You are on page 1of 64

GI 70KV BIMA

OHL BONTO LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

10

11

12

13

14

15
16

17

18

19

20

21

22
SIGNAL LIST IEC 61850

:
:
:
:
:
: 255.255.252.0

OBJECT ID LOGICAL DEVICE


IEC 61850

LOGICAL NODE DATASET NAME


REPORT NAME TIP (IEC 104) Address
GI 70KV BIMA
OHL BONTO LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Distance Zone 1 Trip

2 Distance Zone 2 Trip

3 Distance Zone 3 Trip

4 Autoreclose In Progress

5 Autoreclose Lockout

6 Autoreclose Block

7 Autoreclose Success

8 Distance Carrier Receive

9 Distance Carrier Send

10 SOTF Operated

11 Distance Carrier Aided Trip

12 Power Swing Block

13 Distance Carrier Failure

14 STPAR Mode

15 SPAR Mode
16 TPAR Mode

17 Direct Transfer Trip Send

18 Direct Transfer Trip Receive

19 Autoreclose Close CB Command

20 Distance Pickup Phase R

21 Distance Pickup Phase S

22 Distance Pickup Phase T


SIGNAL LIST IEC 61850

: SIEMENS
: 7SA522 / Distance Protection
:
: F03_F210
: 172.16.129.121
: 255.255.252.0

OBJECT ID LOGICAL DEVICE


IEC 61850

LOGICAL NODE DATASET NAME


REPORT NAME TIP (IEC 104) Address
GI 70KV BIMA
OHL DOMPU LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Relay Trip General

2 Relay Pickup Phase R

3 Relay Pickup Phase S

4 Relay Pickup Phase T

5 Relay Pickup Phase N

6 OCR Time Delay Trip

7 OCR Instant Trip

8 Ground Fault Time Delay Trip

9 Ground Fault Instant Trip


SIGNAL LIST IEC 61850

: SIEMENS
: 7SJ80 / OCR, GFR Protection
:
: F03_F501
: 172.16.129.122
: 255.255.252.0

OBJECT ID LOGICAL DEVICE


IEC 61850

LOGICAL NODE DATASET NAME


REPORT NAME TIP (IEC 104) Address
GI 70KV BIMA
OHL DOMPU LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

10

11

12

13

14

15
16

17

18

19

20

21

22
SIGNAL LIST IEC 61850

:
:
:
:
:
: 255.255.252.0

OBJECT ID LOGICAL DEVICE


IEC 61850

LOGICAL NODE DATASET NAME


REPORT NAME TIP (IEC 104) Address
GI 70KV BIMA
OHL DOMPU LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Distance Zone 1 Trip

2 Distance Zone 2 Trip

3 Distance Zone 3 Trip

4 Autoreclose In Progress

5 Autoreclose Lockout

6 Autoreclose Block

7 Autoreclose Success

8 Distance Carrier Receive

9 Distance Carrier Send

10 SOTF Operated

11 Distance Carrier Aided Trip

12 Power Swing Block

13 Distance Carrier Failure

14 STPAR Mode

15 SPAR Mode
16 TPAR Mode

17 Direct Transfer Trip Send

18 Direct Transfer Trip Receive

19 Autoreclose Close CB Command

20 Distance Pickup Phase R

21 Distance Pickup Phase S

22 Distance Pickup Phase T


SIGNAL LIST IEC 61850

: SCHNEIDER
: MICOM P443 / Distance Protection
:
: F05_F210
: 172.16.129.141
: 255.255.252.0

OBJECT ID LOGICAL DEVICE

16-323E System

16-323F System

16-3240 System

16-3241 System

16-3242 System

16-3243 System

16-3244 System

16-3245 System

16-3246 System

16-3247 System

16-3248 System

16-3249 System

16-324A System

16-324B System

16-324C System
16-324D System

16-324E System

16-324F System
IEC 61850

LOGICAL NODE DATASET NAME

GOSGGIO2.ind1 Goose

GOSGGIO2.ind2 Goose

GOSGGIO2.ind3 Goose

GOSGGIO2.ind4 Goose

GOSGGIO2.ind5 Goose

GOSGGIO2.ind6 Goose

GOSGGIO2.ind7 Goose

GOSGGIO2.ind8 Goose

GOSGGIO2.ind9 Goose

GOSGGIO2.ind10 Goose

GOSGGIO2.ind11 Goose

GOSGGIO2.ind12 Goose

GOSGGIO2.ind13 Goose

GOSGGIO2.ind14 Goose

GOSGGIO2.ind15 Goose
GOSGGIO2.ind16 Goose

GOSGGIO2.ind17 Goose

GOSGGIO2.ind18 Goose
REPORT NAME TIP (IEC 104) Address

urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;


brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
urcbA01; urcbB01; urcbC01; urcbD01; brcbA01;
brcbB01; brcbC01; brcbD01
TYPE DATAPOINT

