 Delivery
Check on arrival that the delivery corresponds with the order and delivery
documents and that no transport damage has occurred.
If any material is missing or if transport damage has occurred, please report this
immediately to ABB Power Technology Products AB, Circuit Breaker Division.
1.2 Unpacking
The operating mechanism is packed in a crate. The crate is marked with a case
number and the gross weight. Other information is written on a plywood
board/label, which is attached to two of the crate’s sides.
The operating mechanism must be lifted using the lifting eyes on top of the cabinet,
see Figure 1-2. Slings must not be placed around the cabinet when lifting.
All packing material can be recycled.
B30079
2 1HSB535432-100 en rev4
Product Description Description
1.3 Storage
Avoid storage. If storage is necessary, this must be done indoors or under cover.
The operating mechanism shall preferably be stored indoors in a dry building. When
stored outdoors, the crate should be opened to promote the exchange of air and a
heater should be used to prevent condensation.
An approved storage area is a store consisting of:
roof
a solid floor
humidity less than 50%
temperature +20 ˚C (±10 ˚C)
1HSB535432-100 en rev4 3
Product Description Assembly and connection
WARNING
Do not operate the mechanism unloaded!
Operations shall take place only after the mechanism has been connected
and adjusted to the associated pressurised circuit-breaker.
2 1
2
Min.
Middle position (Yellow field)
Max. (Green field)
B30161
1HSB535432-100 en rev4 5
Assembly and connection Product Description
N.B. Cables must not be routed so that they obstruct manual cranking.
B30079 1
6 1HSB535432-100 en rev4
Product Description Assembly and connection
CAUTION
The contactor must not be operated manually so that the limit switch
is bypassed.
2
3
B30200 1 5
Item
2 Motor
3 Spring drum
4 Limit switch
5 Contactor
1HSB535432-100 en rev4 7
Assembly and connection Product Description
Item
1 Open interlock
2 Closed interlock
B30054
Item 2
1 Closing catch gear
2 Dashpot
3 Tripping arm
3
B30057
8 1HSB535432-100 en rev4
Product Description Assembly and connection
3
2
Item
1 Closing arm 4
2 Interlock heel
4 Dashpot piston
B30054
1
1HSB535432-100 en rev4 9
Product Description Operations
3. Operations
2 1
Item
1 Switch, Local/Remote
B30207
Item
1 Switch, Local/Remote
3 Limit contact
4 Auxiliary contact 3
B30200 2 1
1HSB535432-100 en rev4 11
Operations Product Description
2 1
Item
1 Switch, Local/Remote
B30208
12 1HSB535432-100 en rev4
Product Description Component parts
4. Component parts
1
Item
1 Motor
B30068
1 2
Item
B30062
1HSB535432-100 en rev4 13
Component parts Product Description
4.3 Dashpot
The operating mechanism is fitted with a dashpot to slow the final phase of the
opening movement.
Item
1 Dashpot
B30063
2 1
Item
1 Limit switch
2 Auxiliary contact
B30200
14 1HSB535432-100 en rev4
Product Description Component parts
Item
1 Heater element
B30058
Data
– 70 W, 220 V: R = 691 Ohm ±10%.
– 140W, 220 V: R = 346 Ohm ±10%.
– 70 W, 110 V: R = 173 Ohm ±10%.
– 140 W, 110 V: R = 86 Ohm ±10%.
1HSB535432-100 en rev4 15
ABB Power Technology Products AB 1HSB535432-100 en rev4
Head Office 0321
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 714 928
SF6 Circuit-Breaker LTB 72.5-170D1/B
with two column frame and
operating mechanism BLK 222
3-pole operation
Assembly Instructions
1HSB425410-30 en rev0
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to a third party or otherwise be used
without authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-05-02
Assembly Instructions
TABLE OF CONTENTS
1. General ................................................................................ 1
2. Safety................................................................................... 3
2.1 Warning text ................................................................................... 3
2.2 Safety, general ................................................................................ 4
3. Delivery ............................................................................... 5
3.1 Weights........................................................................................... 5
3.2 Unpacking ...................................................................................... 6
3.3 Storage............................................................................................ 6
4. Assembly............................................................................. 7
4.1 Preparations.................................................................................... 7
4.2 Frame assembly.............................................................................. 9
4.3 Assembling the frame on the foundation ..................................... 10
4.4 Assembling the pole beam on the frame ...................................... 11
4.5 Assembling the circuit-breaker poles and protective pipe on the
pole beam ..................................................................................... 12
4.6 Assembling the operating mechanism ......................................... 18
4.7 Final assembly of the circuit-breaker pole and frame .................. 20
4.8 Assembling the pull rods.............................................................. 21
4.9 Gas monitoring system................................................................. 27
4.10 Assembling the current transformers ........................................... 28
4.11 Fitting the covers and sign ........................................................... 32
4.12 Inspecting the bolted joints, etc.................................................... 33
7. Commissioning................................................................. 45
1HSB425410-30 en rev0 i
Assembly Instructions
ii 1HSB425410-30 en rev0
Assembly Instructions
FIGURES
iv 1HSB425410-30 en rev0
Assembly Instructions General
1. General
This Assembly Instruction Manual applies to the SF6 circuit-breaker type
LTB 72.5-170D1/B with two column frame and operating mechanism type
BLK 222 for 3-pole operations and contains all essential information for assembly
and commissioning.
Read through the entire Assembly Manual before starting the assembly work.
1HSB425410-30 en rev0 1
Assembly Instructions Safety
2. Safety
DANGER
indicates an immediate hazardous situation that, if not avoided, will result
in death or serious injury.
WARNING
indicates an immediate hazardous situation that, if not avoided, can result
in death or serious injury.
CAUTION
indicates a hazardous situation that can result in minor or moderate
injury.
N.B. is used for hazards that may only result in damage to the installation.
1HSB425410-30 en rev0 3
Safety Assembly Instructions
WARNING
Circuit-breaker with pressurised insulators.
Mechanical damage to the insulator can cause it to explode with the
following risk of splintering.
Work on the circuit-breaker that brings about the risk of mechanical
damage to the insulators should be carried out at a reduced gas pressure,
0.125 MPa (abs).
WARNING
Do not energize, charge or operate the operating mechanism until final
assembly and adjustments on the circuit-breaker are fully completed.
The standard operating cycle is O - 0.3 s - CO - 3 min. - CO. The time between
closing operations should not be less than 1 minute during the testing of circuit-
breakers and relay systems involving more than 3 closing operations.
4 1HSB425410-30 en rev0
Assembly Instructions Delivery
3. Delivery
Check on arrival that the delivery corresponds with the order and delivery
documents and that no transport damage has occurred.
If any material is missing or if transport damage has occurred, please report this
immediately to ABB Power Technology Products AB, HV Products/Circuit-
breakers.
3.1 Weights
The weights of the component parts are as follows:
Från
B30229
1HSB425410-30 en rev0 5
Delivery Assembly Instructions
3.2 Unpacking
The material is packed in crates and on pallets. The crates are marked with a case
number and the gross weight. Other information is written on a board/label, which
is attached to two of the crate’s sides.
The operating mechanism must be lifted using the lifting eyes on top of the cabinet,
see Figure 3-2. Slings must not be placed around the cabinet when lifting.
The circuit-breakers shall be kept in the transport packaging until just before
assembly.
All packing material can be recycled.
B30002
3.3 Storage
Avoid prolonged storage, i.e. > 3 months. If storage is necessary, this must be done
indoors or under cover.
The original transport packaging can be used to store the circuit-breakers. The circuit-
breakers are stored flat above the ground to prevent breakage and damage by water.
The operating mechanism shall preferably be stored indoors in a dry building. When
stored outdoors, the crate should be opened to promote the exchange of air and a
heater should be connected to a suitable power supply to prevent condensation
An approved storage area is a store consisting of:
a roof
a solid floor
humidity less than 50%
temperature +20 °C ( ±10 °C).
6 1HSB425410-30 en rev0
Assembly Instructions Assembly
4. Assembly
4.1 Preparations
Before starting the assembly, make certain that all requisite tools and documents are
on hand.
• Standard tools with torque wrenches (10 - 430 Nm).
• Lifting device and lifting slings.
• Lubricants, see Lubricants 1HSB445409-1 for suppliers and brand names.
Grease “G”: ABB Art. No. 1171 4014-407
Grease “SV”: ABB Art. No. 1171 4016-610.
• Test tool, ABB article number 6889 703-1
• Plastic disc, ABB article number 6834 115-1
• Check pin, ABB article number 1HSB539782-1
• Crank extension, ABB article number 1HSB532188-F
• Crank, ABB article number 2188 754-G
• Applicable dimension drawing and diagrams for the order.
Item 4 3 2
1 Operating mechanism
2 Circuit-breaker pole A
1
3 Circuit-breaker pole B
B30229
1HSB425410-30 en rev0 7
Assembly Assembly Instructions
4.1.2 Foundation
The circuit-breaker’s foundation must be flat and level. Figure 4-2 shows the
permitted deviations in mm for the position of the foundation bolts. For dimensions
of the foundation bolts and nuts, see the dimension drawing.
Adjust any deviations using spacer washers, see “kapitel 4.3, Assembling the frame
on the foundation”. The nominal dimensions are stated on the applicable dimension
drawing for the order.
max. 4 mm
± 2 mm
±1 mm
max. 4 mm
2
±1 mm 1
B30003 M24, Length = >110 mm
Item
8 1HSB425410-30 en rev0
Assembly Instructions Assembly
3 2
TIGHTENING TORQUE
190 Nm
1
B30258
1HSB425410-30 en rev0 9
Assembly Assembly Instructions
N.B. The final tightening of the frame is carried out after alignment and mounting
of the pole beam.
Item
3 Washers 8 pcs
5 Foundation
6 Frame foot
1 2 3
10
6
25
115
4
10
B10006 2
10 1HSB425410-30 en rev0
Assembly Instructions Assembly
TIGHTENING TORQUE
430 Nm
Tighten the frame finally using nuts (2), Figure 4-4, these are tightened with a
tightening torque of 300 Nm.
TIGHTENING TORQUE
300-350 Nm
Item
1 Pole beam
2 Frame
1HSB425410-30 en rev0 11
Assembly Assembly Instructions
4.5 Assembling the circuit-breaker poles and protective pipe on the pole
beam
The circuit-breaker poles are assembled in the order B1, A1 and finally C1.
1. Check that the bolts (1), Figure 4-7, have a tightening torque of 79 Nm.
2. Check that the circuit-breaker pole is sealed before assembling on the frame.
– Unscrew the sealing cap (1).
– Press the non-return valve’s disk (2) inwards using the test tool (3). A
clear hissing noise should be heard from the pole. If no hissing noise is
heard, the pole leaks. This must be rectified before assembly.
1 3
Item
1 Sealing cap
2 Non-return valve
B30231 2
3. Place a lifting sling around the top section of the circuit-breaker pole as set out
in Figure 4-7 and in this way lift the circuit-breaker pole from its horizontal
position in the transport packaging. Start with pole B1.
B30254
12 1HSB425410-30 en rev0
Assembly Instructions Assembly
4. Dismantle the covers (1) from each pole and the indicating sign (2) from pole
A1.
5.
