ROUND1 - PLAZA BONITA

BUILDING CODE INFORMATION TENANT IMPROVEMENT PARADIGM DESIGN


ARCHITECTS | ENGINEERS
GOVERNING CODES
BUILDING CODE 2022 California Building Code
EXISTING BUILDING CODE 2022 California Existing Building Code
ACCESSIBILITY 2010 Americans with Disabilities Act Standards
ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
ENERGY CONSERVATION CODE 2022 California Building Energy Efficiency Standards
2022 California Green Building Standards Code
Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
MECHANICAL CODE 2022 California Mechanical Code
ELECTRICAL CODE 2022 California Electrical Code
PLUMBING CODE 2022 California Plumbing Code
FIRE CODE 2022 California Fire Code
FIRE PROTECTION 2022 California Fire Sprinkler Code
ELEVATOR CODE 2010 International Elevator Rules

PROJECT SUMMARY:
TENANT FIT OUT OF 58,213 SF WITHIN WESTFIELD PLAZA BONITA SHOPPING CENTER WHICH WILL INCLUDE BOWLING, REDEMPTION ARCADE, BILLIARDS,
PARTY ROOMS, A SNACK BAR AND BAR, AND OTHER SUPPORT AREAS.

CODE ANALYSIS:
OCCUPANCY CLASSIFICATION(S): A-2, A-3
DESCRIPTION OF USE: ASSEMBLY USE
TYPE OF CONSTRUCTION: II-B
SPRINKLERS: YES, FULLY - SPRINKLERED
STORIES: 2 - EXISTING
HEIGHT: 40'+/- EXISTING
FLOOR AREA: 58,213 SF
OCCUPANT LOAD: 1520
CBC SECTION 402.4.1.1 COVERED AND OPEN MALL BUILDINGS:
PROJECT
THE BUILDING AREA OF ANY COVERED MALL OR OPEN MALL BUILDING SHALL NOT BE LIMITED PROVIDED THAT THE COVERED MALL OR
OPEN MALL BUILDING DOES NOT EXCEED THREE FLOOR LEVELS AT ANY POINT NOR THREE STORIES ABOVE GRADE PLANE, AND IS OF TYPE I,II,III,
OR IV CONSTRUCTION
CBC SECTION 402.4.1.2 ANCHOR BUILDINGS ROUND1 -
THE BUILDING AREA AND BUILDING HEIGHT OF ANY ANCHOR BUILDING SHALL BE BASED ON THE TYPE OF CONSTRUCTION AS REQUIRED
BY SECTION 503 AS MODIFIED BY SECTIONS 504 AND 506.
EXCEPTION: THE BUILDING AREA OF ANY ANCHOR BUILDING SHALL NOT BE LIMITED PROVIDED THAT THE ANCHOR BUILDING IS NOT
PLAZA BONITA
MORE THAN THREE STORIES ABOVE GRADE PLANE, AND IS OF TYPE I,II,III OR IV CONSTRUCTION.

ASSESSOR PARCEL NUMBERS:


564 471 07 - (6) TENANT SPACES
564 471 08 - FORMER INCREDIBLE JOHNS

3030 PLAZA BONITA RD, SUITE 1025 NATIONAL CITY, CA 91950


TENANT
IMPROVEMENT
PROJECT DIRECTORY SHEET INDEX

3030 PLAZA BONITA RD, SUITE


■ # X-X-XX
PROJECT ADDRESS ARCHITECT MOST RECENT ISSUE DATE
1025
NATIONAL CITY, CA 91950
PARADIGM DESIGN MOST RECENT REVISION NUMBER
3030 PLAZA BONITA RD, SUITE 1025
NATIONAL CITY, CA 91950 415 LEONARD STREET NW, SUITE 200 FILLED IN SQUARE INDICATES DRAWING
INCLUDED WITH THIS SET CLIENT
GRAND RAPIDS, MI 49504

PHONE: 616-785-5589 ■ P-401 RESTROOM ENLARGED PLAN ■ 07-21-23 E.3 ELECTRICAL LOWER LEVEL ROUND1
CONTACT: KIM VANDENBERG
EMAIL: KVANDENBERG@PARADIGMAE.COM
M1002 HOOD INFORMATION ■ P-402 KITCHEN ENLARGED PLAN ■ 07-21-23 EL.1 ELECTRICAL LAYOUT ENTERTAINMENT
■ P-501 PLUMBING DETAILS ■ 07-21-23 P-1 PLUMBING LAYOUT
GENERAL ■ P-601 PLUMBING SANITARY RISER DIAGRAM ■ 07-21-23 P.1 PLUMBING SCHEDULE
■ 07-21-23 G-001 COVER SHEET ■ P-602 PLUMBING DOMESTIC WATER RISER DIAGRAM ■ 07-21-23 P.2 PLUMBING LOWER LEVEL
CLIENT STRUCTURAL ENGINEER ■ 07-21-23 G-002 RESPONSIBILITY MATRIX ■ P-603 PLUMBING COMPLIANCE FORMS ■ 07-21-23 P.3 PLUMBING LOWER LEVEL
ROUND1 ENTERTAINMENT CARUSO TURLEY SCOTT STRUCTURAL ■ 07-21-23 G-003 CODE SUMMARY
3070 SATURN ST. STE. 200 ENGINEERS
BREA, CA 92821
■ 07-21-23 G-101 EGRESS PLAN MECHANICAL AV AND COMMUNICATION (RESOURCE NOT IN CONTRACT)
1215 W. RIO SALADO PKWY SUITE 200
TEMPE, AZ 85281 M-101 MECHANICAL FIRST FLOOR PLAN 'A' ■ 07-21-23 AV-102 Video Plan-R1 Plaza Bonita
PHONE: 714-924-7826 PHONE: 480-774-1705
CONTACT: STEVEN TAKEUCHI CONTACT: RICHARD DAHLMANN
ARCHITECTURAL DEMOLITION M-102 MECHANICAL FIRST FLOOR PLAN 'B' ■ 07-21-23 AV-103 Lighting Plan-R1 Plaza Bonita
EMAIL: TAKEUCHI@ROUND1USA.COM EMAIL: RDAHLMANN@CTSAZ.COM ■ 07-21-23 AD101 DEMOLITION PLAN OVERALL M-103 MECHANICAL FIRST FLOOR PLAN 'C' ■ 07-21-23 AV-104 AV Rack Detail-R1 Plaza Bonita
■ 07-21-23 AD201 DEMOLITION ELEVATIONS M-104 MECHANICAL FIRST FLOOR PLAN 'D' ■ 07-21-23 AV-E101 Power Plan-R1 Plaza Bonita
M-105 MECHANICAL ROOF PLAN ■ 07-21-23 AV-E102 Lighting Power Plan - R1 Plaza Bonita 3070 SATURN ST. STE. 200
ARCHITECTURAL SITE M-501 MECHANICAL DETAILS BREA, CA 92821
MECH/ELEC/PLUMB ENG.
■ 07-21-23 AS101 SITE PLAN M-601 MECHANICAL SCHEDULES
RHOADES ENGINEERING M-602 MECHANICAL TITLE 24 FORMS
1751 BARLOW ST
TRAVERSE CITY, MI 49686 ARCHITECTURAL M-603 MECHANICAL TITLE 24 FORMS CONT.
PHONE: 231-947-1707
■ 07-21-23 A-101 KEYNOTE PLAN M-604 MECHANICAL TITLE 24 FORMS CONT.
CONTACT: PHILIP JAQUISH, P.E. ■ 07-21-23 A-102 FLOOR PLAN A M-605 MECHANICAL TITLE 24 FORMS CONT.
EMAIL: PJAQUISH@RHOADESENGINEERING.COM
■ 07-21-23 A-103 FLOOR PLAN B M-606 MECHANICAL TITLE 24 FORMS CONT.
■ 07-21-23 A-104 FLOOR PLAN C
■ 07-21-23 A-105 FLOOR PLAN D ELECTRICAL GENERAL INFORMATION
■ 07-21-23 A-161 REFLECTED CEILING PLAN 07-21-23 E-001 ELECTRICAL GENERAL INFORMATION
■ 07-21-23 A-162 REFLECTED CEILING PLAN AND DETAILS 05-18-23 ED001 ELECTRICAL GENERAL INFORMATION - DEMOLITION
■ 07-21-23 A-191 ARCHITECTURAL ROOF PLAN
■ 07-21-23 A-201 EXTERIOR ELEVATIONS ELECTRICAL DEMOLITION
■ 07-21-23 A-202 INTERIOR ELEVATIONS 05-18-23 ED101 ELECTRICAL DEMOLITION FIRST FLOOR PLAN
■ 07-21-23 A-203 INTERIOR ELEVATIONS
■ 07-21-23 A-204 INTERIOR ELEVATIONS ELECTRICAL LIGHTING
■ 07-21-23 A-205 INTERIOR ELEVATIONS 07-21-23 EL101 ELECTRICAL LIGHTING FIRST FLOOR PLAN 'A'
■ 07-21-23 A-301 BUILDING SECTIONS 07-21-23 EL102 ELECTRICAL LIGHTING FIRST FLOOR PLAN 'B'
■ 07-21-23 A-302 ENLARGED SECTION DETAILS 07-21-23 EL103 ELECTRICAL LIGHTING FIRST FLOOR PLAN 'C'
■ 07-21-23 A-331 STAIR SECTIONS & DETAILS 07-21-23 EL104 ELECTRICAL LIGHTING FIRST FLOOR PLAN 'D'
■ 07-21-23 A-401 ENLARGED TOILET ROOM PLANS AND ELEVATIONS
■ 07-21-23 A-402 ENLARGED FLOOR PLANS ELECTRICAL POWER RELEASE DATE
■ 07-21-23 A-403 ENLARGED FLOOR PLANS 07-21-23 EP101 ELECTRICAL POWER FIRST FLOOR PLAN 'A' DATE DESCRIPTION
■ 07-21-23 A-501 INTERIOR DETAILS 07-21-23 EP102 ELECTRICAL POWER FIRST FLOOR PLAN 'B' 07-06-23 FOR PERMITS
■ 07-21-23 A-502 INTERIOR DETAILS 07-21-23 EP103 ELECTRICAL POWER FIRST FLOOR PLAN 'C' 07-21-23 FOR BIDS
■ 07-21-23 A-601 DOOR SCHEDULE AND DOOR DETAILS 07-21-23 EP104 ELECTRICAL POWER FIRST FLOOR PLAN 'D'
■ 07-21-23 A-602 FINISH KEY AND ROOM FINISH SCHEDULE 07-21-23 EP105 ELECTRICAL ROOF PLAN
■ 07-21-23 A-701 FLOOR FINISH PLAN
■ 07-21-23 A-702 WALL FINISH PLAN ELECTRICAL
07-21-23 E-401 ELECTRICAL ENLARGED PLAN
STRUCTURAL 07-21-23 E-501 ELECTRICAL ONE-LINE DIAGRAM
■ 07-21-23 S-100 GENERAL STRUCTURAL NOTES 05-18-23 E-502 ELECTRICAL PANEL & CONNECTION SCHEDULES
07-21-23 E-601 LIGHTING CONTROL SCHEDULES AND DETAILS
STRUCTURAL 07-21-23 E-602 LIGHTING FIXTURE SCHEDULE
■ 07-21-23 S-101 TYPICAL DETAILS 07-21-23 E-603 ELECTRICAL DETAILS
■ 07-21-23 S-201 FOUNDATION AND FLOOR FRAMING 07-21-23 E-604 TITLE 24 DOCUMENTATION
■ 07-21-23 S-202 CEILING AND SOFFIT FRAMING 07-21-23 E-605 TITLE 24 DOCUMENTATION
■ 07-21-23 S-301 FOUNDATION DETAILS 07-21-23 E-606 TITLE 24 DOCUMENTATION
■ 07-21-23 S-302 SUSPENDED FRAMING DETAILS P 06-22-23 ED501 DEMOLITION ONE-LINE DIAGRAM
■ 07-21-23 S-303 FLOOR INFILL DETAILS R1

FOOD SERVICE EQUIPMENT (RESOURCE NOT IN CONTRACT) PROJECT


FIRE PROTECTION
■ F-101 FIRE PROTECTION PLAN ■ 07-21-23 E.1 ELECTRICAL SCHEDULE
■ 07-21-23 E.2 ELECTRICAL LOWER LEVEL 2112128GR
PLUMBING DEMOLITION
□ PD101 PLUMBING DEMOLITION FIRST FLOOR PLAN SHEET
7/25/2023 4:02:55 PM

COVER SHEET
PLUMBING
■ P-101 OVERALL SANITARY PLUMBING PLAN
■ P-102 OVERALL DOMESTIC PLUMBING PLAN
G-001
ARCHITECTURAL ABBREVIATIONS
CONSTRUCTION WASTE REDUCTION, A M
ADJ ADJUSTABLE MFR MANUFACTURER
DISPOSAL & RECYCLING ADD ADDENDUM MATL MATERIAL ARCHITECTURAL SYMBOLS
AFF ABOVE FINISHED FLOOR MAX MAXIMUM RESPONSIBILITY SCHEDULE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE AND SAN FRANSISCO ORDINANCE REQUIREMENTS ALUM ALUMINUM MECH MECHANICAL
APPROX APPROXIMATE MEMB MEMBRANE # VIEW TITLE DETAIL / SECTION TITLE
SUPPLY INSTALL NOTES
CONSTRUCTION WASTE MANAGEMENT MIN MINIMUM SHEET SCALE: 1/8" = 1'-0"

Consultant (S&G)

Consultant (S&G)
SAN FRANSISCO ORDINANCE NO. 144-21 100% OF MIXED DEBRIS MUST BE TRANSPORTED BY A REGISTERED B MISC MISCELLANEOUS

Food Service

Food Service
Round 1

Round 1
Vendor

Vendor
HAULER TO A REGISTERED FACILITY AND BE PROCESSED FOR RECYCLING, IN COMPLIANCE WITH THE SAN MLDG MOLDING
BD BOARD ITEM NO. ITEM PARADIGM DESIGN

GC

GC
FRANSISCO CONSTRUCTION & DEMOLITION DEBRIS ORDINANCE. MO MASONRY OPENING
BF
BLK
BARRIER FREE
BLOCK N
VIEW TITLE PLAN TITLE ARCHITECTS | ENGINEERS
RECYCLING BY OCCUPANTS N SCALE: 1/8" = 1'-0"
BLKG BLOCKING
PROVIDE ADEQUATE SPACE AND EQUAL ACCESS FOR STORAGE, COLLECTION AND LOADING OF BLDG BUILDING NA NOT APPLICABLE
COMPOSTABLE, RECYCLABLE AND LANDFILL MATERIALS. BO BOTTOM OF NIC NOT IN CONTRACT
BP BUMP POST Owner will pay permit. G.C. to sign
NTS NOT TO SCALE .
5.504.3. POLLUTANT CONTROL. DURING CONSTRUCTION, ENDS OF DUCT OPENINGS ARE TO BE SEALED, AND BRG BEARING DET # . # . ELEVATION TAG 1 Building/Health Permit ◼ ◼ for/pick up permit from building
MECHANICAL EQUIPMENT IS TO BE COVERED. BULL BULLETIN O # department.
SHEET
Grand Rapids | Phoenix | Traverse City
5.504.4. POLLUTANT CONTROL. VOC's MUST COMPLY WITH THE LIMITATIONS LISTED IN SECTION 5.504.4 AND C OC ON CENTER SIM
2 GC's Construction Permits ◼
www.paradigmae.com
TABLES 4.504.1., 5.504.4.1., 5.504.4.3, AND 5.504.5 FOR: ADHESIVES, SEALANTS, PANTS AND COATINGS, CARPET OPNG OPENING SIM 21
AND COMPOSITION WOOD PRODUCTS. CAB CABINET OPP OPPOSITE SHEET 1 3 Fire Suppression / Sprinkler System / Fire Alarm ◼
CLG CEILING ORD OVERFLOW ROOF DRAIN 0 ELEVATION TAG 4 Signage Permit ◼
CL CENTERLINE DET #
5.504.4 FINISH MATERIAL POLLUTANT CONTROL. FINISH MATERIALS SHALL COMPLY WITH SECTIONS 5.504.4,1 OH OVERHEAD
CT CERAMIC TILE 13
THROUGH 5.504,4.6. 41 SIM MILLWORK COUNTERS
CLR CLEAR P SIM

5.504.4.1 ADHESIVES, SEALANTS, CAULKS. ADHESIVES AND SEALANTS USED ON THE PROJECT SHALL MEET COL COLUMN DET #
CONC CONCRETE PR PAIR . . 1 Bowling Guest Counter ◼ ◼
THE REQUIREMENTS OF THE FOLLOWING STANDARDS. . # . . # .
CONT CONTINUOUS PEMB PRE-ENGINEERED METAL BUILDING BUILDING SECTION
1. ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE PRIMERS, SEALANTS, SEALANT PRIMERS AND PART PARTITION # # 2 Game Counter ◼ ◼
CAULKS SHALL COMPLY WITH LOCAL OR REGIONAL AIR POLLUTION CONTROL OR AIR QUALITY MANAGEMENT CJ CONTROL JOINT SHEET
CORR CORRIDOR PLYWD PLYWOOD 3 Redemption Counter & Display Cases ◼ ◼
DISTRICT RULES WHERE APPLICABLE OR SCAQMD RULE 1168 VOC LIMITS, AS SHOWN IN TABLES 5.504.4.1 AND PLAM PLASTIC LAMINATE
5.504.4.2. CMU CONCRETE MASONRY UNIT DET #
CSMU CONCRETE SILICATE MASONRY UNIT PROP PROPERTY
.
4 Snack Bar Counter ◼ ◼
2. AEROSOL ADHESIVES AND SMALLER UNIT SIZES OF ADHESIVES AND SEALANT OR CAULKING COMPOUNDS PL PLATE . # .
(IN UNITS OF PRODUCT, LESS PACKAGING, WHICH DO NOT WEIGH MORE THAN ONE POUND AND DO NOT
D PVC POLYVINYL CHLORIDE #
WALL SECTION 5 Bar Counter ◼ ◼
CONSIST OF MORE THAN 16 FLUID OUNCES) SHALL COMPLY WITH STATEWIDE VOC STANDARDS AND OTHER SHEET
REQUIREMENTS, INCLUDING
PT POINT 6 Bar Display Shelves ◼ ◼
DBL DOUBLE PVT PAVEMENT
PROHIBITIONS ON USE OF CERTAIN TOXIC COMPOUNDS, OF CALIFORNIA CODE OF REGULATIONS, TITLE 17, DEMO DEMOLITION DET #
Q
COMMENCING WITH SECTION 94507. DET DETAIL . # ..
EQUIPMENT
DETAIL SECTION
DIA DIAMETER #
5.504.4.3 PAINTS AND COATINGS. ARCHITECTURAL PAINTS AND COATINGS SHALL COMPLY WITH TABLE DIM DIMENSION QTY QUANTITY SHEET FOOD SERVICE EQUIPMENT
5,504.4.3 UNLESS MORE STRINGENT LOCAL LIMITS APPLY. DIST DISTANCE 1 Bar Equipment ◼ ◼ ①
R DET #
DN DOWN
5.504.4.3.1 AEROSOL PAINTS AND COATINGS. AEROSOL PAINTS AND DWG DRAWING . # ..
2 Roof Mounted Compressors ◼ ◼ ②
R RISER ENLARGED PLAN / DETAIL CALLOUT PROJECT
COATINGS SHALL MEET THE PRODUCT- WEIGHTED MIR LIMITS FOR ROC IN SECTION 94522(A)(3) AND OTHER RAD RADIUS # 3 Snack Bar & Kitchen Equipment ◼ ◼ ①
REQUIREMENTS, INCLUDING PROHIBITIONS ON USE OF CERTAIN TOXIC COMPOUNDS AND OZONE DEPLETING E REF REFERENCE SHEET

SUBSTANCES (CCR, TITLE 17, SECTION 94520, ET SEQ,).
EA
EIFS
EACH
EXTERIOR INSULATING FINISH SYSTEM
REFR
REINF
REFRIGERATOR
REINFORCE # # COLUMN LABEL (NEW)
4 Exhaust Hoods & Fans
OTHER EQUIPMENT
◼ ◼
ROUND1 -
CARPET: ALL CARPET MUST MEET ONE OF THE FOLLOWING:
1. CARPET AND RUG INSTITUTE GREEN LABEL PLUS PROGRAM
2. CALIFORNIA DEPARTMENT OF PUBLIC HEALTH STANDARD PRACTICE FOR THE TESTING OF VOCS
ELEC
EL
ELECTRICAL
ELEVATION (GRADE)
REQD
RET
REV
REQUIRED
RETURN
REVISION # # COLUMN LABEL (EXISTING)
1
Bowling Equipment - Pin Setters, Lanes, Bowlers Seating,
Framing, and Deck for Raised Bowlers Seating Area. Sound A A ⑤ PLAZA BONITA
(SPECIFICATION 01350) ENCL ENCLOSURE Isolation Pads Under Lane Framing and Pin Setters
EQ EQUAL RA RETURN AIR
3. NSF/ANSI 140 AT THE GOLD LEVEL RD ROOF DRAIN 2 Sound/Draftstopping Insulation @ Bowling Lane Framing ◼ ◼
4. SCIENTIFIC CERTIFICATIONS SYSTEMS SUSTAINABLE CHOICE OR EQUIP EQUIPMENT # # COLUMN LABEL (FUTURE)
EPS EXPANDED POLYSTYRENE RM ROOM
5. CALIFORNIA COLLABORATIVE FOR HIGH PERFORMANCE SCHOOLS EQ 2.3 AND LISTED IN THE CHPS HIGH RO ROUGH OPENING 3 Bowlers Scoring A A ⑤
PERFORMANCE PRODUCT DATABSE. EXH EXHAUST
EXIST EXISTING MATCH LINE - SEE SHEET XXXX MATCH LINE 4 Masking Units, Filler Panels A A
AND CARPET CUSHION MUST MEET CARPET AND RUG INSTITUTE GREEN LABEL S
AND INDOOR CARPET ADHESIVE AND CARPET PAD ADHESIVE MUST NOT EXCEED 50 G.L VOC CONTENT. EXT EXTERIOR
EJ EXPANSION JOINT 5 Mechanic's Equipment ◼ ◼
SECT SECTION TRANSITION IDENTIFICATION
5.504.4.3.2 VERIFICATION. VERIFICATION OF COMPLIANCE WITH THIS SECTION SHALL BE PROVIDED AT THE EWC ELECTRIC WATER COOLER SHT SHEET 6 New Elec. Panels/Light Fixtures ◼ ◼
REQUEST OF THE ENFORCING AGENCY. SIM SIMILAR LEVEL NAME
F SPECS SPECIFICATIONS LEVEL / ELEVATION INDICATOR 7 Audio Equip. PA System & Speakers (including Karaoke Rooms) B B
X' - X"
5.504.4.5 COMPOSITE WOOD PRODUCTS. HARDWOOD PLYWOOD, PARTICLEBOARD AND MEDIUM DENSITY FIN FINISH STD STANDARD 8 Cosmic & Equipment E E ①
FIBERBOARD COMPOSITE WOOD PRODUCTS USED ON THE INTERIOR OR EXTERIOR OF THE BUILDING SHALL FF FINISH FLOOR STL STEEL X' - X" POINT ELEVATION 9 Video Source Equipment (Satellite or Cable Receivers) ◼ B
MEET THE REQUIREMENTS FOR FORMALDEHYDE AS SPECIFIED IN TABLE 5.504.4.5. FE FIRE EXTINGUISHER STOR STORAGE
(ELEVATION / SECTION)
SS STAINLESS STEEL
FEC FIRE EXTINGUISHER CABINET 10 Lane Video Projectors ◼ B B ④
5.504.4.5.3 DOCUMENTATION. VERIFICATION OF COMPLIANCE WITH THIS SECTION SHALL BE PROVIDED AS FHC FIRE HOSE CABINET ST STREET "
REQUESTED BY THE ENFORCING AGENCY. DOCUMENTATION SHALL INCLUDE AT LEAST ONE OF THE FLR FLOOR STRUCT STRUCTURAL X' - X POINT ELEVATION (PLAN) 11 Lane Operable Screens ◼ A A
FOLLOWING: FD FLOOR DRAIN SYS SYSTEM
1. PRODUCT CERTIFICATIONS AND SPECIFICATIONS.
N X' - X" 12 Redemption Store Display Gondola Unit ◼ ◼
FS FLOOR SINK E X' - X"
2. CHAIN OF CUSTODY CERTIFICATIONS. FTG FOOTING T SPOT COORDINATE
3. PRODUCT LABELED AND INVOICED AS MEETING THE COMPOSITE WOOD PRODUCTS REGULATION (SEE FDN FOUNDATION FURNITURE/FIXTURES
TEL TELEPHONE
CCR, TITLE 17, SECTION 93120, ET SEQ.). FP FIRE PROTECTION ROOM
TEMP TEMPORARY
4. EXTERIOR GRADE PRODUCTS MARKED AS MEETING THE PS-1 OR PS-2 STANDARDS OF THE ENGINEERED
WOOD ASSOCIATION, THE AUSTRALIAN AS/NZS 2269 OR EUROPEAN 636 3S STANDARDS.
FRT
FV
FIRE RETARDANT TREATED
FIELD VERIFY
THRU THROUGH
NAME
###
ROOM NAME TAG 1 Billiard (Billiard Tables) A A
TENANT
THK THICK, THICKNESS 2 Bar/Seating Area (Seating, Furniture) ◼ ◼
5. OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY. T TREAD
# 3 Billiards (Stools & Side Tables) ◼ ◼
IMPROVEMENT
TO TOP OF WALL CONSTRUCTION TAG
5.504.5.3. POLLUTANT CONTROL. MECHANICALLY VENTILATED BUILDINGS SHALL PROVIDE REGULARLY G
TOC TOP OF CONCRETE 4 Karaoke Rooms (Soft Furniture) ◼ ◼
OCCUPIED AREAS WITH AIR FILTRATION MEDIA FOR OUTSIDE AND RETURN AIR THAT PROVIDES AT LEAST A TOF TOP OF FOOTING
GA GAUGE # DOOR TAG
MINIMUM EFFICIENCY REPORTING VALUE (MERV) OF 8. MERV8 FILTERS S HALL BE INSTALLED PRIOR TO TOM TOP OF MASONRY 5 Office Area (Desk, Chairs, Cabinets) ◼ ◼
GALV GALVANIZED
OCCUPANCY. TOP TOP OF PRECAST
GC GENERAL CONTRACTOR
GEN GENERAL TOS TOP OF STEEL T TEMPERED GLASS SIGNAGE 3030 PLAZA BONITA RD, SUITE
5.508.1 OZONE DEPLETION AND GLOBAL WARMING REDUCTIONS. INSTALLATIONS OF HVAC, REFRIGERATION TOW TOP OF WALL
GPRFS GEOFOAM PERMANENT RISER 1025
AND FIRE SUPPRESSION EQUIPMENT SHALL COMPLY WITH SECTIONS 5.508.1.1 AND 5.508.1.2. TYP TYPICAL
FORMING SYSTEM # GLAZING TAG 1 Side Wall Graphics (1) D D
GYP GYPSUM BOARD NATIONAL CITY, CA 91950
5.508.1.1 CFC'S. INSTALL HVAC AND REFRIGERATION EQUIPMENT THAT DOES NOT CONTAIN CFC'S. U TYPE 2 Exterior Wall Signage D D ⑧
H A 0'-0" CEILING TYPE & ELEVATION
5.508.1.2 HALONS. INSTALL FIRE SUPPRESSION EQUIPMENT THAT DOES NOT CONTAIN HALONS. UNO UNLESS NOTED OTHERWISE 3 Interior Signage D D ⑧ CLIENT
HD HUB DRAIN ELEVATION A.F.F.
4 Snack Bar Menu Screens B B
RESILIENT FLOORING SYSTEMS: HT HEIGHT
V # TOILET ACCESSORY TAG
5 H.C. Accessibility Signage (Restrooms) D D
ROUND1
HORIZ HORIZONTAL VERT VERTICAL TYPE
FOR 80% OF FLOOR AREA RECEIVING RESILIENT FLOORING, INSTALL RESILIENT FLOORING COMPLYING WITH: HVAC HEATING-VENTILATION-AIR CONDITIONING VEST VESTIBULE AA ## FINISH / MATERIAL TAG ENTERTAINMENT
1. CERTIFIED UNDER THE RESILIENT FLOOR COVERING INSTITUTE (RFCI) FLOORSCORE PROGRAM HSS HOLLOW STEEL SECTION VCT VINYL COMPOSITION TILE NUMBER
MISCELLANEOUS ITEMS
2. COMPLIANT WITH VOC-EMISSION LIMITS AND TESTING REQUIREMENTS OF CALIFORNIA DEPARTMENT VT VINYL TILE
OF PUBLIC HEALTH 2010 STANDARD METHOD FOR THE TESTING AND EVALUATION CHAMBER V.1.1 I # REVISION TAG 1 TV Support Brackets & Poles B B ③
3. COMPLIANT WITH THE COLLABORATIVE FOR HIGH PERFORMANCE SCHOOLS (CHPS) E02.2 AND LISTED W
INSUL INSULATION 2 Individual TV's B B ③
IN THE CHPS HIGH PERFORMANCE PRODUCT DATABASE, OR
INT INTERIOR WC WATER CLOSET DEMOLITION TAG
4. CERTIFIED UNDER THE GREENGUARD CHILDREN & SCHOOLS PROGRAM TO COMPLY WITH 3 Cue Racks A ◼
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH CRITERIA (CALGREEN 5.504.4.4 AND 5.504.4.4.6) W/ WITH
J W/O WITHOUT 4 All Carpet ◼ ◼ ⑦
WD WOOD 3.02 KEYNOTE TAG
JB JUNCTION BOX
5 Video Games F F
X
# EXTERIOR MATERIAL TAG 6 Telephone System G G ⑥
XPS EXTRUDED POLYSTYRENE NUMBER OF
7 Security/Alarm System H H ⑥
OCCUPANTS FOR EXIT
2022 CBC SECTION 1013 EXIT SIGNS
SECTION 1013.1 AND SECTION 1013.4 # # EXITING OCCUPANCY
8 Restroom Floor Matting ◼ ◼
ARROW SHOWING 9 Bar & Snack Bar Matting ◼ ◼
DIRECTION OF
EGRESS 10 Entrance Mats ◼ ◼ 3070 SATURN ST. STE. 200
5"
11 Time Clock ◼ ◼ BREA, CA 92821
LETTERS: MIN 5/8" HIGH
RAISED MIN 1/32" - SANS 12 Key Cabinet ◼ ◼
EXIT SARIF UPPERCASE
13 Safes ◼ ◼
3"