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS
TSS

TSS

TSS

TSS

TSS

TSS

TSS
GI 70KV BIMA
OHL DOMPU LINE 1

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Relay Trip General

2 Relay Pickup Phase R

3 Relay Pickup Phase S

4 Relay Pickup Phase T

5 Relay Pickup Phase N

6 OCR Time Delay Trip

7 OCR Instant Trip

8 Ground Fault Time Delay Trip

9 Ground Fault Instant Trip


SIGNAL LIST IEC 61850

: SIEMENS
: 7SJ80 / OCR, GFR Protection
:
: F05_F501
: 172.16.129.142
: 255.255.252.0

OBJECT ID LOGICAL DEVICE

C3-107 Protection

BF-5E Protection

C0-5E Protection

C1-5E Protection

C2-11 Protection

C3-108 Protection

C3-109 Protection

C3-10A Protection

C3-10B Protection
IEC 61850

LOGICAL NODE DATASET NAME

PTRC1/Tr PROT

PTRC2/Str.phsA PROT

PTRC2/Str.phsB PROT

PTRC2/Str.phsC PROT

PTRC2/Str.neut PROT

PTOC6/Op PROT

PTOC7/Op PROT

PTOC8/Op PROT

PTOC9/Op PROT
REPORT NAME TIP (IEC 104) Address

brcbA01; brcbB01

brcbA01; brcbB01

brcbA01; brcbB01

brcbA01; brcbB01

brcbA01; brcbB01 208

brcbA01; brcbB01

brcbA01; brcbB01

brcbA01; brcbB01

brcbA01; brcbB01
TYPE DATAPOINT

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS
GI 70KV BIMA
BUS COUPLER

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Q50 CB Position

2 Q21 DS Position

3 Q22 DS Position

4 Q50 CB Local/Remote

5 Q21 DS Local/Remote

6 Q22 DS Local/Remote

7 Dummy Breaker

8 Q21 DS Manual Position

9 Q22 DS Manual Position

10 CB Counter

11 AC CRP MCB Fail

12 Lockout 2 (Backup) Operated

13 Lockout 1 (Main) Operated

14 DS 1 Driving Fault

15 SF6 Low Gas Alarm (1st Stage)


16 Spring Charging

17 CB Driving Fault

18 SF6 Low Pressure Block (2nd Stage)

19 DS 2 Driving Fault

20 MK AC MCB Trip

21 Onload Transfer

22 MCB VT Bus 1 Fail

23 MCB VT Bus 2 Fail

24 Trip Circuit - 1 Failure

25 Trip Circuit - 2 Failure

26 Supply T1+/- Fail

27 Supply T2+/- Fail

28 Supply C+/- Fail

29 Supply G+/- Fail

30 Supply S+/- Fail

31 Overcurrent Relay Failure

32 Bay Local/Remote

33 Check Synchro On (S2525)

34 CB Heating Lighting Fail

35 Q50 CB Command

36 Q21 DS Command

37 Q22 DS Command

38 Dummy Breaker

39 Reset Master Trip


: SCHNEIDER
: MICOM C264 / Bay Control Unit
:
: BCU9
: 172.16.129.180
: 255.255.252.0