OPEN
B30232 1 1 1 2
Item
1 Covers, poles
2 Sign
6. Lift the circuit-breaker pole B1 into position and align it on the pole beam, see
Figure 4-9. Fit the bolts (1) and tighten by hand.
N.B. Final tightening is carried out when the operating mechanism is assembled.
Item
B30261
1HSB425410-30 en rev0 13
Assembly Assembly Instructions
7. Lift the circuit-breaker pole A1 into position and align it on the pole beam, see
Figure 4-10. Fit the bolts (1) and tighten by hand.
Item
B30262
14 1HSB425410-30 en rev0
Assembly Instructions Assembly
8. Assemble the protective pipe (1) between the circuit-breaker poles A1 and B1.
Tighten the bolts (2), see Figure 4-11, with a tightening torque of 79 Nm.
The nut (3) on the outside of the mechanism housing.
TIGHTENING TORQUE
79 Nm
9. Insert the pull-rod (4) with the fork coupling at one end inside the protective
pipe. Guide the pull-rod into the protective pipe through the mechanism
housing on circuit-breaker pole B with the end fitted with the fork coupling
last.
N.B. Insert the pull-rod facing the right way in the protective pipe.
10. Secure the pull-rod (4) in the operating lever (5) using the pin (6) and the lock
washer (7) in the mechanism housing on pole A, see Figure 4-11.
4 Pole B1 1 Pole A1
Item
4 Pull-rod
2 3 A
5 Operating lever pole A 4 5 7 6
B10312
6 Pin D=12
Figure 4-11. Assembling the protective pipe between pole A1 and pole B1
1HSB425410-30 en rev0 15
Assembly Assembly Instructions
11. Lift the circuit-breaker pole C1 into position and align it on the pole beam, see
Figure 4-12. Fit the bolts (1) and tighten hand tight.
N.B. Final tightening is done once the operating mechanism has been fitted.
1
Item
Från
B10313
16 1HSB425410-30 en rev0
Assembly Instructions Assembly
12. Fit the protective pipe with the opening spring housing (1) between pole C1
and pole B. Mount the opening spring housing end on pole C1.
N.B. Make sure that the drainage grooves in the opening spring housing are turned
downwards when mounting it to pole C1.
13. Tighten the opening spring housing using the bolts (2) onto pole C1 with a
tightening torque of 79 Nm.
TIGHTENING TORQUE
79 Nm
14. Tighten the protective pipe (1) using the bolts (3) onto circuit-breaker pole B1
with a tightening torque of 79 Nm.
TIGHTENING TORQUE
79 Nm
Pole C1 1 Pole B1
Item
2
B10314 4 3
Figure 4-13. Assembling the protective pipe between pole B1and pole C1
1HSB425410-30 en rev0 17
Assembly Assembly Instructions
WARNING
Do not energize, charge or operate the operating mechanism until final
assembly and adjustments on the circuit-breaker are fully completed.
• Lift the operating mechanism using the four lifting eyes. Align the operating
mechanism’s mounting bracket (1) vertically with the pole beam (2).
• Tighten the operating mechanism’s mounting bracket (1) using the bolts (3)
against the pole beam (2) on the circuit-breaker pole A1.
2 3 1
Item
1 Mounting bracket
2 Pole beam
B10315
18 1HSB425410-30 en rev0
Assembly Instructions Assembly
• Tighten the pipe flange (3) against the circuit-breaker pole A1’s mechanism
housing (4) using the bolts (1). Tightening torque 79 Nm.
TIGHTENING TORQUE
79 Nm
1 2
Item 3
1 Bolts M12x50 4 pcs
Washers 13x24x2.5 8 pcs
3 Pipe flange
4 Mechanism housing
B10316
• Tighten the bolted joints (3), Figure 4-14, with a tightening torque of 190 Nm.
TIGHTENING TORQUE
190 Nm
1HSB425410-30 en rev0 19
Assembly Assembly Instructions
TIGHTENING TORQUE
79 Nm
1
Item
Från
B10313
20 1HSB425410-30 en rev0
Assembly Instructions
2 Latch
3 Roller
B30017
1HSB425410-30 en rev0 21
Assembly Instructions
2. Move the operating mechanism’s pull-rod (1) towards its closed position until
the operating mechanism’s dashpot starts to brake.
3. Move the pull-rod (2) between the poles A1 and B1 towards its open position
as far as possible towards the pull-rod (1) from the operating mechanism.
4. Fit together the pull-rods using pin (3) and lock using the locking washer (4).
Pole A1
Item
2 1
1 Operating mechanism’s pull-rod
3 Pin D=16
B
B-B
3 4
B30235
B
Figure 4-18. Assembling the pull-rod between pole A1 and the operating
mechanism
22 1HSB425410-30 en rev0
Assembly Instructions
N.B. Insert the pull-rod into protective pipe facing the right way.
Pole C1
Item
1 3
1 Pull-rod between pole C1
and B1
B30236
2
Figure 4-19. Assembling the pull-rod between pole C1 and pole B1.
1HSB425410-30 en rev0 23
Assembly Instructions
2. Fit the protective cover (1) on circuit-breaker pole C1. Tighten the bolts (2)
with a tightening torque of 79 Nm.
TIGHTENING TORQUE
79 Nm
3. Screw the crank extension (3) into the protective cover (1) so that it enters the
countersink on the end of the coupling link (4). Tighten so that the pull-rod (5)
is clamped in position between the crank extension and the opening spring
bracket (6), see Figure 4-20. The crank extension (3) and crank (7) are supplied
with the operating mechanism.
4. Crank, using the crank (7), in the crank extension so far that the pull-rods meet
in the mechanism housing on pole B1 (a bit further in than the position
corresponding to the open position).
Item Pole C1
1 Protective cover
7 3 1
2 Bolts M12x 50 4 pcs.
Washers 13x24x2.5 8 pcs.
Nuts M12 4 pcs.
4 Coupling link
5 Pull-rod
24 1HSB425410-30 en rev0
Assembly Instructions
5. Fit together the pull-rods using pin (1) and lock using the lock washer (2)
6. Place the operating lever (3) and coupling link (4) in the mechanism housing
on pole B1 so that the pin (5) can be fitted. Lock the pin (5) using the lock
washer (6).
Pole B1
Item
1 Pin D=16
3 Operating lever
4 Coupling link
5 Pin D=12 3
B
4
6 Lock washer SL12
A
A-A
B-B
B
B30238 A 6 5 1 2
Figure 4-21. Assembling the pull-rods between pole C1 and pole B1.
7. Crank out the crank extension and return it and the crank in the operating
mechanism.
1HSB425410-30 en rev0 25
Assembly Instructions
8. Place the operating lever (1) and coupling link (1) in the mechanism housing
on pole C1 so that the pin (3) can be fitted. Lock the pin (3) using the lock
washer (4). Check that the circuit-breaker (pole A1, B1 and C1) is in the open
position using the check pin (5), with a diameter of 6 mm. If the check pin does
not fit, contact ABB personnel.
N.B. The check pin must be removed after the check is done.
9. Fit the protective bolt (7) on the protective cover (8). Tighten the protective bolt
with a tightening torque of 79 Nm.
TIGHTENING TORQUE
79 Nm
Pole C1
Item
1 Operating lever
8 1
2 Coupling link 7
3 Pin D=12
8 Protective cover
B30239 3, 4 2 5, 6
26 1HSB425410-30 en rev0
Assembly Instructions
N.B. When assembling the gas monitoring system the greatest possible level of
cleanliness must be observed.
• Connect the gas pipes to the circuit-breaker poles, but only screw the union
nuts (2) to the groove (3) on the non-return valves (4). The connection is now
sealed, but the non-return valve has not opened.
N.B. Make sure that the gas pipes do not rest against the pole beam so not galvanic
corrosion will occur.
• When all of the circuit-breaker poles have been connected in this way the union
nuts (1) can be screwed on fully. Tighten them with a tightening torque of
10 Nm.
TIGHTENING TORQUE
10 Nm
• Connect the density monitor to the rear valve on pole A1. Grease the sealing
rings using grease “G” before assembling.
N.B. Only screw the union nut (2) on to the groove (3) on the non-return valve (4).
The connection will then be sealed, but the non-return valve will not be
opened.
Final tightening of the density monitor is done after gas filling.
• Route the cable from the density monitor in to the terminals on the operating
mechanism and strap the cable to frame.
3
2 4 7
Item
6
1 Density monitor 5
2 Union nut
3 Groove
4 Non-return valve
5 Cable
6 Gas pipe
7 Pipe clamps
B10317
8 Plastic disc, ABB
1
Art. No. 6864115-1
1HSB425410-30 en rev0 27
Assembly Instructions
N.B. The flashover distance between the circuit-breaker and the current
transformer must complie with the values accordning to Figure 4-25.
• Fit the beams (1). Tighten the bolts (2) by hand.
• Fit the stays (3). Tighten the bolts (2) by hand.
• Fit the lengthways securing beams (4) and stays (5).
• Tighten all bolts with a tightening torque of 190 Nm.
TIGHTENING TORQUE
190 Nm
28 1HSB425410-30 en rev0
Assembly Instructions
2
2
3
2
1 5 1
B30264
Item
1 Beams 4 pcs.
2 Bolts M16x40 20 pcs.
Washers 17x30x3 40 pcs.
Nuts M16 20 pcs.
3 Stays 4 pcs.
4 Securing beams 2 pcs.
5 Stays 2 pcs.
6 Bolts M16x60 20 pcs.
Washers 17x30x3 20 pcs.
U-washers 20 pcs.
Nuts M16 20 pcs.
1HSB425410-30 en rev0 29
Assembly Instructions
TIGHTENING TORQUE
190 Nm
• Check that the flashover distance between the circuit-breaker and the current
transformers complies with the values according to Figure 4-25.
K
According to System voltage, kV
IEC 60071
72 123 145 170
B30263
30 1HSB425410-30 en rev0
Assembly Instructions
1
TIGHTENING TORQUE
79 Nm
3
1HSB425410-30 en rev0 31
Assembly Instructions
WARNING
Check that the operating mechanism’s closing springs are fully offloaded
and the circuit-breaker is in open position before starting work.1
• Fit the sign (2) on pole A1. Tighten the bolt (3) with a tightening torque of
22.5 Nm.
1
Item 3
1 Mechanism pole A1
2
2 Sign
OPEN
TIGHTENING TORQUE
22.5 Nm
B30241
• Fit the covers (1) on all poles. Tighten the bolts (2) with a tightening torque of
10 Nm.
Item
1 Cover, poles
B30232 1 1 1 2
TIGHTENING TORQUE
10 Nm
32 1HSB425410-30 en rev0
Assembly Instructions
Foundation 300
Circuit-breaker pole 79
Pull-rod 127
Density monitor 10
1HSB425410-30 en rev0 33
Assembly Instructions Electrical connections
5. Electrical connections
B30028 1
WARNING
Work must not be carried out on a pressurised circuit-breaker.
1HSB425410-30 en rev0 35
Electrical connections Assembly Instructions
Using grease
1. Clean all grease and old paste from the contact surfaces.
2. Rub down the surfaces using an abrasive cloth, e.g. Scotch Brite No. 7447 or
emery cloth.
3. Apply immediately:
- Grease “SV”, ABB’s Art. No. 1171 4016-610, on aluminium and copper
surfaces.
