You are on page 1of 9

Blackmonk Engineering About Us Calculators Contact Us Blog

How To Size A Liquid Control Valve


d Mon 25 October 2021
Sizing a control valve means selecting a valve with the correct size orifice to allow good control of
flow rate within a required range.

There are other important factors to consider when selecting a control valve, such as valve type
and valve characteristic but this article will concentrate on valve sizing.

Sizing a control valve for a particular duty is governed by the required flow rate the valve must
pass and the pressure drop that can be allowed across the valve.
Blackmonk Engineering About Us Calculators Contact Us Blog

Steps To Accurately Size A Liquid Control Valve


1. Specify the required design flow rate
2. Specify the allowable pressure drop across the valve
3. Choose a valve type and body size from the manufacturers’ tables
4. Calculate the first estimate of the piping geometry factor
5. Determine if the flow through the valve will be sub-critical or critical. That is, will some of
the liquid vaporise causing flashing or cavitation?
6. Calculate the effective pressure drop across the valve
7. Calculate the first estimate of the required valve Cv
8. Check that the calculated Cv is less than the actual Cv of the selected valve (re-select
Blackmonk Engineering About Us Calculators Contact Us Blog
suitable valve from manufacturers’ tables if required)
9. Check that valve control range is OK
10. If the Cv and control range are suitable the valve is correctly sized. If not re-select another
valve and repeat the sizing procedure from Step 3

Sizing a control valve accurately is an iterative process requiring manufacturer’s information and
knowledge of the piping system in which the valve is to be installed.

However, the procedure is fairly simple and straightforward. It becomes even easier if it is known
that the liquid will not flash or cavitate as it flows through the valve. For preliminary estimates of
control valve size it is usually OK to assume that the piping geometry factor is 1.

Calculate Control Valve Cv


Traditionally, control valves are sized using a special form of the orifice equation which gives the
valve orifice size as a “valve flow coefficient” or Cv.

The Cv is defined as the flow rate of water in US gallons per minute that can pass through a valve
with a pressure drop of 1 psi at a temperature of 60F.

The equation for calculating the Cv in US units is:


−−−−−−
Q SG
Cv = √
Fp ΔPef f

Where:

Cv = valve flow coefficient


Q = volumetric flow rate (USgpm)

Fp = piping geometry factor

S G = specific gravity of liquid relative to water

Δef f = effective pressure drop across valve (psi)


Effective
Blackmonk Engineering Pressure
About Us Calculators Contact Drop
Us Blog
The effective pressure drop across a liquid control valve depends on the nature of the liquid
flowing through the valve and the valve design.

If the pressures upstream, inside and downstream of the control valve are greater than the vapour
pressure of the liquid at the flowing temperature, the effective pressure drop is equal to the
actual pressure difference between the upstream and downstream sides of the valve. In this case,
the flow is said to be “sub-critical” and the fluid remains in the liquid phase throughout the
system.

In the vast majority of cases it is preferable to maintain sub-critical flow as it reduces valve
damage, improves controllability and requires simpler, less expensive valve designs.

However, if the liquid vapour pressure exceeds the system pressure inside or downstream of the
valve, vaporisation will occur and the flow will become “critical”. In this case, the effective
pressure drop across the valve will be limited by the valve design and the physical properties of
the liquid. When the flow is “critical”, the pressure downstream of the valve does not affect the
flow rate.

The flow is sub-critical if:

P1 − P2 < ΔPmax

For sub-critical flow:

ΔPef f = P1 − P2

Where:

2
ΔPmax = F (P 1 − F v P v )
L
−−−
Blackmonk Engineering About Us Calculators Contact Us Blog
FF = 0.96 − 0.28√
Pv

Pc

P1 = pressure upstream of valve


P2 = pressure downstream of valve
Δmax = maximum effective pressure drop across valve
FL = valve liquid pressure recovery factor
FF = liquid critical pressure ratio factor
Pv = liquid vapour pressure at flowing temperature
Pc = liquid critical pressure

For critical flow:

ΔPef f = ΔPmax

Valve Liquid Pressure Recovery Factor, FL


The valve liquid pressure recovery factor is the ratio of effective pressure drop to the pressure
difference between the upstream pressure and the vena contracta pressure.

The valve liquid pressure recovery factor is usually measured experimentally and is tabulated in
valve manufacturers’ catalogues.

Liquid Critical Pressure Ratio Factor, FF


The liquid critical pressure ratio factor is a means of estimating the pressure at the vena contracta
of the valve under critical flow conditions.

Piping Geometry Factor, Fp


The piping geometry factor is an allowance for the pressure drop associated with fittings that may
be connected directly upstream and/or downstream of the valve.

If no fittings are connected to the valve, the piping geometry factor is 1.