OBJECT ID LOGICAL DEVICE

69-44F CONTROL

69-450 CONTROL

69-451 CONTROL

69-456 CONTROL

69-457 CONTROL

69-458 CONTROL

69-453 CONTROL

16-34B8 CONTROL

16-34B9 CONTROL

CONTROL

16-34CD CONTROL

16-34CE CONTROL

16-34CF CONTROL

16-34BA CONTROL

16-34BD CONTROL
16-34BE CONTROL

16-34BF CONTROL

16-34C0 CONTROL

16-34C1 CONTROL

16-34C2 CONTROL

16-34C3 CONTROL

16-34C4 CONTROL

16-34C5 CONTROL

16-34D0 CONTROL

16-34D1 CONTROL

16-34DA CONTROL

16-34DB CONTROL

16-34DC CONTROL

16-34DD CONTROL

16-34DE CONTROL

16-34D2 CONTROL

69-459 CONTROL

69-45B CONTROL

16-34BC CONTROL

69-44F CONTROL

69-450 CONTROL

69-451 CONTROL

69-453 CONTROL

CONTROL
SIGNAL LIST IEC 61850

LOGICAL NODE

CSWI1|ST|Pos

CSWI2|ST|Pos

CSWI3|ST|Pos

CSWI1|ST|Ind1

CSWI2|ST|Ind1

CSWI3|ST|Ind1

CSWI4|ST|Pos

CSWI2|ST|Ind2

CSWI3|ST|Ind2

GGIO5|ST|Cnt1

GGIO6|ST|Ind1

GGIO6|ST|Ind2

GGIO6|ST|Ind3

GGIO5|ST|Ind1

GGIO5|ST|Ind4
GGIO5|ST|Ind5

GGIO5|ST|Ind6

GGIO5|ST|Ind7

GGIO5|ST|Ind8

GGIO5|ST|Ind9

GGIO5|ST|Ind10

GGIO5|ST|Ind11

GGIO5|ST|Ind12

GGIO6|ST|Ind4

GGIO6|ST|Ind5

GGIO6|ST|Ind14

GGIO6|ST|Ind15

GGIO6|ST|Ind16

GGIO6|ST|Ind17

GGIO6|ST|Ind18

GGIO6|ST|Ind6

GGIO7|ST|Ind1

GGIO7|ST|Ind4

GGIO5|ST|Ind3

CSWI1|CO|Pos

CSWI2|CO|Pos

CSWI3|CO|Pos

CSWI4|CO|Pos

GGIO3|CO|SPCSO3
SIGNAL LIST IEC 61850

DATASET

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs
LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

LLN0BRptStDs

GGIO3URptStDs
REPORT ID

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST
BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/LLN0$BR$brcbST

BCU9CONTROL/GGIO3$RP$urcbST
Data in CID Reload to Database

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Not Success

Available Success

Available Success

Available Success

Available Success

Available Success
Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Success

Available Not Success


Remarks
needs to be moved to LLN0 dataset LLN0BRptStDs (?)
104 Address

1009

1010

1011
GI 70KV BIMA
BUS COUPLER

Manufacturer
Type
Ordercode
IED Name
IP Address
Subnet Mask

NO. SIGNAL NAME

1 Relay Trip General

2 OCR Pickup Phase R

3 OCR Pickup Phase S

4 OCR Pickup Phase T

5 OCR Pickup Phase N

6 OCR TRIP PHASE A

7 OCR TRIP PHASE B

8 OCR TRIP PHASE C

9 OCR Time Delay Trip

10 OCR Instant Trip

11 Ground Fault Time Delay Trip

12 Ground Fault Instant Trip

13 Check Synchro In Progress


SIGNAL LIST IEC 61850

: SCHNEIDER
: MICOM P143 / OCR, GFR Protection
:
: F09_F501
: 172.16.129.182
: 255.255.252.0

OBJECT ID LOGICAL DEVICE

16-327E System

16-372F System

16-3280 System

16-3281 System

16-3282 System

16-3283 System
IEC 61850

LOGICAL NODE DATASET NAME

LedGGIO1.ind1 Protection

LedGGIO1.ind2 Protection

LedGGIO1.ind3 Protection

LedGGIO1.ind4 Protection

LedGGIO1.ind5 Protection

LedGGIO1.ind6 Protection
REPORT NAME TIP (IEC 104) Address

urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;


brcbF01; brcbG01; brcbH01
urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;
brcbF01; brcbG01; brcbH01
urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;
brcbF01; brcbG01; brcbH01

urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;


brcbF01; brcbG01; brcbH01
urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;
brcbF01; brcbG01; brcbH01
urcbE01; urcbF01; urcbG01; urcbH01;brcbE01;
brcbF01; brcbG01; brcbH01
TYPE DATAPOINT

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS

TSS