4. Fit together the joint with the grease still applied.
5. Wipe off any excess grease.
N.B. Position the bimetallic washers so that their aluminium sides face the
aluminium surfaces and the copper sides are turned towards the copper
surfaces or the silver-plated surfaces.
N.B. The contact paste may only be used on fixed joints. It must not be used
inside the breaking units.
36 1HSB425410-30 en rev0
Assembly Instructions Electrical connections
CAUTION
The contactor must not be pushed manually so that the limit position
switch is bypassed.
2
3
B30200 1 5
Item
2 Motor
3 Spring drum
5 Contactor
1HSB425410-30 en rev0 37
Assembly Instructions Pressurising the poles
6.1 Preparations
WARNING
During commissioning, the SF6 gas or the gas mixture needs to be refilled
to the pressure stated on the rating plate. Different gas pressures can occur,
depending on different requirements with regard to the lowest ambient
temperature.
Pressurisation takes place directly from a gas cylinder using the gas filling
equipment, ABB Art. No. 1HSB 445439-A for SF6 gas or 1HSB445439-B for
mixed gas.
The gas hose for the filling equipment is supplied vacuum-pumped and filled with
SF6 gas.
WARNING
To avoid personal injury while refilling, due to possible transport damage
to the insulator, assembly personnel must exercise great care and stay in a
protected and safe area (with regard to splintering) away from the circuit-
breaker. The gas cylinder and refilling equipment should be placed in the
same area.
• Connect the control cables to the operating mechanism’s terminal blocks for
opening and closing. The cables are routed to the control room or protected
area away from the circuit-breaker.
• Connect the cables to appropriate pushbutton switches.
• Set the operating mechanism’s control switch in the remote position.
• Switch on the motor starter so the closing spring are tensioned.
• Open the terminal blocks to which the density monitors’ cables are connected
and interrupt the circuit to the interlocking relays.
• Connect the operation testing device with variable control voltage and time
measurement.
1HSB425410-30 en rev0 39
Pressurising the poles Assembly Instructions
3
3
8 Item
5 4 7 6
1 Gas cylinder
2 Regulator
3 Density monitor
4 Coupling
5 Valve
6 Hose
7 Adapter
1 10 Valve
2
9 10
B30198
40 1HSB425410-30 en rev0
Assembly Instructions Pressurising the poles
5. Connect coupling (4) to the circuit-breaker’s rear gas valve on pole C1.
6. Connect the gas-filled hose (6) to the coupling (4).
7. Connect the gas-filled hose(6) to the gas cylinder (1) via the regulator (2).
8. Go from the circuit-breaker to the protected area and let the gas flow until the
regulator switches off.
9. Wait until the gas temperature is the same as the breaker’s temperature before
reading off the gas pressure on the density monitor. Adjust the pressure if
necessary.
N.B. When reading off from the precision gauge, correct the filling pressure
depending on the temperature as set out in Table 6-1.
10. Dismantle the hose (6) from the coupling (4) on the circuit-breaker.
11. Close the valve to the pressure gauge.
12. Dismantle the coupling from the circuit-breaker.
13. Release the pressure on the pressure gauge by opening valve (5) or valve (10).
14. Dismantle the pressure gauge from the coupling...
1HSB425410-30 en rev0 41
Pressurising the poles Assembly Instructions
N.B. When the density monitor (1) is finally fitted, tighten the union nut with a
torque of 10 Nm.
1
Item
1 Density monitor
B30199
TIGHTENING TORQUE
10 Nm
18. Operate the breaker Close and Open 3 times from the control room.
42 1HSB425410-30 en rev0
Assembly Instructions Pressurising the poles
N.B. When filling with mixed gas, always fill the SF6 gas first.
The proportions of gas for pressurisation should be 52% SF6 and 48% N2 or CF4.
Example.
For a circuit-breaker with a filling pressure of 0.70 MPa abs (+20 ˚C), first fill
0.52 x 0.7 = 0.36 MPa abs (+20 ˚C) SF6 gas and then N2 or CF4 gas to
0.70 MPa abs (+20 ˚C)
N.B. When reading off from the precision gauge, correct the filling pressure
depending on the temperature as set out in Table 6-2.
Gas filling takes place one pole at a time, otherwise as set out in Chapter 6.2. Once
all poles have been filled with gas, the gas monitoring system is fitted as set out in
Chapter 4.9 before the circuit-breaker is operated.
1HSB425410-30 en rev0 43
Pressurising the poles Assembly Instructions
44 1HSB425410-30 en rev0
Assembly Instructions Commissioning
7. Commissioning
Before commissioning the circuit-breaker, carry out all the checks as set out in
“Check list for assembling and commissioning 1HSB445410-100” and fill in the
operating values for the installation.
Reset all the controll circuits according to applicable circuit diagrams and check
that all terminal blocks are tightened.
Put the tools in the appropriate holders in the operating mechanism.
1HSB425410-30 en rev0 45
Assembly Instructions Operating values
8. Operating values
The operating values in this instruction apply to the SF6 circuit-breaker type
LTB 72.5-170D1/B with operating mechanism type BLK 222.
8.1 Times
8.3 Resistance
Main circuit resistance per pole:
LTB 72D1/B <40 µΩ
LTB 145D1/B <40 µΩ
LTB 170D1/B <46 µΩ
1HSB425410-30 en rev0 47
ABB Power Technology Products AB 1HSB425410-30 en rev0
Head Office 0502
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 782 320
SF6 Circuit-Breaker Circuit-breakers HPL and LTB
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to a third party or otherwise be used wit-
hout authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-02-14
Check list Check list for assembly and commissioning
Date:_______________
Installation:______________________________________________
Serial number:_____________________________
Circuit-breaker pole
1. Check that the circuit-breaker and operating mechanism have been assembled
in accordance with the assembly instructions.
2. Check that all bolted joints are tightened to the tightening torques stated in the
assembly instructions.
3. Ensure that all poles are in the open position. The alignment hole in the
operating lever shall align with the predrilled hole in the mechanism housing.
Operating mechanism
4. Make an ocular inspection to check that oil from the oil dashpots has not
leaked in the operating mechanism.
5. Tighten all screws in terminal blocks involved in the assembly work.
Gas filling
6. Connect the operating mechanism for remote control from a protected area in
connection with gas filling and test operations.
Set the control switch to remote.
7. Connect the gas filling equipment for gas filling from the protected area.
8. Fill with gas each pole one after the other and perform an operational test three
times as set out in the assembly instructions.
9. Check the heater element.
10. Make sure the thermostat, if provided, is set to 10°C 1.
1HSB445410-100 en rev2 1
Check list for assembly and commissioning Check list
Operating values
11. Check the breaker’s operating values with the applicable operating values for
the breaker in the Assembly Instructions and note down the measured values in
the table below.
CAUTION
The circuit-breaker must not be switched Open - Close without an
intermediate delay of 300 ms.
Measured values
Check the following
Close-Open time ms ms ms
2 1HSB445410-100 en rev2
ABB Power Technology Products AB 1HSB445410-100 en rev2
Head Office 0202
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 714 928
SF6 Circuit-Breaker Type LTB D with
operating mechanism BLK 222
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to third party or otherwise be used
without authorisation. Infringement hereof will be subject to action in accordance with applicable
laws.
Date: 2002-03-11
Operating and Maintenance Instructions
TABLE OF CONTENTS
1. General ................................................................................ 1
1.1 Warning text ................................................................................... 1
1.2 Warning .......................................................................................... 2
3. Inspection intervals.......................................................... 11
3.1 Maintenance summary ................................................................. 12
3.2 Maintenance category A .............................................................. 13
3.3 Maintenance category B............................................................... 14
3.4 Maintenance category C............................................................... 16
3.5 Maintenance category D .............................................................. 21
1HSB425409-130 en rev0 i
Operating and Maintenance Instructions
FIGURES
ii 1HSB425409-130 en rev0
Operating and Maintenance Instructions General
1. General
These Operating and Maintenance Instructions are applicable for the
SF6 circuit-breaker type LTB D.
The instructions contain recommendations for handling and guidelines for the
maintenance of high-voltage circuit-breakers of the LTB D type. The instructions
are divided up into four parts:
• Inspection intervals
• Instruction for preventive maintenance of circuit-breakers
• Instruction for preventive maintenance of operating mechanisms
• Fault correction maintenance
Periodic maintenance must be carried out at the time or operation intervals
specified.
Fault correction maintenance is related to the faults detected. The fault correction
maintenance described in this manual involves the replacement of defective units. If
the user chooses to try and repair a defective unit instead, specialist knowledge is
often needed. This will not be found in the Manual.
The equipment must be overhauled in accordance with specified criteria, e.g. after a
certain number of operations. Overhaul of the equipment must be entrusted to
authorised service personnel.
DANGER
indicates an immediate hazardous situation that, if not avoided, will result
in death or serious personal injury.
WARNING
indicates an immediate hazardous situation that, if not avoided, can result
in death or serious personal injury.
CAUTION
indicates a hazardous situation than can result in minor or moderate injury.
N.B. used for hazards that may only result in damage to the installation.
1HSB425409-130 en rev0 1
General Operating and Maintenance Instructions
1.2 Warning
The risks set out below must be observed and corresponding measures followed
with all work on high-voltage circuit-breakers.
WARNING
Circuit -breakers with pressurised insulators.
Mechanical damage to the porcelain can cause it to explode with the
subsequent risk of splintering. Work on the circuit-breaker that brings
about the risk of mechanical damage to the insulators should be carried
out at a reduced gas pressure, 0.125 MPa (abs).
Risk Measure
Working next to high voltage. Isolate and earth close to the work place. If work must
be carried out close to live installation components, the
safety distance applying in the country's applicable
safety regulations must be observed.
Working on ladders and platforms. Work shall be carried out in accordance with applicable
safety regulations in the country concerned. Difficult
weather conditions that require short shifts with a great
deal of climbing on ladders and platforms, should be
avoided.
Working with low voltage. Switch off the control current and, if necessary, the
Both alternating (AC) and direct heating current too.
(DC) current can be routed to the
operating mechanism.
Risk of crushing in the operating Operate the circuit-breaker to the open position. Isolate
mechanism and link system. and earth the high-voltage side. Off-load the springs by
There is stored energy in the switching off the motor current and perform a Close-
opening and closing springs. The Open operation or move the operating mechanism's
mechanism can be tripped by drive shaft backwards by hand (see the Product
heavy vibrations or by unintentional Information for the operating mechanism). For reasons
contact with mechanical latch of safety the closing springs must be off-loaded during
components. transportation as well as during assembly and storage.
Working close to pressurised Work close to the circuit-breaker's insulators that may
insulators. result in damage to the insulator, must not be carried
The normal working pressure is up out until the gas has been emptied to
to 0.8 MPa. Damage to the max. 0.125 MPa (abs.) pressure.
porcelain can result in splintering.
2 1HSB425409-130 en rev0
Operating and Maintenance Instructions Preventative maintenance
2. Preventative maintenance
2.1 Circuit-breaker
N.B. Opening the breaking unit requires special instructions and may only be done
by trained and authorised personnel.