4'-0"
14 Register/POS ◼ ◼
GRADE 2 BRAILLE
15 Misc. Furniture ◼ ◼
16 Soda Dispensing System J J
OWNER 17 Beer Lines & System ◼ ◼
INFORMATION
NOTE: G.C. TO PROVIDE AND INSTALL A VINYL 18 Under Floor Conduits for Soda & Beer Lines ◼ ◼
BANNER (ARTWORK SUPPLIED BY
1. COLORS: BACKGROUND - BLUE / GRAPHIC - WHITE
ARCHITECT) AND ATTACH TO 4'x8'x3/4"
19 Washing Machine/Dryer ◼ ◼
2. TACTILE CHARACTERS ON SIGNS SHELL BE LOCATED 48 INCHES MINIMUM ABOVE THE PLYWOOD SUBSTRATE. 20 Breakroom Hand Sink ◼ ◼
ARCHITECT DISPLAY / INSTALL AT MALL SIDE

8'-0"
FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST 21 Mechanic's Room Hand Sink ◼ ◼
BRAILLE CELLS AND 60 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE, INFORMATION ENTRANCE
MEASURED FROM THE BASELINE OF THE HIGHEST LINE OF RAISED CHARACTERS. 22 Karaoke Room Mirrors ◼ ◼
3. WHERE A TACTILE SIGN IS PROVIDED AT A DOOR, THE SIGN SHELL BE LOCATED
ALONGSIDE THE DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE Specific Keynotes:
DOORS WITH ONE ACTIVE LEAF, THE SIGN SHALL BE LOCATED ON THE INACTIVE LEAF. CONTRACTOR ① G.C. TO CONNECT / HOOK UP ALL POWER & PLUMBING TO EQUIPMENT A LICENSED PLUMBER SHALL HOOK UP PLUMBING. A
WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE DOORS WITH TWO ACTIVE LEAFS, THE INFORMATION LICENSED ELECTRICIAN SHALL HOOK UP POWER. REGARDING S&G PROVIDED COUNTERS: ALL POWER RECEPTACLES AND DATA
SIGN SHALL BE LOCATED TO THE RIGHT OF THE TIGHT HAND DOOR. WERE THERE IS NO BOXES WILL BE PRE-INSTALLED INTO COUNTERS. REFER TO S&G DRAWINGS FOR ENTIRE SCOPE OF WORK BY S&G AND G.C. -
WALL SPACE AT THE LATCH SIDE OF A SINGLE DOOR OR AT THE RIGHT SIDE OF DOUBLE G.C. SHALL BRING POWER TO COUNTERS AND CONNECT TO ALL RECEPTACLES, IN-COUNTER LIGHTING AND SWITCHES.
DOORS, SIGNS SHALL BE LOCATED ON THE NEAREST ADJACENT WALL. SIGN CONTAINING
TACTILE CHARACTERS SHALL BE LOCATED SO THAT A CLEAR FLOOR SPACE OF 18 INCHES
MINIMUM BY 18 INCHES MINIMUM, CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED ② G.C. TO RECEIVE VENDOR SUPPLIED COMPRESSORS AND INSTALL ON EXISTING ROOF. G.C. TO COORDINATE WITH LANDLORD'S
BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 45 DEGREE
OPEN POSITION. WHERE PROVIDED, SIGNS IDENTIFYING PERMANENT ROOMS AND SPACES
CONSTRUCTION SIGN ROOFER TO CUT OPENING IN ROOF FOR COMPRESSOR LINES, HOSES, CONDUIT AND PROVIDE ROOF ACCESSORIES AND FLASH
ROOF AS NEEDED.
SHELL BE LOCATED AT THE ENTRANCE TO, AND OUTSIDE OF THE ROOM OR SPACE. WHERE
PROVIDED, SIGNS IDENTIFYING EXITS SHELL BE LOCATED AT THE EXIT DOOR WHEN
APPROACHED IN THE DIRECTION OF EGRESS TRAVEL. EXCEPTION: IN ALTERATIONS WHERE ③ VENDOR TO PROVIDE AND INSTALL UNISTRUT BETWEEN EXISTING OVERHEAD FRAMING TO SUPPORT VENDOR SUPPLIED TV RELEASE DATE
SIGN INSTALLATION LOCATIONS IDENTIFIED IN SECTION 11B-703.4.2 ARE OBSTRUCTED ON MONITORS.
OTHERWISE UNAVAILABLE FOR SIGN INSTALLATION, SIGNS WITH TACTILE CHARACTERS DATE DESCRIPTION
SHALL BE PERMITTED ON THE PUSH SIDE OF DOORS WITH CLOSERS AND WITHOUT HOLD- ④ G.C. TO PROVIDE UNISTRUT, VENDOR WILL INSTALL PROJECTORS AND BRACKETS.
OPEN DEVICES. 07-06-23 FOR PERMITS
⑤ G.C. RESPONSIBLE FOR PROVIDING STRUCTURAL SUPPORT FOR OVERHEAD SCORING MONITORS AND CURTAIN WALL. 07-21-23 FOR BIDS
4. TACTILE EXIT SIGNS SHALL BE REQUIRED AT THE FOLLOWING LOCATIONS: NOTE: NOTES:

A. EACH GRADE-LEVEL EXTERIOR EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, PROVIDE SIGNS STATING "EXIT" IN 1. SIGNS SHALL BE TACTILE W/1-1/4" LETTERING MOUNTED ON WALL
⑥ G.C. TO PROVIDE MOUNTING BOARDS AS REQUIRED FOR TELEPHONE, SECURITY SYSTEM.
SHALL BE IDENTIFIED A TACTILE EXIT SIGN WITH THE WORD, "EXIT." RAISED CHARACTERS AND BRAILLE AND ADJACENT TO LATCH SIDE OF DOOR AT INDICATED HEIGHT REQUIREMENTS.
COMPLYING WITH ICC A117.1 ADJACENT REFER TO STATE (LOCAL) BARRIER FREE REQUIREMENTS.
B. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, AND THAT LEADS DIRECTLY TO EACH EXIT DISCHARGE DOOR. ⑦ G.C. SHALL CONFIRM EXACT QUANTITIES OF ITEMS. CONTACT TENANT TO ORDER AND COORDINATE DELIVERIES. CARPET
TO A GRADE-LEVEL EXTERIOR EXIT BE MEANS OF A STAIRWAY OR RAMP SHALL BE IDENTIFIED BY A TACTILE 2. PROVIDE SIGNS STATING "MEN" AND "WOMEN" WITH ACCESSIBILITY AND SUPPLIED BY OWNER. INSTALLATION AND ALL ACCESSORIES NECESSARY TO INSTALL CARPET BY GENERAL CONTRACTOR.
EXIT SIGN WITH THE FOLLOWING WORDS AS APPROPRIATE: GENDER SYMBOL IN RAISED CHARACTERS AND BRAILLE AND COMPLYING REFER TO SPECIFICATION
1. "EXIT STAIR DOWN" WITH ICC A117.1 ADJACENT TO CORRESPONDING TOILET ROOM DOORS.
2. "EXIT RAMP DOWN"
3. "EXIT STAIR UP" ⑧ G.C. SHALL CONFIRM FINAL ELECTRICAL POWER REQUIREMENTS (IE: VOLTAGE AND AMP LOAD) WITH OWNER'S SIGN VENDOR
4. "EXIT RAMP UP" TACTILE TACTILE PRIOR TO INSTALLATION OF ELECTRICAL POWER.
IDENTIFICATION IDENTIFICATION
C. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, AND THAT LEADS DIRECTLY CONTRACTED CONTRACTED
TO A GRADE-LEVEL EXTERIOR EXIT BY MEANS OF AN EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL BE (GRADE 2) BRAILLE (GRADE 2) BRAILLE
VENDOR LIST:
IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE."
A BRUNSWICK BOWLING AND BILLIARDS F GAME VENDOR
D. EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR HALLWAY THAT IS B DECIBEL - STUDIOS G TELEPHONE SYSTEM VENDOR
SYMBOL OF
REQUIRED TO COMPLY WITH SECTION 1013.1, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS COMPLIANCE C NOT USED H SECURITY ALARM VENDOR
"EXIT ROUTE."
D CROSS DESIGN & LIGHTING J SODA VENDOR
E. EACH EXIT DOOR THROUGH A HORIZONTAL EXIT THAT IS REQUIRED TO COMPLY WITH SECTION E COSMIC EQUIPMENT VENDOR
1013.1, SHALL BE IDENTIFIED BY A SIGN WITH THE WORDS "TO EXIT."
MIN.

5. RAISED CHARACTER AND BRAILLE EXIT SIGNS SHALL COMPLY WITH CHAPTER 11A,
NOTE TO ALL CONTRACTORS
6"

SECTION 1143A OR CHAPTER 11B, SECTIONS 11B-703.1, 11B-703.2, 11B-703.3 AND 11B-703.5 9" 9"
PROJECT
CL CL
60" MAX

60" MAX
5'-0"
48" MIN

48" MIN

UNFORESEEN CONDITIONS: IF ANY INTERFERENCES OR VIOLATIONS APPEAR AND DEPARTURE FROM THE
DESIGN INTENT OF THE CONTRACT DOCUMENTS IS REQUIRED, THE GENERAL CONTRACTOR SHALL NOTIFY
2112128GR
THE ARCHITECT AND PROJECT MANAGER IMMEDIATELY, IN WRITING, BEFORE ENTERING INTO A CONTRACT
WITH THE CLIENT. FAILURE TO PROVIDE ARCHITECT AND CONSTRUCTION MANAGER WITH AFOREMENTIONED
SHEET
7/25/2023 3:41:24 PM

NOTIFICATION SHALL RESULT IN THE SPECIFIC CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL
WORK REQUIRED TO MEET THE DESIGN INTENT OF THE CONTRACT DOCUMENTS AT HIS/HER OWN COSTS
WITH NO ADDITIONAL EXPENSES (EXTRAS) BEING INCURRED. RESPONSIBILITY MATRIX
EXIT DISCHARGE DOOR SIGNAGE TOILET ROOM SIGNAGE THE CONTRACTOR SHALL FULLY EXECUTE ALL WORK SHOWN AND SPECIFIED IN THE DRAWINGS AND
SPECIFICATIONS, EXCEPT AS SPECIFICALLY INDICATED IN THE DRAWINGS AND SPECIFICATIONS TO BE THE
RESPONSIBILITY OF OTHERS. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR
TACTILE SIGNAGE OMISSIONS IN THE WORK SHOWN AND SPECIFIED IN THE DRAWINGS AND SPECIFICATIONS, NOR MAKE CLAIM G-002
FOR ADDITIONAL COSTS RESULTING FROM SUCH OMISSIONS.
CHAPTER 9 - Fire Protection Systems CHAPTER 11 - Accessibility
BUILDING CODE INFORMATION Section 903 - Automatic Sprinkler Systems Section 11B-206.2.2 Accessible Routes At least one accessible route shall connect accessible buildings, accessible
GOVERNING CODES Section 903.2.1.2 Group A-2: An automatic sprinkler system shall be provided for fire areas containing facilities, accessible elements and accessible spaces that are on the same
BUILDING CODE 2022 California Building Code Group A-2 occupancies and intervening floors of the building where one of the site.
EXISTING BUILDING CODE 2022 California Existing Building Code following conditions exists:
1. The fire area exceeds 5,000 sf Section 11B-206.2.11 Bowling Lanes Where bowling lanes are provided, at least 5 percent, but no fewer than one
ACCESSIBILITY 2010 Americans with Disabilities Act Standards 2. The fire area has an occupant load of 100 or more of each type of bowling lane, shall be on an accessible route.
ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES 3. The fire area is located on a floor other than a level of exit discharge
ENERGY CONSERVATION CODE 2022 California Building Energy Efficiency Standards serving such occupancies Required: (10) lanes provided*5% = .5 ~ 1 space required PARADIGM DESIGN
2022 California Green Building Standards Code Provided: 1
MECHANICAL CODE 2022 California Mechanical Code Section 11B-213.3.1 Toilet compartments Where toilet compartments are provided, at least 5% of the toilet ARCHITECTS | ENGINEERS
compartments or 5% of the combination of toilet compartments and urinals but
ELECTRICAL CODE 2022 California Electrical Code Section 903.2.1.3 Group A-3: An automatic sprinkler system shall be provided for fire areas containing group not fewer than one toilet compartment shall comply with Section 11B-604.8.1.
PLUMBING CODE 2022 California Plumbing Code A-3 occupancies and intervening floors of the building where one of the In addition to the compartments required to comply with Section 11B-604.8.1,
FIRE CODE 2022 California Fire Code following conditions exists: where six or more toilet compartments are provided, or where the combination
FIRE PROTECTION 2022 California Fire Sprinkler Code 1. The fire area exceeds 12,000 sf of urinals and water closets totals six or more fixtures, toilet compartments
2. The fire area has an occupant load of 300 or more complying with Section 11B-604.8.2 shall be provided in the same quantity as
ELEVATOR CODE 2010 International Elevator Rules 3. The fire area is located on a floor other than a level of exit discharge the toilet compartments required to comply with Section 11B-604.8.1 Grand Rapids | Phoenix | Traverse City
serving such occupancies.
www.paradigmae.com
PROJECT DESCRIPTION
Tenant Fit Out of 58,213 SF within Westfield Plaza Bonita shopping center which will include bowling, redemption arcade, billiards, party rooms,
a snack bar and bar, and other support areas.
Section 903.3.1.1 NFPA 13 Sprinkler Systems: Where the provisions of the code require that a building or portion thereof be
SUMMARY equipped throughout with an automatic sprinkler system in accordance with Chapter 4 - Plumbing Fixtures and Fixture Fittings - California Plumbing Code
Section 903, sprinklers shall be installed throughout in accordance with NFPA
Use Group: A-2, A-3 13 except as provided in Section 903.3.1.1.1 and 903.3.1.1.2 Section 422.1 Fixture Count The minimum number of fixtures shall be calculated at 50 percent male and 50 percen...
Construction Class: II-B
Building Height (ft): 75' Allowed
40'-0" +/- Existing Section 906 - Portable Fire Extinguishers Table 422.1 Minimum Plumbing Facilities
Building Stories: 3 Allowed Section 906.1 Where required: Type K fire extinguisher: Within 30 feet of commercial cooking equipment Water Closets
2 Existing Type B fire extinguisher: in areas where flammable or combustible liquids ar...
Type of Occupancy Occupant Load Male Female
Building Area: Unlimited Allowed Table 906.3: 4-A fire extinguisher = 6,000 SF max floor area (4x1,500 SF) per extinguishe...
Class C fire extinguisher required at electrical - allowable area and travel... Assembly A-3 760 Required: 4 11
58,213 SF Existing
Type K fire extinguisher: required within 30' of cooking equipment Provided: 5 10 + (1 unisex)
Occupancy Count: 1520 Fire Extinguisher designed: (1) unisex toilet provided
4-A, 60-B:C AND 2-A:K at Kitchen
Section 907 - Fire Alarm and Detection Systems
Section 907.2.1 Group A: A manual fire alarm system that activates the occupant notification system in Urinals
CHAPTER 3 - USE AND OCCUPANCY CLASSIFICATION accordance with Section 907.5 shall be installed in Group A occupancies
Type of Occupancy Occupant Load Male
SECTION 303 BLDG CODE having an occupant load of 300 or more.
Group: A-2, A-3 Section: 303.3, 303.4 Assembly A-3 760 Required: 5
Exception: Manual fire alarm boxes are not required where the building is equipped
Accessory Occupancies: B, M, S Section 508.2 Provided: 6
throughout with an automatic sprinkler system installed in accordance with PROJECT
Section 903.3.1.1 and the occupant notification appliances will activate
CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY throughout the notification zones upon sprinkler water flow.
Section 402 - Covered Mall and open mall buildings
Section 402.4.1.1 Covered and open mall The building area of any covered mall or open mall building shall not be limited
Section 907.2.1.1 System Initiation in Group A occupancies with an occupant load of
1,000 or more
Type of Occupancy Occupant Load
Lavatories
Male Female ROUND1 -
buildings provided that the covered mall or open mall building does not exceed three
floor levels at any point nor three stories above grade plane, and is of Type I,
II, III or IV construction
Activation of the fire alarm in Group A occupancies with an occupant load of
Assembly A-3 760 Required:
Provided:
5
5
7
6 + (1 unisex)
PLAZA BONITA
1,000 or more shall initiate a signal using an emergency voice/alarm
communications system in accordance with Section 907.5.2.2
Section 402.4.1.2 Area and types of The building area and building height of any anchor building shall be based on
construction - Anchor the type of construction as required by Section 503 as modified by Sections Drinking Fountain Other
Buildings 504 and 506 Type of Occupancy Occupant Load
Exception: The building area of any anchor building shall not be CHAPTER 10 - Means of Egress Assembly A-3 760 Required: 4 1 service sink
limited provided that the anchor building is not more Section 1004 - Occupant Load
than three stories above grade plan, and is of Type I, II, Provided: 2 1 service sink
Table 1004.5 Maximum Floor area allowances per occupant
III or IV construction. SECTION 415.2 OF 2022 CPC DRINKING FOUNTAIN ALTERNATIVES
LOWER LEVEL Location Area (SF) load factor Occupants
Section 402.4.2 Fire-resistance rated Fire-resistance-rated separation is not required between tenant spaces and Assembly A-2 Areas Where food is consumed indoors, water stations shall be permitted to be substituted for
separation the mall. Fire-resistance-rated separation is not required between a food court Party Rooms (net): 2181 15 148 drinking fountains. Bottle Filling stations shall be permitted to be substituted for drinking
and adjacent tenant spaces or the mall. fountains up to 50 percent of the requirements for drinking fountains. Drinking fountains
Seating Area (booths): 90
shall not be required for an occupant load of 30 or less.
Seating Area (net): 1096 15 74
Section 402.4.2.2 Anchor building separation An anchor building shall be separated from the covered or open mall building
by fire walls complying with Section 706. Bar Seating 26
Kitchen (gross): 901 200 5
Exceptions: 1. Anchor buildings of not more than three stories
above grade plane that have an occupancy Section 2902.1.2 of 2022 CBC
classification the same as that permitted for tenants of Assembly A-3 Areas Single-user toilet facility and The plumbing fixtures located in single-user toilet and bathing rooms, including family or
the mall building shall be separated by 2-hour fire Bowling Lanes: (10) Lanes 5 per lane 50 bathing room fixtures assisted-use toilet and bathing rooms that are required by Section 1109.2, shall
resistance-rated fire barriers complying with Section Game Room(*) (gross): 14476 15 966 contribute toward the total number of required plumbing fixtures for a building or tenant
707. space. Single-user toilet and bathing rooms, and family or assisted-use toilet and
Billiards (net): 1274 15 85
bathing rooms shall be identified as being available for use by all persons regardless of
their sex.
Section 402.4.2.2.1 Openings between anchor
building and mall
Except for the separation between Group R-1 sleeping units and the mall,
openings between anchor buildings of Type IA, IB, IIA, or IIB construction and
Mercantile
TENANT
the mall need not be protected. Redemption Store (gross): 763 60 13
IMPROVEMENT
Designed: fully sprinklered Business
Office (gross): 397 150 3
CHAPTER 5 - General Building Heights and Areas Employee Lounge (net): 290 15 20
Section 504 - Building height and Guest Counters (gross): 500 150 4
number of stories
Snack Bar (gross): 435 150 3 3030 PLAZA BONITA RD, SUITE
Section 506.2 Allowable area determination The allowable area of a building shall be determined in accordance with the... Bar, Redemption Store, 800 150 7 1025
Guest Counter, Snack Bar
Section 504.3 Height in feet The maximum height, in feet, of a building shall not exceed the limits specifi...
(Employees) NATIONAL CITY, CA 91950
Table 504.3 Allowable Building Height: 75'
Existing Building Height: 40'-0" +/- CLIENT
Section 504.4 Number of Stories: The maximum number of stories of a building shall not exceed the limits... Storage
Game Mechanics Room 190 300 1
Table 504.4 Allowable Number of Stories: 3
Existing # of Stories: 2
Storage 435 300 2 ROUND1
Storage/Lactation 182 300 1
Section 507.13 Covered and open mall buildings and anchor buildings
High Value Storage 276 300 1 ENTERTAINMENT
Storage 683 300 3
The area of covered and open mall buildings and anchor buildings not exceeding three stories in height that
Mechanic's Room 166 300 1
comply with Section 402 shall not be limited
AV 174 300 1
Section 508 - Mixed Use and Occupancy
Electrical 493 300 2
Section 508.2 Accessory Occupancies: B, M, S
Redemption Storage 554 300 2
Janitor 126 300 1
Section 508.3 Nonseparated occupancies: Mechanical 129 300 1
Plush Storage 1770 300 6
Yes Pinsetter Service 1164 300 4
TOTAL OCCUPANCY 1520
CHAPTER 6 - Types of Construction (*) Notes:
Section 602.2 Type: II-B 1. Unlike a large assembly room where the occupants may utilize the entire floor area, our game rooms have large fixed games that cannot be
occupied by a person. We calculated the Game Room occupant load calculations based on this principle:
Table 601 Fire-Resistance Rating Requirements for Building Elements (hours):
Gross Floor Area (Arcade): 28,952 S.F.
Primary Structural Frame: 0
Unoccupied (Arcade) Area: 28,952 S.F. x 50% Floor Area Unoccupied = 14,476 3070 SATURN ST. STE. 200
Bearing walls Exterior: 0
Bearing walls Interior: 0
Net Floor Area (Arcade): 14,476 S.F. BREA, CA 92821
2. Estimated game total by tenant. The occupant load would account for every game being able to be play/occupied at the same time

Section 1004.9 - Posting of occupant load

Nonbearing walls and partitions Exterior: 0 Every room or space that is an assembly occupancy shall have the occupant load of the room or space
posted in a conspicuous place, near the main exit or exist access doorway from the room or space, for the
Nonbearing walls and partitions Interior: 0 intended configurations. Posted signs shall be of an approved legible permanent design and shall be
maintained by the owner or the owner's authorized agent.

Floor construction and associated secondary members: 0


Roof construction and associated secondary members: 0
Section 1005 - Means of Egress Sizing
Table 602 exterior wall separation distance to adjacent property or property line x ≥ 30 Section 1005.3 Required capacity based on occupant load. The required capacity, in inches, of the means of egress for a...
Exterior wall fir... 0 Section 1005.3.1 Stairways The capacity, in inches, of means of egress stairways shall be calculated by...
Exterior wall fir... 0 Exception 1: For other than Group H and I-2 occupancies, the capacity, in inches, of mea...
Section 1005.3.2 Other egress components. The capacity, in inches, of means of egress components other than stairways
shall be calculated by multiplying the occupant load served by such...
Section 602.3 Type III
Type III Construction is that type of construction in which the exterior walls are Exception 1: For other than Group H and I-2 occupancies, the capacity, in inches, of mea...
of noncombustible materials and the interior building elements are of any Required Main Exit Width
material permitted by this code. Fire-retardant-treated wood framing and Design load / 2 = 1520/2= 760 occupants
sheathing compying with Section 2303.2 shall be permitted within exterior wall Main Exit Width Required: 760 x 0.15 = 114"
assemblies of a 2-hour rating or less.
Main Exit Width Provided: 153.5"

CHAPTER 7 - Fire Partitions Required Additional Exit Width


Section 707 - Fire Barriers Required: Stair enclosure walls. Shaft enclosures Design load / 2 = 1520 / 2 = 760 occupants
Section 713 - Shaft Enclosures Add'l Exit Width Required: 760 x 0.15 = 114"
Section 713.4 Fire-resistance rating: 1-hour rated for less than 4 stories... Add'l Exit Width Provided: 88" + 32" + 42" =
162"
Rating required: 1-hr
Table 716.1 Door Rating required: 1-hr RELEASE DATE
Table 716.1 Max door glass area: 100 sq in Section 1017 - Exit Access Travel
Distance
DATE DESCRIPTION
CHAPTER 8 - Interior Finishes
Section 803.1.1 Interior Wall and Ceiling finish materials: 07-06-23 FOR PERMITS
Table 1017.2 Exit Access Travel Distance: 250' with sprinkler
Class A: = Flame Spread Index 0-25 Smoke Developed Index 0-450 system 07-21-23 FOR BIDS
Class B: = Flame Spread Index 26-75 Smoke Developed Index 0-450
Section 1029 - Assembly
Class C: = Flame Spread Index 76-200 Smoke Developed Index 0-450
Section 1029.2 Assembly main exit: Main exit shall accommodate not less than one-half of the occupant load.
Section 803.13 Interior finish requirements... Interior wall and ceiling finish shall have a flame spread index not greater tha...
Table 803.13 Interior Wall and Ceiling Finish Requirements By Occupancy:
Group A-2 and A-3 Sprinkled:
Interior exit stairways, ramps, and passageways: B
Corridors and enclosure for exits: B
Rooms and enclosed spaces: C

PROJECT

2112128GR
SHEET
7/25/2023 3:49:11 PM

CODE SUMMARY

G-003
CHAPTER 10 - Means of Egress
Section 1004 - Occupant Load
TACTILE EXIT SIGN LEGEND Table 1004.5 Maximum Floor area allowances per occupant
LOWER LEVEL Location Area (SF) load factor Occupants
EXIT 3 (DOOR S-1A AND S-1B AND STAIR S-1) Assembly A-2 Areas
EXIT WIDTH: 32" Party Rooms (net): 2181 15 148
MATERIAL
ALLOWED: 32" ÷ 0.15" = 213 Seating Area (booths): 90
ACTUAL: 156
1 TACTILE "EXIT" SIGN Seating Area (net): 1096 15 74
2 TACTILE "EXIT STAIR UP" SIGN Bar Seating 26
GRADE AT EXTERIOR STAIR 1 Kitchen (gross): 901 200 5
1 S-1
Assembly A-3 Areas PARADIGM DESIGN
156 Bowling Lanes: (10) Lanes 5 per lane 50
WALL TYPE - FIRE RATING LEGEND Game Room(*) (gross): 14476 15 966 ARCHITECTS | ENGINEERS
Billiards (net): 1274 15 85

N N
UPPER LEVEL FLOOR PLAN EGRESS 2 HOUR FIRE BARRIER Mercantile
SCALE: 3/32" = 1'-0"
Redemption Store (gross): 763 60 13
ACTUAL PLAN Grand Rapids | Phoenix | Traverse City
Business www.paradigmae.com
CLASS II VAPOR RETARDER REQUIRED ON
Office (gross): 397 150 3
INTERIOR OF STUD FRAMING @ EXTERIOR
EXIT 3 (DOOR S-1A AND S-1B AND STAIR S-1) Employee Lounge (net): 290 15 20
WALLS, TYP.
EXIT WIDTH: 32" Guest Counters (gross): 500 150 4
ALLOWED: 32" ÷ 0.15" = 213
Snack Bar (gross): 435 150 3
ACTUAL: 156
Bar, Redemption Store, 800 150 7
Guest Counter, Snack Bar
(Employees)
FIRE
MENS STORAGE
UP RISER
Storage
2 STAIR 1 113
108 111 STORAGE Game Mechanics Room 190 300 1
S-1
435 SF 112 Storage 435 300 2
PARTY 3
JANITOR 683 SF Storage/Lactation 182 300 1
ROOM 1 39 FEC
107 156 2 ELECTRICAL High Value Storage 276 300 1
PLUSH 1 110
124 SF 114 Storage 683 300 3
STORAGE 584 SF
493 SF Mechanic's Room 166 300 1
105 6 AV 174 300 1
2246 SF
Electrical 493 300 2
2
FAMILY WOMENS Redemption Storage 554 300 2
TOILET 109 Janitor 126 300 1
106 Mechanical 129 300 1
Plush Storage 1770 300 6 PROJECT
Pinsetter Service 1164 300 4
FEC

PER CBC SECTION 402.4.2.2.1 OPENINGS BETWEEN 4


(*) Notes:
TOTAL OCCUPANCY 1520
ROUND1 -
ANCHOR BUILDING AND MALL: EXCEPT FOR THE 1. Unlike a large assembly room where the occupants may utilize the entire floor area, our game rooms have large fixed games that cannot be
SEPARATION BETWEEN GROUP R-1 SLEEPING UNITS
AND THE MALL, OPENINGS BETWEEN ANCHOR 38 36
FREIGHT
ELEVATOR
occupied by a person. We calculated the Game Room occupant load calculations based on this principle: PLAZA BONITA
PARTY ELEV-1 Gross Floor Area (Arcade): 28,952 S.F.
BUILDINGS OF TYPE IA, IB, IIA, OR IIB CONSTRUCTION
ROOM 4 PARTY Unoccupied (Arcade) Area: 28,952 S.F. x 50% Floor Area Unoccupied = 14,476
AND THE MALL NEED NOT BE PROTECTED
124 ROOM 2
Net Floor Area (Arcade): 14,476 S.F.
563 SF 121 FE
2. Estimated game total by tenant. The occupant load would account for every game being able to be play/occupied at the same time
REDEMPTION 528 SF PINSETTER
BOWLER'S BOWLING BOWLING 1
STORAGE SERVICE
SEATING APPROACH LANES Section 1004.9 - Posting of occupant load
123 117 A.V.
120 119 118
554 SF 1164 SF 115
174 SF
Every room or space that is an assembly occupancy shall have the occupant load of the room or space
posted in a conspicuous place, near the main exit or exist access doorway from the room or space, for the
2 50 @ BOWLING LANES intended configurations. Posted signs shall be of an approved legible permanent design and shall be

FEC
maintained by the owner or the owner's authorized agent.
PARTY
ROOM 3
35
REDEMPTION 122
MAINTAIN EXISTING FIRE RATING OF STORE 512 SF 2
13 Section 1005 - Means of Egress Sizing
EXISTING DEMISING WALL BETWEEN 125
Section 1005.3 Required capacity based on occupant load. The required capacity, in inches, of the means of egress for a...
ANCHOR BUILDING AND MALL 777 SF
Section 1005.3.1 Stairways The capacity, in inches, of means of egress stairways shall be calculated by...
THROUGHOUT CONSTRUCTION
MECHANIC'S Exception 1: For other than Group H and I-2 occupancies, the capacity, in inches, of mea...
VENDING 116 Section 1005.3.2 Other egress components. The capacity, in inches, of means of egress components other than stairways
124 365 SF shall be calculated by multiplying the occupant load served by such...
Exception 1: For other than Group H and I-2 occupancies, the capacity, in inches, of mea... TENANT
24X24 24X48
Required Main Exit Width
Design load / 2 = 1520/2= 760 occupants
IMPROVEMENT
Main Exit Width Required: 760 x 0.15 = 114"
UP

CWI
FE
Main Exit Width Provided: 153.5"

CWO
D

FE-K
24X48
24X48
Required Additional Exit Width
3030 PLAZA BONITA RD, SUITE

24X48
Design load / 2 = 1520 / 2 = 760 occupants
Add'l Exit Width Required: 760 x 0.15 = 114" 1025

24X48
24X48
EXIT 2 (DOOR 135A) - EGRESS ONLY

24X48

24X48
Add'l Exit Width Provided: 88" + 32" + 42" =

18"X18"X12"
EXIT WIDTH: 105.5"

24X48
KITCHEN
24X48

162"
NATIONAL CITY, CA 91950
ALLOWED: 105.5" ÷ 0.15" = 703
128 90 BOOTH OCCUPANTS ACTUAL: 404
34DR

24X48
24X48 900 SF Section 1017 - Exit Access Travel
CLIENT
Distance
5
ROUND1

24X48
BAR
85 404
CWI

MECHANICAL 130 1274 SF ENTERTAINMENT


C
NOT IN CONTRACT LEASELINE Table 1017.2 Exit Access Travel Distance: 250' with sprinkler

D
TS14BLW

CH
127 H
CWO

system
D

D
G
SEATING
Section 1029 - Assembly

D
6'-0" SEATING BOOTH BACK LENGTH, 131 74 TABLES AND CHAIRS

CRC-63C
1
G

CH
D
GUEST Section 1029.2 Assembly main exit: Main exit shall accommodate not less than one-half of the occupant load.
TYP. x 24" PER OCCUPANT = (6)
G

D
COUNTER 1096 SF
D C OCCUPANTS PER BOOTH x (15)

SC-15-TS

CH
D
126 H
C
D

BOOTHS = 90 BOOTH OCCUPANTS


2 2 SNACK 3

CRI-12-30-7

D
BAR
129
C
H
RC
R

D
D
C
UP
FEC
4 3 26 @ BAR SEATING

EXIT SEPARATION = 169' - 6" > 119'

FEC
1

UP
3070 SATURN ST. STE. 200
PER CBC SECTION 402.4.2.2.1 OPENINGS BETWEEN BREA, CA 92821
ANCHOR BUILDING AND MALL: EXCEPT FOR THE
SEPARATION BETWEEN GROUP R-1 SLEEPING UNITS
AND THE MALL, OPENINGS BETWEEN ANCHOR
BUILDINGS OF TYPE IA, IB, IIA, OR IIB CONSTRUCTION
AND THE MALL NEED NOT BE PROTECTED

MIN.
FEC

N CE
TA
1 /3 = N DIS
L x IO GAME
O NA RA T
A
IAG EP ROOM
X . D IT S 143
A X
'M .E
357 9' MIN 14,476 SF
11
966

1 760

OFFICE
FEC

CLASS II VAPOR RETARDER REQUIRED ON


VESTIBULE 136 EMPLOYEE STORAGE/ INTERIOR OF STUD FRAMING @ EXTERIOR
101 HIGH 397 SF LOUNGE LACTATION WALLS, TYP. RELEASE DATE
VALUE 135 134
STORAGE 290 SF 182 SF
137
DATE DESCRIPTION
200 20 1
276 SF 07-06-23 FOR PERMITS
ELECTRICAL 1 3 07-21-23 FOR BIDS
FEC

103

200

EXIT 1 (DOOR 101A AND 101B) - MAIN EGRESS


EXIT WIDTH: 153.5"
ALLOWED: 153.5" ÷ 0.15" = 1023
ACTUAL: 760

EXIT 4 (DOOR 102)


EXIT WIDTH: 42"
ALLOWED: 42" ÷ 0.15" = 280
ACTUAL: 200

N N
EGRESS PLAN
SCALE: 3/32" = 1'-0" PROJECT
ACTUAL PLAN
2112128GR
SHEET
7/25/2023 3:50:19 PM

EGRESS PLAN

G-101
DEMOLITION LEGEND

DEMOLITION

EXIST. TO REMAIN

CONCRETE REMOVAL
PARADIGM DESIGN
ARCHITECTS | ENGINEERS
1. REMOVE DOOR, FRAME AND ASSOCIATED HARDWARE

2. REMOVE LOAD-BEARING WALL - REFER TO STRUCTURAL 550 3 Mile NW Suite B


Grand Rapids, MI 49544
3. REMOVE PORTION OF WALL AS REQUIRED FOR NEW (616) 785-5656
CONSTRUCTION - PATCH AND REPAIR WALL AS REQUIRED.
REFER TO STRUCTURAL Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
4. REMOVE EXISTING STOREFRONT SYSTEM

I I.5 J K L L.1 M.1 M 1 2 3 4 5 6 7 8 5. REMOVE EXISTING DOOR FRAME. PREPARE OPENING FOR
NEW FRAME AND DOOR.

