RTHD

Job Information
Job01

Tag CRTHD-3 Compressor configuration E3 Compressor


Quantity 1 Evaporator configuration G2 Evaporator
Condenser configuration G1 Condenser
TOPSS version number 259

Unit Information
Refrigeration capacity 1434 kW Cooling efficiency 0.178 kW/kW
AHRI NPLV.IP 0.108 kW/kW Refrigerant charge (HFC-134a) 318 kg
Shipping weight 7917 kg Operating weight 8761 kg
Full Load Sound Pressure-AHRI 83 dBA Acoustic Insulation
Condition
Pressure vessel code
Refrigeration isolation No refrigerant isolation valves
valves
Oil cooler Without oil cooler

Operating weights include refrigerant, oil, and water charges.


Sound pressure measured in accordance with AHRI Standard 575-94.

Evaporator Information
Leaving fluid evap 7.00 C Flow evap 68.40 L/s
Entering fluid evap 12.00 C Fluid pressure drop evap 7693.97 mm H2O
Minimum flow evap 25.93 L/s Fouling factor evap 0.017610 m2-deg C/kW
Number of evaporator passes 4 pass Fluid freeze point evap 0.00 C
Evap fluid type Water Fluid concentration evap

Condenser Information
Entering fluid cond 32.00 C Flow cond 79.09 L/s
Leaving fluid cond 37.00 C Fluid pressure drop cond 5713.41 mm H2O
Number of cond passes 2 pass condenser Fouling factor cond 0.044025 m2-deg C/kW
Cond fluid type Water Fluid concentration cond
Condenser tube type Enhanced fin - copper Maximum flow cond 123.7 L/s
Pressure drop at min flow cond Pressure drop at max flow cond 127 kPa
Minimum flow cond

Electrical Information
Unit voltage 380. Volt 3 phase Unit hertz 50. Hertz
Total power 255.4 kW Starter type AdaptiR-2
Minimum circuit ampacity 535.69 A Maximum overcurrent protection 800.00 A
Starter expected inrush 428.55 A Motor locked rotor amps 2303.00 A
Run load amps/chiller input amps 428.55 A AFD output amps 467.86 A

2023/5/9 TOPSS version number 259


Data generation date 9/5/2023 Page 1 of 2
RTHD
Job Information
Job01

Tag CRTHD-3 Compressor configuration E3 Compressor


Quantity 1 Evaporator configuration G2 Evaporator
Condenser configuration G1 Condenser
TOPSS version number 259

This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.

2023/5/7 TOPSS version number 259


Data generation date 9/5/2023 Page 2 of 2