The curve that defines the permissible number of short-circuits can be expressed
approximately as:
Σ n x I2 = 20000
where
n = the number of short-circuits
I = short-circuit current kA (RMS)
All short-circuit current levels can be included in the total of the number of short-
circuits x short-circuit current to the power 2.
e.g. 10x302+20x202+20x102=19000
1. Load currents from normal Closing and Opening operations should not be included in
the formula. These are only included when calculating the total number of mechanical
CO operations.
1HSB425409-130 en rev0 3
Preventative maintenance Operating and Maintenance Instructions
Number of operations
n
5000
2000
1000
500
200
100
50
20
kA
2 3 4 5 10 20 30 40 50 63
Short-circuit current
4 1HSB425409-130 en rev0
Operating and Maintenance Instructions Preventative maintenance
WARNING
Manual operation of the circuit-breaker may only be carried out by
specially trained personnel to prevent damage to the circuit-breaker and
personal injury.
Item
1 Switch Local/Remote
2 Motor protection
B30206
2 1
• Connect a buzzer across the main breaking point to check the position of the
contacts when the contacts are made.
1HSB425409-130 en rev0 5
Preventative maintenance Operating and Maintenance Instructions
Operating
mechanism
Item
1 Crank 2
N.B. The link system must not engage with the roller on the Open latch.
8 2 3
Item 1
1 Dog
7 Link system
8 Open latch
B30054
6 1HSB425409-130 en rev0
Operating and Maintenance Instructions Preventative maintenance
• Crank the crank until the operating lever (1) aligns with the score mark on the
mechanism housing (2), see Figure 2-5.
– Place a small square against the mechanism housing to get the correct
position and measure horizontally the measurement "d".
– Continue to crank towards the Closed position until the buzzer indicates
electrical contact in the circuit-breaker pole.
– If the horizontal measurement "d" has increased by 6 mm or more, the
circuit-breaker pole should be overhauled and the contacts replaced.
2
Item
2 Mechanism housing
1
Score mark
d
B30242
• Continue to crank the crank clockwise after reading off the reference
measurement until the link system (7) engages with the Open latch (8).
OBS Check that the link system has engaged with the roller on the Open latch.
• Turn the crank attachment (2), Figure 2-3, around and crank the crank 1-2 turns
anti-clockwise and remove the tool (2), Figure 2-4, from the dog.
• Continue to crank anti-clockwise
until the dog returns to its original
position. When the dog passes the
closing catch gear’s roller (5) this is
lifted up with a slotted head
B30056
screwdriver, see Figure 2-6.
Figure 2-6. Closing catch gear’s roller.
The circuit-breaker is now in the closed position and a normal opening operation
can be performed.
1HSB425409-130 en rev0 7
Preventative maintenance Operating and Maintenance Instructions
2.2.1 Maintenance
WARNING
Work on the operating mechanism with the circuit-breaker in the Closed
position and with tensioned closing springs always involves a certain risk.
It is therefore important that the guidelines in the document “Maintenance for BLK
222”, Safety regulations, are followed before the work is started.
1. See the document “Lubricants” 1HSB445409-1 for the names of suppliers and brands for
grease and oils.
8 1HSB425409-130 en rev0
Operating and Maintenance Instructions Preventative maintenance
2.2.2 Cleaning
Clean the operating mechanism when necessary using a vacuum cleaner.
2.2.3 Lubrication
The ball, roller and needle bearings as well as the worm gear in the operating
mechanism are permanently lubricated and require no maintenance. Shafts in the
latch mechanisms should be greased after 2,000 operations using Grease “L”1 . The
sliding surfaces on the dashpot should be lubricated using Grease “G”1 .in
connection with an overhaul.
When supplied the dashpot is filled with Oil “S”1.
N.B. Tectyl 506 forms a waxy protective skin when it dries and therefore it must
not be sprayed into bearings and latch mechanisms or on to gear-wheels.
1. See the document “Lubricants” 1HSB445409-1 for the names of suppliers and brands for
grease and oils.
2. Approved storage space:
roof, solid foundation, relative humidity less than 50%, temperature +20oC
1HSB425409-130 en rev0 9
Operating and Maintenance Instructions Inspection intervals
3. Inspection intervals
Important checkpoints, acceptable tolerances, certain functional values for
adjustments, and recommended inspection intervals can be found in the following
inspection chart.
In corrosive or polluted air and in climates with a high relative humidity, it can be
necessary to halve the inspection intervals.
The specified inspection intervals should be considered as recommended guide
values, which can be increased or decreased depending on local conditions.
1HSB425409-130 en rev0 11
Inspection intervals Operating and Maintenance Instructions
Condition of Com-
Explan- circuit- petence
Type of measure Inspection interval
ation breaker require-
during work ments
B Preventive maintenance
Intermediate inspection
• Operation testing including 3-6 years, 2 000 mech. 1) b1 b2
time checks oper.
• Thermovision inspections
D Overhaul
• Overhaul of the breaker 2) c1 c2
chamber ΣnxI2=20 000
• Line breaker ΣnxI2=20 000
• Transformer breaker
• Capacitor bank
Reactor breaker
Filter breaker
• Non-synchronised 2 500 el. oper.
• Synchronised 5 000 el. oper.
Explanation:
1) Mech. oper. =Mechanical Close-Open operations.
2) El. oper. = Close-Open operations with electrical load.
3) Special demands on resistance inspections for circuit-breakers operated
> 100 Close and Open operations/year.
12 1HSB425409-130 en rev0
Operating and Maintenance Instructions Inspection intervals
Competence requirements:
a2) Substation personnel with no special training.
b2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work.
c2) Personnel authorised by ABB to carry out assembly, commissioning and
maintenance work. In certain cases, with instructions from ABB.
1.
Ocular inspection 1-2 years Check external cleanliness, heater
element function, gas pressure, valves
and drainage holes.
No special tools needed.
See Chapter 2.1.4 and Chapter 2.1.5.
1HSB425409-130 en rev0 13
Inspection intervals Operating and Maintenance Instructions
1.
Ocular inspection 3-6 years or 2,000 mechanical Check external cleanliness, heater
Close-Open operations. element function, gas pressure, valves
and drainage holes.
No special tools needed.
See Chapter 2.1.4 and Chapter 2.1.5.
2.
Rating plates 3-6 years or 2,000 mechanical Make a note of the serial number.
Close-Open operations.
3.
Operation counter 3-6 years or 2,000 mechanical Make a note of the number of
Close-Open operations. operations.
4.
Ocular inspection of 3-6 years or 2,000 mechanical Check that there are no loose bolts or
operating mechanism Close-Open operations. nuts. Make sure there is no oil leakage
from the dashpots.
In the event of leakage change the
complete dashpot.
No tools needed.
See Manual Maintenance of the
operating mechanism.
5.
Corrosion inspection 3-6 years or 2,000 mechanical Ocular inspection.
Rust protection Close-Open operations. Remove patches of rust and treat with a
rust inhibitor
See Chapter 2.2.4
6.
Lubrication 3-6 years or 2,000 mechanical The circuit-breaker is in the Open
Close-Open operations. position and the closing spring is off-
loaded. Grease the latches on the
operating mechanism using Grease "L".
See Chapter 2.1.6, Chapter 2.2.3 and
the Manual Maintenance of the
operating mechanism.
14 1HSB425409-130 en rev0
Operating and Maintenance Instructions Inspection intervals
7.
Thermovision 3-6 years or 2,000 mechanical Carried out at full load before shutdown
measurements Close-Open operations. of the circuit-breaker.
Check on temperature increase in the
outer parts of the circuit-breaker.
The highest permitted temperature
difference between the phases is 5˚C.
Thermovision camera.
The load current must be taken into
consideration during the measurements
as well as large variations in the load
current 3-4 hours before the
measurements.
See the Manual for the Thermovision
camera
8.
Operating test 3-6 years or 2,000 mechanical Operation test, if possible in
Close-Open operations. combination with measurement of the
operating times (including Close-Open
times).
See the Assembly Instructions for the
circuit-breaker in question.
1HSB425409-130 en rev0 15
Inspection intervals Operating and Maintenance Instructions
1.
Ocular inspection 15 years or 5,000 mechanical Check external cleanliness, heater
Close-Open operations. element function, gas pressure, valves
and drainage holes.
No special tools needed.
2.
Rating plates 15 years or 5,000 mechanical Make a note of the serial number.
Close-Open operations.
3.
Operation counter 15 years or 5,000 mechanical Make a note of the number of
Close-Open operations. operations.
4.
SF6 Gas 15 years or 5,000 mechanical Gas filling equipment.
• Gas filling. Close-Open operations. See the applicable Assembly
Instructions for the circuit-breaker in
question.
Dew point measuring instrument.
• Dew point at normal
gas pressure in the Dew point max. -5oC at stated filling
circuit-breaker. pressure and +20˚C.
5.
Insulators
• Ocular inspection and 15 years or 5,000 mechanical Clean the insulators by spraying and
cleaning. Close-Open operations. rubbing. Check the bolts and nuts.
Spraying equipment, drying cloths,
torque wrenches.
See Chapter 2.1.5.
16 1HSB425409-130 en rev0
Operating and Maintenance Instructions Inspection intervals
R= Permissible increase in
resistance
Rn = Max. resistance as specified
in operating values
In = Rated current as specified on
rating plate
I= Current for which max.
resistance is calculated.
7a.
Mechanism 15 years or 5,000 mechanical Inspection of reference holes in outer
Open position. Close-Open operations. lever and mechanism housing. See
applicable Assembly Instructions for the
circuit-breaker in question.
7b.
Operating times 15 years or 5,000 mechanical Measurement with electronic timer.
• Opening time Close-Open operations. Nominal operating voltage.
• Closing time For times, see the applicable Assembly
• Close-Open time Instructions for the circuit-breaker in
question.
• Deviation between
phases Maximum time deviation between
phases 4 ms when closing and 3 ms
• Connection times
when opening.
• Contact dampening
See the Manual Maintenance of the
operating mechanism.
1HSB425409-130 en rev0 17
Inspection intervals Operating and Maintenance Instructions
8a.
Operational availability
• Pull rod system 15 years or 5,000 mechanical Check tightening torque on bolts in the
Close-Open operations. pull-rod system.
See applicable Assembly instructions
for the circuit-breaker.
8b.
Motor current 15 years or 5,000 mechanical The motor current shall be measured
Close-Open operations. towards the end of the tensioning
stroke. See applicable Assembly
Instructions for the circuit-breaker
Max. tensioning time: 15 s.
The motor must be able to tension the
springs at 85% of the nominal voltage
(IEC).
See the Manual Maintenance of the
operating mechanism.
8c.
Dashpot 15 years or 5,000 mechanical Inspection of oil level.
Close-Open operations. The oil level can be checked by
removing the dashpot or by means of
an ultrasonic test.
See the Manual Maintenance of the
operating mechanism.
18 1HSB425409-130 en rev0
Operating and Maintenance Instructions Inspection intervals
8e. 15 years or 2,000 mechanical The resistance and current of the coils
Coils Close-Open operations. is permitted to fluctuate 10% of the
obtained measurement value taken
during routine testing.
8f.
Limit switch 15 years or 2,000 mechanical The closing circuit must be closed
Close-Open operations. before the motor current is switched off,
in the final phase of tensioning of the
spring package.
See Maintenance for the operating
mechanism.
8g.