6. REMOVE PORTION OF SIDEWALK AS REQUIRED FOR NEW


EXTERIOR PIN FOUNDATION. PATCH AND REPAIR TO MATCH
4.1 EXISTING

A 7. REMOVE PORTION OF EXISTING WALL AS REQUIRED FOR


NEW DOUBLE DOOR. REFER TO DEMO ELEVATION.

PROJECT

5.1
B
ROUND1 -
PLAZA BONITA

6.1 C

TENANT
IMPROVEMENT
2
6.8

6.9 3030 PLAZA BONITA RD, SUITE


D
1025
7.1 NATIONAL CITY, CA 91950

TENANT

ROUND1
ENTERTAINMENT
7

2
AD201
8.1 E

8.2

8.3

3070 SATURN ST. STE. 200


BREA, CA 92821

3'-5 1/2"
9.1

8'-4"
3

10.1
3
ABOVE
RELEASE DATE
7
DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

11.1

1
AD201

I I.5 K L L.1 M.1 M 1 2 3 4 5 6 7 8

PROJECT

N
DEMOLITION PLAN - OVERALL
SCALE: 3/32" = 1'-0"
SHEET
7/25/2023 3:41:01 PM

DEMOLITION PLAN
OVERALL
AD101
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

REMOVE 'TRIM PIECE'

REMOVE EXISTING CANOPY AND


ASSOCIATED HARDWARE IN ITS ENTIRETY
T.O. (E) PARAPET
NOTE: 140' - 0"

NEW AND EXISTING BUILDINGS SHALL HAVE APPROVED


ADDRESS NUMBERS, BUILDING NUMBERS OR APPROVED
BUILDING IDENTIFICATION PLACED IN A POSITION THAT IS
PLAINLY LEGIBLE AND VISIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. THESE NUMBERS SHALL
CONTRAST IN COLOR TO BACKGROUND. NUMBERS SHALL PROJECT
BE A MINIMUM OF 4" HIGH WITH A MINIMUM STROKE WIDTH
OF 1/2 INCH." CFC 505.1 ROUND1 -
PLAZA BONITA

10'-0"
F. F.
100' - 0"
REMOVE LIGHTING FIXTURE DEMO TILE AND REMOVE LIGHTING FIXTURE
BACKER BOARD, TYP. REMOVE PORTION OF WALL AS REQUIRED FOR NEW STOREFRONT
SYSTEM - REFER TO FLOOR PLAN
REMOVE HOLLOW METAL DOORS, FRAMES, AND ASSOCIATED HARDWARE

1 EXTERIOR ELEVATION - SOUTH DEMO


AD101 SCALE: 1/8" = 1'-0"

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

REMOVE PORTION OF EXISTING WALL


CAP AS REQUIRED FOR INSTALLATION
ROUND1
OF NEW EIFS - REFER TO ELEVATIONS
ENTERTAINMENT
REMOVE TRIM AND EIFS. CMU WALL
BEHIND TO REMAIN
T.O. (E) PARAPET
140' - 0"

3070 SATURN ST. STE. 200


BREA, CA 92821
REMOVE EXISTING CANOPY AND
ASSOCIATED HARDWARE IN ITS ENTIRETY
REMOVE LIGHTING FIXTURE, TYP.

8'-4" +/-
TO MATCH HEIGHT OF DOOR FRAME

TO MATCH DOOR FRAME


10'-4" +/-

REMOVE LIGHTING FIXTURE, TYP.

F. F.
100' - 0"
REMOVE PORTION OF EXTERIOR DEMO TILE AND
WALL AS REQUIRED FOR NEW BACKER BOARD, TYP. REMOVE EXISTING STOREFRONT SYSTEM
DOOR - REFER TO STRUCTURAL

2 EXTERIOR ELEVATION - EAST DEMO


AD101 SCALE: 1/8" = 1'-0"

RELEASE DATE

DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

2112128GR
SHEET
7/25/2023 3:41:02 PM

DEMOLITION ELEVATIONS

AD201
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

AREA OF CONSTRUCTION ROUND1 -


PLAZA BONITA

FIRE RISER
S
ROOM
126 1

S
ROOM 3
PARTY

ROOM 2
PARTY
ROOM 4
130

T
S
CO2

STORAGE
109
S

REDEMPTION
STORE

VENDING
FE-K
108
S

S
KITCHEN
113

115
BAR
CWI
FEC

MECHANICAL

D
CWO
D

7'-6"
CWI
112

D
D
H

BAR
SNACK
S

REF.
S
2
AS101

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT
10−01−08

5 6
PHASE 1B

TILLY'S

3070 SATURN ST. STE. 200


BREA, CA 92821
LIMITED TOO

G G

FEC
HIGH
VESTIBULE VALUE
101 STORAGE
137
OFFICE
136
L
vv

11−15−08

H H

EXISTING LANDSCAPE
EXTERIOR PIN STRUCTURE - REFER RELEASE DATE
TO DETAILS 3/A-201 & S-501
DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS
EXISTING CURB RAMP
EXISTING CONCRETE CURB

EXISTING LANDSCAPE

5 6

N N
PLAZA BONITA MAP
SCALE: 1" = 80'-0"
2 ENLARGED MAIN ENTRY FLOOR PLAN
ACTUAL PLAN AS101 SCALE: 1/8" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:41:05 PM

SITE PLAN

AS101
FLOOR PLAN KEYNOTES
NOTE
NOTE: OMITTED NUMBERS ARE INTENTIONALLY SKIPPED TO REMOVE
NOTES NOT APPLICABLE TO THIS PROJECT.

REFER TO SHEETS G-002 FOR RESPONSIBILITY OF WHO IS FURNISHING


AND INSTALLING EACH ITEM.
1 GAMES SUPPLIED AND INSTALLED BY VENDOR, G.C. TO
COORDINATE INSTALLATION & PROVIDE POWER DROPS
PER ELECTRICAL PLANS - COORDINATE WITH FINAL GAME
LAYOUT.
PARADIGM DESIGN
2 BILLIARD TABLES BY BILLIARDS VENDOR ARCHITECTS | ENGINEERS
5 FURNITURE BY TENANT
6 FURNITURE BY MILLWORK VENDOR
7 WASHER & DRYER PURCHASED AND INSTALLED BY G.C.
8 BOWLING SCORING CONSOLE / PEDESTAL BY BOWLING
VENDOR
9 BI-PARTING BLACK CURTAINS TO THE FLOOR AND Grand Rapids | Phoenix | Traverse City
CURTAIN TRACKS BY G.C. (FIELD VERIFY WIDTHS) REFER www.paradigmae.com
TO 3/A-502
11 FURNITURE BY BOWLING VENDOR
NOTE: DO NOT ANCHOR 12 CUSTOM MASKING UNIT AND FILLER PANELS BY BOWLING
MILLWORK TO FLOOR IN VENDOR
PARTY ROOMS, TYP. 21 13 BOWLING BALL RACKS SUPPLIED BY BOWLING VENDOR
14 COSMIC FIXTURE BY A/V VENDOR, FINAL LOCATION TO BE
FIRE DETERMINED BY TENANT
MENS 22 STORAGE UP
STAIR 1
RISER 15 VIDEO PROJECTOR AND MOUNTING HARDWARE BY
108 30 111 113
S-1 30 VENDOR - G.C. TO PROVIDE AND INSTALL 14 GA. (MIN.)
STORAGE UNISTRUT SUPPORT TO STRUCTURE - REFER TO
6 6 112
TYP. 16 OVERHEAD SCORING MONITORS (TRIPLE LCD
FEC CONFIGURATION) BY BOWLING VENDOR, STRUCTURAL
SUPPORT BY G.C. REFER TO
JANITOR
PLUSH 107 34 ELECTRICAL 18 REDEMPTION STORE DISPLAY GONDOLA UNIT BY TENANT
30 VENDOR
STORAGE 114
105 21 (3) 19 FOOD SERVICE EQUIPMENT, WALK-IN COOLERS AND
PARTY
CONDENSING UNITS BY FOOD SERVICE VENDOR
ROOM 1
FAMILY WOMENS 20 POINT OF SALE EQUIPMENT BY VENDOR, SEE ELEC.
110
TOILET 109 21 21 WALL OR CEILING MOUNT T.V. AND MOUNTING BRACKET
106 BY A/V VENDOR - REFER TO INTERIOR ELEVATIONS AT
2/A-502. PROVIDE BLOCKING OR STRUCTURAL SUPPORT PROJECT
FEC TYP. AS REQUIRED. COORDINATE CONDUIT, DATA AND POWER
14 WITH E.C.
48
21 22 22 21 (3) FREIGHT
22 PARTY ROOM AUDIO / VIDEO EQUIPMENT BY A/V VENDOR ROUND1 -
23 BOWLING SERVER BY BOWLING VENDOR, COORDINATE

6 TYP.
6
ELEVATOR
ELEV-1
24
POWER
KARAOKE SERVER BY VENDOR, COORDINATE POWER
PLAZA BONITA
TYP.
6 PARTY 25 SECURITY/SURVEILLANCE SYSTEM BY VENDOR
8
PARTY ROOM 2 26 A/V EQUIPMENT, RACK BY VENDOR. COORDINATE
13 TYP. FE
ROOM 4 121 23 CONDUIT AND POWER
TYP. 21 (3) 24
124 27 GAME NETWORKING SERVER / SYSTEM LOCATION BY
A.V. 25 VENDOR
21 26
BOWLER'S BOWLING BOWLING PINSETTER 115 27
6 28 SATELLITE OR CABLE SYSTEM EQUIPMENT BY TENANT
21 SEATING APPROACH LANES SERVICE 39 28
TYP. 29 29 TELEPHONE BOARD AND PHONE SYSTEM LOCATION
30 6 120 119 118 117
30 STORAGE RACK BY TENANT
TYP. 31 TIME CLOCK BY TENANT, COORDINATE POWER AND DATA
REDEMPTION 11 12 42 34

FEC
STORAGE 32 SAFE EQUIPMENT BY TENANT
123 PARTY TYP. 33 METAL LOCKERS - 12"W x 18"D x 72"H - 6 TIER. (72)
6 ROOM 3 21 (3) 15 LOCKERS TOTAL, REFER TO SPECIFICATIONS
TYP. 34 UTILITY SHELF WITH MOP RACK
122
7
35 EXTERIOR BOWLING PIN SCULPTURE BY TENANT
18 16 MECHANIC'S 36 MOVEABLE BOWLING PIN SCULPTURE BY TENANT
TYP. TYP. 116 37 EXHAUST HOOD BY FOOD SERVICE EQUIPMENT VENDOR,
SEE MECHANICAL
6 21 (3) 38 MILLWORK, COUNTER, AND FINISHES BY MILLWORK
VENDOR
21
22 39 EMBED/TERMINAL SERVER BY VENDOR, COORDINATE
POWER
TENANT
REDEMPTION
STORE
24X24 24X48
41 CUE RACK PROVIDED BY BILLIARDS VENDOR IMPROVEMENT
42 EYE WASH STATION - REFER TO PLUMBING

CWI
125 9 47 KIOSK, BY TENANT
FE

CWO
D

FE-K
19 48 DRINKING FOUNTAIN - REFER TO SPECIFICATIONS. REFER

24X48
24X48
TO SHEET A-401 FOR MOUNTING HEIGHTS, TYP.
(2)

24X48
TYP. 41 TYP.
21 2 21 (3) 3030 PLAZA BONITA RD, SUITE

24X48
24X48
NOTES: 1025

24X48

24X48

18"X18"X12"

24X48
24X48 1. GENERAL CONTRACTOR TO COORDINATE REQUIREMENTS
21 (2) 6 AND INSTALLATION WITH ALL VENDOR AND TENANT ITEMS - NATIONAL CITY, CA 91950
KITCHEN BAR TYP. REFER TO SHEET G-002.

34DR
20 VESTIBULE

24X48
128 130
CLIENT

24X48
SEATING 133
19 TYP. 6
MECHANICAL 131 21 (2)

24X48
MALL
ENTRANCE 21 (2)
38
127 21 BILLIARDS ROUND1

CWI
37 132

C
104
ENTERTAINMENT

D
TS14BLW

CH
H
MATCH LINE - SEE SHEET A-105

CWO
D
MATCH LINE - SEE SHEET A-102 GUEST

D
G
MATCH LINE - SEE SHEET A-103 COUNTER MATCH LINE - SEE SHEET A-104

D
37

CRC-63C
G

CH
D
126

D
(2)
D C
21 (2)

SC-15-TS

CH
20

D
D
C
21 TYP.
H

NOT IN CONTRACT LEASELINE (2) SNACK 6


21 (4) BAR

CRI-12-30-7
38 38

D
21
129
RC
C
H R
D
C 21 21
D

FEC 20
20
36

FEC
20

UP
1 3070 SATURN ST. STE. 200
47 STAIR BREA, CA 92821
S-2

GAME
ROOM
143
FEC

21 (2)

8'-3 7/8"

FEC
VESTIBULE OFFICE 33
32
101 HIGH 21 136 EMPLOYEE STORAGE/
21
VALUE LOUNGE LACTATION RELEASE DATE
STORAGE 135 134
137 DATE DESCRIPTION
5
21
07-06-23 FOR PERMITS
ELECTRICAL 5 07-21-23 FOR BIDS
FEC

103 31 21
PORTRAIT

35

N
FIRST FLOOR KEYNOTE PLAN
SCALE: 3/32" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:39:16 PM

KEYNOTE PLAN

A-101
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT
IMMEDIATELY.
PARADIGM DESIGN
3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF
ARCHITECTS | ENGINEERS
STUD ONLY SHALL BE 24" O.C., U.N.O.
4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF
STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O.
REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING...
Grand Rapids | Phoenix | Traverse City
6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR www.paradigmae.com
SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-
ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,
D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
CEILING
F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
FE BRACKET MOUNTED EXTINGUISHER
5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
G- FE-K TYPE 'K' EXTINGUISHER & CABINET
BOARD ABOVE TO MIN 6" ABOVE CEILING
5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING 10. ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE

MATCH LINE - SEE SHEET A-105


FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
I I.5 J K L L.1 M.1 M 1 2 3 K-
CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL.
L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN PROJECT
5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6" STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE.
M-
MIN. ABOVE CEILING
13. PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT
ROUND1 -

J-J-19-J-J
1 N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
4.1 EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT
A-401 P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING UNATTACHED END(S.)

67'-10 3/4" A 14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED
PLAZA BONITA
R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.
15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL

A-2-X
SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
S-

10'-2 1/4"
1'-6 1/4" PLAN & DETAIL 16/A-501
MENS 16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
ALIGN ALIGN 108 T- 6" HIGH WALL PADDING 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
A-23-A 5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.

J-J-19-J-J
2-HR FIRE BARRIER - U 419 U-
111 FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
JANITOR FROM FACE OF ADJACENT WALL.
107 1 5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
F-J-J-19-J-J 4 V- 19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
UNDERSIDE OF DECK ABOVE
LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO
A-205
24'-2 1/4"

5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE CLOSE OFF SPACES AT TOP OF FURRING.
PLUSH 2 W-
RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
STORAGE 3 110A WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S

15'-0"
105 X- EXISTING TO REMAIN
PARTY INSTRUCTIONS AND FINAL SHOP DRAWINGS.
ROOM 1 Z- NO SHEATHING
WOMENS 110 FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
Z-17-A

Z-17-A

Z-17-A

Z-17-A

Z-17-A
FAMILY 109 4'-3 7/8" 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.)

2'-2 1/8"
TOILET BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
DESIGNED AND DETAILED BY CFMF SUPPLIER.
106 4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
1- EXISTING WALL TO REMAIN 4/A-501

2'-1 7/8"
5.1
105 2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE
A-22-A FEC
110B
B
3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED TENANT

1'-0 3/4"
LOCATIONS BEFORE COMPLETING PROJECT.
IMPROVEMENT

1'-0 3/4"
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F.

A-23-A
3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN 24. PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
12-

3'-1 5/8"
SUPPORT PER DETAIL 5/A-501 G-002 FOR TYPICAL SIZE AND LOCATIONS.
25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
16'-6 5/8"

2-HR FIRE BARRIER - U 419 EXTENTS OF EXISTING STAIR 13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501 SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S
OPENING - CREATE WALLS FROM 7 PARTY A-23-A CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT
. 3 .
2 FLOOR TO CEILING AROUND A-204 ROOM 4 5 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER.
OPENING ON UPPER LEVEL ONLY - A-102 8 3030 PLAZA BONITA RD, SUITE
B A-202 124 15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING.
REFER TO 3 / A-102 1025

18'-6"
A-205

23'-6"
14 121A 16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501

18'-6"
NATIONAL CITY, CA 91950

27'-1 7/8"
124 13 6 DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE.
7 17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
A-205
A-23-A PARTY 18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT CLIENT
15 NOTE:
2'-8"

F-17-J-J-19-J-J 16 ROOM 2 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
121 19-
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ALL EXPOSED STEEL STRUCTURE, INCLUDING BUT NOT LIMITED TO, COLUMNS, ROUND1
4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL BEAMS, DECK AND K-BRACING MUST HAVE MONOCOATING APPLIED.
. 2 .
20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION ENTERTAINMENT
A-23-A
T.O.W. = 4'-0" T.O.W. = 4'-0" A-301 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
13'-6 1/8"

121B 21-
D-26-D

D-26-D

D EXISTING K BRACING A-23-A STUD CAVITY WITH 6" UNFACED BATT INSULATION

A-23-A
22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
6.1 C
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
WALL TYPE - FIRE RATING LEGEND

11'-6"
122 23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
PARTY THERMAFIBER SAFB 2 HOUR FIRE BARRIER
EXISTING K BRACING 12A TYP. REDEMPTION ROOM 3
F-17-J-J-19-J-J STORAGE 9 24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
A-501 122
123 12

23'-10 3/4"
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
Z-17-A TYP. A A-205 STUD CAVITY WITH 6" UNFACED BATT INSULATION
6 10

A-23-A
A-204 11 26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
F-17-J-J-19-J-J
A-23-A

12'-4 3/4"
2-HR FIRE BARRIER - U 419
X-2-A 6 3070 SATURN ST. STE. 200
(2) LAYERS TYPE X GYPSUM
16'-8 3/8" VENDING A-402 BOARD FROM FLOOR TO BREA, CA 92821
. 2 .
124 DECK ABOVE
A-301
6" ACOUSTICAL BATT INSULATION
12B TYP.
24X24 24X48

A-501 6" METAL STUDS @ 16" O.C.

6.8 2 REDEMPTION

CWI
C A-102 STORE ACRYLIC PANEL
125

CWO
D

FE-K
6.9 D LED PANEL, REFER TO ELECTRICAL

24X48
24X48

1'-0"
F-17-A-A-19-A-A Z-17-A U CHANNEL - BRUSHED STAINLESS STEEL
7.1

24X48
T.O. (E) PARAPET
140' - 0"
NOT IN CONTRACT LEASELINE

24X48
24X48

24X48

24X48

18"X18"X12"
A

1'-0"
24X48
24X48

1
4 SCHLUTER RONDEC @
A-202 1N

34DR
A-203 OUTSIDE CORNER, TYP. - 3 5/8" STUD @ 16" O.C. WITH

24X48
BRUSHED STAINLESS STEEL 5/8" GYPSUM BOARD ON

24X48

1'-0"
. 1 . BOTH SIDES (BEYOND).
KITCHEN WALL TILE OVER 5/8"
A-302 EXTEND TO DECK ABOVE
CEMENT BOARD, FROM

24X48
128
MECHANICAL BAR FLOOR TO BULKHEAD
3 5/8" STUD @ 16" O.C. WITH
127 ABOVE - REFER TO

CWI
130 5/8" GYPSUM BOARD ON

C
104A ELEVATION

1'-0"
BOTH SIDES. EXTEND TO

TS14BLW

CH
H
CWO
D
DECK ABOVE

D
G
MATCH LINE - SEE SHEET A-103 MALL 5/8" GYPSUM BOARD @

D
CRC-63C
G

CH
ENTRANCE RECESS - PAINT - PT12, TYP.

D
G

D
104 GUEST

1'-0"
2N COUNTER D C UPPER LEVEL

SC-15-TS

CH
D
D
126 H
C 117' - 0"
4 10'-10" +/- V.I.F
RELEASE DATE
A-202 EXISTING FLOOR
RETURN WALL TILE TO CONSTRUCTION

1'-0"
STOREFRONT, TYP. DATE DESCRIPTION

F-17-A-A-19-A-A EXISTING FLOOR OPENING - 07-06-23 FOR PERMITS


TO REMAIN OPEN 07-21-23 FOR BIDS
5 1/4"
I I.5 K L L.1 M.1 M 1 2 3
STOREFRONT

F. F.
100' - 0"

N
FIRST FLOOR PLAN - A 2 SLOT LIGHT PLAN DETAIL 3 SECTION THROUGH EXISTING STAIR OPENING
SCALE: 1/8" = 1'-0" A-102 SCALE: 3/4" = 1'-0" A-102 SCALE: 1/8" = 1'-0"

A D
PROJECT

2112128GR
SHEET
B C
7/25/2023 3:51:00 PM

FLOOR PLAN A

A-102
KEY PLAN
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT
IMMEDIATELY.
PARADIGM DESIGN
3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF
ARCHITECTS | ENGINEERS
STUD ONLY SHALL BE 24" O.C., U.N.O.
4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF
STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O.
REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING...
Grand Rapids | Phoenix | Traverse City
6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR www.paradigmae.com
SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-
ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,
D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
CEILING
F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
FE BRACKET MOUNTED EXTINGUISHER
I I.5 J K L L.1 M.1 M 1 2 3 5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
G- FE-K TYPE 'K' EXTINGUISHER & CABINET
BOARD ABOVE TO MIN 6" ABOVE CEILING
5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING 10. ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
6 AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE
H-
A-402 FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
K-
KITCHEN CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL.

24X48
128 L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING
MECHANICAL 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN PROJECT
3 BAR
. .
127 5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6" STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE.

CWI
A-301 130 M-

C
104A MIN. ABOVE CEILING

D
ROUND1 -

TS14BLW

CH
13. PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT

H
CWO
D
MATCH LINE - SEE SHEET A-102 N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT

D
G
P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING UNATTACHED END(S.)
MALL
PLAZA BONITA

D
CRC-63C
G

CH
ENTRANCE

D
14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED

D
104 GUEST R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.
2N 2N COUNTER D C

SC-15-TS

CH
T.O.W. = 5' - 0" 15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL

D
D
126 H
C
ABOVE GAME SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
4 S-
SNACK ROOM FLOOR PLAN & DETAIL 16/A-501
16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
A-202 BAR

CRI-12-30-7
D
T- 6" HIGH WALL PADDING 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
129
E 5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.
8.1 U-
F-17-A-A-19-A-A Z-17-A TYP. FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
RC D FROM FACE OF ADJACENT WALL.
8.2
C
H R C 5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
V- 19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
D
3 UNDERSIDE OF DECK ABOVE
FEC
. . LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO
C A-301 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE CLOSE OFF SPACES AT TOP OF FURRING.
8.3 W-
RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S
X- EXISTING TO REMAIN
INSTRUCTIONS AND FINAL SHOP DRAWINGS.
4 Z- NO SHEATHING
2-HR FIRE BARRIER - UL419

6'-0"
A-203 FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
F-17-J-J-19-J-J D-16-D ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.) 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
DESIGNED AND DETAILED BY CFMF SUPPLIER. BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
T.O.W. = 4'-0"
1 4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
9'-9 1/2" 1- EXISTING WALL TO REMAIN 4/A-501
A-202
2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE
3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED TENANT

12'-2 1/2"
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F.
24.
LOCATIONS BEFORE COMPLETING PROJECT.
PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
IMPROVEMENT
3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN
12- G-002 FOR TYPICAL SIZE AND LOCATIONS.
SUPPORT PER DETAIL 5/A-501
12A TYP. 1 25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
A-501 A-203 13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501 SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S
F CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT
FEC 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER. 3030 PLAZA BONITA RD, SUITE
9.1 15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING. 1025
16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501 NATIONAL CITY, CA 91950
17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE.
18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT CLIENT
NOTE:
3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
19-
F
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ALL EXPOSED STEEL STRUCTURE, INCLUDING BUT NOT LIMITED TO, COLUMNS,
BEAMS, DECK AND K-BRACING MUST HAVE MONOCOATING APPLIED.
ROUND1
4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION ENTERTAINMENT
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
X-2-A 21-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
WALL TYPE - FIRE RATING LEGEND
7'-7 3/4"
23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
12A TYP. THERMAFIBER SAFB
F-17-J-J-19-J-J
A-501 24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
2 HOUR FIRE BARRIER
2-HR FIRE BARRIER - UL419 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
12B TYP. G STUD CAVITY WITH 6" UNFACED BATT INSULATION
A-501
26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
10.1
3070 SATURN ST. STE. 200
BREA, CA 92821

3
E 5
A-203
A-202
X-R-20-A-A
X-R-20-A-A
X-R-20-A-A

X-R-20-A-A

2-HR FIRE BARRIER - U 415


104B
103
FEC

X-2-A
X-2-A

X-R-20-A-A X-R-20-A-A
H
A-17-Z

11.1

RELEASE DATE

DATE DESCRIPTION

I I.5 K L L.1 M.1 M 1 2 3 07-06-23 FOR PERMITS


07-21-23 FOR BIDS

N
FIRST FLOOR PLAN - B
SCALE: 1/8" = 1'-0"

A D
PROJECT

2112128GR
SHEET
B C
7/25/2023 3:51:01 PM

FLOOR PLAN B

A-103
KEY PLAN
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT
IMMEDIATELY.
PARADIGM DESIGN
3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF
ARCHITECTS | ENGINEERS
STUD ONLY SHALL BE 24" O.C., U.N.O.
4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF
STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O.
REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING...
Grand Rapids | Phoenix | Traverse City
6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR www.paradigmae.com
SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-
ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,
4 5 6 7 8 D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
CEILING
. 1 . F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
A-301 FE BRACKET MOUNTED EXTINGUISHER
5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
2 G- FE-K TYPE 'K' EXTINGUISHER & CABINET
BOARD ABOVE TO MIN 6" ABOVE CEILING
A-201 10. ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING

24X48
H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE
BAR 134 133A FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
130 PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
10 J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE

D
TS14BLW

CH
MATCH LINE - SEE SHEET A-105 WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
D
A-601 3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
K-
CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL.
SEATING D-14-D

D
CRC-63C

CH
D
131 T.O.W. = 5' - 0" L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN PROJECT
D
D-14-H ABOVE GAME VESTIBULE 5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6" STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE.
ROOM FLOOR M-
SC-15-TS

CH T.O.W. = 5' - 0" 133 MIN. ABOVE CEILING


D

SNACK
ABOVE GAME
ROOM FLOOR 1'-6"
56'-0 5/8" T.O.W. = 5' - 0" N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
13. PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT
EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT ROUND1 -

D-14-H
5'-0" ABOVE GAME A-22-A P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING UNATTACHED END(S.)
BAR
PLAZA BONITA
CRI-12-30-7
D

HOLD ROOM FLOOR


129 14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED
E E R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.