The piping geometry factor is often listed in valve manufacturers catalogues. Alternatively, it can
Blackmonk Engineeringbe calculated
About Us Calculators Contact Us Blog
using:

ΣK Cv
Fp = [1 + ( )]
2
890 d
valve

Where:

ΣK = sum of fittings factors


d valve = control valve body nominal size (inches)
Cv = Cv of selected control valve

Most commonly, the fittings connected to a control valve are upstream and downstream
reducers. In this case the sum of the fittings factors for the reducers is:

2
2
d
valve
ΣK = 1.5(1 − )
2
d
pipe

d pipe = piping nominal diameter (inches)

Note:
Determining the control valve Cv becomes an iterative process when the piping geometry factor
doesn’t equal 1.

1. Estimate the required Cv


2. Select an appropriate valve from the manufacturers’ tables
3. Calculate Fp using the actual Cv of the selected valve
4. Re-calculate the required Cv using the value of Fp determined in Step 3
5. Check that the re-calculated Cv is less than the actual Cv of the selected valve
6. If the re-calculated Cv is less than the actual Cv, the selected valve is adequately sized
7. If the re-calculated Cv is greater than the actual Cv of the selected valve, select another
valve with a larger Cv and return to Step 3
Control
Blackmonk Engineering Valve Sizing
About Us Calculators Contact Us Rules
Blog Of Thumb
There are many rules of thumb designed to help with control valve sizing. The following
guidance is taken from “Rules of Thumb For Chemical Engineers” by Carl Brannan and the
author’s personal notes.

1. Set the design flow as the greater of:


1.3 x normal flow rate
1.1 x maximum required flow rate
2. Set the control pressure drop to equal 50% - 60% of the frictional pressure loss of the
piping system
3. Limit the maximum flow rate : minimum flow rate turndown to 5:1 for linear trim valves and
10:1 for equal percentage trim valves
4. The valve should be able to control the required range of flow rates between 10% and 80%
of valve opening
5. Ideally select a valve that has a body size 1 pipe size smaller than the pipe in which it is to
be installed (e.g. select a 3” valve for a 4” pipe)
6. Never select a valve larger than the pipe in which it is to be installed

How To Size A Liquid Control Valve Example


The following example has been adapted from the Emerson Control Valve Handbook.

We need to size a valve in liquid propane duty. The required information is given below:

Design flow rate = 800 US gpm


Upstream pressure = 314.7 psia
Downstream pressure = 289.7 psia
Pressure drop across valve = 25 psi
Liquid temperature = 70F
Propane specific gravity = 0.5
Propane vapour pressure = 124.3 psia
Propane critical pressure = 616.3 psia
Pipe size = 4 inch
Calculation
Blackmonk Engineering About Us Calculators Contact Us Blog
Following the steps given at the start of this article:

1. Design flow rate = 800 US gpm


2. Allowable pressure drop across the valve = 25 psi
3. We will choose an Emerson 3” ES globe valve with linear trim as the preliminary selection.
From the valve table we can see that the actual Cv is 135 and FL is 0.89
![Valve Table]({static}/static/valve-table.png)
4. We will assume that 4” x 3” reducers will be used to install the selected 3” valve in the 4”
pipe. In this case the piping geometry factor is: ΣK = 1.5 (1 – (32 / 42))2 = 0.287 FP = [1 +
(0.287 / 890)(135 / 32)2]-0.5 = 0.96
5. Check if flow through the valve is sub-critical or critical: FF = 0.96 – 0.28 (124.3 / 616.3) =
0.83 DPmax = (0.89)2 (314.7 – 0.83 x 124.3) = 167.6 psi P1 – P2 = 314.7 – 289.7 = 25 psi
Therefore: P1 – P2 < DPmax so the flow is sub-critical
6. The effective pressure drop across the valve is P1 – P2 because the flow is sub-critical DPeff
=25 psi
7. Calculate the first estimate of Cv: Cv = (800 / 0.96)(0.5 / 25)0.5 = 117.9
8. The calculated required Cv of 117.9 is less than the actual Cv of the selected valve of 135 so
the valve is large enough
9. Check if the control valve range is OK: From the valve table, the selected valve will be about
75% open to give the required Cv of 117.9. This is within the acceptable control range of
10% to 80% of valve opening.
10. The selected 3” linear trim valve is correctly sized for the specified duty

Result
The selected valve is an Emerson 3” ES globe valve with linear trim and a maximum Cv of 135.

Blackmonk Engineering Calculator Result


The output from the Blackmonk Engineering Liquid Control Valve Calculator is attached below for
comparison. The values used in the example have been converted to metric units. As you can
see the calculated Cv is virtually identical to the hand calculation (118.2 compared to 117.9).
Blackmonk Engineering About Us Calculators Contact Us Blog

© 2021 Blackmonk Engineering · Powered by Pelican

You might also like