Heater element 15 years or 2,000 mechanical Resistance measurement:
Close-Open operations. • for BLK 222
70 W, 220v: R = 691 Ohm ±10%.
140W, 220V: R = 346 Ohm ±10%.
Check the signal for voltage failure, if
there is such a signal.
8h.
Terminal blocks 15 years or 5,000 mechanical Check the screws and clamps.
Close-Open operations.
8i.
Motor starter 15 years or 5,000 mechanical Check the signal for voltage failure, if
Close-Open operations. there is such a signal.
1HSB425409-130 en rev0 19
Inspection intervals Operating and Maintenance Instructions
9.
Tightness of the SF6
gas 15 years or 5,000 mechanical Check the pressure sensor and
• Density monitoring Close-Open operations. signal/break contacts on the density
monitors. Pressurise the density
monitors with air or nitrogen, reduce the
pressure slowly and take readings of
the pressure.
If the density monitor is not equipped
with a pressure gauge, the pressure
must be recorded using a separate
gauge.
Min. permissible voltage during check:
30 V.
Permissible deviation from filling
pressure at 20oC:
• Pressure gauge: - 0.02/ + 0.05 MPa.
• Density monitor: 0.015 MPa
Difference between signal and blocking
pressure: >0.01 MPa
See Assembly Instruction för the for the
circuit-breaker in question.
10.
Blocking relays 15 years or 5,000 mechanical The relays shall break when a density
Close-Open operations. monitor is removed from a circuit-
breaker pole pressurised to filling
pressure. (Must be done when the
circuit-breaker is not operational.)
11.
Corrosion 15 years or 5,000 mechanical External ocular inspection.
Close-Open operations. Treat with rust inhibitor when
necessary.
See Maintenance for the operating
mechanism.
12a.
Lubrication 15 years or 2,000 mechanical Inspect and lubricate the latches.
Close-Open operations. See Maintenance for the operating
mechanism.
12b.
Worm gear 15 years or 2,000 mechanical • For BLK 222:
Close-Open operations. Check the oil level in the worm gear
housing
See Maintenance for the operating
mechanism
13.
Operating test 5 years or in accordance with the Operating test, if possible in
customer’s routines combination with measurement of
operating times, (incl. Close-Open
times).
20 1HSB425409-130 en rev0
Operating and Maintenance Instructions Inspection intervals
1.
Overhaul of the
breaking unit
• Line and transformer ΣnxI 2 =20,000. Gas evacuation, dismantling of the
breaker circuit-breaker poles and mechanism.
Transport to a clean workshop.
• Capacitor battery Non synchronised: Insulator removed, replacement of
breaker 2,500 electric Close-Open contacts and PTFE components.
• Reactor breaker operations. Standard equipment, well-fitting face
• Filter breaker Synchronised: mask for dust protection, long sleeve
5,000 electric Close-Open overall, plastic or rubber protective
operations. gloves.
See the Overhaul Instructions for the
circuit-breaker in question.
• All types of Alarm with diagnostic testing.
maintenance
2.
Overhaul of complete 30 years or 10,000 mechanical Removal of circuit-breaker pole and
circuit-breaker and Close-Open operations. mechanism. Fitting new contacts and
operating mechanism PTFE components. Replacement of
other worn parts.
If the overhaul of the circuit-breaker
and operating mechanism is being
done for a further 10,000 operations,
all moving parts should be replaced.
If the overhaul of the circuit-breaker
and operating mechanism is being
done for a further 2,000 operations,
certain worn parts shall be replaced.
Protection against decomposition
products in accordance with standard
equipment above.
See the Overhaul Instructions for the
circuit-breaker in question.
Directions and instruction from ABB for
the operating mechanism
3.
Capacitor 30 years or 10,000 mechanical Check the values:
Close-Open operations. C = CN +5%, -0%
PD < 5 pC
Tan d < 0.2%.
1HSB425409-130 en rev0 21
ABB Power Technology Products AB 1HSB425409-130 en rev0
Head Office 0302
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 782 320
SF6 Circuit-Breaker Circuit-breakers HPL and LTB
Lubricants
1HSB445409-1 en1
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to a third party or otherwise be used
without authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-02-14
Lubricants
LIST OF CONTENTS
1. General ................................................................................ 1
1.1 Safety instructions.......................................................................... 1
2. Oil........................................................................................ 3
3. Grease ................................................................................. 5
1HSB445409-1 en1 i
Lubricants General
1. General
As a guide to the selection of oils and greases for circuit-breakers, Combined,
Compact HPL and LTB with operating mechanisms, a description is given below of
the application areas as well as trade names and suppliers.
1HSB445409-1 en1 1
Lubricants
2. Oil
Oil “A”
Thin, fully synthetic lubricating oil for precision components in the operating
mechanism and circuit-breaker. Also used for post lubrication of bearings that
cannot be lubricated with grease “G” without dismantling, e.g. links and link gears.
Viscosity at 40˚C: 62-65 cSt
Lowest pour temperature: -52˚C
Oil “D”
Breaker oil with a low viscosity ~ 6.0 cSt at 20˚C. Also used as oil in dashpots.
Dashpots with the letter “s” punched on the cover shall be filled with oil “S”.
Oil “S”
Silicone oil intended for dashpots in heavy-duty operating mechanisms, type BLG.
Only dashpots with the letter “s” punched on the cover shall be filled with this oil.
CASTROL FORMULA RS - -
5W-50
SHELL TMO Synthetic NYSWITCHO 3 DC 200 Fluid 200
5W-30 NYSWITCHO 3X CS
1HSB445409-1 en1 3
Lubricants
3. Grease
Grease “G”
Low-temperature grease for all types of bearings, gearing and worm gears and
valves in air-blast circuit-breakers.
Also used for greasing sealing rings and crevice corrosion protection on breakers
type HPL and for moving contacts (opening contacts9 for disconnectors.
Grease “K”
Molykote grease for lubricating pins in link gears and in earthquake dampers.
Grease “N”
For lubricating moving contacts and puffer cylinders in SF6 circuit-breakers. The
grease shall be applied in a very thin layer on the contact’s sliding surfaces.
Grease “L”
Low-temperature grease especially suitable for lubricating precision components,
for example, latch mechanisms in operating mechanisms that shall work in severe
cold.
Grease “M”
Low-temperature grease for long-term and permanent lubrication of worm gears,
and spur gears and other machine elements. Counteracts wear and corrosion. Also
for lubricating moving contacts (opening contacts) for earthing switches.
Grease “P”
Vaseline for coating contact surfaces on fixed joints on the inside of the breaking
unit.
Grease “S”
Fluoro-silicone grease for lubricating the EPDM-O-rings and as crevice corrosion
protection on circuit-breakers type ED as well as for lubricating rotating shaft seals
on circuit-breakers types LTB and HPL.
Grease “SV”
For lubricating moving contacts (opening contacts) for disconnectors, silver-plated
contacts and brushed aluminium surfaces on fixed joints outdoors
1HSB445409-1 en1 5
Lubricants
ABB art. No. 1171 4014-407 1263 0011-102 1171 4016-607 1171 4016-606
ABB spare part No. 5316 381-A 5316 381-M 5316 381-L 5316 381-H
ABB art. No. 1171 4016-612 1171 5011-102 1171 4014-406 1171 4016-610
ABB spare part No. 5316 381-J 5316 381-N 5316 381-G 5316 381-C
Fluortech AB TP55
1HSB445409-1 en1 6
ABB Power Technology Products AB 1HSB445409-1 en1
Head Office 0202
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 714 928
SF6 Circuit-Breaker Operating mechanism
type BLK 222
Maintenance
1HSB535409-100 en rev4
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to third party or otherwise be used wit-
hout authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-03-21
Maintenance Operating Mechanism
LIST OF CONTENTS
1. General ............................................................................... 1
2. Safety................................................................................... 3
2.1 Warning text ................................................................................... 3
2.2 Safety directives ............................................................................. 4
4. Maintenance........................................................................ 9
4.1 General ........................................................................................... 9
4.2 Preparations for maintenance....................................................... 18
4.3 Cleaning ....................................................................................... 19
4.4 Corrosion...................................................................................... 19
4.5 Lubrication ................................................................................... 20
4.6 Heater element ............................................................................. 20
4.7 Drive unit...................................................................................... 21
4.8 Catch gear..................................................................................... 23
4.9 Dashpot ........................................................................................ 25
4.10 Limit switch with auxiliary contact.............................................. 26
4.11 Terminal blocks ............................................................................ 28
1HSB535409-100 en rev4 i
Maintenance Operating Mechanism
FIGURES
ii 1HSB535409-100 en rev4
Maintenance Operating Mechanism General
1. General
This information applies for the spring operating mechanism BLK 222 intended for
operating circuit-breakers with integrated opening springs. Information is provided
in this instruction for maintenance and fault correction maintenance.
Preventive maintenance and overhaul of the mechanism BLK 222 should be carried
out at regular intervals.
• Visual inspection at 1-2 year’s intervals.
• Lubrication after 15 years or 2000 mechanical On-Off operations.
• Preventive maintenance after 15 years or 5000 mechanical On-Off operations.
• Overhaul after 30 years or 10 000 mechanical On-Off operations.
Overhaul and repair work may only be carried out by service personnel authorised
by ABB Power Technology Products AB.
1HSB535409-100 en rev3 1
Maintenance Operating Mechanism Safety
2. Safety
DANGER
indicates an immediate hazardous situation that, if not avoided, will result
in death or serious personal injury.
WARNING
indicates an immediate hazardous situation that, if not avoided, can result
in death or serious personal injury.
CAUTION
indicates a hazardous situation than can result in minor or moderate
injury.
N.B. used for hazards that may only result in damage to the installation.
1HSB535409-100 en rev3 3
Safety Maintenance Operating Mechanism
WARNING
Circuit-breakers with pressurised insulators.
Mechanical damage to the insulator can cause it to explode with the
following risk of splintering.
Work on the circuit-breaker that brings about the risk of mechanical
damage to the insulators should be carried out at a reduced gas pressure,
0.125 MPa (abs).
WARNING
Do not operate the mechanism unloaded!
Operations shall take place only after the mechanism has been connected
and trimmed with the associated circuit-breaker.
The standard operating cycle is O - 0.3 s - CO - 3 min. - CO. The time between
closing operations should not be less than 1 minute during the testing of circuit-
breakers and relay systems involving more than 3 closing operations.
4 1HSB535409-100 en rev3
Maintenance Operating Mechanism Safety
WARNING
Work requires training and product knowledge and may only be carried
out by authorised personnel.
Risk Measure
Working next to high voltage. Isolate and earth close to the work
place. If work must be carried out
close to live installation components,
the safety distance applying in the
country’s applicable safety
regulations must be observed.
Working with low voltage. Switch off the control voltage and if
Both alternating (AC) and direct (DC) necessary the heating voltage.
current can be routed to the
operating mechanism.
1HSB535409-100 en rev3 5
Maintenance Operating Mechanism Maintenance, general
3. Maintenance, general
All requisite equipment should be available before work is started so that
maintenance work can be carried out in the best way.
The following equipment is required.
3.1 Tools
• A normal set of tools including a torque wrench (10-100 Nm).
• Measuring scale.
• Vernier gauge.
• Lifting slings.