9"
RAMP UP T.O.W. = 5' - 0" RAMP UP 133B 15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL

4'-6"

4'-6"
D-14-H
C
ABOVE GAME SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
S-
H-14-D PLAN & DETAIL 16/A-501
ROOM FLOOR 16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
T.O.W. = 5' - 0" T- 6" HIGH WALL PADDING 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
T.O.W. = 5' - 0" 2'-0" 1 T.O.W. = 5' - 0" ABOVE GAME

FEC
D-14-H

D-14-H
. . WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.
6 5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD
ABOVE GAME A-331 1'-7" ABOVE GAME ROOM FLOOR U-
FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
A-402 ROOM FLOOR ROOM FLOOR FROM FACE OF ADJACENT WALL.
7'-8" 20'-0" 5'-1" 11'-5 1/2" 20'-0" 9'-5 1/2" UP V-
5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
UNDERSIDE OF DECK ABOVE
19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO
1 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE CLOSE OFF SPACES AT TOP OF FURRING.
W-
A-203 A-2-X RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S
X- EXISTING TO REMAIN
STAIR INSTRUCTIONS AND FINAL SHOP DRAWINGS.
S-2 Z- NO SHEATHING
FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.) 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
12A TYP. DESIGNED AND DETAILED BY CFMF SUPPLIER. BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
A-501 1- EXISTING WALL TO REMAIN 4/A-501
2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE 23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
TENANT

A-2-X
F 2 F 3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED

3'-5 1/2"
A-203
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F.
24.
LOCATIONS BEFORE COMPLETING PROJECT.
PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
IMPROVEMENT
3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN
12- G-002 FOR TYPICAL SIZE AND LOCATIONS.
SUPPORT PER DETAIL 5/A-501
25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501 SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S
143 CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT
GAME
ROOM 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER. 3030 PLAZA BONITA RD, SUITE
143 15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING. 1025
16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501 NATIONAL CITY, CA 91950
CONFIRM EXISTING OR 17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE.
PROVIDE CLASS II
VAPOR RETARDER ON 18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT CLIENT
NOTE:
INTERIOR OF STUD 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
19-
A-2-X
FRAMING @ ALL
EXTERIOR WALLS, TYP.
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ALL EXPOSED STEEL STRUCTURE, INCLUDING BUT NOT LIMITED TO, COLUMNS,
BEAMS, DECK AND K-BRACING MUST HAVE MONOCOATING APPLIED.
ROUND1
3 4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
A-203
20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION ENTERTAINMENT
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
21-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
G G 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
B-21-A

. 2 .
23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
THERMAFIBER SAFB
WALL TYPE - FIRE RATING LEGEND
A-302
6'-6 1/4" 19'-0" 24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
2 HOUR FIRE BARRIER
101B 136 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
A-21-B

A-23-A

A-21-A
A-21-B

B-21-A

A-23-A
B-21-A B-21-A
FEC

MAINTAIN EXISTING 2 HR FIRE BARRIER 26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
X-2-A

X-2-B

X-2-B
VESTIBULE A-23-A OFFICE
101 136 STORAGE/
EMPLOYEE
LACTATION 3070 SATURN ST. STE. 200
X-2-A

HIGH
LOUNGE
101A VALUE 134 BREA, CA 92821

REF.
A-2-X STORAGE 135
17
137 18 A-2-X
A-205
103
X-2-A

X-2-B

X-2-B

X-2-A
137 134
UP
H H
. 1 .
A-301

CONFIRM EXISTING OR
PROVIDE CLASS II
VAPOR RETARDER ON
INTERIOR OF STUD
FRAMING @ ALL
EXTERIOR WALLS, TYP.

1
A-201

4 7 8

RELEASE DATE
5 6 DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

N
FIRST FLOOR PLAN - C
SCALE: 1/8" = 1'-0"

A D
PROJECT

2112128GR
SHEET
B C
7/25/2023 3:51:10 PM

FLOOR PLAN C

A-104
KEY PLAN
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT
IMMEDIATELY.
PARADIGM DESIGN
3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF
ARCHITECTS | ENGINEERS
STUD ONLY SHALL BE 24" O.C., U.N.O.
4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF
STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O.
REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING...
Grand Rapids | Phoenix | Traverse City
6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR www.paradigmae.com
SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-
ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,
D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
CEILING
F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
FE BRACKET MOUNTED EXTINGUISHER
5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
CONFIRM EXISTING OR G- FE-K TYPE 'K' EXTINGUISHER & CABINET
BOARD ABOVE TO MIN 6" ABOVE CEILING
PROVIDE NEW CLASS II 10. ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
VAPOR RETARDER ON 5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING
H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE
INTERIOR OF STUD
FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
WALLS @ EXISTING
J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
4 EXTERIOR WALLS, 5 6 7 8 WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
TYP. 3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE
K- LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL.

1 L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN
. . FIRE PROJECT
A-301 5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6" STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE.
RISER M-
MIN. ABOVE CEILING
113
N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
13. PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT
EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT ROUND1 -
A A P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING UNATTACHED END(S.)

STAIR 1 14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED
PLAZA BONITA
R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.
STORAGE S-1
113 PROVIDE TAPE ON FLOOR 15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL
111 OUTLINING REQUIRED

A-22A
435 SF SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
STORAGE CLEARANCES - REFER TO S-
PLAN & DETAIL 16/A-501

ALIGN
112 ELECTRICAL 16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
A-23-A T- 6" HIGH WALL PADDING
111 S-1A 683 SF 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
FEC A-22-A 5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.

A-22-A

B-22-A
T.O.W. = 5' - 0"

A-14-A
U-
ALIGN ABOVE GAME FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
112 FROM FACE OF ADJACENT WALL.
1 ROOM FLOOR 5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
V- 19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
A-403 ELECTRICAL UNDERSIDE OF DECK ABOVE
A-20-B LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO
114 CLOSE OFF SPACES AT TOP OF FURRING.
110A 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE
W-
PARTY RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
ROOM 1 C-19-K WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S
X- EXISTING TO REMAIN
110 ABOVE INSTRUCTIONS AND FINAL SHOP DRAWINGS.
Z- NO SHEATHING
FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
LINE OF CURTAIN WALL ABOVE BOTTOM OF 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
WALL AT 6'-0" ABOVE LANES. REFER TO ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.)
L-X DESIGNED AND DETAILED BY CFMF SUPPLIER. BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
REFLECTED CEILING PLANS AND DETAIL 3/A-502 4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
B B 1- EXISTING WALL TO REMAIN 4/A-501
2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE 23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
TENANT
RAMP UP

3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED
A-23-A

FREIGHT
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F.
24.
LOCATIONS BEFORE COMPLETING PROJECT.
PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
IMPROVEMENT
BLACK MASONITE CLOSURE PANEL ALONG 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN
ELEVATOR 12- G-002 FOR TYPICAL SIZE AND LOCATIONS.
BACK SIDE OF MASKING UNIT ON SELF SUPPORT PER DETAIL 5/A-501
SUPPORTING 2X4 FRAME FROM TOP TO ELEV-1 25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
BOTTOM OF MASKING @ LANE BREAK 13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501 SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S

ALIGN
CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT
114 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER. 3030 PLAZA BONITA RD, SUITE
121A
5 FE 15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING. 1025
16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501 NATIONAL CITY, CA 91950
PARTY A-203 DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE.
17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
ROOM 2

12'-3 3/8"
A.V. 18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
121 6 115 NOTE: CLIENT
BOWLER'S BOWLING BOWLING PINSETTER L-A-22-V 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.

U-22-V
19-
SEATING
120
APPROACH
119
LANES
118
SERVICE
117 115
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ALL EXPOSED STEEL STRUCTURE, INCLUDING BUT NOT LIMITED TO, COLUMNS,
BEAMS, DECK AND K-BRACING MUST HAVE MONOCOATING APPLIED.
ROUND1
A-23-A 4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
12A TYP. 20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION ENTERTAINMENT
A-501
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
A-23-A

116 21-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
FEC

C C

W
22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE

U-18-U
L-A-22-U
122
PARTY 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH

D
ROOM 3 23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
122 THERMAFIBER SAFB
2 15'-6 1/4"
23'-10 3/4"

A-203 24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE

25'-8 1/8"
64'-4 1/8"
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
A-23-A

A-23-A
CO2 TANK - REFER 26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
TO MECHANICAL
6 VENDING MECHANIC'S
124 116 3070 SATURN ST. STE. 200

L-A-22-A
A-402 BREA, CA 92821
1/4" MASONITE CLOSURE PANEL ATTACHED 5 ALIGN
. .
TO SIDE OF LANE FROM SLOPED FLOOR TO
SERVICE AISLE. PAINT PT-7 A-331

D-14-H

A-17-B

A-22-B
Z-17-H

. .
T.O.W. = 5'-0" ABOVE
43'-3 5/8" A-331 30'-6" SLOPED FLOOR GAME ROOM FLOOR FE

D 117 D
4'-6"
9"

T.O.W. = 5' - 0" T.O.W. = 5' - 0"


D-14-H

D-14-H

A-22-B
24X48

ABOVE GAME ABOVE GAME


A-17-Z

A-17-Z
TYP.

TYP.
ROOM FLOOR ROOM FLOOR
12'-2 7/8"

1
24X48

D-14-D
5'-7 1/8" 50'-0 5/8" 2
A-204 T.O.W. = 5' - 0" 5
ABOVE GAME A-204 A-22-A
24X48

D-14-H ROOM FLOOR


3 2
T.O.W. = 5' - 0" 4 VESTIBULE
ABOVE GAME 133 A-201
24X48

ROOM FLOOR
BAR 134 133A . 3 .
130 A-301
D
TS14BLW

CH
D

SEATING MATCH LINE - SEE SHEET A-104


D
CRC-63C

CH
D

131
D
SC-15-TS

CH
D

56'-0 5/8"

RELEASE DATE
. 1 .
A-301 DATE DESCRIPTION

07-06-23 FOR PERMITS


4 5 6 7 8 07-21-23 FOR BIDS

. 3 .
A-301

N
FIRST FLOOR PLAN - D
SCALE: 1/8" = 1'-0"

A D
PROJECT

2112128GR
SHEET
B C
7/25/2023 3:39:46 PM

FLOOR PLAN D

A-105
KEY PLAN
_CEILING LEGEND _
HEIGHT ABOVE
A 8'-0" FINISHED FLOOR

CEILING TYPE

GYPSUM BOARD BULKHEAD / CEILING


PARADIGM DESIGN
6" SOUND BATT INSULATION ON TOP
OF CEILING TILES ARCHITECTS | ENGINEERS
A 2x4 ROCKFON ARTIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION
SYSTEM FINISH: WHITE

. 1 .
C 2x4 ROCKFON TROPIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION
A-301
SYSTEM FINISH: WHITE
I I.5 J K L L.1 M.1 M 1 2 3 4 5 6 7 8 Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
D 2x2 ROCKFON ARTIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION
SYSTEM FINISH: WHITE

4.1
E SUSPENDED GYPSUM BOARD CEILING. PROVIDE W. P. GYP. BOARD
@ ALL "WET LOCATIONS". REFER TO PLAN FOR LOCATIONS
A
STAIR 1 FIRE F 2x4 ROCKFON HYGIENIC PLUS LAY IN WITH 15/16" SUSPENSION
STORAGE
S-1 RISER SYSTEM FINISH: WHITE
MENS 111 STORAGE 113
108 N 112
M 9' - 0" H SUSPENDED CEILING SYSTEM - SEE DETAIL
N
PARTY
L 6"HIGH ARMSTRONG AXIOM TRIM - "SILVER SATIN"
PLUSH ROOM 1
STORAGE 110 ELECTRICAL
105 F JANITOR
9' - 0" WOMENS 114 M 2x2 ROCKFOHYGIENIC PLUS LAY IN WITH 15/16" SUSPENSION
D 11' - 6" SYSTEM COLOR: WHITE
N 107 109

FAMILY
N
N EXPOSED CONSTRUCTION
TOILET
106 S REFLECTIVE CEILING PANEL - ISC 2'X2' MIRROR CEILING PANELS
5.1 M 9' - 0"
B PROJECT

8
.
A-162
.
FREIGHT
ELEVATOR
ROUND1 -
BULKHEAD @ PARTY
ROOM 2
ELEV-1 _REFLECTED CEILING PLAN GENERAL NOTES_
1 CEILING GRID ALIGNMENT AND LOCATIONS TO COORDINATE WITH
PLAZA BONITA
8'-6" A.F.F. MECHANICAL AND ELECTRICAL REQUIREMENTS
PARTY 121
ROOM 4 REDEMPTION BULKHEAD @ 6'-0" AFF - 2 REFER TO ELECTRICAL LIGHTING PLANS FOR LIGHTING LAYOUT
D 11' - 6"
STORAGE REFER TO DETAIL 3 / A-502
124
123 A.V. 3 REFER TO MECHANICAL PLANS AND SPECIFICATIONS FOR PAINTING
D 11' - 6" BOWLING BOWLING 115 OF DIFFUSERS AND GRILLES
N APPROACH LANES N 4 PROVIDE TYPICAL CONTROL JOINTS IN ALL GYP. BD. BULKHEADS @
119 118 PINSETTER 30'-0" MAX. SPACING
SERVICE
5 REFER TO SHEET A-602 FOR FINISH KEY
117
6.1 C 11' - 6" C
6 FIRE-WRAPPED GREASE DUCTS SHALL NOT BE PAINTED - REFER TO
PARTY MECHANICAL
ROOM 3 7 ALL PIPING, CLAMPS, SUPPORTS, ETC. SHALL BE FASTENED TO JOISTS
122 OR BEAMS. DO NOT ATTACH ANYTHING DIRECTLY TO THE DECK,
D 11' - 6" N CEILING SUPPORT SYSTEM OR DUCTWORK ABOVE.
VENDING
124
MECHANIC'S
REDEMPTION E 6' - 6" 116
STORE
125

NOT IN CONTRACT LEASELINE TENANT


6.8 IMPROVEMENT
6.9 D
2
7.1 KITCHEN A-162
128
3030 PLAZA BONITA RD, SUITE
VESTIBULE 1025
1N BAR NATIONAL CITY, CA 91950
133
130
. 1 .
SEATING D 12' - 6"
A-302 131 CLIENT
MECHANICAL
MALL 127 ROUND1
ENTRANCE
104
ENTERTAINMENT
GUEST
2N COUNTER
126

E 10' - 0" SNACK


BAR E
8.1
129

6'-0 7/8"

6'-0 7/8"
8.2

8.3 25'-0" 1'-11 1/8" 12'-8 1/2" 25'-0"

L 14' - 0" E 14' - 0" L 14' - 0" E 14' - 0"

3070 SATURN ST. STE. 200


BREA, CA 92821
1
A-162

F
9.1

9'-0 1/4" 3'-0" 8'-0" 3'-0"


PLASTIC LAMINATE ON
BOTTOM AND FACE -
WILSONART TAN ECHO

3'-0"
E 8' - 0" 7941K-18
. 4 .

6'-0"
A-162 VINYL WALL COVERING
ON INSET - GRAVITY G

4'-4 3/8"
DIGITAL WALL G1-12-04

3'-0"
EVENING LIGHT - LOVE
10.1 LETTER TWV-C-IL

VESTIBULE
101 HIGH
VALUE STORAGE/
EMPLOYEE
STORAGE LACTATION
OFFICE LOUNGE
137 134 RELEASE DATE
136 135
E 9' - 0" A 9' - 0" A 9' - 0" A 9' - 0"
DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS
H

11.1

I I.5 K L L.1 M.1 M 1 2 3 4 7 8

5 1 6
.
A-301
.

N
FIRST FLOOR REFLECTED CEILING PLAN
SCALE: 3/32" = 1'-0"
PROJECT

2112128GR
SHEET
7/25/2023 3:47:48 PM

REFLECTED CEILING
PLAN

A-161
_CEILING LEGEND _
5 HEIGHT ABOVE
A 8'-0" FINISHED FLOOR

CEILING TYPE
1'-1 7/8"

7'-2 7/8" 10 3/4" EXISTING STRUCTURE GYPSUM BOARD BULKHEAD / CEILING


L 12' - 0"
6" SOUND BATT INSULATION ON TOP
OF CEILING TILES

2'-0"
D 12' - 0" A 2x4 ROCKFON ARTIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION PARADIGM DESIGN

4'-9"
SYSTEM FINISH: WHITE
L 12' - 0" ARCHITECTS | ENGINEERS
C 2x4 ROCKFON TROPIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION
SYSTEM FINISH: WHITE
THREADED ROD

10'-0"

4'-9"
D 12' - 8" LOCATION, TYP. D 2x2 ROCKFON ARTIC WHITE SQ. LAY IN WITH 15/16" SUSPENSION
REFER TO DETAIL SYSTEM FINISH: WHITE
213/S-302 Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
5/8" GYPSUM BOARD ON METAL STUDS - EXTEND TO STRUCTURE E SUSPENDED GYPSUM BOARD CEILING. PROVIDE W. P. GYP. BOARD
@ ALL "WET LOCATIONS". REFER TO PLAN FOR LOCATIONS
2 3

6"
F 2x4 ROCKFON HYGIENIC PLUS LAY IN WITH 15/16" SUSPENSION

7'-8 7/8"
2'-0"
B.O. CEILING
ANIT-THEFT MIRROR, B B SYSTEM FINISH: WHITE
13'-6" A.F.F.
REFER TO ELEVATION

2'-5"
H SUSPENDED CEILING SYSTEM - SEE DETAIL
C C NEW BEAMS - REFER TO STRUCTURAL
LAY IN CEILING - REFER TO RCP
L 6"HIGH ARMSTRONG AXIOM TRIM - "SILVER SATIN"

2'-0"
5/8" PLYWOOD BEHIND SIGN FOR SIGN ATTACHMENT
M 2x2 ROCKFOHYGIENIC PLUS LAY IN WITH 15/16" SUSPENSION

4'-9"
SYSTEM COLOR: WHITE
. 9 . TYP.
B.O. BULKHEAD
S 13' - 6" A-162 11'-6" A.F.F. N EXPOSED CONSTRUCTION
SIGNAGE BY SIGNAGE VENDOR
L 12' - 0"
S REFLECTIVE CEILING PANEL - ISC 2'X2' MIRROR CEILING PANELS

4'-9"
5/8" GYPSUM BOARD ON METAL STUD - _REFLECTED CEILING PLAN GENERAL NOTES_
L 12' - 0" EXTEND STUD TO STRUCTURE ABOVE 1 CEILING GRID ALIGNMENT AND LOCATIONS TO COORDINATE WITH
MECHANICAL AND ELECTRICAL REQUIREMENTS

1'-7 1/4"
18'-0"
EDGE OF COLUMN WRAP - BEYOND
D 12' - 8" 2 REFER TO ELECTRICAL LIGHTING PLANS FOR LIGHTING LAYOUT PROJECT
. 3 .
3 REFER TO MECHANICAL PLANS AND SPECIFICATIONS FOR PAINTING
A-162
D 12' - 0" OF DIFFUSERS AND GRILLES ROUND1 -

4'-9"
D 13' - 6"
4 PROVIDE TYPICAL CONTROL JOINTS IN ALL GYP. BD. BULKHEADS @

REDEMPTION 5
30'-0" MAX. SPACING
REFER TO SHEET A-602 FOR FINISH KEY
PLAZA BONITA
STORE
D 125 D
6 FIRE-WRAPPED GREASE DUCTS SHALL NOT BE PAINTED - REFER TO

4'-9"
MECHANICAL
7 ALL PIPING, CLAMPS, SUPPORTS, ETC. SHALL BE FASTENED TO JOISTS

2'-0"
OR BEAMS. DO NOT ATTACH ANYTHING DIRECTLY TO THE DECK,
. 5 .
CEILING SUPPORT SYSTEM OR DUCTWORK ABOVE.

3'-0 7/8"
KITCHEN A-162

5'-6 5/8"
128
E 13' - 6 3/8" 1'-10 5/8" F 9' - 0" C C 3 REDEMPTION STORE ENTRY

1'-1"

1'-1"
E 14' - 0" F 9' - 0" BAR SCALE: 3/4" = 1'-0"

3'-1"
A-162
130

2'-0"
E 14' - 0"
E 12' - 6"

4'-9"
MECHANICAL
127 . 9 . TYP.
A-162

A 9' - 0"

4'-9"
23'-4 7/8"

D 12' - 0"
GUEST 13' - 11" L 12' - 0" TENANT

1'-7 1/4"

1'-7 1/4"
COUNTER
IMPROVEMENT

18'-0"

22'-0"
126 SUPPORT - ATTACH TO
M 11' - 2" D 12' - 8" STRUCTURE ABOVE
SNACK

20'-0"
E D 10' - 0" BAR E
6

4'-9"
. . 129
5'-0"

A-162 DOWNLIGHT - REFER TO ELECTRICAL


L 12' - 0"
3030 PLAZA BONITA RD, SUITE
E 9' - 8" E 10' - 10"
3 5/8" METAL STUDS @ 16" O.C. 1025
5'-0"

7 NATIONAL CITY, CA 91950


5'-3 7/8"

. . E 10' - 10"

4'-9"
A-162
7'-10 3/8" 24'-7 1/8" EQ 3'-0" 4'-11 3/8" 3'-0" EQ 8'-3 1/8" 10'-6 1/2" PLASTIC LAMINATE ON (2)
LAYERS OF 3/4" PLYWOOD
CLIENT

2'-0"
2 3
3'-0"

2'-0" 12'-0" 2'-0"


PANEL AND SUPPORT ROUND1
ENTERTAINMENT
2'-6"

16'-0"

H 14' - 0"

8"
10'-0" 27'-4 1/2" H 14' - 3" 24'-4 7/8"

4"
PLASTIC LAMINATE ON
BOTTOM, INSET AND SIDES - REFER TO CEILING PLAN
NEVAMAR CUTTING EDGE
WZ2009 ARP 5

1 ENLARGED CEILING PLAN - REDEMPTION STORE, STORAGE, KITCHEN, SNACK BAR, BAR 2 ENLARGED CEILING PLAN - BOWLER'S SEATING 4 CEILING - CLOUD DETAIL
A-161 SCALE: 1/8" = 1'-0" A-161 SCALE: 3/16" = 1'-0" A-161 SCALE: 1" = 1'-0"

REFER TO STRUCTURAL FOR


ATTACHMENT TO EXIST. STRUCTURE.
3070 SATURN ST. STE. 200
PAINT ALL EXPOSED WIRES AND BREA, CA 92821
STRUCTURAL ELEMENTS PT-1.
PROVIDE J-TRIM AT ALL
PROVIDE J-TRIM AT ALL EXPOSED EDGES, TYP.
EXPOSED EDGES, TYP.

REFER TO RCP REFER TO RCP


B
REFER TO STRUCTURAL FOR
REFER TO STRUCTURAL FOR ATTACHMENT TO EXIST. STRUCTURE.
PROVIDE J-TRIM AT ALL PAINT ALL EXPOSED WIRES AND
ATTACHMENT TO EXIST. STRUCTURE. EXPOSED EDGES, TYP.
PAINT ALL EXPOSED WIRES AND STRUCTURAL ELEMENTS PT-1.
3"

STRUCTURAL ELEMENTS PT-1. B.O. CEILING


(1) LAYER 5/8" GYP. BD. 14'-0" A.F.F. (1) LAYER 5/8" GYP. BD. ON

2'-10"
ON 6" 20 GA. METAL 3 5/8" 20 GA. METAL STUDS
STUDS AT 24" O.C. PLASTIC LAMINATE OVER @ 24" O.C., TYP.
(1) LAYER OF 5/8" PT-3
PLYWOOD
B.O. CEILING
14'-0" A.F.F. 6"x20 GA. METAL STUDS @
24" O.C. 6"x20 GA. METAL STUDS @ 24" O.C.
2'-6"

PT-2 8 3/4"
CEILING, REFER TO PT-2
1/2"

REFLECTED CEILING PLAN B.O. BULKHEAD


LIT SIGN - REFER TO ELECTRICAL (1) LAYER 5/8" GYP. BD. ON
LIGHT FIXTURE, REFER
PT-17
8" 10'-10" A.F.F.
6" 20 GA. METAL STUDS @
TO ELECTRICAL 24" O.C., TYP.
7 3/4"

6" MIN.

PT-3

1'-2"
B.O. BULKHEAD BOTTOM OF BULKHEAD
6" MIN.

12'-6" A.F.F. 7'-0" A.F.F.


(1) LAYER 5/8" GYP. BD. PT-6
4"

PT-17 ON 3 5/8" 20 GA. METAL


1'-4" B.O. BULKHEAD RELEASE DATE
PT-5 STUDS @ 24" O.C. 9'-8" A.F.F.
NOTE: REFER TO STRUCTURAL FOR
4"

ADDITIONAL METAL STUD FRAMING PT-2 DATE DESCRIPTION


B.O. BULKHEAD
AND FASTENER SIZES, SPACING, AND 10'-10" A.F.F.
QUANTITIES, ETC. NOTE: REFER TO STRUCTURAL FOR 07-06-23 FOR PERMITS
ADDITIONAL METAL STUD FRAMING
AND FASTENER SIZES, SPACING, AND 07-21-23 FOR BIDS
QUANTITIES, ETC.

5 LIGHT COVE DETAIL @ BAR 6 SNACK BAR SOFFIT 7 GUEST AND AMUSEMENT COUNTER SOFFIT 8 BULKHEAD @ DRINKING FOUNTAIN
A-162 SCALE: 1" = 1'-0" A-162 SCALE: 1" = 1'-0" A-162 SCALE: 1" = 1'-0" A-161 SCALE: 3/4" = 1'-0"

CEILING - REFER TO
REFLECTED CEILING PLAN
6" 6"
B.O. CEILING
6" AXIOM TRIM 12'-8" A.F.F.
LED - REFER TO
B.O. CEILING ELECTRICAL
REFER TO RCP B.O. CEILING
12'-0" A.F.F. PROJECT
CEILING - REFER TO
REFLECTED CEILING PLAN CEILING - REFER TO 6" AXIOM TRIM CEILING - REFER TO
REFLECTED CEILING PLAN REFLECTED CEILING PLAN
2112128GR
9 BOWLER'S SEATING SOFFIT DETAIL 10 BOWLER'S SEATING SOFFIT DETAIL SHEET
7/25/2023 3:49:08 PM

A-162 SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"

REFLECTED CEILING
PLAN AND DETAILS

A-162
ROOF PLAN LEGEND
SYMBOL DESCRIPTION

AREA OF TAPERED ROOF INSULATION

PARADIGM DESIGN
ROOF SLOPE DUE TO STRUCTURE
2 3 ARCHITECTS | ENGINEERS
ROOF SLOPE DUE TO TAPERED INSULATION

RD = ROOF DRAIN
ORD = OVERFLOW ROOF DRAIN
Grand Rapids | Phoenix | Traverse City
www.paradigmae.com

ROOF PLAN GENERAL


I I.5 J K L L.1M.1 M1 4 5 6 7 8 NOTES
NO. NOTE

1. ALL ROOF SURFACES (INSULATION, TAPERED


EXISTING OVERFLOW DRAIN EXISTING OVERFLOW DRAIN INSULATION, CRICKETS, ETC.) SHALL SLOPE 1/4" PER 1'-0"
4.1 4.1
MIN, UNLESS NOTED OTHERWISE.
A A 2. ROOFING MEMBRANE IS TO BE SINGLE PLY 60 MIL. FULLY
ADHERED EPDM
3. ALL FLASHING MATERIALS TO BE COMPATIBLE WITH
ROOFING MEMBRANE PER MANUFACTURER'S
RECOMMENDATIONS.
EXISTING ROOF DRAIN EXISTING ROOF DRAIN
4. REFER TO DETAIL #/A-XXX FOR TYPICAL ROOF
EXISTING CRICKET PENETRATIONS.
EXISTING CRICKET 5. ROOF INSULATION IS TO BE MIN. (2) LAYERS OF 1.8"
MINIMUM (3.6" MINIMUM TOTAL) THICKNESS
POLYISOCYANURATE WITH A MINIMUM LONG TERM
THERMAL RESISTANCE (LTTR) VALUE OF R-20. STAGGER
JOINTS BETWEEN LAYERS.
6. PROVIDE TAPERED ROOF INSULATION AT ALL PROJECT
LOCATIONS SHOWN SHADED ON ROOF PLAN AND
DRAINAGE SADDLES AS REQUIRED AT ALL LOCATIONS
WHERE ROOF-TOP EQUIPMENT CURBS INTERFERE WITH
ROOF SLOPE TO DRAINS.
ROUND1 -
EXISTING
5.1
B
5.1
RTU
EXISTING
B
7. PROVIDE WALKWAY PADS AROUND PERIMETER OF HVAC
ROOF-TOP EQUIPMENT PLAZA BONITA
8. PROVIDE ADDITIONAL WALKWAY PADS BELOW ALL HIGH
RTU
ROOF THAT SPILL ONTO LOW ROOFS. ADHERE TO ROOF
PER MANUFACTURER'S RECOMMENDATIONS.
9. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR OTHER ROOF PENETRATIONS NOT
EXISTING SHOWN ON THIS SHEET.
EXHAUST
VENT

EXISTING EXISTING SLOPE EXISTING SLOPE

EXISTING EXISTING
EXHAUST EXHAUST
FAN FAN
EXISTING
6.1 C 6.1 EXHAUST C
FAN

TENANT
IMPROVEMENT

EXISTING
6.8 6.8 EXHAUST 3030 PLAZA BONITA RD, SUITE
VENT 1025
6.9 D 6.9 EXISTING RTU TO BE D NATIONAL CITY, CA 91950
REPLACED, TYP. EXISTING
7.1 7.1 RTU
REMOVE STRUCTURE CLIENT
TO ALLOW REMOVAL
OF EXISTING RTU
UNITS, REBUILD ROUND1
STRUCTURE AFTER
NEW RTU UNITS ARE
EXTERIOR WALL
BELOW
ENTERTAINMENT
INSTALLED
EXISTING SLOPE

EXISTING SLOPE
EXISTING
RTU

8.1 E 8.1 E
EXISTING SLOPE

EXISTING SLOPE
8.2 8.2

8.3 8.3 3070 SATURN ST. STE. 200


BREA, CA 92821

EXISTING EXISTING
RTU AC EXISTING
EXHAUST
VENT
F F
9.1 9.1

PATCH / REPAIR / REPLACE ROOF SYSTEM (ROOFING, DECK, EXISTING SLOPE EXISTING SLOPE
INSULATION, ETC.) AS NECESSITATED BY REMOVAL OF
MECHANICAL, ELECTRICAL, PLUMBING, EQUIPMENT, ETC.
REPLACE ROOF SYSTEM AS REQUIRED TO INSTALL ALL NEW
CONSTRUCTION.
EXISTING
RTU

EXISTING
RTU

G G

10.1 10.1
RELEASE DATE

DATE DESCRIPTION
EXTERIOR WALL
BELOW 07-06-23 FOR PERMITS
EXISTING CRICKET EXISTING CRICKET 07-21-23 FOR BIDS

EXISTING ROOF DRAIN EXISTING ROOF DRAIN

H H

EXISTING OVERFLOW DRAIN EXISTING OVERFLOW DRAIN


11.1 11.1

N
ROOF PLAN
SCALE: 3/32" = 1'-0"
I I.5 K L L.1M.1 M1 2 3 4 7 8

PROJECT

5 6
2112128GR
SHEET
7/25/2023 3:39:59 PM

ARCHITECTURAL ROOF
PLAN

A-191
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

SIGNAGE NOTE: NEW 'ROUND 1' WALL SIGN BY SIGN VENDOR ATTACHED
TO EXISTING WALL; FIELD VERIFY WALL CONSTRUCTION. G.C. TO
REMOVE AND REPLACE PORTION OF EXTERIOR WALL AS REQUIRED TO
INSTALL FIRE RETARDANT TREATED 3/4" PLYWOOD BLOCKING PANEL AND
BLOCKING. REPAIR WALL TO MATCH EXISTING CONSTRUCTION AND
FLUSH SURFACE WITH ADJACENT. PROVIDE ELECTRICAL TO NEW SIGN IN
SIMILAR PROCESS. SEE ELECTRICAL PLANS. T.O. (E) PARAPET
140' - 0"

PT 2 TYP. PT 12 TYP.

EXISTING EXTERIOR BLOCK, TYP.


PROJECT

ROUND1 -
PROVIDE NEW METAL PLAZA BONITA
PROVIDE NEW METAL VERTICAL SLOT LIGHTS VERTICAL SLOT LIGHTS COPING, AND EIFS
COPING, AND EIFS PT 2 WHERE METAL CANOPY
WHERE METAL CANOPY PT 14 WAS REMOVED, PAINT

1'-0"
TYP. PT 2 PT 12 TYP.
WAS REMOVED, PAINT PT 14 PT-2 TYP.
PT-2 TYP.

3'-0"
TYP. PT 12 PT 14
PT 14

TYP. PT 14

NEW
EQ EQ EQ EQ
LIGHTING 101A NEW
FIXTURE
LIGHTING
FIXTURE
F. F.
100' - 0"
SCHLUTER JOLLY, TYP

2'-6"
SCHLUTER JOLLY, TYP

+/-
TYP. WT PT 12 TYP. WT TYP.

1 EXTERIOR ELEVATION - SOUTH NEW TILE AND BACKER BOARD, TYP. TO MATCH
HEIGHT AND EXTENTS OF EXISTING TILE BEING
TENANT
A-104 SCALE: 1/8" = 1'-0" REPLACED, VERIFY IN FIELD
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
NEW METAL COPING
ENTERTAINMENT
SIGNAGE NOTE: NEW 'ROUND 1' AND 'EXIT ONLY' WALL SIGN BY SIGN
VENDOR ATTACHED TO EXISTING WALL; FIELD VERIFY WALL NEW EIFS WALL SYSTEM
CONSTRUCTION. G.C. TO REMOVE AND REPLACE PORTION OF EXTERIOR 2
. .
WALL AS REQUIRED TO INSTALL FIRE RETARDANT TREATED 3/4"
A-301
PLYWOOD BLOCKING PANEL AND BLOCKING. REPAIR WALL TO MATCH
EXISTING CONSTRUCTION AND FLUSH SURFACE WITH ADJACENT. REPAIR EIFS WHERE TRIM
PIECE WAS REMOVED
VERTICAL SLOT LIGHTS, TYP. T.O. (E) PARAPET
140' - 0"
PT 2

PROVIDE NEW METAL


COPING, AND EIFS
WHERE METAL CANOPY
PT 12 TYP. WAS REMOVED, PAINT 3070 SATURN ST. STE. 200
PT-2 TYP. BREA, CA 92821

17'-0"
18'-0"
LOUVER- REFER TO
MECHANICAL - PAINT TO
PT 2 PT 2 MATCH WALL
PROVIDE NEW METAL 5'-4 1/2"±
COPING, AND EIFS PT 14 TYP.
WHERE METAL CANOPY
WAS REMOVED, PAINT TYP. PT 14 PT 14
2'-4 7/8"

1'-6"
PT-2 TYP.
1'-0" PT 12
+/-

PT 2 TYP. PT 14 PT 2

PT 14
OPEN
10 AM - 2 AM

EQ. EQ. 143


133A PIN SCULPTURE BY TENANT -
TYP. PT 12 POLYURETHANE FINISHES FRP OVER
STEEL SKIN AND STEEL FRAMING -
F. F. INSTALLED BY G.C.
100' - 0"
NEW TYP. WT PT 2 SCHLUTER - JOLLY, TYP. TYP. WT CONCRETE BASE -
LIGHTING REFER TO DETAIL
EXTERIOR FACE OF SCHLUTER - JOLLY, TYP.
FIXTURE,
DOOR AND FRAME 2 1" CHAMFER EDGE,
TYP. . .
A-301 TYP.

1'-0"
NEW TILE AND BACKER BOARD, TYP. TO MATCH RELEASE DATE
HEIGHT AND EXTENTS OF EXISTING TILE BEING
4'-0" Ø
REPLACED, VERIFY IN FIELD DATE DESCRIPTION

07-06-23 FOR PERMITS


2 EXTERIOR ELEVATION - EAST 3 PIN SCULPTURE 07-21-23 FOR BIDS
A-104 SCALE: 1/8" = 1'-0" A-201 SCALE: 1/2" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:40:03 PM

EXTERIOR ELEVATIONS

A-201
VERTICAL ACRYLIC PANEL W/ RECESSED
LED LIGHT - REFER TO DETAIL 2 / A-102 8/4 X 6 AZEK BOARD WITH RECESSED SIGNAGE NOTE: NEW 'ROUND 1' WALL
LIGHTS - REFER TO SECTION AND ELEC. SIGN BY VENDOR. PROVIDE FIRE 14'-0"
RETARDENT TREATED 3/4" PLYWOOD
STRIP LIGHTS, TYP. PT 12 WT 10 BLOCKING PANEL - REFER TO ELEC. VERTICAL SLOT LIGHTS PT 12 WT 10 PT 12
B.O. SOFFIT
113' - 3 3/4"
NOT IN CONTRACT LEASELINE
FINISHES BY LANDLORD

12'-0"
WT 11
WT 11 WT 11 WT 11

8'-0"
B D C OPEN TO GAME FLOOR C F E

6'-0"
PARADIGM DESIGN
F. F. ARCHITECTS | ENGINEERS
100' - 0"

1'-0"
60 DEGREE ANGLE WT 11 SCHLUTER DILEX AHKA - TYP. PT 12 SCHLUTER DILEX AHKA - TYP.
@ WALL TO FLOOR TRANSITION @ WALL TO FLOOR TRANSITION

1 INTERIOR ELEVATION - WEST ENTRANCE Grand Rapids | Phoenix | Traverse City


A-102 SCALE: 1/8" = 1'-0" www.paradigmae.com

PT 1 TYP.
PAINT CHANGE
112' - 9"

PT 36

105

F. F.
100' - 0"
PROJECT
TYP. RB 1
2 INTERIOR ELEVATION - NORTH ARCADE ROUND1 -
A-102 SCALE: 1/8" = 1'-0"

PLAZA BONITA

LIT SIGNS - REFER TO ELECTRICAL

PT 1 TYP.
PT 26
PAINT CHANGE
112'-9"

PT 36

PT 37 OPEN TO PT 37
ARCADE OPEN TO
BEYOND ARCADE
BEYOND

F.F.
100'-0"
RB 1 TYP. TENANT
IMPROVEMENT
3 INTERIOR ELEVATION - EAST ARCADE
A-702 SCALE: 1/8" = 1'-0"

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

PT 1 TYP.
PAINT CHANGE
112'-9"
PT 12 ALL SIDES PT 37

ALL SIDES PT 37

PT 37
E F C OPEN TO MALL C PT 37 D B

F.F. 3070 SATURN ST. STE. 200


100'-0"
BREA, CA 92821
TYP. RB 1

4 INTERIOR ELEVATION - WEST MALL CONCOURSE


A-102 SCALE: 1/8" = 1'-0"

PT 1 TYP.
PAINT CHANGE
112'-9"
PT 36

PT 36

104B

F.F.
RELEASE DATE
100'-0"
TYP. RB 1 DATE DESCRIPTION

5 INTERIOR ELEVATION - SOUTH ARCADE 07-06-23 FOR PERMITS


07-21-23 FOR BIDS
A-103 SCALE: 1/8" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:40:05 PM

INTERIOR ELEVATIONS

A-202
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

SIGNAGE BY VENDOR - BEYOND

LIT SIGN BY VENDOR (ON BULKHEAD)


REFER TO ELECTRICAL PT 5

PAINT CHANGE
112'-9"
PT 17 PT 14* PT 12 PT 1 TYP.
PT 29 GR 1
PL 5
PT 12 SS 3 SS 3 SS 3 PT 37
WT 1 PT 5 OPEN TO BEYOND
PT 3 128 117
PT 15 PT 15 PT 15 PT 15 PT 15

PROJECT
PT 29 TYP. RB 1

MILLWORK BY VENDOR 1 INTERIOR ELEVATION - NORTH


SCALE: 1/8" = 1'-0"
ROUND1 -
A-102
PLAZA BONITA

PT 1 TYP.
PAINT CHANGE
112'-9"
PT 14
PT 37 PT 37 PT 36 PT 36

SS 3 SS 3 SS 3 PT 37
133G
112 103
PT 15 PT 15 PT 15

RB 1 TYP.
RB 1 TYP.
2 INTERIOR ELEVATION - EAST TENANT
A-102 SCALE: 1/8" = 1'-0"
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
PT 1 TYP. NATIONAL CITY, CA 91950
PAINT CHANGE
112'-9" TENANT
PT 12

PT 36 PT 36 PT 36 ROUND1
ENTERTAINMENT
136 101B

RB 1 TYP. RB 1 TYP.

3 INTERIOR ELEVATION - SOUTH


A-102 SCALE: 1/8" = 1'-0"

3070 SATURN ST. STE. 200


BREA, CA 92821
PT 1 TYP. TYP. PT 1
PAINT CHANGE
112'-9"
PT 26

PT 37 PT 37

OPEN TO ARCADE
OPEN TO
ARCADE

2'-6" 2'-6"
RB 1 TYP. RB 1 TYP.

4 INTERIOR ELEVATION - WEST


A-102 SCALE: 1/8" = 1'-0"

PT 1 TYP.
PAINT CHANGE
112'-9"
PT 14 10'-0"
PT 14 PT 14 RELEASE DATE

5"
4"
PT 9 DATE DESCRIPTION

5'-0" 4"
12'-0"
111 07-06-23 FOR PERMITS
PT 14
07-21-23 FOR BIDS

RB 1 TYP.
RB 1 TYP.

5 INTERIOR ELEVATION - BOWLING NORTH WALL


A-105
A-102 SCALE: 1/8" = 1'-0"

PT 9

117 PT 14 PT 14 PROJECT
PT 14

RB 1 TYP.

6 INTERIOR ELEVATION - BOWLING SOUTH WALL SHEET


7/25/2023 3:40:07 PM

A-105 SCALE: 1/8" = 1'-0"

INTERIOR ELEVATIONS

A-203
PT 1 TYP.
PT 17
PAINT CHANGE
112'-9"

PT 5
PT 14* PT 12 PT 20 PT 16
PT 12 TV LIT SHELVES BY VENDOR - REFER TO ELECTRICAL TV GR 1 GR 1 TYP. PARADIGM DESIGN
ARCHITECTS | ENGINEERS
PT 17 PT 17
TV TV TV

PT 14
SS 3
Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
122 121A 110A
PT 5
ALL SIDES

MILLWORK - BY VENDOR RB 1 TYP. RB 1 TYP. GR 1 TYP. RB 1 TYP. GR 1 TYP.

1 ENLARGED INTERIOR ELEVATION - BAR


A-105 SCALE: 1/4" = 1'-0"

PT 1 TYP.
ALL SIDES PT 12 PT 1 TYP.

PAINT CHANGE PAINT CHANGE PROJECT


112'-9" 112' - 9"
PT 29 7'-0"

WT 15
PT 14
ROUND1 -
PT 22

WT 14
PLAZA BONITA
PT 3 PT 3 PT 12

OPEN TO
GR 1 TYP. M W

11'-4"

11'-4"
REDEMPTION STORE
OPEN TO OPEN TO
MENS WOMENS
124 106

RB 1 TYP. WT 15 VERTICAL
GR 1 TYP. RB 1 TYP. RB 1 TYP.

6 ENLARGED INTERIOR ELEVATION - REDEMPTION STORE 7 MENS 108, WOMENS 109 - NORTH ELEVATION
A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0"
TENANT
IMPROVEMENT

PT 1 TYP. PT 1 TYP.

PAINT CHANGE PAINT CHANGE 3030 PLAZA BONITA RD, SUITE


112'-9" 112'-9"
1025
NATIONAL CITY, CA 91950

PT 14* CLIENT
PT 14* GR 1
GR 1 ROUND1
ENTERTAINMENT
SS 3 CR 1 SS 3

WC 1 WC 1

RB 1 TYP. RB 1 TYP.

2 INTERIOR ELEVATION - BILLIARDS NORTH 3 INTERIOR ELEVATION - BILLIARDS EAST


A-105 SCALE: 1/4" = 1'-0" A-105 SCALE: 1/4" = 1'-0"
3070 SATURN ST. STE. 200
BREA, CA 92821

PT 15
PT 15 SS 3 PT 15 PT 14 SS 3

WC 1 WC 1
WC 1 WC 1

RB 1 TYP. RB 1 TYP. RB 1 TYP.

4 INTERIOR ELEVATION - BILLIARDS SOUTH 5 INTERIOR ELEVATION - BILLIARDS WEST


A-101
A-105 SCALE: 1/4" = 1'-0" A-105 SCALE: 1/4" = 1'-0" RELEASE DATE

DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

2112128GR
SHEET
7/25/2023 3:40:11 PM

INTERIOR ELEVATIONS

A-204
CEILING MOUNTED
PROJECTOR

GR 1 TYP. @ PARTY ROOM STOREFRONT CEILING MOUNTED


CEILING MOUNTED GR 1 TYP. SPEAKER
CEILING MOUNTED PROJECTOR CEILING MOUNTED PARADIGM DESIGN
SPEAKER, TYP. SCREEN SPEAKER
SPEAKER TV PT 14* TYP. TV TV ARCHITECTS | ENGINEERS
GR 1 TYP. GR 1 TYP.
PT 14* TYP. PT 25 GR 1 PT 14* TYP.
PT 19 GR 1
PT 14* PT 14*
CR 1 PT 19 PT 25

5'-0"
CR 1 @ DOOR
CR 1 TYP.
110B Grand Rapids | Phoenix | Traverse City
110A
110B www.paradigmae.com

A.V. CABINET RB 1 RB 1 TYP. RB 1 TYP. RB 1 TYP. A.V. CABINET A.V. CABINET RB 1 TYP.
BY VENDOR BY VENDOR BY VENDOR

5 PARTY ROOM 2 - NORTH ELEVATION


1 PARTY ROOM 1 - NORTH ELEVATION 2 PARTY ROOM 1 - EAST ELEVATION 3 PARTY ROOM 1 - SOUTH ELEVATION 4 PARTY ROOM 1 - WEST ELEVATION A-102 SCALE: 1/4" = 1'-0"
A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0"

CEILING MOUNTED
PROJECTOR

PT 19 GR 1 TYP. @ PARTY ROOM STOREFRONT PT 19 TYP.


GR 1 TYP. CEILING MOUNTED
PT 14* TYP. SPEAKER CEILING MOUNTED
TV PROJECTOR CEILING SPEAKER TV GR 1 TYP. @ PARTY ROOM STOREFRONT PROJECT
SCREEN MOUNTED
PT 21 SPEAKER, TYP. GR 1 TYP.
GR 1 GR 1 PT 14* TYP.
PT 19 TYP.
ROUND1 -
PT 14*
@ DOOR CR 1
CR 1
PT 14*
@ DOOR CR 1 PLAZA BONITA
121A 121B 121B 122
CR 1 TYP.

RB 1 TYP. RB 1 TYP. RB 1 TYP. A.V. CABINET RB 1 TYP. RB 1 TYP.


BY VENDOR

6 PARTY ROOM 2 - EAST ELEVATION 7 PARTY ROOM 2 - SOUTH ELEVATION 8 PARTY ROOM 2 - WEST ELEVATION 9 PARTY ROOM 3 - NORTH ELEVATION 10 PARTY ROOM 3 - EAST ELEVATION
A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
A-102

GR 1 TYP. @ PARTY ROOM STOREFRONT TENANT


CEILING MOUNTED CEILING MOUNTED
TV
SPEAKER
PROJECTOR CEILING GR 1 TYP. TV
SPEAKER PROJECTOR CEILING IMPROVEMENT
PT 22 PT 26 SCREEN MOUNTED
SCREEN MOUNTED PT 14* TYP. SPEAKER, TYP.
PT 19 GR 1 TYP. SPEAKER, TYP.
PT 14* TYP.
PT 19 TYP.

CR 1 TYP. CR 1 TYP. CR 1
CR 1
3030 PLAZA BONITA RD, SUITE
CR 1
1025
124 NATIONAL CITY, CA 91950
TO CENTER
30" AFF

CLIENT

ROUND1
A.V. CABINET
RB 1 A.V. CABINET
BY VENDOR
A.V. CABINET
BY VENDOR
RB 1 TYP. RB 1 TYP. RB 1 TYP.
A.V. CABINET
BY VENDOR
BY VENDOR RB 1 TYP. ENTERTAINMENT
11 PARTY ROOM 3 - SOUTH ELEVATION 12 PARTY ROOM 3 - WEST ELEVATION 13 PARTY ROOM 4 - WEST ELEVATION
SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0"
A-102
14 PARTY ROOM 4 - NORTH ELEVATION 15 PARTY ROOM 4 - EAST ELEVATION
A-102 SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0"

PAINTER TO PREP WALL RECEIVING WALL


GRAPHICS AS REQUIRED TO PROVIDE A
SMOOTH PAINT FINISH FREE OF DEBRIS TO
ALLOW FOR PROPER INSTALLATION OF
CUSTOM VINYL GRAPHICS, TYP.

3070 SATURN ST. STE. 200


GR 1 TYP. BREA, CA 92821
PT 14* TYP.

2'-6"
GR 1 TYP.
PT 14* TYP.

8"
LOCKERS - REFER DISPLAY SHELF, TYP. -
TV TO SPECIFICATIONS REFER TO DETAIL 12 / A-502
REFRIGERATOR GLASS DISPLAY CASE, TYP. -
- BY VENDOR REFER TO DETAILS 13 / A-502 ,

6'-0"
TA-7
PT 18 14 / A-502 & 15 / A-502
TA-4 PT 18 WS 1 WS 1 WS 1
CR 1 GR 1 TYP.
OPEN TO PT 14* TYP.
OFFICE

GR 1 TYP. DISPLAY CUBBIES, TYP. -


2'-10"

2'-10"
TOP

PT 14* TYP. REFER TO DETAILS 10 / A-502 &


11 / A-502

RB 1 TYP. RB 1 REFER TO SHEET A-401 FOR WALL MOUNTED RB 1 RB 1 TYP.


TOILET ACCESSORIES HAND SINK - BY
LEGEND VENDOR

19 REDEMPTION STORE- NORTH ELEVATION


16 PARTY ROOM 4 - SOUTH ELEVATION 17 BREAK ROOM - NORTH ELEVATION 18 BREAK ROOM - WEST ELEVATION A-402 SCALE: 1/4" = 1'-0"
A-102 SCALE: 1/4" = 1'-0" A-104 SCALE: 1/4" = 1'-0" A-104 SCALE: 1/4" = 1'-0"

RELEASE DATE

DATE DESCRIPTION

07-06-23 FOR PERMITS


PAINTER TO PREP WALL RECEIVING WALL PAINTER TO PREP WALL RECEIVING WALL 07-21-23 FOR BIDS
PAINTER TO PREP WALL RECEIVING WALL
GRAPHICS AS REQUIRED TO PROVIDE A GRAPHICS AS REQUIRED TO PROVIDE A GRAPHICS AS REQUIRED TO PROVIDE A
SMOOTH PAINT FINISH FREE OF DEBRIS TO SMOOTH PAINT FINISH FREE OF DEBRIS TO SMOOTH PAINT FINISH FREE OF DEBRIS TO
ALLOW FOR PROPER INSTALLATION OF ALLOW FOR PROPER INSTALLATION OF ALLOW FOR PROPER INSTALLATION OF
CUSTOM VINYL GRAPHICS, TYP. CUSTOM VINYL GRAPHICS, TYP. CUSTOM VINYL GRAPHICS, TYP.
PT 14* TYP.
GR 1 TYP.
GR 1 TYP. PT 12 ALL SIDES GR 1 TYP.
PT 14* TYP. PT 14* TYP.
WS 1 TYP.
2'-6"

2'-6"

GR 1 WS 1
TYP.
PT 14* TYP.
8"

8"

8"
DISPLAY SHELF, TYP. -
WS 1 TYP. REFER TO DETAIL 12 / A-502 MIRROR - 24"X102"

GR 1 GLASS DISPLAY CASE, TYP. -


OPEN TO
6'-0"

6'-0"

6'-0"
REFER TO DETAILS 13 / A-502, OPEN TO
PT 14* WS 1 GAME ROOM
14 / A-502 & 15 / A-502
GUEST
@ DOOR WS 1 TYP. COUNTER
DISPLAY CUBBIES, TYP. -
MIRROR - 24" X 102" 123 GR 1 TYP. REFER TO DETAILS 10 / A-502 &
11 / A-5022
PT 14* TYP.
DISPLAY CUBBIES, TYP. -
2'-10"

2'-10"
REFER TO DETAILS 10 / A-502 & PROJECT
11 / A-502
F. F.
100' - 0"
T-SHIRT WALL, TYP. - REFER TO DETAILS 16-18/A-502 RB 1 TYP. RB 1 TYP. RB 1 TYP. MILLWORK BY
VENDOR RB 1 TYP. 2112128GR
SHEET
7/25/2023 3:40:17 PM

20 REDEMPTION STORE - EAST ELEVATION 21 REDEMPTION STORE - SOUTH ELEVATION 22 REDEMPTION STORE - WEST ELEVATION
A-402 SCALE: 1/4" = 1'-0" A-402 SCALE: 1/4" = 1'-0" A-402 SCALE: 1/4" = 1'-0" INTERIOR ELEVATIONS

A-205
NOTE:
REFER TO INTERIOR ELEVATIONS, ROOM FINISH
SCHEDULE, AND WALL FINISH PLAN FOR FINISHES

PARADIGM DESIGN
ARCHITECTS | ENGINEERS

A B C D E F G H
Grand Rapids | Phoenix | Traverse City
www.paradigmae.com

. 2 . . 3 .

A-301 A-301 2
A-302

UPPER LEVEL
117' - 0"

BOWLING
STAIR 1 SEATING
LANES VESTIBULE
S-1 112 131
118 101

F. F.
100' - 0"
2 3
. .
. . PROJECT
A-301 A-301

ROUND1 -
PLAZA BONITA
1 BUILDING SECTION NORTH-SOUTH
A-104 SCALE: 1/8" = 1'-0"

. 3 .
I I.5 J L.1 M.1 M 1 A-102 2 3 4 5 6 7 8

. 1 .
A-301

UPPER LEVEL
117' - 0"
TENANT
. 8 . IMPROVEMENT
A-162

BOWLER'S BOWLING
SEATING APPROACH
120 119 BOWLING PINSETTER
PARTY REDEMPTION PARTY LANES SERVICE 3030 PLAZA BONITA RD, SUITE
A.V. 1025
ROOM 4 STORAGE ROOM 2 118 117
105 110B 111 114 115
124 123 121 NATIONAL CITY, CA 91950
F. F.
100' - 0" CLIENT

. 1 .
ROUND1
A-301 ENTERTAINMENT

2 BUILDING SECTION EAST-WEST


A-102 SCALE: 1/8" = 1'-0"

3070 SATURN ST. STE. 200


BREA, CA 92821

I I.5 J K L L.1 M.1 M


1 2 3 4 5 6 7 8

. 1 .
A-301

UPPER LEVEL
117' - 0"
1 SIM.
8
. .
A-302 A-162

GUEST SNACK
COUNTER BAR BAR SEATING
126 129 130 131
128 117
F. F.
100' - 0"

. 1 .
A-301

RELEASE DATE
3 BUILDING SECTION EAST-WEST VESTIBULE DATE DESCRIPTION
A-103 SCALE: 3/32" = 1'-0"
07-06-23 FOR PERMITS
07-21-23 FOR BIDS

PROJECT

2112128GR
SHEET
7/25/2023 3:40:22 PM

BUILDING SECTIONS

A-301
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

I I.5

UPPER LEVEL UPPER LEVEL


117' - 0" 117' - 0" PROJECT

ROUND1 -
EXISTING
EXISTING FLOOR DECK
EXISTING FLOOR DECK PLAZA BONITA
STRUCTURE

5/8" GYPSUM BOARD -


EXTEND TO DECK ABOVE

EXISTING STRUCTURE
6" METAL FRAMING - ATTACH
TO EXISTING STRUCTURE
B.O. CEILING
113'-3 3/4"
EXISTING
MALL CEILING HORIZONTAL BRACING @ 24".
ATTACH TO VERTICAL STUDS EACH
END WITH (2) #10 SCREWS.
5/8" PLYWOOD FOR SIGN OVERHEAD ROLLING GRILL W/ SELF-
ATTACHMENT - SUPPORTING STEEL COLUMNS, AND
PAINTED/SMOOTH FINISH TRACK BY DOOR MANUFACTURER.
REFER TO DOOR SCHEDULE
ROUND1 SIGN BY SIGN
VENDOR - REFER TO
INTERIOR ELEVATION TENANT
8/4 X 6 AZEK BOARD -
SPACED EVENLY BOX HEADER - REFER
IMPROVEMENT
TO DETAIL X / S-502 B.O. BULKHEAD
5/8" GYP. BOARD
110'-0"
METAL CORNER BEAD 5/8" GYP. BOARD ONE SIDE
10 3/8" 1'-4 1/8"
BOX HEADER - REFER 3030 PLAZA BONITA RD, SUITE
TO DETAIL X / S-502 9 1/2" 1025
NEW STOREFRONT SYSTEM -
ATTACH TO EXISTING STRUCTURE NATIONAL CITY, CA 91950

CLIENT

ROUND1
MALL CONCOURSE ROUND 1 ENTERTAINMENT

NEW STOREFRONT SYSTEM -


REFER TO DOOR SCHEDULE

VESTIBULE
101 3070 SATURN ST. STE. 200
BREA, CA 92821

EXISTING FLOOR SLAB


F. F. F. F.
100' - 0" 100' - 0"

RELEASE DATE

DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

1 SECTION - MALL CONCOURSE ENTRANCE 2 SECTION @ MAIN ENTRANCE


A-102 SCALE: 3/4" = 1'-0" A-104 SCALE: 3/4" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:40:23 PM

ENLARGED SECTION
DETAILS

A-302
NOTE:
REFER TO INTERIOR ELEVATIONS, ROOM FINISH
SCHEDULE, AND WALL FINISH PLAN FOR FINISHES

1'-0" 6
PARADIGM DESIGN
1 1/2 Ø . .