1HSB535409-100 en rev3 7
Maintenance Operating Mechanism Maintenance
4. Maintenance
4.1 General
The Operating and Maintenance Instructions for the circuit-breaker should be read and
followed before work on the circuit-breaker is started and while work is in progress.
WARNING
Do not operate the operating mechanism unloaded!
Operations shall take place only after the mechanism has been connected
and trimmed with the associated pressurized circuit-breaker.
The component parts of the operating mechanism are integrated in a cabinet which
also contains a control panel with operating equipment. The top of the cabinet can
be removed and the operating panel opened to facilitate service and overhaul work.
2 1
5
3
B30200
Item
1 Drive unit
2 Operating mechanism
3 Operating panel
4 Closing spring
5 Heater element
• Measure all operating values and record them. If the measured values
correspond with the specified values for the circuit-breaker, then only a visual
inspection, cleaning and lubrication are required.
1HSB535409-100 en rev3 9
Maintenance Maintenance Operating Mechanism
1 4 2
Item
1 Motor protection
2 Switch Local/Remote
3 Spring indicator 3
B30201
The motor protection should be reset when work has been completed.
10 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
Mechanism
Item
1 Cover
2 Screw M6 4 pcs.
3 Crank 4 2
4 Crank attachment
5 Spring indicator 3 1
B30202
1HSB535409-100 en rev3 11
Maintenance Maintenance Operating Mechanism
Mechanism
Item
1 Cover
2 Crank
3 Crank attachment 3 1
4 Spring indicator
B30202
12 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
CAUTION
Slow manual closing and opening operations may only be carried out by
persons that are well conversant with the operation of the mechanism and
circuit-breaker as there is a risk of personal injury and mechanical
damage.
Item
1 Switch Local/Remote
2 Motor protection
B30206
2 1
Mechanism
Item
1 Crank 2
2 Crank attachment 1
B30052
1HSB535409-100 en rev3 13
Maintenance Maintenance Operating Mechanism
2. Connect the crank and crank anti-clockwise so it is possible to attach the tool
(2) on the heel (3) and dog (1), see Figure 4-7.
3. Crank clockwise until the crank shaft stops against the closing catch gear (4).
Crank a further number of turns so that the roller (5) is under pressure.
4. Press using a screwdriver on the latch (6) for the closing catch gear.
5. Continue to crank clockwise until the link system (7) engages with the Open-
lock (8).
N.B. Check that the link system has engaged with the roller on the Open-lock.
6. Crank the crank 1-2 turns anticlockwise and remove the tool (2) from the dog.
8 2 3
Item 1
1 Dog
7 Link system
8 Open-lock
B30054
The circuit-breaker is now in the closed position and a normal opening operation
can be made.
14 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
Item
1 Switch Local/Remote
2 Motor protection
2 3 1
B30206
Mechanism
Item
2
1 Crank
1HSB535409-100 en rev3 15
Maintenance Maintenance Operating Mechanism
2 3
Item
1
1 Dog
5 Roller
5
6 Latch, closing catch gear
7 Latch, Open-lock
B30057 8
4
8 Link system
16 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
1HSB535409-100 en rev3 17
Maintenance Maintenance Operating Mechanism
1 2 3
Item
1 Operating panel
4
2 Operating switch
Close/Open
3 Switch Local/Remote
4 Spring indicator
B30203
18 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
WARNING
Unused SF6 gas is non-toxic, odourless and colourless. It is heavier than
air and can therefore easily collect in low-lying places, e.g. cable trenches,
tanks, etc., if released in large volumes
When large quantities of SF6 gas collect in such places, a risk of
asphyxiation may occur due to a lack of oxygen.
The SF6 gas is evacuated by using gas handling equipment, which cleans and
compresses the gas so that it can be reused or destructed.
N.B. Mixed gas, SF6 mixed with N2 or CF4, must not be reused unless the mixture
ratio is under control. (Can be checked with a meter that indicates the
percentage of SF6.)
4.3 Cleaning
• Clean the inside of the operating mechanism using a vacuum cleaner.
• Check that the filters in the valves are clean. If they are heavily soiled they
should be replaced.
4.4 Corrosion
Some of the steel mechanism parts have been surface treated with manganese
phosphate and then rust protected by dipping in oil. This applies to, among others,
latches and components in the link system.
Despite good rust protection small signs of rust attack can appear after a number of
years, especially on circuit-breakers erected in aggressive environments.
• Rust spots should be removed and new anti-corrosive agent should be applied
by brush or spray. Recommended anti-corrosive agents are Grease “G” or
Tectyl 506.
N.B. After drying Tectyl 506 forms a protective wax-like cover and must not be
sprayed on bearings as well as catch gears and gears.
1HSB535409-100 en rev3 19
Maintenance Maintenance Operating Mechanism
4.5 Lubrication
The ball, roller and needle bearings as well as worm gears in the operating
mechanism are permanently lubricated and require no maintenance. Therefore only
the shafts in the catch gears need to be lubricated.
Sliding surfaces for the dashpot should be lubricated during an overhaul with
Grease “G”.
1
Item
1 Heater element
B30058
Data
– 70 W, 220 V: R = 691 Ohm ±10%.
– 140W, 220 V: R = 346 Ohm ±10%.
– 70 W, 110 V: R = 173 Ohm ±10%.
– 140 W, 110 V: R = 86 Ohm ±10%.
20 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
Item
1 Drive unit
B30160
1HSB535409-100 en rev3 21
Maintenance Maintenance Operating Mechanism
TIGHTENING TORQUE
9 Nm
1
Item
1 Closing arm
2 Roller
2
3 3
B30168
6. Lock the bolts using locking fluid, Loctite 242, ABB Art. No. 1269 0014-410.
7. Refit the cover.
22 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
1
Item
B30204
Item
1 Auxiliary catch
2 1 mm
2 Magnet arm
B20013
1HSB535409-100 en rev3 23
Maintenance Maintenance Operating Mechanism
TIGHTENING TORQUE
40 Nm
Item
B30062 1 1
24 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
4.9 Dashpot
The operating mechanism is fitted with a dashpot to dampen the final phase of the
opening movement.
Item
1 Dashpot
B30063
The oil level should be up to the mark. If necessary, fill up with oil “S”.
1HSB535409-100 en rev3 25
Maintenance Maintenance Operating Mechanism
2 1
Item
1 Limit switch
2 Auxiliary contact
B30200
26 1HSB535409-100 en rev3
Maintenance Operating Mechanism Maintenance
1. Connect a time-meter across the signal contacts 10, 19, 121 and 122 in
accordance with the circuit diagram.
2. Measure the times t1, t2 and t3
3. Turn the switch “Local/Remote” to the “LOCAL” position.
4. Connect the time-meter across terminals X1:190 and X1:192.
5. Turn the switch “Close/Open” to “OPEN” and then to the “CLOSED” position.
6. Note down the times t1, t2 and t3.
7. Disconnect the time-meter.
8. Turn the switch “Local/Remote” to the “REMOTE” position.
Contact movement
Arcing contact
Closed
Auxiliary contact
Contact
movement
Open
t1 t3 Time
t2
B20018
1HSB535409-100 en rev3 27
Maintenance Maintenance Operating Mechanism
8
Item
1 Opening coil
1
2 Closing coil
3 Motor
2
4 Switch Local/Remote
6 Electric counter
7 Limit contact
8 Auxiliary contact
9 Anti-condensation heater
11 Interlock relay
12 Interlock relay 15 14 6 5 4
13 Motor contactor
14 Motor protection
3 7
15 Miniature switch, heater
12
11
10 9
13
B30205
28 1HSB535409-100 en rev3
ABB Power Technology Products AB 1HSB535409-100 en rev4
Head office 0321
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 714 928
SF6 Circuit-Breaker LTB 72.5-170D1/B with
operating mechanism BLK 222
3-pole operation
Overhaul Instructions
1HSB425409-230 en rev0
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of
this document.
The document, or parts thereof, may not be reproduced or copied without prior permission from
ABB Power Technology Products AB. It may not either be imparted to third party or otherwise be
used without authorisation. Infringement hereof will be subject to action in accordance with appli-
cable laws.
Date: 2002-04-26
Overhaul Instructions
TABLE OF CONTENTS
1. General ............................................................................... 1
2. Safety................................................................................... 3
2.1 Warning text ................................................................................... 3
2.2 Safety directives ............................................................................. 4
1HSB425409-230 en rev0 i
Overhaul Instructions
ii 1HSB425409-230 en rev0
Overhaul Instructions
FIGURES
1. General
This Overhaul Instruction applies to the SF6 circuit-breaker type LTB 72.5-
170D1/B with two column frame and operating mechanism type BLK 222 for three
pole operations. It contains information for overhaul and repair work.
Overhaul and repair work may only be carried out by technicians trained by
ABB Power Technology Products AB.
1HSB425409-230 en rev0 1
Overhaul Instructions Safety
2. Safety
DANGER
indicates an immediate hazardous situation that, if not avoided, will result
in death or serious personal injury.
WARNING
indicates an immediate hazardous situation that, if not avoided, can result
in death or serious personal injury.
CAUTION
indicates a hazardous situation than can result in minor or moderate
injury.
N.B. used for hazards that may only result in damage to the installation.
1HSB425409-230 en rev0 3
Safety Overhaul Instructions
WARNING
Circuit-breakers with pressurised insulators.
Mechanical damage to the insulator can cause it to explode with the
following risk of splintering.
Work on the circuit-breaker that brings about the risk of mechanical
damage to the insulators should be carried out at a reduced gas pressure,
0.125 MPa (abs).
WARNING
Do not energize, charge or operate the operating mechanism until final
assembly and adjustments on the circuit-breaker are fully completed.
4 1HSB425409-230 en rev0
Overhaul Instructions Safety
WARNING
Work requires training and product knowledge and may only be carried
out by authorised personnel.
Risk Measure
Working close to high voltage. Isolate and earth close to the work
place. If work must be carried out
close to live installation components,
the safety distance applying in the
country’s applicable safety
regulations must be observed.
Working with low voltage. Switch off the control voltage and if
Both alternating (AC) and direct (DC) necessary the heating voltage.
current can be routed to the
operating mechanism.
1HSB425409-230 en rev0 5
Overhaul Instructions Overhaul, general
3. Overhaul, general
Before the overhaul work is started, all the necessary equipment and replacement
parts should be made available so that the overhaul work can be carried out in the
best possible way.
The following equipment is needed.
3.1 Tools
• A normal set of tools and torque wrenches (10-100 Nm).
• Lifting devices and lifting slings. The weights of the circuit-breaker parts to be
lifted can be found on the applicable dimension drawing for the order.
1HSB425409-230 en rev0 7
Overhaul, general Overhaul Instructions
3.7 Premises
The circuit-breaker or breaking unit must be opened indoors in dry and clean
premises.
When the weather is good and settled and outdoor working conditions are similar to
indoor conditions, the breaking units can be removed outdoors and transported to
dry and clean premises for the overhaul.
8 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the circuit-breaker
4.1 General
Before the circuit-breaker is dismantled and during the course of the dismantling
work, the directives in the Operating and Maintenance Instructions
1HSB425409-100 must be read and followed:
Check and note down the circuit-breaker’s operating values before dismantling.