STAINLESS STEEL A-331 ARCHITECTS | ENGINEERS


RETURN END
PIPE HANDRAIL 1'-0" (4) EQUAL SPACES @5'-0"= 20'-0" 1'-0" TO WALL
1'-0"
FINISH WALL SURFACE - RETURN END TO WALL 1 1/2"Ø STAINLESS
REFER TO FLOOR PLAN OR TURN DOWN TO STEEL PIPE RAIL
FLOOR, PROVIDE SLEEVE
Grand Rapids | Phoenix | Traverse City

2'-10" HANDRAIL
AND CONCEALED

2'-10"

TRANSITION
FLOOR FRAMING BY RESILIENT STAIR 1 1/2" Ø STAINLESS FASTENERS AT FLOOR www.paradigmae.com

BRUNSWICK TREAD AND 2 1/4" STEEL PIPE HANDRAIL


CONT. RESILIENT
RISER (TYP.) TRANSITION STRIP
5'-0" CLEAR MIN. RAMP (1:12 SLOPE MAX., TYP.) 5'-0" CLEAR MIN.
CL HANDRAIL FLOOR FRAMING
1'-0" 1'-0" 2'-10" A.F.F.
BY BRUNSWICK

TRANSITION
2"
EQ
3/4" DIA. STAINLESS STEEL
1'-6"

EQ
ROD WELD TO HANDRAIL

EQ
RAILING MOUNT BRACKET
(2) LAYERS OF 3/4" FIRE RETARDANT TREATED GENERAL CONTRACTOR TO
ANCHOR w/ EXPANSION HEAD
PLYWOOD SHEATHING OVER 3 5/8" METAL STUDS COMPLETELY FILL VOIDS BETWEEN
BOLTS INTO
BOWLING LANE SLEEPERS WITH
BLOCKING
UNFACED FIBERGLASS BATT INSULATION
FIREBLOCKING, SEE PLAN 3/4" FIRE RETARDANT 2X FIRE RETARDANT TREATED
TREATED SHEATHING WOOD BLOCKING AS REQ'D AT
TREAD AND RISER STUD WALL LOCATIONS
METAL STUD
FRAMING AT 16" O.C. PROJECT
2 HANDRAIL DETAIL 3 RAMP SECTION AT BOWLER'S SEATING
1 SECTION AT BOWLER'S STAIR A-331 SCALE: 3" = 1'-0" A-103
A-403 SCALE: 1/2" = 1'-0"
A-104 SCALE: 3/4" = 1'-0" A-402 ROUND1 -
PLAZA BONITA

2
A-331

1/4" MASONITE CLOSURE


. 5 . PANEL ATTACHED TO
TRANSITION

A-331 SIDE OF LANE AT SLOPED


FLOOR. PAINT PT-7
30'-6" SLOPED FLOOR (1:20 SLOPE MAX.)
(2) LAYERS OF 3/4" FIRE
CONT. RESILIENT EXIST. WALL (2) LAYERS OF 3/4" FIRE RETARDANT TREATED PLYWOOD
FLOOR FRAMING TRANSITION STRIP (2) LAYERS OF 3/4" FIRE RETARDANT RETARDANT TREATED SHEATHING
BY BRUNSWICK TREATED PLYWOOD SHEATHING OVER PLYWOOD SHEATHING

TRANSITION
3 5/8" METAL STUDS @ 16" O.C.
3 5/8" METAL STUDS
TENANT

1'-6"
EXIST. SLAB
IMPROVEMENT

3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 2'-6" O.C. 3030 PLAZA BONITA RD, SUITE
MAX - ATTACH TO EACH JOIST 3 5/8" METAL STUDS @ 2'-6" O.C.
MAX - ATTACH TO EACH JOIST 1025
EXIST. SLAB NATIONAL CITY, CA 91950

CLIENT
4 SERVICE AISLE SLOPED FLOOR SECTION 5 SERVICE AISLE SLOPED FLOOR SECTION 6 TYPICAL RAMP SECTION @ LOW WALLS
A-105
A-102 SCALE: 1/2" = 1'-0" A-105
A-102
A-331
SCALE: 3/4" = 1'-0" A-331 SCALE: 3/4" = 1'-0" ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

RELEASE DATE

DATE DESCRIPTION

07-06-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

2112128GR
SHEET
7/25/2023 3:40:25 PM

STAIR SECTIONS &


DETAILS

A-331
_TOILET ROOM GENERAL NOTES_ _TOILET ACCESSORIES LEGEND WALL CONSTRUCTION LEGEND
1 FOR TYPICAL MOUNTING HEIGHTS OF FIXTURES AND ACCESSORIES REFER
TO DETAILS 1-2/A-401
LEGEND SYMBOL INDICATOR
KEY
2 INSULATE ALL EXPOSED PIPES PER BARRIER FREE STANDARDS
TA-1 TOILET PARTITION
3 G.C. TO PROVIDE BACKING IN WALLS FOR ALL GRAB BARS, PARTITIONS AND TA-2 URINAL SCREEN
ACCESSORIES TA-3 TOILET PAPER DISPENSER
4 REFER TO DETAILS 17-22/A-401 FOR WALL TILE PATTERN IN RESTROOMS TA-4.1 PAPER TOWEL DISPENSER
PARADIGM DESIGN
5 PROVIDE SCHLUTER - SATIN ANODIZED ALUMINUM RONDEC AT ALL WALL TA-6.1 WASTE RECEPTACLE
OUTSIDE CORNERS TA-6.2 WASTE CHUTE ARCHITECTS | ENGINEERS
6 PROVIDE SCHLUTER - SATIN ANODIZED ALUMINUM DILEX COVE WHERE WALL TA-7 SOAP DISPENSER - WALL MOUNTED
TILE MEETS FLOOR TILE TA-7.1 SOAP DISPENSER
7 REFER TO FLOOR PLAN FOR WALL CONSTRUCTION LEGEND TA-8 GRAB BAR - REFER TO TYP. BARRIER FREE ELEVATIONS
TA-9 SANITARY NAPKIN DISPOSAL
TA-10 SEAT-COVER DISPENSER
Grand Rapids | Phoenix | Traverse City
TA-11 MIRROR
www.paradigmae.com
TA-13 HAND DRYER WITH RECESS KIT
TA-14 DIAPER CHANGING STATION
PROVIDE GRAB BARS:
A. 42" MIN. LONG ON SIDEWALL STARTING 12" MAX. FROM THE REAR WALL. TA-15 MOP HOLDER
TA-16 SOLID SURFACE COUNTERTOP
SHEATHING TYPES
B. 36" MIN. LONG ON REAR WALL; FROM CENTERLINE, 24" MIN. TO FLUSH SIDE, 12" MIN. TO WALL SIDE.
C. 18" MIN. LONG VERTICAL ON SIDEWALL STARTING 40" FROM FLOOR, AND 40" OFF OF BACK WALL A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
D. GRAB BAR TO WITHSTAND 250# OF FORCE AND DEFLECTION NOT TO EXCEED 1/2" AT MIDPOINT OF BAR. M 1 2 B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING
E. FOR AMBULATORY BATHROOM STALLS PROVIDE (1) 42" HORIZONTAL GRAB BAR AND (1) 18" VERTICAL 5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK
GRAB BAR ON EACH SIDE WALL C-
ABOVE
NOTES: D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING
• ALL DIMENSIONS SHOWN COMPLY A.D.A. STANDARDS, G.C. TO CONFIRM
COMPLIANCE WITH STATE AND LOCAL BARRIER FREE CODES. 5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE
E-
• CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF CEILING
ACCESSORIES IN COMPLIANCE WITH ALL BUILDING CODES. A A F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING
• DIMENSIONS SHOWN HERE ARE MEASURED FROM FACE/SURFACE OF
FINISH MATERIAL TO FACE OF FINISH MATERIAL. 5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
G-
BOARD ABOVE TO MIN 6" ABOVE CEILING

G-22-Z
G-21-A
Z-22-G 5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING
15'-7 1/4" 4'-7 1/4" 36'-4 1/4" H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT
FULL HEIGHT STUDS.
10
54" MIN A-401 TYP. TA-1 J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
A-402
30" CLEAR MENS 3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE PROJECT

10'-11 1/4"
42" MIN 12" MIN TA-13 108 TYP. TA-3 TA-8 K-
2 CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502
CL MAX TYP. TA-7.1
39" - 41" TA-6.2 F-22-G
L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING
ROUND1 -

9'-5 1/8"

3'-9 7/8"
36" MAX 15" CL 15"
TA-16 5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6"
SEE DISPENSER MIN MIN A-22-F M-
MIN. ABOVE CEILING
18" MIN

TYP. TA-2 TYP. TA-10 TA-8


CENTERLINE OF
& RECEPTACLE 36" MIN TA-14
PLAZA BONITA

Z-17-G
LOCATION C
12" L 24" N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
12" MIN

24" MIN. DISPENSER OUTLET

Z-17-G

2'-3 7/8"
REQUIREMENTS MIN MIN P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
LOCATED IN
HATCHED AREA E-21-F
FLUSH
39" MIN - 41" MAX

JANITOR TA-15
48" MAX

R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE

E-21-F
TOP OF GRIP
TOP OF GRIP
1 1/2"
MIN

CONTROL

36" MAX TO
36" MAX TO

33" MIN TO
33" MIN TO

107 E-21-Z

SURFACE
SURFACE

OPEN LOCATED ON
CENTERLINE OF OPEN SIDE SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH
SIDE OF A-22-E S-
18" MIN

DISPENSER OUTLET

1'-1 3/4"
17"-19"

17"-19"
PLAN & DETAIL 16/A-501
SEAT

MAX
STALL

17"
LOCATED IN

8'-7 3/8"
TYP. TA-10

G-17-Z
HATCHED AREA T- 6" HIGH WALL PADDING

5'-11 1/2"
42" MAX TYP. TA-9 5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD
16"-18" U-
TA-8 FRAMING
E-21-A TYP. TA-3
CENTERLINE OF

Z-17-E
5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
WATER CLOSET V-
UNDERSIDE OF DECK ABOVE

9 3/4"
WALL MOUNT DISPENSER LOCATIONS SIDE WALL - GRAB BAR LOCATIONS BACK WALL - GRAB BAR LOCATIONS URINAL CLEARANCE
(SURFACE, SEMI-RECESSED, OR RECESSED) A-22-F 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE
TA-14 TYP. TA-1 TA-8 W-
RESISTANT GYPSUM BOARD ABOVE TO DECK
3

9 3/4"

15'-6 1/4"
X- EXISTING TO REMAIN
TA-16 WOMENS
TYP. BARRIER FREE ELEVATIONS

16'-2"
TA-11 A-401 Z- NO SHEATHING

F-17-Z
TA-8 109
TA-13 FRAMING TYPES
5 TA-9 4

10'-9 3/4"
TA-6.1 8 F-21-A ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.)
10

7'-0"
TA-3 DESIGNED AND DETAILED BY CFMF SUPPLIER.
A-22-G
A-401
FAMILY A-402 F-22-F TENANT

W-22-G
6 1- EXISTING WALL TO REMAIN

MIRROR
7
TOILET
106
TA-8
TA-6.2
TA-7.1 TYP. TA-11 TA-14 2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE IMPROVEMENT

5'-1"
G-22-A

Z-22-F
3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE

Z-17-F
SEAT COVER 11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F.
ELECTRIC WASTE HAND DRYER KID'S HEIGHT SOAP FIRE EXTINGUISHER BABY CHANGING
DISPENSER 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN
WATER RECEPTACLE HAND DRYER DISPENSER CABINET STATION

1'-1 3/4"
F-22-Z 12-
COOLER F-22-Z Z-22-F SUPPORT PER DETAIL 5/A-501
BFEC B
ADA HEIGHT 30" TO 45"
13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501
3030 PLAZA BONITA RD, SUITE
1025

7 3/4"
W-22-G
W-22-A

A-22-G
14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT NATIONAL CITY, CA 91950
SPOUT OUTLET

A-22-F

A-22-Z
45" TO 59"
TO CONTROLS
REFLECTING
36" MAX. TO

TO CONTROLS

ABOVE
40" MAX. TO

SURFACE

15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING
40" MAX.

MAX.

4'-0"
35" MAX.

48"

W-22-A
W-22-Z
A-22-B
44"
2'-7 1/2"

2'-7 1/2"

ABOVE ABOVE 16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501 CLIENT
17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
1'-0 1/4"
6'-11 1/2" 19'-0 1/2" 16'-0 1/2" 13'-6" 18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT ROUND1
M 1 2
SPOUT OUTLET LOCATED
5" MAX. FROM FRONT NOTE:
REFER TO ELEVATION FOR EXTENT OF CEMENTBOARD BEHIND TILE 19-
3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ENTERTAINMENT
EDGE AND 15" MIN. FROM MOUNT ALL NON-BARRIER FREE
VERTICAL SUPPORT 4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
ACCESSORIES ACCORDING TO 20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION
MANUFACTURER'S RECOMMENDATIONS.
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
21-
STUD CAVITY WITH 6" UNFACED BATT INSULATION

BARRIER FREE ACCESSORY HEIGHTS 1 ENLARGED PLAN - FAMILY RM, JANITOR, MENS AND WOMENS 22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
SCALE: 1/4" = 1'-0" A-102 SCALE: 1/4" = 1'-0" 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
THERMAFIBER SAFB
24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
VERTICAL AND STAGGER STUD CAVITY WITH 6" UNFACED BATT INSULATION
WT 4
AT SINK WALL (FIELD)
WT 5 SINK WALL (ACCENT) NOTE: REFER TO A-402 FOR 26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT 3070 SATURN ST. STE. 200
NOTE: REFER TO A-402 FOR WALL TILE PATTERNS, TYP
WALL TILE PATTERNS, TYP 6" 2'-0" 6" 2'-0" 6" 2'-0" 6" 2'-0" 6" 2'-0" 2'-6"
BREA, CA 92821

REFER TO
1" 3'-0" 1" 3'-0" 1" 3'-0" 1" DETAIL 3/A-402 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 3'-0" 1" 5'-0"
FOR WALL TILE
TYP. TA-1 TYP. TA-1
TYP. TA-8 TYP. TA-2 TYP. TA-8

TA-6.2 TA-13 TYP. TYP. TA-10


TYP. TA-3 TA-16 TYP. TA-7.1
TA-14
TYP. TA-10 TYP. TA-3
TA-6.1
TA-16 TYP. TA-9

5'-1" 3'-1" 3'-1" 3'-1" 19'-11" 1'-6" 2'-6" 2'-6" 2'-6" 2'-6" 3'-6"
3'-1" 3'-1" 3'-1" 3'-1" 3'-1" 3'-1" 3'-1" 5'-1"

2 MENS 108 - SOUTH ELEVATION 3 WOMENS 109 - NORTH ELEVATION


A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0"

10 1/8" 14'-0" +/- 10 1/8" NOTE: REFER TO A-402 FOR


WALL TILE PATTERNS, TYP RELEASE DATE
FULL TILES

DATE DESCRIPTION
36"X168" OPEN TO 07-06-23 FOR PERMITS
3'-0" TA-11 REFER TO DETAIL 5 / A-402 REFER TO DETAIL 4 / A-402
TA-1 GAME FOR WALL TILE FOR WALL TILE REFER TO DETAIL 4 / A-402 07-21-23 FOR BIDS
FLOOR REFER TO DETAIL 4 / A-402 FOR WALL TILE
TA-11 FOR WALL TILE
TA-10 TA-10
TA-8
TA-14 TA-8 TA-13
TA-6.2 TA-13
TA-14
TA-3 TA-3
TA-6.1
TA-6.1
TA-9 TA-16
TYP. TA-7.1 TA-6.1 TA-9
TA-16
1'-6" 1'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 7'-9"

4 WOMENS 109 - SOUTH ELEVATION 5 FAMILY TOILET 106 - NORTH ELEVATION 6 FAMILY TOILET 106 - EAST ELEVATION 7 FAMILY TOILET 106 - SOUTH ELEVATION 8 FAMILY TOILET 106 - WEST ELEVATION
A-401 SCALE: 1/4" = 1'-0"
A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 3:40:31 PM

ENLARGED TOILET ROOM


PLANS AND ELEVATIONS

A-401
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT PARADIGM DESIGN
REFER TO ELEVATION REFER TO ELEVATION RANDOM ACCENT TILE IMMEDIATELY.
REFER TO ELEVATION REFER TO ELEVATION 6" TOP (3) ROWS OF TILE TURN TILE VERTICAL AND STAGGER ARCHITECTS | ENGINEERS
REFER TO ELEVATION 6" 1'-0"
REFER TO ELEVATION SCHLUTER RONDEC PT 14 2'-0" PT 14 AT BACK OF SINK WALL ONLY 3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF
TYP.
PT 14 TYP. STUD ONLY SHALL BE 24" O.C., U.N.O.
WT 8 WT 4 PT 14 SCHLUTER RONDEC SCHLUTER RONDEC PT 14 4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
SCHLUTER RONDEC WT 4
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
TURN TILE VERTICAL
SCHLUTER RONDEC

TYP.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF

2'-0"
AND STAGGER FAMILY
WT 8 WT 5 RESTROOM WT 4 STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O. Grand Rapids | Phoenix | Traverse City
AT BACK OF SINK
WT 6 (TYP. ACCENT) FAMILY REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING... www.paradigmae.com
WALL ONLY VERTICAL
1'-4" RESTROOM
WT 3 6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR
WT 9 TYP. SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.

8'-0"

2'-0"

8'-0"

8'-0"
8'-0"

8'-0"
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
FAMILY 7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
RESTROOM
(TYP. FIELD) 5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-

3'-0"
WB 3 WB 3 ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,
WB 3 D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
WB 3 E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
WB 3 CEILING
F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
WOMENS RESTROOM TILE TYPICAL MEN AND FAMILY TOILET FAMILY TOILET RESTROOM 5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
FE BRACKET MOUNTED EXTINGUISHER
G-
1 PATTERN @ SINK WALL 2 WOMENS TILE PATTERN 3 MENS RESTROOM SINK TILE PATTERN 4 RESTROOM TILE PATTERN 5 TILE PATTERN @ SINK WALL BOARD ABOVE TO MIN 6" ABOVE CEILING
10.
FE-K TYPE 'K' EXTINGUISHER & CABINET
ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" A-401 SCALE: 1/4" = 1'-0" 5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING
H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE
A-602 A-602 A-602 A-602 A-602
A-702 A-702 A-702 A-702 A-702 FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
K-
CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL. PROJECT
L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN

2'-3" 3"
M-
5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6"
MIN. ABOVE CEILING
13.
STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE.

PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT


ROUND1 -
1/2"
2'-0" STAINLESS STEEL UNDER
MOUNT SINK AND FAUCET,
N-
P-
1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
(2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT
UNATTACHED END(S.)
PLAZA BONITA
. 8 .
SEE PLUMBING 14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED
2 3 R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.
A-402 L2x2x1/4 STEEL ANGLE
FASTENED TO HSS 15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL
T.O. TUBE STEEL SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
2'-8 3/4" A.F.F. SOLID SURFACE COUNTER S-
PLAN & DETAIL 16/A-501

5"
OVER 3/4" MARINE GRADE 16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
PLYWOOD T- 6" HIGH WALL PADDING 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.
HSS 3.5x3.5x3/8 U-
FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
B-22-A

8" FROM FACE OF ADJACENT WALL.

2'-10"
5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
NOTE: WATER SUPPLY AND DRAIN V- 19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
UNDERSIDE OF DECK ABOVE
LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO

2'-3"
PIPES UNDER LAVATORIES AND
SINKS SHALL BE INSULATED OR 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE CLOSE OFF SPACES AT TOP OF FURRING.
C C W-
ACCESSIBLE
2'-9 1/2"

A-22-Z OTHERWISE CONFIGURED TO RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
KNEE AND TOE 11" WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S
PROTECT AGAINST CONTACT. X- EXISTING TO REMAIN
TYP. T.O.W.
2'-0"

CLEARANCE

9"
INSTRUCTIONS AND FINAL SHOP DRAWINGS.
9'-6" A.F.F.

THERE SHALL BE NO SHARP OR


A-22-B Z- NO SHEATHING
D-18-Z

ABRASIVE SURFACES UNDER


1'-5"
LAVATORIES AND SINKS FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.) 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
B-22-A BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
DESIGNED AND DETAILED BY CFMF SUPPLIER.
4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
6'-0"

1'-4" 1- EXISTING WALL TO REMAIN 4/A-501 TENANT


7 TOILET - LAVATORY SECTION 2- 1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE 23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
SCALE: 3/4" = 1'-0" 3- 2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED IMPROVEMENT
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F. LOCATIONS BEFORE COMPLETING PROJECT.
19 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN 24. PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
A 22 12- G-002 FOR TYPICAL SIZE AND LOCATIONS.
SUPPORT PER DETAIL 5/A-501
CERAMIC TILE OVER CEMENT 25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
A-205 BD. AND METAL STUD WALL SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S
4'-9 1/4"

13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501
20 123 CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT 3030 PLAZA BONITA RD, SUITE
21 SOLID SURFACE COUNTER 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER. 1025
OVER 3/4" MARINE GRADE 15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING. NATIONAL CITY, CA 91950
ATTACH STEEL HSS TO TRACK WITH PLYWOOD
16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501
(2) POWDER ACTUATED FASTENERS L2x2x1/4 STEEL 17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE. CLIENT
INTO EACH TRACK ANGLE FASTENED 18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
TO STEEL HSS
19-
3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. ROUND1
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION
PROVIDE TOP AND BOTTOM
TRACK 600T200-54 (50 KSI) AT
ENTERTAINMENT
B-22-A 4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
HSS BETWEEN VERTICAL HSS 3.5x3.5x3/8 20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION
STUDS. ATTACH TRACKS TO
VERTICAL STUDS WITH 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
21-
9 SIMPSON FCB43.5 FRAMING STUD CAVITY WITH 6" UNFACED BATT INSULATION
CLIPS 22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
A-501
24X24 24X48 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
THERMAFIBER SAFB

A-22-A
M-22-A

24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
CWI

6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
STUD CAVITY WITH 6" UNFACED BATT INSULATION
TYP @ THIS COLUMN 8 TOILET - LAVATORY DETAIL
Z-15-D

D-18-Z
25'-4"

1'-1 3/4"

A-402 SCALE: 3/4" = 1'-0"


TYP. T.O.W. 26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
CWO

5/8" FIRE RETARDENT TREATED


D

4 3/4"

REDEMPTION 9'-6" A.F.F.


PLYWOOD ON (1) ONE SIDE OF 3 5/8" 2'-0" 3070 SATURN ST. STE. 200
STORE
METAL STUDS. T.O.W. = 6" ABOVE BREA, CA 92821
FE-K

FACE OF WALL/FINISH
D 125 D
24X48
24X48

CEILING
SOLID SURFACE ON 3/4"
MARINE GRADE PLYWOOD
M-22-A COUNTERTOP
1'-1 3/4"

24X48
4 3/4" COUNTERTOP MOUNTED
KITCHEN DIAPER CHANGING STATION

3 1/4"
24X48

128
9'-11 3/8"

B-22-M 24X48
1x HARDWOOD EDGE

3"
24X48

24X48

18"X18"X12"

TOP OF DIAPER CHANGING STATION


24X48
1'-4"
24X48

3/4" PLYWOOD COUNTERTOP SUPPORTS AT

1'-4 1/4"
8" 2'-6" O.C. MAX, WITH HARDWOOD EDGES

2'-10"

2'-6 3/4"
34DR

3/4" X 3" PLYWOOD SUPPORT


24X48

2'-3"
BACKER BOARD - FULL HEIGHT OF
PLYWOOD COUNTERTOP SUPPORT
24X48

11"
F-22-M

BAR
3'-6"

ACCESSIBLE KNEE AND TOE CLEARANCE

9"
130 BAR LOW WALL
4 1/4"
A-22-B

A-22-Z

BY VENDOR
24X48

1'-5"

A-22-A
CWI

A-22-B A-22-M
C

9 DIAPER CHANGING STATION COUNTER


D

MECHANICAL
TS14BLW

CH

127 PROVIDE FIRE RETARDENT TREATED A-401 SCALE: 3/4" = 1'-0"


H
CWO
D

PLYWOOD UNDER BAR BACK COUNTER -


F-22-A RELEASE DATE
COORDINATE W/ VENDOR
D

M-22-F
A-22-B

DATE DESCRIPTION
127
D

REFER TO DETAIL 2/A-402


07-06-23 FOR PERMITS
CRC-63C

4'-0" 1'-0" 4'-0" 1'-0"


G

FOR WALL TILE


CH

SCHLUTER RONDEC
WT 5
D

07-21-23 FOR BIDS


G

REFER TO DETAIL 4/A-402


FOR WALL TILE
SCHLUTER RONDEC
D C
SC-15-TS

CH
D

D
A-22-M WT 3
A-22-A

C
H
GUEST
COUNTER 128 WT 3

8'-0"

8'-0"
126
ABOVE
B-22-M
F-22-M

SHOE CUBBIE CABINET BY VENDOR. CEMENT BOARD SHEATHING


CRI-12-30-7

HEIGHT OF COUNTER 42" A.F.F. REFER TO WHERE WALL TILE INDICATED


D

SNACK
ELECTRICAL AND COORDINATE HEIGHT AS
BAR
REQUIRED ABOVE THIS COUNTER TA-4.1 129
E E
TA-7 WB 3 WT 9 WB 3
MEN WOMEN
RC D
H R C
C

D 10 RESTROOM TILE AT ENTRANCE


A-401 SCALE: 1/4" = 1'-0"
A-602
PROJECT

2 3
2112128GR
SHEET
7/25/2023 4:04:46 PM

ENLARGED FLOOR PLANS


6 ENLARGED PLAN - REDEMPTION STORE, GUEST COUNTER, KITCHEN, SNACK BAR, BAR
A-102 SCALE: 1/4" = 1'-0"

A-402
WALL CONSTRUCTION LEGEND _FLOOR PLAN GENERAL NOTES _
1. DO NOT SCALE DRAWINGS. USE DIMENSIONS SHOWN ON DRAWINGS AND
KEY ACTUAL FIELD MEASUREMENTS. NOTIFY ARCHITECT OF ALL
DISCREPANCIES IN WRITING
2. IMPORTANT NOTICE: TOTAL FLOOR LAYOUT TO BE INITIALLY "CHALK
DRAWN" TO MATCH DRAWING DIMENSIONS BY THE G.C. TO CHECK FOR
4 5 FLOOR PLAN DIMENSIONAL DISCREPANCIES BROUGHT ON BY EXISTING
BUILDING MEASUREMENTS. THIS IS TO BE DONE PRIOR TO ANY LANE OR
PARTITION WORK, PLUMBING LINES AND ELECTRICAL WORK/
CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ARCHITECT
PARADIGM DESIGN
IMMEDIATELY. ARCHITECTS | ENGINEERS

3. ALL GENERAL METAL STUD FRAMING WITH SHEATHING ON BOTH SIDE OF


STUD ONLY SHALL BE 24" O.C., U.N.O.
4. ALL GENERAL METAL STUD FRAMING AND FURRING WITH SHEATHING ON
ONE SIDE OF STUDS ONLY TO BE 16" O.C., U.N.O.
5. HEIGHT OF TENANT METAL STUD WALLS TO BE TIGHT TO BOTTOM OF Grand Rapids | Phoenix | Traverse City
STRUCTURAL STEEL MEMBERS OR METAL ROOF/FLOOR DECK U.N.O.
www.paradigmae.com
REFER TO FRAMING PLANS, WALL DETAILS AND REFLECTED CEILING...

H-14-A
5'-9 1/4"
6. PROVIDE SOUND ATTENUATION BATT INSULATION IN ALL STUD WALLS FOR
SHEATHING TYPES VESTIBULE, PARTY ROOMS, OFFICES, AND TOILET ROOMS.
A- 5/8" GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
4'-6" 7. PROVIDE TYPICAL CONTROL JOINTS IN ALL GYPSUM BOARD BULKHEADS AT
B- 5/8" GYPSUM BOARD FROM FLOOR TO 6" MIN. ABOVE CEILING 30'-0" MAX SPACING
5/8" GYPSUM BOARD FROM BOTTOM TRACK UP TO TO UNDERSIDE OF DECK 8. PROVIDE MOISTURE RESISTANT GYP. BOARD AT ALL TOILET ROOM WALLS
C-

13'-5 3/4"
ABOVE AND LOCATIONS THAT ARE TO RECEIVE WALL TILE OR FRP WALL FINISH,

1'-3"
D- 5/8" GYPSUM BOARD TO MATCH HEIGHT OF STUD FRAMING UNLESS NOTED OR SPECIFIED OTHERWISE.

5/8" MOISTURE RESISTANT GYPSUM BOARD FROM FLOOR TO 6" MIN ABOVE 9. EXACT LOCATION OF CABINET AND BRACKET MOUNTED FIRE
E- EXTINGUISHERS TO BE APPROVED BY LOCAL FIRE OFFICIAL. PROVIDE...
CEILING
F- 5/8" CEMENTBOARD FROM FLOOR TO 6" MIN ABOVE CEILING FEC RECESSED EXTINGUISHER & CABINET
FE BRACKET MOUNTED EXTINGUISHER
5/8" CEMENTBOARD TO 8'-0" AFF WITH 5/8" MOISTURE RESISTANT GYPSUM
D-14-D D-14-H G- FE-K TYPE 'K' EXTINGUISHER & CABINET
BOARD ABOVE TO MIN 6" ABOVE CEILING
5/8" ABUSE RESISTANT GYPSUM BOARD - MATCH HEIGHT OF STUD FRAMING 10. ALL DIMENSIONS ARE SHOWN TO THE FACE OF THE FINISHED MATERIAL
H- AT LOW WALLS; TO 8'-0" A.F.F. WITH 5/8" GYPSUM BOARD ABOVE TO DECK AT UNLESS NOTED OTHERWISE
FULL HEIGHT STUDS. 11. METAL FABRICATIONS - HANDRAILS:
B B PROVIDE STEEL HANDRAILS DESIGNED & FABRICATED TO BE CAPABLE OF
J- 5/8" TYPE 'X' GYPSUM BOARD FROM FLOOR TO UNDERSIDE OF DECK ABOVE
WITHSTANDING CONCENTRATED & UNIFORM LOADS AS SPECIFIED BY THE
3/4" FIRE RETARDANT TREATED PLYWOOD, BOTTOM TRACK TO 6" ABOVE LOCAL BUILDING CODE. PROVIDE SHOP DRAWINGS TO ARCHITECT FOR
K- PROJECT
CEILING - REFER TO DETAIL 3/A-502 OR 2/S-502 APPROVAL.
L- ACOUSTIC ABSORPTION PANELS, FLOOR TO CEILING 12. GENERAL TRADES CONTRACTOR TO PROVIDE SOLID WOOD BLOCKING IN
M-
5/8" FIRE RETARDANT TREATED PLYWOOD SHEATHING FROM FLOOR TO 6"
MIN. ABOVE CEILING
STUD WALLS TO ANCHOR HANDRAILS, ACCESSORIES, AND HARDWARE. ROUND1 -
N- 1/2" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING
13. PROVIDE DIAGONAL BRACING OF ALL NEW STUD WALLS (THAT DO NOT
EXTEND TO ROOF DECK) TO STRUCTURE ABOVE AT 48" O.C. AND AT PLAZA BONITA
P- (2) LAYERS 1/4" PLYWOOD TO MATCH HEIGHT OF STUD FRAMING UNATTACHED END(S.)
14. REFER TO ROOM FINISH SCHEDULE FOR FINAL WALL FINISH TO BE APPLIED
R- 1" TYPE SLX GYPSUM LINER PANEL FROM FLOOR TO DECK ABOVE OVER BASE WALL MATERIALS AS INDICATED ON THIS PLAN.
15. SEAL ALL WALL PENETRATIONS - SEE MECHANICAL AND ELECTRICAL
SPORT NET & SUPPORT SYSTEM, REFER TO KEYNOTE PLAN, WALL FINISH DRAWINGS FOR ADDITIONAL INFORMATION.
S-
PLAN & DETAIL 16/A-501
16. VERIFY KNOX BOX LOCATIONS AND TYPES WITH LOCAL FIRE DEPARTMENT.
T- 6" HIGH WALL PADDING 17. PROVIDE DEFLECTION TRACK FOR 1 1/2" MOVEMENT AT TOP OF STUD
5/8" MOISTURE RESISTANT GYPSUM BOARD TO MATCH HEIGHT OF STUD WALLS THAT EXTEND TO BOTTOM OF DECK. REFER TO DETAIL 9/A-501.
U-
FRAMING 18. DOORS ADJACENT TO WALLS BUT NOT DIMENSIONED ARE LOCATED 4"
FROM FACE OF ADJACENT WALL.
5/8" FIRE RETARDENT TREATED PLYWOOD SHEATHING FROM FLOOR TO
V- 19. PROVIDE HORIZONTAL METAL CLOSURE AT TOP OF FURRING AT ALL
UNDERSIDE OF DECK ABOVE
28'-0"
LOCATIONS WHERE SHEATHING IS NOT INSTALLED TO ROOF DECK TO
UP 5/8" CEMENTBOARD FROM FLOOR TO 11'-4" AFF WITH 5/8" MOISTURE CLOSE OFF SPACES AT TOP OF FURRING.
W-
RESISTANT GYPSUM BOARD ABOVE TO DECK 20. G.C. SHALL PROVIDE CONSTRUCTION AND INSTALLATIONS THAT COMPLY
BOWLER'S BOWLING BOWLING WITH THE MOST STRINGENT REQUIREMENTS OF MANUFACTURER'S
X- EXISTING TO REMAIN
SEATING 2 APPROACH LANES INSTRUCTIONS AND FINAL SHOP DRAWINGS.
. 3 . . . Z- NO SHEATHING
120 119 118
A-331 A-501
FRAMING TYPES 21. ALL RAMP SLOPES SHALL NOT EXCEED ONE FOOT IN 12 FEET.
ALL COLD FORMED METAL FRAMING (CFMF) SHALL BE 20 GA. MIN. MATERIAL (U.N.O.) 22. ALL OUTSIDE CORNERS OF GYPSUM BOARD WALLS TO HAVE 2"x2"x48"
DESIGNED AND DETAILED BY CFMF SUPPLIER. BRUSHED ALUMINUM CORNER GUARDS INSTALLED FROM TOP OF BASE TO
FLOOR FRAMING AND SUBFLOOR IN
BOWLERS SEATING AREA BY BOWLING 1- EXISTING WALL TO REMAIN
4'-4" A.F.F. UNLESS SPECIFICALLY NOTED "NO CORNER GUARD". SEE DETAIL
4/A-501 TENANT

68'-8 3/4"
14'-0 5/8"

VENDOR
D-14-H
2-
3-
1 5/8" HAT CHANNEL TO UNDERSIDE OF DECK ABOVE
2-1/2" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
23. CONTRACTOR SHALL FURNISH AND INSTALL OCCUPANT LOAD SIGNS AS
REQUIRED BY THE BUILDING CODE. SIGNS SHALL BE POSTED AT REQUIRED
IMPROVEMENT
11- 3-5/8" CFMF STUDS, COLUMN WRAP FROM FLOOR TO 12'-0" A.F.F. LOCATIONS BEFORE COMPLETING PROJECT.
3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 3'-6" A.F.F., PROVIDE STEEL COLUMN 24. PROVIDE TACTILE EXIT SIGNS AT ALL EXTERIOR EXIT DOORS. REFER TO
12- G-002 FOR TYPICAL SIZE AND LOCATIONS.
SUPPORT PER DETAIL 5/A-501
25. RELOCATION OF ANY EXISTING BUILDING SYSTEMS AND REPAIR OF ROOF
13- 3-5/8" CFMF STUDS, 16" O.C. T.O.W. = 4'-8" A.F.F.,REFER TO DETAIL 3/A-501 SYSTEM MUST BE WORK CONTRACTED THROUGH LANDLORD'S 3030 PLAZA BONITA RD, SUITE
CONTRACTOR AT TENANT'S EXPENSE. COORDINATE REQUIRED TENANT 1025
CONT. TRANSITION THRESHOLD AT JOINT OF 14- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT WORK WITH LANDLORD'S OPERATIONS MANAGER.
WOOD FINISH AND SEATING FLOOR FINISH, TYP.
NATIONAL CITY, CA 91950
15- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO 6" ABOVE CEILING 26. PATCH AND REPAIR EXISTING WALLS REQUIRED TO PREP FOR PAINTING.
16- 3-5/8" CFMF STUDS, 16" O.C. REFER TO DETAIL 5/A-501
FEC

C C CLIENT
17- 3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE DENOTES WINDOW - REFER TO SHEET A-601 FOR WINDOW SCHEDULE.