Any deviation from the recommended values indicates that something must be
carefully checked during the overhaul.
There are two different methods of implementing the overhaul:
• First and foremost it is recommended that the entire circuit-breaker is
dismantled for transport to a service workshop, where it can be dismantled in
detail for an overhaul.
• Alternatively, and secondly only the breaking unit is dismantled.
The latter method does not entail so much work, but it may only be used when the
weather is settled and the outdoor working conditions are similar to indoor
conditions.
N.B. Removal and assembly of breaking units must not be done when the
weather is such that there is a risk of rain.
WARNING
This work requires trained staff with product knowledge and may only be
carried out by authorised personnel.
1HSB425409-230 en rev0 9
Dismantling the circuit-breaker Overhaul Instructions
4.2 Gas
Work on the circuit-breaker’s insulators or other live components as well as
transport and dismantling of complete circuit-breaker poles from the frame, may not
be done until the gas has been evacuated to a pressure of max 0.125 MPa (abs).
Gas shall be emptied fully to atmospheric pressure when a normal pressurised
space, e.g. the breaking unit, shall be opened.
WARNING
When nitrogen gas is used for cleaning inside the circuit-breaker, the gas
must be emptied to the atmosphere via a dust and absorption filter.The
emptying operation must be done outdoors and at ground level.
WARNING
Unused SF6 gas is non-toxic, odourless and colourless. It is heavier than
air and can therefore easily collect in low-lying places, e.g. cable trenches,
tanks, etc., if released in large volumes.
When large quantities of SF6 gas collect in such places, a risk of
asphyxiation may occur due to lack of oxygen.
N.B. Mixed gas, SF6 mixed with N2 or CF4, must not be reused unless the
mixture ratio is under control. (Can be checked with a meter that indicates
the percentage of SF6.)
After vacuum pumping, the circuit-breaker is filled with dry nitrogen gas until
atmospheric pressure is reached and is then vacuum pumped again. In this way any
free-floating dust inside the circuit-breaker will be extracted.
Finally the circuit-breaker is filled again with dry nitrogen gas until atmospheric
pressure is reached. The circuit-breaker is now ready to be dismantled.
10 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the circuit-breaker
CAUTION
Some decomposition products formed in the breaking unit can, when
coming in contact with moisture, become corrosive and can irritate the
skin, eyes and mucous membranes.
Protective gloves of plastic or rubber, long-sleeved overalls and a full face mask
with a fine particle and acidic gas filter must be worn during cleaning the inside of
the circuit-breaker.
The dust (decomposition products) that forms in the circuit-breaker can be removed
using a vacuum cleaner fitted with a micro-filter and wiped off using a soft cloth
dampened with alcohol.
N.B. All dust, old absorption agent, used cloths, etc., should be collected in
a sealed vessel and treated as chemical waste according to applicable
local directives.
Protective gloves must be worn during all waste handling.
N.B. Drying cloths, protective gloves and vacuum cleaner bags should be rinsed
thoroughly in water after waste handling.
1HSB425409-230 en rev0 11
Dismantling the circuit-breaker Overhaul Instructions
12 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the circuit-breaker
1 Pole C1
3 2
10 7 8
5, 6
9
4
Poles A1 and B1
Pole C1
12
16 11
B30243
14 15 17, 18 19, 20
13
Item Item
1 Groove 11 Crank extension, ABB Art. No. 1HSB532188-F
2 Non-return valve 12 Protective cover
3 Sealing cap 13 Coupling link
4 Opening spring 14 Pull-rod
5 Lock washer SL12 15 Opening spring bracket
6 Pin, pole C1 D=12 16 Crank, ABB Art. No. 2188 754-G
7 Outer lever 17 Lock washer, pole A1 and B1 SL12
8 Opening spring housing 18 Pin, pole A1 and B1 D=12
9 Bolt M12x40 19 Lock washer, pole A1 and B1 SL16
Washer 13x24x2.5
10 Safety bolt M16x30 20 Pin, pole A1 and B1 D=16
Washer 17x30x3
1HSB425409-230 en rev0 13
Dismantling the circuit-breaker Overhaul Instructions
4. Place a lifting sling under the breaking unit’s upper flange as shown in Figure
4-2 and prepare to lift with a crane. Now loosen the circuit-breaker pole (1),
removing the four bolts (2) on the frame.
5. Lift up the circuit-breaker pole and carefully lay it down on a transport
carriage. Block up the circuit-breaker pole so it lies horizontal. The block (3)
under the breaking unit’s insulator should be of an elastic material, e.g. wood
or rubber.
N.B. If possible, keep the supports supplied on delivery for this purpose.
Transport to the workshop or new site should take place with care so as not damage
the insulators.
1
Item
2
1 Circuit-breaker pole
3 Blocks
3
3
B10320
14 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the circuit-breaker pole
3 A
A-A
Item
1 Operating lever
4 Breaking unit
B30244
5 Lock washer SL12
6 Pin D=12
1HSB425409-230 en rev0 15
Dismantling the circuit-breaker pole Overhaul Instructions
N.B. Use personal safety equipment such as overalls, protective gloves and face
mask.
1. Position the lifting sling from the top of the post insulator to the crane or
overhead crane.
2. Remove the post insulator’s bolts (2) from the mechanism housing (3).
3. Lift the post insulator straight up until the operating insulator is released. Hold
the operating insulator when performing the lift.
Item
4 1 Post insulator
A-A
2 Bolts M16x50 4 pcs
Washers 17x30x3 4 pcs
3 Mechanism housing
1 4 Lock washer SL12
5 Pin D=12
5
A
3 A
B30245
16 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the circuit-breaker pole
N.B. Use personal safety equipment such as overalls, protective gloves and face
mask.
Take care of the decomposition products in the breaking unit, in the form of powder,
as the breaking unit is successively opened. First use a vacuum cleaner and
thereafter carefully wipe the dismantled components.
1. Remove the bolts (1) and the cover (2) and lift
out the absorption agent container (3). 1 3 2 4 5
Item
2 Cover
5 Upper flange
The main components of the breaking unit are now accessible for inspection,
cleaning and replacement of burnt or damaged components.
1HSB425409-230 en rev0 17
Overhaul Instructions Contact and puffer replacement
N.B. All contact surfaces must be treated before assembly, see section 8.1,
Treatment of contact surfaces.
Item
1 Nozzle
B30039 max. 24 mm
Item
1 Bolt M8x16
Washer 8.4x16x1.6 2
2 Upper current path
TIGHTENING TORQUE
22.5 Nm B30040
1HSB425409-230 en rev0 19
Contact and puffer replacement Overhaul Instructions
1
Item
1 Nozzle
2 Operating rod
3 Puffer cylinder
B30246
20 1HSB425409-230 en rev0
Overhaul Instructions Contact and puffer replacement
Item
5
1 Flange 4
2 Bolt M6x12
Washer 6.4x12x1.6 3
3 Lower current path
4 Contact element
2
5 Teflon band 1
B30247
1. Assemble the puffer on the puffer guide. When the puffer starts to go down
over the teflon band (5) it should be turned carefully to avoid damaging the
teflon band.
N.B. Exercise care so that the teflon band (5) on the piston is not damaged when
the puffer slides down and that the contact element (4) is held in position
in its groove.
2. Assemble the lower current path (3) above the puffer and puffer guide. Tighten
the bolts (2) with a tightening torque of 10 Nm.
TIGHTENING TORQUE
10 Nm
1HSB425409-230 en rev0 21
Overhaul Instructions Overhaul of the mechanism
N.B. Turn the bearing’s sealing rings in towards the gas chamber.
5. Refit the shaft (4) through the inner operating lever (11) and press in the
bushing (8) with its sealing rings.
6. Fit the circlip (5), felt washer (12) and outer lever (3).
7. Tighten the bolt (2) with a tightening torque of 45 Nm.
Item 7 6
9
1 Mechanism housing 2 1
3 12
2 Bolt M10x45
Washers 10.5x20x2
3 Outer lever
4 Operating shaft
5 Circlip
6 Bearing
5 8
7 Bearing
10
8 Bushing
11
9 X-ring 44.2x5.7
1HSB425409-230 en rev0 23
Overhaul Instructions Assembling the circuit-breaker pole
N.B. When re-assembling all sealing rings must be new. Careful cleaning and
treatment of sealing surfaces is required.
N.B. Polishing using Scotch Brite or grinding must not take place.
• Copper surfaces
Copper surfaces must be clean and free from oxide. If necessary, clean with a
cloth and solvent (alcohol) or with Scotch Brite.
N.B. After cleaning with Scotch Brite, always remove all loose particles from
the surfaces using alcohol.
• Aluminium surfaces
Brush clean contact surfaces of aluminium, using Scotch Brite. Immediately
thereafter carefully clean the surfaces to remove any loose particles with a dry,
clean cloth. Then coat the surfaces with a thin layer of Vaseline.
N.B. Grease should be applied within five minutes of cleaning and the joint
should be fitted within 15 minutes.
1HSB425409-230 en rev0 25
Assembling the circuit-breaker pole Overhaul Instructions
N.B. Sealing grooves and other sealing surfaces must not have lateral scratches.
Any small scratches on sealing surfaces can be removed by polishing with a
fine abrasive, e.g. Scotch Brite. Polishing shall take place along the sealing
line but never across it.
When re-assembling the circuit-breaker, replace all seals with new ones.
Grease sealing surfaces and seals sparingly to facilitate the seal’s union against the
surface and as corrosion protection. Excess grease that can squeeze out on flanges in
the gas chamber must not occur.
Coat flange surfaces outside the outer seal with a thin, well-covering layer of anti-
corrosion agent matched to the flange material in question, usually Grease “G”
(ABB Art. No. 1171 4014-407).
Degreasing and cleaning material:
• Alcohol.
Greases for seals:
• Grease “G” for static seals
Grease “S” for moving seals, e.g. shaft seals.
26 1HSB425409-230 en rev0
Overhaul Instructions Assembling the circuit-breaker pole
TIGHTENING TORQUE
79 Nm
Item
1 Operating insulator
3 A-A
2 Pin D=12
5 Mechanism housing
6 Post insulator A
2
7 Bolts M16x50 4 pcs
Washers 17x30x3 4 pcs
7
1
5 A
B30245
1HSB425409-230 en rev0 27
Assembling the circuit-breaker pole Overhaul Instructions
28 1HSB425409-230 en rev0
Overhaul Instructions Assembling the circuit-breaker pole
9 8
6. Tighten the bolts (6) on the lower flange
(3) with a tightening torque of 22.5 Nm.
TIGHTENING TORQUE
22.5 Nm 7
TIGHTENING TORQUE
2
79 Nm
Item
1 Lower current path 1
2 Puffer
3 Lower connection flange
4 O-ring 194.6x5.6
3
5 Breaking chamber insulator
6 Bolts M8x25 2 pcs.
Washers 8.4x16x1.6 2 pcs.
7 Upper current path
6
8 Upper connection flange B30033 4
9 Bolts M12x60 4 pcs.
Washers 13x28x3 8 pcs.
Nuts M12 4 pcs.