9
18- 3-5/8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
ROUND1
3-5/8" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
A-601 19-
FILL STUD CAVITY WITH 3 5/8" UNFACED BATT INSULATION ENTERTAINMENT
4" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
20-
STUD CAVITY WITH 4" UNFACED BATT INSULATION
T.O.W.: 5'-0" ABOVE GAME
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
ROOM FLOOR, TYP. 21-
D-14-H STUD CAVITY WITH 6" UNFACED BATT INSULATION
22- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE WITH
23- RC-1 CHANNEL ONE SIDE SPACED 16" O.C. FILL STUD CAVITY w/ 6"
THERMAFIBER SAFB
24- 6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE
6" CFMF STUDS, 16" O.C. FROM FLOOR TO UNDERSIDE OF DECK ABOVE. FILL
25-
STUD CAVITY WITH 6" UNFACED BATT INSULATION

. 3 .
26- 8" CFMF STUDS, 16" O.C. REFER TO FLOOR PLAN FOR T.O.W. HEIGHT
A-501 3070 SATURN ST. STE. 200
BREA, CA 92821
4 1/8"

CROSSHATCH INDICATES FLOOR FRAMING CAVITY


FILLED WITH BATT INSULATION FOR FIRE BLOCKING

1'-6"
4'-2"
D-14-D

UP
HANDRAIL - REFER TO
5'-9 3/4"

DETAIL 1/A-331

H-14-D
T.O.W.: 5'-0" ABOVE GAME
ROOM FLOOR, TYP.

D D
D-14-D

H-14-D

5'-7 1/8"

SIM

RELEASE DATE

DATE DESCRIPTION
4 5 07-06-23 FOR PERMITS
07-21-23 FOR BIDS

1 ENLARGED PLAN - BOWLERS SEATING


A-102 SCALE: 1/4" = 1'-0"

PROJECT

2112128GR
SHEET
7/25/2023 4:04:47 PM

ENLARGED FLOOR PLANS

A-403
TRASH
ENCLOSURE
7/16" LANE LAMINATE SURFACE BY VENDOR -
BY BOWLING VENDOR (TYP.) REFER TO
ATTACH EACH STUD
1-1/2" UNDERLAYMENT BY TO BOTTOM
FLOOR PLAN PARADIGM DESIGN
BOWLING VENDOR (TYP.) TRACK w/ (1) #10
ARCHITECTS | ENGINEERS
SCREW EACH FLANGE
G.C. TO PAINT EXPOSED 7

EDGE OF APPROACH
HOLD INSULATION IN 5/8" ABUSE RESISTANT GYP.
SIDE OF LANES (PT-7) BATT INSULATION IN FLOOR IS BUILDING BOARD ON 362S162-54 A-501
PLACE AND 6" CLEAR 1'-0" CODE REQUIRED FIREBLOCKING AND

3'-2"
EACH SIDE OF BALL G.C. TO PROVIDE AND INSTALL BLACK TRANSITION METAL STUDS @ 24" O.C.
DRAFTSTOPPING PER SECTION 718 5/8" GYP. BOARD
RETURN CENTER (TYP.) STRIP "DETAIL C" BY POLYMER FABRICATION INC.
REFER TO FLOOR PLAN JUAN LOEBEL ATTACH EACH STUD TO 3-5/8" CFMF TRACK,20 GA.
FOR WALL CONSTRUCTION VINYL FLOORING, SEE WWW.POLYMERFAB.NET Grand Rapids | Phoenix | Traverse City
6" 6" SUBFLOOR w/ SIMPSON H2.5A WITH FIRE RETARDANT
FINISH FLOOR PLAN 638-673-3012 www.paradigmae.com
ANCHOR TREATED NAILER
INFILL JOIST FRAMING & GYPSUM BOARD EACH
FLOOR DECK BY BOWLING WOOD SUBFLOOR BY SIDE OF CFMF STUDS
VENDOR. FLOOR FINISH BY BRUNSWICK 2"x2"x48" MECHANICALLY AT 24" O.C., SEE
G.C. FASTENED ALUMINUM FLOOR PLANS MAX. WALL HEIGHT FOR
WOOD FRAMING CORNER GUARD, FROM TOP THIS DETAIL = 4'-0"
AND BLOCKING BY OF BASE TO 4'-4" A.F.F. CLARK DIETRICH (PW36)
BOWLING VENDOR BOWLING VENDOR TO SUPPLY AND PROVIDE PAZWALL PLASTIC SUPPORTS AT EACH END
CONT. BTM TRACK 362T150-43 INSTALL 3/4" SOUND ISOLATION CAP (PART #PWS-836TC) AT OF WALL AND AT 4'-0" O.C
ATTACH TO FLOOR SLAB PADS UNDER ALL BOWLING EQUIPMENT TOP OF CORNER GUARD
EXIST. FLOOR w/ (1) HILTI X-U 0.157 ⌀ PAF . 6 .
AND LANE FRAMING TO SEPARATE

1'-6"
TO REMAIN BOWLING VENDOR TO SUPPLY AND @ 24"O.C. w/ 3/4" EMBEDMENT FRAMING FROM DIRECT CONTACT TO A-501
INSTALL 3/4" SOUND ISOLATION BOWLING VENDOR TO SUPPLY AND INSTALL G.C. TO FILL JOIST FRAMING BASE PLATE FOR
CAVITY TO UNDERSIDE OF FLOOR THE EXISTING FLOOR.
WOOD I-JOIST FRAMING, SLEEPERS, AND PADS UNDER ALL BOWLING 3/4" SOUND ISOLATION PADS UNDER ALL WALL CONSTRUCTION, CLARK DIETRICH (PW36) -
EQUIPMENT AND LANE FRAMING TO BOWLING EQUIPMENT AND LANE FRAMING SHEATHING WITH UNFACED BATT REFER TO FINISH SEE FLOOR PLANS REFER TO DETAIL 13 / A-501
SHIMS AT BOWLING LANE AND BOWLER'S
SEPARATE FRAMING FROM DIRECT TO SEPARATE FRAMING FROM DIRECT OR MINERAL WOOL INSULATION FLOOR PLAN FOR FINISH
SEATING BY BOWLING VENDOR
CONTACT TO THE EXISTING FLOOR. CONTACT TO THE EXISTING FLOOR. (TYP. U.N.O.)

BATT INSULATION FIREBLOCKING BY G.C.


1 BOWLING LANE FRAMING DETAIL 2 BOWLING LANE AT FINISH TRANSITION 3 BOWLING RAIL SECTION FLOOR FRAMING BY BRUNSWICK 4 TYP. CORNER GUARD DETAIL 5 LOW WALL SUPPORT DETAIL
A-104 SCALE: 3/4" = 1'-0" A-403 SCALE: 3/4" = 1'-0" A-403 SCALE: 1" = 1'-0" A-103 SCALE: 1 1/2" = 1'-0" A-103
A-501 SCALE: 3/4" = 1'-0" PROJECT
A-104 A-104
A-104-A-105 A-105-A-106
A-602 A-501
ROUND1 -
PLAZA BONITA
REDEMPTION STORE SECURITY GATES - CHECKPOINT CLASSIC IP STREET SYSTEM -
PLACE POWER/POWER SUPPLY EQUIPMENT ABOVE CEILING. GYP. BD., SEE FLOOR
ROUTE ALL CABLES ON INSIDE OF PORTAL TO ABOVE CEILING. PROVIDE PAZWALL PLASTIC CAP PLAN
COORDINATE REQUIREMENTS WITH ELEC. GATES PURCHASED (PART #PWS-836TC) AT TOP CAP TO MATCH WHITE
AND INSTALLED BY TENANT, G.C. TO PROVIDE ALL POWER TOP OF CORNER GUARD, TYP. 2" ALUMINUM CORNER GUARDS SLATWALL
LINE OF BULKHEAD ABOVE FASTENED TO EXPOSED CORNERS
BOTTOM OF EXIST. DECK
362S162-33 EACH SIDE OF 2'-0" 11'-0" 2'-0"
WALL, SEE
CLARK DIETRICH (PW36). RESILIENT SHEET VINYL (RS-1)
FLOOR PLAN
ATTACH TOP OF EACH STUD SS -3 SOLID SURFACE. ADHERED TO WALL SURFACE WITH
TO PW36 w/ (2) #10 SCREWS PROVIDE EASED EDGE. J-MOLD TRIM AT ALL EXPOSED
5

4'-2" (U.N.O.)
. . TYP. EDGES NOT PROTECTED BY SLATWALL ATTACHED

3"

1'-2 1/4"
A-501 CORNER GUARD OR BASE. REFER TO WOOD BLOCKING
TO WALL FINISH PLANS FOR TOP AND BOTTOM

2 1/4"
DEFLECTION TRACK - COLUMN LOCATIONS
HOLD GYPSUM BOARD REFER TO DETAIL

FOR WALL HEIGHT


DOWN FROM LEG OF EXTEND WALL FINISH 1"x6" WOOD BLOCKING ON

4"
FINISH GYPSUM END WALL HORZ. AND VERT.

3'-1 5/8"
REF. PLAN
DEFLECTION TRACK BEHIND RUBBER BASE
WITH CORNER GUARD AT SLATWALL JOINTS

3'-1 5/8"
ON OUTSIDE CORNER 5 3/8"
FILL TOP 6" OF STUD BASE PER FINISH SCHEDULE

4"
WALL WITH MINERAL STUD WALL BOTTOM CAP TO MATCH

1'-7 3/8"
GYPSUM BOARD EACH SIDE 6" 4'-0" O.C. 4'-0"
WOOL, FIXED IN PLACE REFER TO HSS STEEL WHITE SLATWALL
OF CFMF STUDS AT 24" O.C.,
FLOOR PLAN
SEE FLOOR PLANS (TYP.)
CLARK DIETRICH (PW36)
COLUMN - REFER TO
STUCTURAL
TENANT
SUPPORTS AT EACH END
OF WALL AND AT 4'-0" O.C. 4 7/8" REFER TO STRUCTURAL FOR
IMPROVEMENT
ADDITIONAL INFORMATION
5/8" GYP. BOARD ON CFMF
STUD FRAMING

6 LOW WALL SUPPORT DETAIL 7 WALL CAP DETAIL 8 DEFLECTION TRACK AT WALL 9 REDEMPTION ENTRY DETAIL 10 BOWLING LANES COLUMN WRAP ELEVATION 11 REDEMPTION SLATWALL DETAIL 3030 PLAZA BONITA RD, SUITE
A-501 SCALE: 1 1/2" = 1'-0" A-501 SCALE: 3" = 1'-0" A-102 SCALE: 3" = 1'-0" A-204
A-402 SCALE: 3/4" = 1'-0" A-501 SCALE: 1 1/2" = 1'-0" A-502 SCALE: 1 1/2" = 1'-0"
A-602 A-103 A-403 A-602 A-602 1025
A-701 NATIONAL CITY, CA 91950
A-702

CLIENT
2x2 ANGLE 20 GA. 2x2 ANGLE 20 GA.
T.O. BRACE T.O. BRACE ROUND1
5/8" TYPE 'X' GYP. BOARD

5/8" TYPE 'X' GYP. BOARD


12' A.F.F.
ON 3 5/8" CFMF STUD
12' A.F.F.
ENTERTAINMENT
FRAMING FROM FLOOR
A ON 3 5/8" CFMF STUD (4) 1/2" PAF A TO 12'-0" A.F.F. (4) 1/2" PAF
SEE FLOOR PLANS
TYP. FRAMING FROM FLOOR TYP. FOR WALL TYPE
EXIST. STEEL EXIST. STEEL
TO 12'-0" A.F.F. CONSTRUCTION
COLUMN COLUMN
1'-1"

TOP BRACE TOP BRACE FRT WOOD BLOCKING


EXIST. COLUMN EXIST. COLUMN
2'-2" TYP. U.N.O.

AT 4'-0" O.C.
10 1/2"

1'-9" TYP. U.N.O.

(4) SCREWS TRACK (4) SCREWS TRACK 1/2"x6" HDPE CHAIR


COORDINATE w/ OWNER FURNITURE
TO ANGLE TO ANGLE RAIL, RADIUSED AT
FOR CHAIR RAIL HEIGHT IN SEATING
EXPOSED EDGES (CR-1)
(2) 1/2" PAF (2) 1/2" PAF AREA - REFER TO WALL FINISH PLAN
1'-1"
10 1/2"

AT BOWLING 8" CL FOR LOCATIONS OF CHAIR RAILS


LANES ANGLE 3X3 ANGLE 3X3 4" 4"

30" A.F.F. @ PARTY ROOMS


(2) 1/2" PAF (2) SCREWS (2) 1/2" PAF (2) SCREWS 1"

44" A.F.F. @ BILLIARDS


WALL FINISH, (2) SCREWS ANGLE TO WALL FINISH, (2) SCREWS ANGLE TO
REFER TO WALL TRACK REFER TO WALL TRACK CLARK DIETRICH (PW36)
TRACK TRACK

3 3/8"
10 1/2" 10 1/2" 1'-1" 1'-1" w/ 8" x 3 3/8" BASEPLATE
FINISH PLAN 2"x2" ALUMINUM CORNER FINISH PLAN 2"x2" ALUMINUM CORNER
1'-9" TYP. U.N.O. GUARD 4'-0" LONG ON EACH MID BRACE A MID BRACE B 2'-2" TYP. U.N.O. GUARD 4'-0" LONG ON EACH MID BRACE A MID BRACE B 3070 SATURN ST. STE. 200
ANCHOR BASEPLATE 1/8" BREA, CA 92821

1/8"
CORNER. PROVIDE MID BRACE A OR B - CORNER. PROVIDE MID BRACE A OR B - VCT CARPET
w/ (4) 1/2" DIA. HILTI

3/4"
PAZWALL PLASTIC CAP T.O. BRACE @ 6' A.F.F. PAZWALL PLASTIC CAP T.O. BRACE @ 6' A.F.F. KWIK BOLT-3
(PART #PWS-836TC) AT TOP (PART #PWS-836TC) AT TOP EXPANSION ANCHORS
OF EA. CORNER GUARD SECTION A (NTS) OF EA. CORNER GUARD SECTION A (NTS) w/ 3 1/2" EMBEDMENT 2 1/2"

1/4"
1/4"
12A COLUMN WRAP DETAIL 12B COLUMN WRAP DETAIL 2 13 BASE PLATE DETAIL 14 CHAIR RAIL DETAIL 15 FLOOR TRANSITION DETAIL
A-102 SCALE: 3/4" = 1'-0" A-102 SCALE: 3/4" = 1'-0" A-501 SCALE: 1 1/2" = 1'-0"
A-104 A-202 SCALE: 1" = 1'-0" A-701 SCALE: 12" = 1'-0"
A-105-A-106 A-602
A-602 A-702

Suspended Lay-in Panel Ceiling Structural Requirements (Seismic Design Category D)


The following support requirements shall apply to all suspended lay-in ceiling systems. Ceilings with a plan area greater
than 1000sf (Redemption Store and Service Aisle) shall have lateral force bracing installed IN ADDITION to the standard
requirements.

Ceiling Grid
1. Ceiling grid shall have a heavy duty rating as defined in ASTM C635.
2. Grid members shall be connected to resist an allowable force of 180lbs. This requirement shall apply
to main runner splices and cross runner intersections.

20 GA. TOP TRACK ATTACH TO EXIST. Vertical Suspension Wires


DECK/CONCRETE w/ (2) "HILTI" DN27P87 1. Ceiling grid main runners shall be supported by No. 12 gage wire at a maximum spacing of 4ft
P.A.F. w/ 3/4" EMBEDMENT o/c.
2. Hanger connections shall be bent and wrapped with three turns in 3inches or less. (Figure 3)
3 5/8x1 5/8 x 20 GA. COMPRESSION POST. 3. Hanger wires out of plumb by more than 1/6 must be counter splayed using an additional
ATTACH TO MAIN RUNNER w/ (2) #10 12gage wire. (Figure 4)
SCREWS. ATTACH EACH FLANGE TO TOP 4. Hanger wires shall be connected to the supporting structure in accordance with Figure A and B.
TRACK w/ (1) #10 SCREW 5. Hangers wires may not attach to or bend around interfering equipment. RELEASE DATE
6. Hanger wires must be straight and shall not use bends or localized kinks for leveling of the
(4) #12 SPLAY system. DATE DESCRIPTION
WIRES
Ceiling Perimeter 07-06-23 FOR PERMITS
1. Ceiling grid support members must be connected to perimeter walls on two adjacent sides and 07-21-23 FOR BIDS
unattached on two adjacent sides. (Figure 7 and Figure 8)
2. A minimum clearance of ¾” must be maintained on two unattached adjacent sides. (Figure 8)
45
°O

3. Unattached perimeter runner ends must be tied together to prevent spreading. (Figure 8)
SS

R
LE

4. Perimeter runners must be supported by vertical hanger wires located not greater than 8inches from
LE
R

SS
°O

the perimeter wall. (Figure 7 and Figure 8)


45

5. Perimeter closure (molding) must have a minimum width of 2 inches. (Figure 7 and Figure 8)

Penetrations
1. Sprinkler heads and other penetrations shall have a minimum clear space of 1inch in all directions.
(Figure 6)
45° OR LESS
45° OR LESS

Lighting Fixtures
1. Lighting fixtures must be positively attached to the grid by at least two connections each
CROSS TEE capable of independently supporting the fixture weight.
2. Surface mounted light fixtures shall be positively clamped to the grid. Clamping devices shall
have safety wires attached to the grid or structure above.
3. Rigid conduit is not permitted for the attachment of fixtures.
4. Required support by fixture weight:
a. 10lbs or less: use a minimum of one No. 12 gage hanger wire connected to fixture housing and to the
structure above. This wire may be slack.
b. Greater than 10lbs and less than 56lbs: use a minimum of two No. 12 gage hanger wires connected to the
fixture housing on opposite diagonal corners and connected to the structure above. These wires may be
MAIN BEAM slack.
1. Pendant-hung light fixtures shall be supported via one No. 9 gage wire to the structure above. PROJECT
22 COMPRESSION POST AND SPLAY WIRE Lateral Force Bracing
SCALE: 3" = 1'-0" 1. Lateral force bracing is required for all ceiling areas with a plan area greater than 1000sf.
2. Lateral force bracing elements shall be installed at a maximum spacing of 12ft o/c (each direction) 2112128GR
starting 6ft from two adjacent walls.
3. A lateral force bracing element consists of four(4) splay wires in combination with a vertical
compression post. (Figure C) SHEET
7/25/2023 3:40:41 PM

4. The centerline of each bracing element shall occur within 2 inches of the main runner/cross runner
intersection. The four(4) splay wires shall be splayed approximately 90degrees apart in plan at a
maximum angle of 45degrees from the horizontal. INTERIOR DETAILS

A-501
CEILING MOUNTED SPEAKERS BY A/V
VENDOR (G.C. TO PROVIDE BLOCKING) 5/8" GYP. BOARD ON
VERIFY FINAL LOCATIONS WITH 4" METAL STUD

PINSETTER
BACK OF
ARCHITECT AND A/V VENDOR FRAMING @ 24" O.C.

APPROACH
EDGE OF
GYP. BOARD PAINT
REFER TO INT. ELEV. 70'-6"
12'-10 1/2" 36" 29"

METAL STUDS AND LATERAL


BRACING PER STRUCTURAL
POWER OUTLETS FOR PARADIGM DESIGN
6" 11" PROJECTION SCREENS (REFER
EQ EQ TO ELEC.) INSTALL IN FRONT ARCHITECTS | ENGINEERS
1" 1" 5/8" GYP. BOARD ON FACE OF CURTAIN WALL
BOTTOM OF CURTAIN WALL CEILING - REFER TO
REFLECTED CEILING PLAN MOTORIZED PROJECTION
1/4" MIRROR FLAT
POLISHED EDGES SCREEN ASSEMBLY ATTACHED
1/2" S.S. TRIM & (2) 1100A CURTAIN TRACKS
TO & SUPPORTED FROM
PERIMETER, TYP. "SPECIFINE" BY ADC
COSMIC FIXTURE MASKING
PROVIDE PLYWOOD BOWLING SCORING EQUIPMENT UNIT HARDWARE Grand Rapids | Phoenix | Traverse City
NOTE: SPLIT THE OPENING
BLOCKING FOR (WEIGHT: 100 LBS)
AND PROVIDE 8" OVERLAP OF www.paradigmae.com
BRACKET/T.V. SUPPORT CURTAIN FABRIC AND TRACK PROJECTION SCREEN
3'-6" TYP.

AT CENTER OF OPENING COORDINATE WITH A/V DRAWINGS REFER TO STRUCTURAL


NO MIRROR ELEC. AND DATA OUTLETS TO
AVOID CONFLICT WITH TV UPPER MASKING UNIT FOR HEIGHTS AND LOCATIONS DRAWINGS FOR SUPPORT
3/4" FRT PLYWOOD ON BACK WALL
2'-1"

BRACKET. CONFIRM FINAL GRAPHIC PANEL (FIXED) REQUIREMENTS


SIDE OF CURTAIN WALL - REFER TO
LOCATION WITH A.V VENDOR G.C. TO PROVIDE POWER ELECTRICAL - VERIFY WITH BOWLING EXISTING FRAMING ROUTE ELECTRICAL CONDUIT IN SIDE
VENDOR FOR FINAL LOCATIONS
14 GA. (MIN.) UNISTRUT AT STRUCTURE BY G.C. WALLS AS NEEDED TO FEED ELEC. -
T.V BRACKET PROVIDED VENDOR TO PROVIDE REFER TO ELECTRICAL
AND INSTALLED BY A/V CABLE/DATA

HEIGHT OF 11'-9" ABOVE BOWLING LANES


VENDOR, BLOCKING BY G.C. LOWER MASKING UNIT G.C. TO PROVIDE DUPLEX
GRAPHIC PANEL (MOVES UP) RECEPTACLE SUPPORTED BY CONTRACTOR TO INSTALL
OF OUTLETS SK SOUND SHOCK

G.C.TO PROVIDE POWER TO A


CONDUIT INSTALLED ADJACENT TO DUPLEX RECEPTACLES ONTO
(U.N.O.) 26 oz. FABRIC SUSPENDED MOUNT LOCATION FOR VENDORS TRUSS (AFTER TRUSS IS
OVERHEAD MONITORS &

10"
3'-2" A CLEAN INSTALLATION. (PAINT SUPPORT TRUSS SUPPLIED AND INSTALLED) - REFER TO ELECTRICAL

6'-0"
BLACK)

68"
PINSETTER BY BOWLING INSTALLED BY BOWLING VENDOR
4'-8 3/4"

OF MOUNTING
VENDOR A/V EQUIPMENT INCLUDING BUT (BOWLING VENDOR TO PROVIDE
BRACKET

7 1/2"
BOTTOM OF T.V.
BASE OF MASKING UNIT NOT LIMITED TO SPEAKERS, ALL DATA / VIDEO CABLING)
3'-8 1/8"

VERTICAL SUPPORT LEGS PROJECTORS, MONITORS, ETC.


3'-4" TYP.

LANE SURFACE & FOUNDATION

8'-4"
3'-6"
AND ALL MOUNTING HARDWARE

37"
SYSTEM BY BOWLING VENDOR NOTE: REFER TO

BOWLING VENDOR
ELEC. AND DATA FOR A/V/ BY A/V VENDOR (U.N.O.)
GYP. BOARD PAINT STRUCTURAL FOR
EQUIPMENT. VERIFY
CENTER OF OUTLET

REFER TO INT. ELEV. G.C. TO PROVIDE FLOOR SLAB


REQUIREMENTS WITH A/V TV AND MOUNTING BRACKET ADEQUATE WOOD BRACING

VERIFY W/
KARAOKE VENDOR BY VENDOR, SEE ELEVATIONS BLOCKING FOR TV MOUNTS REQUIREMENTS PROJECT
TOP OF BOWLING LANES
1'-6"

FOR MOUNT HEIGHT 1'-6" A.F.F.

VERIFY WITH
VERIFY WITH
ROUND1 -

BOWLING
BOWLING

VENDOR
VENDOR
17"
NOTE:
REFER TO A / V PLANS AND INTERIOR
ELEVATIONS FOR MOUNTING HEIGHTS EXISTING FLOOR
PLAZA BONITA
A/V EQUIPMENT BOWLING OVERHEAD
1 PARTY ROOM T.V. WALL MOUNT DETAIL 2 TYP. WALL MOUNT TV 3 TYPICAL SECTION AT BOWLING MASKING WALL 4 INSTALLATION DETAIL 5 MONITOR INSTALLATION DETAIL
A-203 SCALE: 3/4" = 1'-0" A-101 SCALE: 3/4" = 1'-0" A-101 SCALE: 1/2" = 1'-0" A-101 SCALE: 1/2" = 1'-0" A-101 SCALE: 1/2" = 1'-0"
S-502 S-502

11 1'-4" OR 2'-0" 1'-4" OR 2'-0"


. .
REFER TO FLOOR PLAN REFER TO FLOOR PLAN
PL-2 A-502
4'-0"
PL-2

PROVIDE 12" OF CEMENT


1'-3"

1'-1 7/8"
COOLER WALL BOARD AT BOTTOM OF
BY VENDOR WALLS - ENTIRE KITCHEN PL-2 BACK TO BE UNFINISHED
BAR/SNACK BAR PL-2
PERIMETER.
BY VENDOR FRP OVER CEMENT PL-2
BOARD/GYP BD. OVER PROVIDE CEMENT

3/4"
METAL STUD FRAMING -

1'-0"
BOARD BEHIND ALL
TENANT

2'-10"

2'-10"

2'-10"
REFER TO FLOOR PLAN WALL TILE, TYP. PL-2
FLOOR TILE, SEE CONT. CLEAR FRP TRIM PIECES (TYP.
FINISH SCHEDULE SILICONE SEALANT ALL FRP JOINTS & EDGES)
PL-2
IMPROVEMENT

1'-2 5/8"
1'-0" 1'-0" TYP.
COVED TILE BASE COVED TILE BASE
COVED TILE BASE
FLOOR TILE FLOOR TILE FLOOR TILE

3030 PLAZA BONITA RD, SUITE

4"

4"
1025
RB-1 3" 1'-1" 3" 1'-1" NATIONAL CITY, CA 91950
WATERPROOF WATERPROOF TYP.
LEAVE FLOOR UNFINISHED AROUND BAR AND SNACK WATERPROOF MEMBRANE MEMBRANE (TURN UP MEMBRANE (TURN UP
BAR MILLWORK PERIMETER PRIOR TO MILLWORK (CONT. UNDER COOLER WALL) WALL) - REFER TO SPECS. WALL) - REFER TO SPECS. FRONT ELEVATION SIDE ELEVATION CLIENT
INSTALLATION. COMPLETE TILE AND BASE INSTALLATION
AFTER MILLWORK IS INSTALLED.
ROUND1
ENTERTAINMENT
6 FLOOR FINISH DETAIL 7 COOLER FLOOR/WALL DETAIL 8 KITCHEN WALL BASE DETAIL 9 TILE FINISH/WALL DETAIL 10 REDEMPTION CUBBY DETAIL 11 REDEMPTION CUBBY SECTION
A-202 SCALE: 1" = 1'-0" A-501 SCALE: 3" = 1'-0" A-501 SCALE: 3" = 1'-0" A-501 SCALE: 3" = 1'-0" A-203 SCALE: 1" = 1'-0" A-203
A-502 SCALE: 1" = 1'-0"
A-602 A-602 A-602 A-602 A-502 A-502
A-702 48"
. 17 . 46 3/8"
A-502 GLASS SHELVES GENERAL CONSTRUCTION NOTES FOR T-SHIRT DISPLAY CASE:
1. CABINET CONSTRUCTION TO BE FROM 3/4" THICK PARTICLE BOARD
2'-8"
2. ALL CABINET EXTERIOR SURFACES TO BE: PL-2 - REFER TO FINISH KEY
3. ALL CABINET INTERIOR SURFACES TO BE: PL-2 - REFER TO FINISH KEY

14 1/4" OR 22 1/4"
GLASS SHELVES
4. RESTS FOR GLASS SHELVES TO BE 5MM NICKEL FINISH - 5 PER SHELF.