1HSB425409-230 en rev0 29
Assembling the circuit-breaker pole Overhaul Instructions
Item
6
1 Puffer pull-rod
A 5
2 O-ring 169.5x5.6
4, 7
3 Post insulator
4 Lower flange
5 Pin D=12
2
6 Lock washer SL12 A
1
7 Bolts M12x80
Washers 13x28x3
Nuts M12 3
B30244
5. When the pin is fitted, carefully lower the breaking unit on to the post insulator
and centre it. Tighten the breaking unit using the bolts (7) with a tightening
torque of 79 Nm.
TIGHTENING TORQUE
79 Nm
30 1HSB425409-230 en rev0
Overhaul Instructions Assembling the circuit-breaker pole
6. Clean the sealing surface on the upper flange (1) and coat with grease “G”.
Place the sealing rings (2) on top of the upper flange.
7. Open the new absorption agent package and place the agent into the absorption
agent container (3).
8. Fit the absorption agent container (3) and
5
the cover (4) and tighten the bolts (5) with
a tightening torque of 45 Nm. 3 4
1, 2
TIGHTENING TORQUE
45 Nm
Item
1 Upper flange
2 O-ring 194.6x5.6
4 Cover
5 Bolts M10x30
Washers 10.5x20x2
B30249
1HSB425409-230 en rev0 31
Assembling the circuit-breaker pole Overhaul Instructions
32 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the breaking unit for transport
1HSB425409-230 en rev0 33
Dismantling the breaking unit for transport Overhaul Instructions
Pol e C1
5 4
2, 3
Poles A1 and B1
Pole C1
7
11 6
B30243
9 10 12, 13 14, 15
8
Item Item
34 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the breaking unit for transport
6. Remove the bolts (1) and very carefully lift the breaking unit (2)
100 - max 120 mm.
N.B. Do not lift the breaking unit more than 120 mm so as not to damage the
circuit-breaker’s internal components.
Item
1 Bolts M12x80
Washers 13x28x3 2
Nuts M12
A 4
2 Breaking unit
3 Pin 1
4 Pin
5 Post insulator
A
A-A
5
B30244
If a large amount of moisture should enter the post insulator, fill it immediately with
nitrogen gas and transport it to a workshop as soon as possible for dismantling and
careful cleaning.
7. Disconnect the breaking unit (2) by removing the lock washer (3) and the pin
(4).
N.B. Ensure that neither the circlips nor washers fall into the post insulator
during dismantling. Cover the openings by, for example, tying a cloth over
them.
1HSB425409-230 en rev0 35
Dismantling the breaking unit for transport Overhaul Instructions
8. Push down the insulator rod as far into the support porcelain so that the entire
rod is under the edge. Fit the protective cover,
ABB Art. No. 5439 142-A, with the sealing ring over the post insulator (5), see
Figure 9-2. When the cover has been bolted in position, increase the nitrogen
pressure in the post insulator to 0.125 MPa (abs).
9. Slide the puffer pull-rod (4) in the breaking unit (2) and fit the protective cover,
ABB Art. No. 5237 736-R, with the sealing ring, see Figure 9-2.
The breaking unit is now ready for transport.
If the post insulator or breaking unit is left in this condition for a long period
without the breaking unit being re-assembled, vacuum pump the post insulator or
breaking unit and fill with nitrogen gas, see Chapter 8.6.
TIGHTENING TORQUE
79 Nm
8. Clean the upper flange (7) and coat with grease “G”. Place the sealing rings (8)
on top of the upper flange.
9. Open the packaging of the new absorption agent and fit the agent into the
absorption agent container (9).
36 1HSB425409-230 en rev0
Overhaul Instructions Dismantling the breaking unit for transport
10. Fit the absorption agent container (9) and the cover (10) and tighten the bolts
(11) to a torque of 45 Nm.
TIGHTENING TORQUE
45 Nm
11
10
Item
9
1 Puffer pull-rod 7, 8
2 Post insulator
3 O-ring 169.5x5.6
4
4 Breaking unit 1
A
5 Pin
6 Bolts M12x80 4 pcs 6
Washers 13x28x3 8 pcs
Nuts M12 4 pcs
5
A
7 Upper flange
8 O-ring 194.6x5.6 3
A-A
9 Absorption agent container
10 Cover 2
12 Lock washer
13 Outer lever B30250
13
Figure 9-3. Assembling the breaking unit.
1HSB425409-230 en rev0 37
Overhaul Instructions Assembling the circuit-breaker and commissioning
First overhaul.
Measured values
Check the following
Close-Open time(1) ms ms ms
(1) The circuit breaker must not be operated Open-Close without an intermediate delay of 300 ms.
(2) Filling pressure according to rating plate.
1HSB425409-230 en rev0 39
Assembling the circuit-breaker and commissioning Overhaul Instructions
Second overhaul.
Measured values
Check the following
Close-Open time(1) ms ms ms
(1) The circuit breaker must not be operated Open-Close without an intermediate delay of 300 ms.
(2) Filling pressure according to rating plate.
40 1HSB425409-230 en rev0
ABB Power Technology Products AB 1HSB425409-230 en rev0
Head Office 0402
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 782 320
SF6 Circuit-Breaker LTB 72.5-170D1/B
with operating mechanism
BLK 222
3-pole operation
Spare Parts
1HSB425409-330 en rev1
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of
this document.
The document, or parts thereof, may not be reproduced or copied without prior permission from
ABB Power Technology Products AB. It may not either be imparted toa third party or otherwise be
used without authorisation. Infringement hereof will be subject to action in accordance with applica-
ble laws.
Date: 2002-04-26
Spare Parts
TABLE OF CONTENTS
1. General ................................................................................ 1
1.1 Circuit-breaker pole ....................................................................... 2
2. Breaking unit....................................................................... 3
2.1 Breaking unit.................................................................................. 3
2.2 Contact set...................................................................................... 4
3. Post insulator...................................................................... 5
4. Mechanism .......................................................................... 7
4.1 Mechanism ..................................................................................... 7
4.2 Tripping mechanism....................................................................... 7
5. Accessories ........................................................................ 9
5.1 Absorption agent container ............................................................ 9
5.2 Density monitor.............................................................................. 9
5.3 Set of seals.................................................................................... 10
5.4 Assembly sets............................................................................... 10
5.5 Non-return valve .......................................................................... 10
1HSB425409-330 en rev1 i
Spare Parts
FIGURES
ii 1HSB425409-330 en rev1
Spare Parts General
1. General
Spare parts for the SF6 circuit-breaker LTB 72.5-170D1/B with operating
mechanism BLK 222 mounted on a pole beam or on separate hot-dipped galvanised
column frame are supplied by:
ABB Power Technology Products AB
SE-771 80 Ludvika
Sweden
Tel: +46 (0) 240-78 20 00
Spare parts recommended to be kept in stock are marked with an R. With more than
ten circuit-breakers in operation, the spare parts marked with RR are also
recommended to be kept in stock. To be able to make quick replacements and avoid
long periods of downtime, the parts marked by RRR can also be stocked.
Please state the type designation and serial number with all enquiries and orders of
spare parts or tools. Please also state the order number if possible.
1
Item Designation Note
1 Circuit-breaker pole RRR
2 Operating RRR
mechanism
3 Pole beam with gas 2
pipe
Från
4 Gas pipe
5 Frame 3
Från
4
B30259
5
1HSB425409-330 en rev1 1
General Spare Parts
Item Designation
1
1 Breaking unit
2 Post insulator
3 Mechanism
B10321
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
2 1HSB425409-330 en rev1
Spare Parts Breaking unit
2. Breaking unit
B30033
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
1HSB425409-330 en rev1 3
Breaking unit Spare Parts
B30251
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
4 1HSB425409-330 en rev1
Spare Parts Post insulator
3. Post insulator
2
B30072
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
1HSB425409-330 en rev1 5
Spare Parts Mechanism
4. Mechanism
4.1 Mechanism
1
B30252
B30253
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
1HSB425409-330 en rev1 7
Spare Parts Accessories
5. Accessories
1 1 Absorption agent
container
2 1 Absorption agent R B30075
1 1 Density monitor, R
temperature-compensated 1
- reference volume
2 1 Density monitor, R
temperature-compensated
- bimetal
B10322
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
1HSB425409-330 en rev1 9
Accessories Spare Parts
B30077
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
10 1HSB425409-330 en rev1
Spare Parts Tools and lubricants
6.2 Lubricants
6.2.1 Oil
6.2.2 Grease
Please state the type designation and serial number with all enquiries and orders of spare
parts or tools. Please also state the order number if possible.
1HSB425409-330 en rev1 11
ABB Power Technology Products AB 1HSB425409-330 en rev1
Head Office 0402
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 782 320
SF6 Circuit-Breaker Operating mechanism
type BLK 222
Spare Parts
1HSB535409-200 en rev3
ABB Power Technology Products AB is not responsible for damage incurred due to the misuse of this
document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB
Power Technology Products AB. It may not either be imparted to third party or otherwise be used wit-
hout authorisation. Infringement hereof will be subject to action in accordance with applicable laws.
Date: 2002-03-21
Spare Parts
LIST OF CONTENTS
1. General ................................................................................ 1
2. Motor.................................................................................... 3
3. Dashpot ............................................................................... 5
5. Heater element.................................................................... 9
7. Lubricants ......................................................................... 13
7.1 Oil................................................................................................. 13
7.2 Grease........................................................................................... 13
1HSB535409-200 en rev3 i
Spare Parts
FIGURES
ii 1HSB535409-200 en rev3
Spare Parts General
1. General
Spare parts for the operating mechanism BLK 222 are supplied by:
ABB Power Technology Products AB
SE-771 80 Ludvika
Sweden
Tel: +46 (0) 240-78 20 00
Replacement modules are supplied complete and fully tested.
Please state the type designation and the serial number with all enquiries and orders
of spare parts. Please also state the order number if possible.
2 1
5
3
B30200
Item
1 Drive unit
2 Operating mechanism
3 Operating panel
4 Closing spring
5 Heater element
1HSB535409-200 en rev3 1
Spare Parts Motor
2. Motor
B30068
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 3
Spare Parts Dashpot
3. Dashpot
30063
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 5
Spare Parts Catch gear
4. Catch gear
2
110-127 V 1HSB535436B5
220-250 V 1HSB535436B7 4
2 Opening catch gear 24 V 1HSB535436-AP
42-48 V 1HSB535436-Z 1
60-72 V 1HSB535436-AR
110-127 V 1HSB535436B3
220-250 V 1HSB535436B8
Opening catch gear, 42-48 V 1HSB535436-AA
with man trip device 110-127 V 1HSB535436-L
220-250 V 1HSB535436-M
3
3 Coils, Y1 and Y3 24 V LA 516 771-AV B30062
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 7
Spare Parts Heater element
5. Heater element
B30058
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 9
Spare Parts Electrical equipment
6. Electrical equipment
Spare parts for electrical equipment BLK 222
1
2
B30209
Figure 6-1. Electrical equipment,
BLK 222.
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 11
Spare Parts Lubricants
7. Lubricants
7.1 Oil
7.2 Grease
Please state the type designation and the serial number with all enquiries and orders of spare
parts. Please also state the order number if possible.
1HSB535409-200 en rev3 13
ABB Power Technology Products AB 1HSB535409-200 en rev3
Head Office 0321
SE-771 80 LUDVIKA
SWEDEN
Telephone: +46 (0) 240 782 000
Telefax: +46 (0) 240 714 928