16" OR 24"
ALL GLASS TO BE CLEAR TEMPERED, POLISHED ALL EDGES.
1'-4"

1'-4" OR 2'-0" 1'-4" OR 2'-0"


PLAN
14 REFER TO FLOOR PLAN REFER TO FLOOR PLAN 3070 SATURN ST. STE. 200
. .
A-502 TOP TO BE FINISHED GENERAL CONSTRUCTION NOTES FOR GLASS DISPLAY CASE: PLAN BREA, CA 92821
16" 16"
1/8"

DISPLAY LIGHT 1. CABINET CONSTRUCTION TO BE FROM 3/4" THICK PARTICLE BOARD


DOOR LOCKS 3/8" THICK TEMPERED 13 1/4" 2 3/4"
2. ALL CABINET EXTERIOR SURFACES TO BE: PL-4 - REFER TO FINISH KEY . 17 .
3. ALL CABINET INTERIOR SURFACES TO BE: PL-4 - REFER TO FINISH KEY GLASS TOP. ALL EDGES 3/8" THICK TEMPERED
PL-4 A-502

2 1/2" 3/8"
4. HINGES FOR GLASS DOORS TO BE HAFELE #344.04.010 GLASS TO GLASS INSET POLISHED. GLASS TOP. ALL EDGES
(4) 1/2" THICK HINGE CHROME FINISH - 3 PER DOOR POLISHED.
3/4" GLASS SHELVES
PARTICLE 5. LOCKS FOR GLASS DOORS TO BE RICHELIEU #BP641112130 CAM LOCK CHROME
(3) 1/2" THICK TEMPERED 2 1/2"
BOARD FINISH KEYED ALIKE - 2 PER DOOR
GLASS SHELVES. ALL EDGES 14 1/2"
1" TYP. SLATWALL AT 6. RESTS FOR GLASS SHELVES TO BE 5MM NICKEL FINISH - 4 PER SHELF. ALL GLASS
POLISHED.
BACK TO BE CLEAR TEMPERED, POLISHED ALL EDGES.
15 7. MILLWORK SUBCONTRACTOR TO PROVIDE DISPLAY LIGHT IN EACH CASE
. .
6'-2 5/8"
6'-2 5/8"
6'-0 7/8"

6'-2 5/8"

A-502
6'-1"

(3) 1/2" THICK TEMPERED


EQ. EQ. GLASS SHELVES. ALL EDGES
POLISHED.

38 3/4"

38 3/4"

38 3/4"
42 3/4"

42 3/4"

42 3/4"
14 1/4"

1/8" . 16 . . 16 .
BLOCKING AS 1/8" 1/8"
1'-3" 1'-3" A-502 A-502
REQUIRED 3/4" PLYWOOD
8"

CONSTRUCTION BACK PANEL TO


REFER TO FLOOR
7 1/4"

PL-4 DOOR 2'-6 1/2"


1/8"

PLAN FOR WALL LOCKS BE REMOVABLE


1'-7 3/8"

CONSTRUCTION TO INSTALL 2'-6 1/4" SLATWALL AT


RB-1 SLATWALL ON SITE GLASS SHELVES BACK
TYP.
5/8" GYP. BOARD ON
4"

1'-4"

4"

4"

4"
PL-3

1'-3 1/4"
3-5/8" 20 GA. METAL TYPICAL ALL

1'-4"
STUDS @ 24" O.C. 3" 1'-1"
EXPOSED SURFACES ELEVATION END VIEW 3" 13" 3" 1'-1"
OF DISPLAY SHELF 16" 16"
RB-1
2'-8" TYP.
ELEVATION END VIEW SECTION RELEASE DATE
1'-0"
DATE DESCRIPTION

07-06-23 FOR PERMITS


12 REDEMPTION DISPLAY SHELF SECTION @ 16" SHELF DEPTH 13 GLASS DISPLAY CASE 14 GLASS DISPLAY SECTION 15 GLASS DISPLAY SECTION 16 T-SHIRT DISPLAY CASE ELEVATION AND PLAN 17 T-SHIRT DISPLAY CASE SIDE VIEW AND SECTION 07-21-23 FOR BIDS
A-203 SCALE: 1 1/2" = 1'-0" A-101 SCALE: 1/2" = 1'-0" A-101
A-502 SCALE: 1/2" = 1'-0" A-101
A-502 SCALE: 1/2" = 1'-0" A-204
A-502 SCALE: 1" = 1'-0" A-204
A-502 SCALE: 1" = 1'-0"
S-502 S-502 S-502

2'-4"

FINGER HOLE ACCESS TO


REMOVE ACCESS COVERS

T.O. SHELF
9'-6" A.F.F.
BLOCKING AS BLOCKING AS
REQUIRED 3/4" PLYWOOD REQUIRED 3/4" PLYWOOD
8"

8"

CONSTRUCTION CONSTRUCTION
7 1/4"

REFER TO FLOOR REFER TO FLOOR


PLAN FOR WALL PLAN FOR WALL
CONSTRUCTION CONSTRUCTION

5/8" GYP. BOARD ON PL-3 5/8" GYP. BOARD ON 2'-0" PL-3


3-5/8" 20 GA. METAL TYPICAL ALL 3-5/8" 20 GA. METAL TYPICAL ALL
STUDS @ 24" O.C. EXPOSED SURFACES STUDS @ 24" O.C. PROJECT
EXPOSED SURFACES
OF DISPLAY SHELF OF DISPLAY SHELF

LIGHT FIXTURE - REFER TO 2112128GR


ELECTRICAL DRAWINGS.
1'-0" 1'-4"
SHEET
7/25/2023 3:40:45 PM

18 REDEMPTION DISPLAY SHELF SECTION AT T-SHIRT DISPLAY 19 REDEMPTION DISPLAY SHELF SECTION @ 24" SHELF DEPTH INTERIOR DETAILS
A-204 SCALE: 1 1/2" = 1'-0" A-203 SCALE: 1 1/2" = 1'-0"

A-502
Hardware Group No. 01
For use on mark/door #(s):
9x30 VISION PANEL 2" DOOR SIZE 2" 2" DOOR SIZE 2"
101A, 133A
SEE SCHED. SEE SCHEDULE

2"
DOOR SCHEDULE

2"
Each To Have:
Qty Description Catalog Number Finish Mfr DOOR FRAME

NUMBER
REMOVABLE SIZE
1 EA MORTISE HOUSING C987 626 FAL FIRE
MULLION

SEE SCHEDULE

SEE SCHEDULE
1 EA PERMANENT CORE C606 626 FAL WIDTH HEIGHT THICKNESS TYPE LABEL MAT. FINISH TYPE DETAIL HW SET REMARKS

DOOR SIZE

DOOR SIZE
T
T 101A (2) 6' - 0" 7' - 1" 1 3/4" FG - AL ANOD AL-1 01 GLASS TYPE GL-1; AUTOMATIC SLIDER UNIT SIZE
BALANCE OF HARDWARE BY DOOR MANUFACTURER 14'-0"W x 7'-8"H; ALUMINUM FRAME AL-1; PARADIGM DESIGN
EMERGENCY BREAKOUT WIDTH = 153.5"; EGRESS
DOOR ARCHITECTS | ENGINEERS

3'-6"
VERIFY EXACT CYLINDER TYPE REQ'D. BALANCE OF EXISTING
T 101B (2) 6' - 0" 7' - 0" 1 3/4" FG - AL ANOD AL-1 02 GLASS TYPE GL-1; AUTOMATIC SLIDER UNIT SIZE
HARDWARE BY SLIDING DOOR MANUFACTURER. 14'-0"W x 7'-8"H; ALUMINUM FRAME AL-1;
EMERGENCY BREAKOUT WIDTH = 153.5"; EGRESS
DOOR
F G FG N FDV OCG HM1 HM2
Hardware Group No. 02
103 (2) 3' - 0" 7' - 0" 1 3/4" EXIST - EXIST PAINT EXIST - 04 UNDERCUT DOOR 1"
FLUSH HALF GLASS FULL GLASS NARROW LITE For use on mark/door #(s): 104A 29' - 3 1/2" 10' - 0" 1 1/2" OCG - ST PREFIN - 1/A-302 10 Grand Rapids | Phoenix | Traverse City
FLEXIBLE DOUBLE OVERHEAD COILING GRILLE 2" GWB 2" GWB 101B, 133B 104B 3' - 10" 7' - 0" 1 3/4" EXIST - EXIST PAINT EX EX PAINT EXISTING DOOR AND FRAME ON ROUND1 www.paradigmae.com
ACTING WITH VISION LITE (EXISTING) HOLLOW METAL FRAME HEAD HOLLOW METAL FRAME HEAD Each To Have: SIDE, PROVIDE PANIC HARDWARE
105 (2) 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 06
Qty Description Catalog Number Finish Mfr
106 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 07 UNDERCUT DOOR 1"
DOOR TYPES DOOR FRAME TYPES HARDWARE BY MANUFACTURER 107 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05 UNDERCUT DOOR 1"
ALL HARDWARE BY SLIDING DOOR MANUFACTURER. 110A (2) 3' - 0" 7' - 0" 1 3/4" FG - AL ANOD AL-5 2/A-601 08
30'-0 3/4" 110B (2) 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 11
2" 3'-1 1/2" 2" 3'-2 1/2" 2" 3'-2 1/2" 2" 9'-8" 2" 3'-2 1/2" 2" 3'-2 1/2" 2" 3'-1 1/2" 2" Hardware Group No. 03 111 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05
112 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05
For use on mark/door #(s):
114 4' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 09 PROVIDE PANIC HARDWARE
3'-11" 1 1/8"

19'-0"
128
2" 2'-4" 2" 13'-8" 2" 2'-4" 2" 15'-0" 115 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05 ADD LATCH GUARD
Each To Have:

4'-10 1/8"
2" 2'-6" 2" 2'-10" 2" 6'-0" 2" 2'-10" 116 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05

2"

2"
Qty Description Catalog Number Finish Mfr 117 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601

2'-10"
2'-8"
121A (2) 3' - 0" 7' - 0" 1 3/4" FG - AL ANOD AL-5 2/A-601 08

2"
HARDWARE BY MANUFACTURER

1'-8"
121B (2) 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 11
ALL HARDWARE BY DUAL ACTION TRAFFIC DOOR MANUFACTURER
2"

122 (2) 3' - 0" 7' - 0" 1 3/4" FG - AL ANOD AL-5 2/A-601 08
11'-11 1/8"

2"
123 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601
Hardware Group No. 04 124 3' - 0" 7' - 0" 1 3/4" FG - AL ANOD AL-5 2/A-601 08

10'-0"
For use on existing mark/door #(s): 127 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05

9'-0"

8'-8"
128 - 3' - 0" 7' - 0" 1 1/2" FDV - HDPE PREFIN ST1 3&4/A-601 03
7'-7"

103 PROJECT

6'-10"

7'-2"
7'-1"

7'-0"
Each To Have: 133A (2) 6' - 0" 7' - 1" 1 3/4" FG AL ANOD AL-1 01
133B (2) 6' - 0" 6' - 11" 1 3/4" FG AL ANOD AL-1 02
Qty Description Catalog Number Finish Mfr
134
136
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
F
F
-
-
HM
HM
PAINT
PAINT
HM1
HM1
1/A-601
1/A-601
07
05 ADD FULL LENGTH LATCH GUARD
ROUND1 -
T T T T T T T T T T 1 EA PERMANENT CORE - AS REQ'D C606 626 FAL
PLAZA BONITA

2"
137 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 1/A-601 05A ADD FULL LENGTH LATCH GUARD
2"

2"
T T T T T T T T T T T
143 (2) 4' - 0" 10' - 0" 1 3/4" F - HM PAINT HM1 6/A-601
BALANCE OF HARDWARE BY DOOR MANUFACTURER S-1A 3' - 0" 7' - 0" 1 3/4" F - HM PAINT HM1 PROVIDE PANIC HARDWARE
AL 1 AL 2 S1-B 3' - 6" 7' - 0" 1 3/4" EXIST - EXIST PAINT EX PROVIDE PANIC HARDWARE
GLASS TYPE 'GL-2' AL 3 FIELD VERIFY EXACT CYLINDER TYPE REQ’D., BALANCE OF HARDWARE EXISTING BY DOOR MANUFACTURER.
NOTE: FIELD VERIFY GLASS TYPE 'GL-1' @ EXTERIOR GLASS TYPE 'GL-2'
EXISTING OPENING GLASS TYPE 'GL-2' @ INTERIOR
FIELD VERIFY EXISTING HARDWARE AND REMOVE & REPLACE DAMAGED/NON-FUNCTIONAL HARDWARE WITH NEW.
DOOR GENERAL NOTES
18'-6" 11'-6"
_DOOR KEY SCHEDULE_ 1. ALL HOLLOW METAL DOORS AND FRAMES TO BE PAINTED WITH
TYPE DESCRIPTION
2" 2'-10" 2" 2'-11" 2" 6'-0" 2" 2'-11" 2" 2'-10" 2" 2'-5" 2" 6'-0" 2" 2'-5" 2" Hardware Group No. 05 QTY ISSUED LABEL ALKYD PAINT (SEMI GLOSS SHEEN) TO MATCH ADJACENT WALL
2"
2"

2"

For use on mark/door #(s): MASTER ALL DOORS


INTERNAL/EXTERNAL 2 GM/AGM M 1,2 2. GL = GLAZING TYPES - REFER TO SPECIFICATIONS
107, 111, 112, 115*, 116, 127, 136*
1'-8"

1'-8"

Each To Have: INTERNAL ALL INTERNAL DOORS -


MOD GL-1: 1" INSULATED GLASS
EXCLUDING SAFE ROOM 4 I 1,2,3,4
Qty Description Catalog Number Finish Mfr KEYSETS GL-2: 1/4" CLEAR GLASS
GL-3: 1/2" CLEAR GLASS
EXTERNAL ENTRANCE DOOR ONLY -
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE OPENING/CLOSING ACCESS 5
KEY
E 1,2,3,4,5
HOLDERS 3. T TEMPERED GLASS
1 EA PUSHBUTTON LOCK CO-100-CY-70-KP-SPA-B 626 SCH
9'-0"
8'-8"

9'-0"
8'-8"

1 EA PERMANENT CORE C606 626 FAL


7'-2"

7'-2"

1 EA SURFACE CLOSER SC81 RW/PA FC 689 FAL Hardware Group No. 06

PULL SIDE For use on mark/door #(s):


TENANT
1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE 105
T T T T
FULL LENGTH LATCH GUARD - VERIFY SIZE PRIOR TO
Each To Have: IMPROVEMENT
2"

T T T T T T
2"

*1 EA LATCH GUARD 630 RBS


ORDER Qty Description Catalog Number Finish Mfr
1 EA WALL STOP WS406/407CCV 630 IVE 6 EA HINGE 5BB1 4.5 X 4.5 NRP 652 IVE
Entrance by pushbutton code or key override.
AL 4 AL 5 2 EA MANUAL FLUSH BOLT FB458 626 IVE

GLASS TYPE 'GL-2' GLASS TYPE 'GL-2' Self-Closing. 1 EA DUST PROOF STRIKE DP2 626 IVE 3030 PLAZA BONITA RD, SUITE
* - ONLY DOORS TO GET LATCHGUARD
1 EA PUSHBUTTON LOCK CO-100-CY-70-KP-SPA-B 626 SCH 1025
1 EA PERMANENT CORE C606 626 FAL NATIONAL CITY, CA 91950
Hardware Group No. 05A
1 EA SURFACE CLOSER SC81 SS FC 689 FAL
For use on mark/door #(s): 1 EA DOOR STOP 410S US32D GLYNN CLIENT
ALUM DOOR FRAMES 137* 2 EA KICK PLATE 8400 10" X 1" LDW B4E 630 IVE
Entrance by pushbutton code or key override. Self-Closing.
ROUND1
Each To Have:

Qty
ENTERTAINMENT
Description Catalog Number Finish Mfr
Hardware Group No. 07
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
For use on mark/door #(s):
3'-3" 2" 3'-4" 2" 3'-3" 16'-6 5/8"
8'-0" 13'-6 1/8" 1 EA PUSHBUTTON LOCK CO-100-CY-70-KP-SPA-B 626 SCH
2" 2" 2" 2" 2" 106, 134
3'-10 5/8" 3'-11 5/8" 3'-11 5/8" 3'-10 5/8" 2" 2" 2" 2" 2" 2" 2" 1
3'-9" 3'-9" 4'-3" 4'-4" 4'-3" EA PERMANENT CORE C606 626 FAL Each To Have:
2"

1
2"

EA SURFACE CLOSER SC81 RW/PA FC 689 FAL Qty Description Catalog Number Finish Mfr
3 EA HW HINGE 5BB1HW 4.5 X 4.5 652 IVE
PULL SIDE
2"

1 EA DORMITORY LOCK T571BDC QUA 626 FAL


5'-8"

1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE 1 EA SURFACE CLOSER SC81 RW/PA FC - PULL SIDE 689 FAL
1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE
FULL LENGTH LATCH GUARD - VERIFY SIZE PRIOR TO 1 EA MOP PLATE 8400 4" X 1" LDW B4E CS 630 IVE
*1 EA LATCH GUARD ORDER 630 RBS
11'-6"

8'-0"

8'-0"

8'-0"

1 EA CORE SFIC C606 626 FAL


1
10'-0"

10'-0"

10'-0"

EA WALL HOLDER WS40 US28 IVE 1 EA WALL STOP WS406/407CCV 630 IVE
2'-0"

Entrance by pushbutton code or key override. 3070 SATURN ST. STE. 200
Deadlocking latch bolt by levers except when locked by push button in inside lever. Key in outside lever locks
GR BREA, CA 92821
Self-Closing. or unlocks outside lever and releases button. Closing door releases push button. Inside lever always free.
2"

2"
2"

*- ONLY DOORS TO GET LATCHGUARD


3'-6"

Hardware Group No. 08


1'-6"

1'-6"

1'-6"

For use on mark/door #(s):


T T T T T T T T T T T T
2"

110A, 121A, 122, 124


Each To Have:
2"
2"

2"

A B Qty Description Catalog Number Finish Mfr


C D
2 SET PIVOT SET 7255 626 IVE
GLASS TYPE 'GL-4' GLASS TYPE 'GL-4' GLASS TYPE 'GL-4' GLASS TYPE 'GL-4'
2 SET DOOR PULL (Back-to Back mount) 8103 EZHD 10” N 630 IVE
28'-2 7/8" 26'-0" 2 EA CONCEALED CLOSER 6033 689 LCN
2" 2" 2" 2" 2" 2" 2" 2" 2" 2" 2" 2" 2" 4 EA WALL STOP WS406/407CCV 630 IVE
4'-6 1/8" 4'-6 1/8" 4'-6 1/8" 4'-6 1/8" 4'-6 1/8" 4'-6 1/4" 4'-11 3/8" 5'-0 3/8" 5'-0 3/8" 5'-0 3/8" 4'-11 3/8"

Hardware Group No. 09


2"

2"

For use on mark/door #(s):


114
Each To Have:
Qty Description Catalog Number Finish Mfr
EXISTING EIFS SYSTEM
8'-0"

8'-0"

3 EA HINGE 5BB1 4.5 X 4.5 NRP 652 IVE


10'-0"

10'-0"

1 EA PUSHBUTTON LOCK CO-100-993R-70-KP-SPA-B 626 SCH


EXISTING WALL SYSTEM 1 EA EXIT DEVICE LD-22-EO-SP28 626 VON
1 EA PERMANENT CORE C606 626 FAL
1 EA SURFACE CLOSER SC81 RW/PA FC 689 FAL
2"

2"

PUSH SIDE
1 EA KICK PLATE 8400 10" X 2" LDW B4E 630 IVE
1'-6"

1'-6"

T T T T T T T T T T T BOX HEADER, IF REQUIRED - 1 EA WALL STOP WS406/407CCV 630 IVE RELEASE DATE
REFER TO STRUCTURAL Entrance by pushbutton code or key override.
2"

2"

EIFS STARTER Self-Closing. DATE DESCRIPTION


F TRACK AS PART OF CONTINUOUS PRESSURE
E TREATED 2x WOOD BLOCKING 07-06-23 FOR PERMITS
DRAINAGE SYSTEM
GLASS TYPE 'GL-4' Hardware Group No. 10 07-21-23 FOR BIDS
GLASS TYPE 'GL-4'
24 GA. GALVANIZED For use on mark/door #(s):
ALUMINUM WINDOW FRAMES METAL DRIP EDGE -
FULL LENGTH OF DOOR
SEALANT - ENTIRE PERIMETER 104A
HOLLOW METAL FRAME Each To Have:
GYP BD JAMB BEYOND Qty Description Catalog Number Finish Mfr
SEALANT - ENTIRE
5/8" GYP. BD. - PAINT DOOR - REFER TO SCHEDULE 1 EA PERMANENT CORE C606 626 FAL
DRYWALL ON MTL. STUD PERIMETER
FRAMING, REFER TO 2" x 5 1/2" H.M. DRYWALL FRAME EIFS JAMB BEYOND - TO BALANCE OF HARDWARE BY DOOR MANUFACTURER
FLOOR PLAN FOR WALL BULKHEAD LINTELMATCH
- EXISTING FINISH
STEEL CHANNEL REFER TO DETAIL
CONSTRUCTION
2 x WOOD STUD HEAD VERIFY EXACT CYLINDER TYPE REQ'D., BALANCE OF HARDWARE BY OVERHEAD COILING GRILLE MANUFACTURER.
CAULK CAULK METAL STUD TRACK PROVIDE MTL.
GYP. BD. ON METAL STUD RECEPTOR HEADS
FRAMING - REFER TO FLOOR 2x WOOD NAILER WOOD JAMB
DOOR - REFER TO SCHEDULE TO ALLOW FOR MIN.
PLAN FOR WALL CONSTRUCTION HEAD FASTENED Hardware Group No. 11
ALUMINUM FRAME 3/4" DEFLECTION
TO STEEL CHANNEL
2 x WOOD STUD EXISTING WALL SYSTEM For use on mark/door #(s):
HEAD CAULK 110B, 121B
2" H.M. DRYWALL FRAME Each To Have:
REFER TO FLOOR PLAN NOTE: Qty Description Catalog Number Finish Mfr
DOOR - REFER TO SCHEDULE DRYWALL ON MTL. STUD FOR WALL CONSTRUCTION HEAD
HEAD FRAMING, REFER TO REFER TO DOOR 6 EA HINGE 5BB1 4.5 X 4.5 NRP 652 IVE
2 x WOOD STUD SCHED. FOR FRAME EIFS JAMB - TO MATCH
FLOOR PLAN FOR WALL
METAL STUD CONSTRUCTION ADJACENT EXISTING FINISH 1 EA CONST LATCHING BOLT FB51T/FB41T (AS REQ'D) 630 IVE
2" x 5 1/2" H.M. DRYWALL FRAME w/
CAULK CAULK (3) JAMB ANCHORS PER STEEL PLATE SEALANT - ENTIRE PERIMETER 2 EA DBL CYL STORE LOCK ND66BDC SPA 626 FAL
MANUFACTURER'S REQUIREMENTS ANCHORED TO SEALANT - ENTIRE PROJECT
2" DRYWALL JAMB SECTION w/ 2x WOOD NAILER 2 EA SFIC CORE C606 626 FAL
(3) ANCHORS PER JAMB FLOOR PERIMETER HOLLOW METAL JAMB SECTION
ALUMINUM FRAME WITH (3) ANCHORS PER JAMB 2 EA WALL STOP WS406/407CCV 630 FAL
JAMB
DOOR - REFER TO SCHEDULE
DOOR - REFER TO SCHEDULE
DOOR - REFER TO SCHEDULE
2 EA AUTO DOOR BOTTOM 355AA AA ZERO 2112128GR
JAMB JAMB 1 EA THRESHOLD 164AA A ZERO
AXONOMETRIC JAMB JAMB
1 EA MEETING STILES SEAL 383AA AA ZERO SHEET
7/25/2023 3:40:46 PM

1 EA PERIMETER GASKET 870AA-S AA ZERO


1 METAL STUD DOOR DETAIL 2 (ALUM) MTL. STUD WALL 3 DOUBLE ACTING SECTION 4 DOUBLE ACTING DOOR FRAME 5 INTERIOR WINDOW HEAD & JAMB 6 EXT. DOOR - H.M. FRAME IN EIFS & STUD WALL VERIFY EXACT CYLINDER / CORE TYPE AND LEVER STYLE REQ'D PRIOR TO PURCHASE. DOOR SCHEDULE AND
SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 1 1/2" = 1'-0" NO CLOSER SO DOORS CAN SWING OPEN 180 DEGREES TO THE WALL STOPS DOOR DETAILS

A-601
FINISH LEGEND FINISH LEGEND _FINISH GENERAL NOTES_
1 BEFORE STARTING ANY WORK OR ORDERING MATERIALS; CONTRACTOR SHALL SECURE
FINISH DESCRIPTION SPECIFICATION LOCATION COMMENTS CONTACT FINISH DESCRIPTION SPECIFICATION LOCATION COMMENTS CONTACT WRITTEN APPROVAL OF FINAL INTERIOR COLOR SCHEDULE AND WALL ELEVATIONS FROM
ARCHITECT. SCOPE OF PROJECT SHOULD INCLUDE MULTIPLE COLORS AND TRANSITIONS.
FLOOR TILE FINISHES WALL TILE FINISHES(CONT.)
DALTILE; FABRIQUE; PORCELAIN FOR PRICING AND ASSISTANCE WITH ORDERING, 2 CARPET CONTRACTOR SHALL CALCULATE YARDAGE FOR PATTERN REPEAT AND PROVIDE
DALTILE; VOLUME 1.0; GLAZED PORCELAIN FAMILY TOILET RESTROOMS; JANITOR GROUT: MAPEI GROUT PLEASE CONTACT: NATIONAL ACCOUNT HELP
EPOXY GROUT; WT-8 WALL TILE COLOR: CRÈME LINEN P686 WOMEN YARDAGE NEEDED TO TENANT AT MOST SIX (6) WEEKS PRIOR TO SCHEDULED INSTALLATION.
FT-1 FLOOR TILE COLOR: DEGRESS SILVER VL71 FLOOR, CUSTOMER SIDE OF BAR &
COLOR: MAPEI #27 SILVER SIZE: 12"x24"
COLOR: #11 "SAHARA BEIGE" DESK 877-556-5728 PARADIGM DESIGN
SIZE: 12"x24" SNACK BAR National.Accounts@daltile.com 3 CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF BASE MATERIAL ON EXPOSED ARCHITECTS | ENGINEERS
DALTILE; CARYSTAL SHORES WOMEN SINK WALL, WOMEN'S ACCENT GROUT: MAPEI GROUT FOR SPECIAL CONCERNS AND ESCALATIONS, PLEASE PERIMETER OF ALL MILLWORK.
WT-9 MOSAIC WALL TILE CONTACT: DONNA APCAR-NATIONAL ACCOUNT
COLOR: CS95 SAPPHIRE LAGOON 2X1 BRICK JOINT MOSAIC AT ENTRANCE COLOR: #11 "SAHARA BEIGE"
DALTILE, QUARRY TEXTURES™ QUARRY TILE; COLOR ASHEN EPOXY GROUT; MANAGER 4 PROVIDE FLOOR LEVELING COMPOUND OVER CONCRETE FLOOR AS REQUIRED AT THE TILE
FT-2 FLOOR TILE SNACK BAR; KITCHEN; BAR FLOORING TO ALIGN THE TOP OF THE TILE WITH THE TOP OF THE CARPET PILE.
GRAY - OT03, ABRASIVE GRAIN; SIZE: 6"x6" COLOR: MAPEI #11 SAHARA BEIGE DALTILE; COLOR WHEEL LINEAR 818-303-6911 Donna.apcar@dalitile.com
GROUT: MAPEI GROUT
WT-10 WALL TILE COLOR: CURRANT GLOSSY SH17 MALL ENTRANCE
COLOR: #27 "SILVER" REFER 5 IN AREAS NOT ACCESSED BY PUBLIC (E.G. OFFICE, STORAGE, BACKROOMS, ETC.) PROVIDE
SIZE: 8"x24" AND 6"x18"
DALTILE; VOLUME 1.0; CONT. BLACK RESILIENT TRANSITION MOULDING AT DISSIMILAR MATERIALS. COORDINATE Grand Rapids | Phoenix | Traverse City
EPOXY GROUT; DALTILE; VOLUME 1.0 GROUT: MAPEI GROUT SHAPE AND STYLE OF TRANSITION PIECE WITH ADJACENT FLOOR FINISH. www.paradigmae.com
FT-3 FLOOR TILE COLOR: DEGRESS SILVER VL71 CUSTOMER SIDE OF BAR
COLOR: MAPEI #27 SILVER WT-11 WALL TILE COLOR: AMPLIFY BLACK VL70 MALL ENTRANCE COLOR: #27 "SILVER" REFER
SIZE: 12"x12"
SIZE: 12"x24" VERTICAL STACK
6 ALL PUBLIC AREAS PROVIDE TANDUS METAL EDGE TRANSITION BETWEEN DISSIMILAR
WT-12 NOT USED MATERIALS
DALTILE; VOLUME 1.0;
COLOR: DEGRESS SILVER VL71 DALTILE; COLOR WHEEL LINEAR 7 TILE CONTRACTOR SHALL USE PROPER TRIMS, BULLNOSE, AND COVED BASE. NO TILE WORK
FT-4 FLOOR TILE WOMENS RESTROOM ADDITION GROUT: MAPEI GROUT COLOR: #27
WT-13 WALL TILE COLOR: ARCTIC WHITE 0190 SNACK BAR SHALL END ON AN EXPOSED OUTSIDE CORNER. FAILURE TO CORRECT TILE INSTALLATIONS
SIZE: 12"x12" "SILVER" TO COMPLY WILL RESULT IN REJECTION OF WORK. ALL WORK MUST BE APPROVED BY THE
SIZE: 4"x16" HERRINGBONE PATTERN
LOCAL HEALTH DEPARTMENT IN FOOD PREPARATION AREAS.
CARPET FINISHES VIRGINIA TILE; PERSPECTICA GROUT: TEC
WT-14 WALL TILE COLOR: GRAVITY GRAY PE10 RESTROOM ENTRY COLOR: #934 SLATE GRAY VERTICAL 8 CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY FLOOR LEVELING TO MAKE FINISH
ASTRO CARPET: BROADLOOM SIZE: 8"x24" STACK
IN FRONT OF GUEST COUNTER AND SURFACE FLUSH WITH ADJACENT SURFACE. THIS INCLUDES NECESSARY SLOPED FLOOR
STYLE: L7545 R1 STRIATION
CP-1 CARPET SNACK BAR; PARTY ROOMS; OFFICE; TRANSITION TO FLUSH TENANT FINISH SURFACE WITH ADJACENT EXISTING MALL FLOOR
COLOR: 2755/CU5462 FINISH.
HIGH VALUE STORAGE, VIRGINIA TILE; PERSPECTICA GROUT: TEC
REPEAT: 36"x36"
WT-15 WALL TILE COLOR: PACIFIC BLUE PE11 OUTSIDE RESTROOMS COLOR: #934 SLATE GRAY REFER TO
9 TILE INSTALLATION OVER EXISTING CONSTRUCTION OR CONTROL JOINTS SHALL INCLUDE
ASTRO CARPET: BROADLOOM SIZE: 8"x24" ELEVATIONS FOR STACK DIRECTION INSTALLATION OF AN ANTI FRACTURE MEMBRANE INSTALLED OVER JOINT PER
STYLE: L7676 HEXAGON MANUFACTURERS INSTRUCTIONS.
CP-2 CARPET BILLIARDS WALLCOVERING FINISHES
COLOR: 7447/CU7447
10 PROVIDE WATERPROOFING MEMBRANE ADJACENT TO ALL WET AREAS. TURN AND EXTEND
REPEAT: 72"x62" MEMBRANE EDGE 6" UP WALL FINISH OR HEIGHT OF CABINET BASE INSTALLED PER
PAINTER TO PREP WALLS AS REQUIRED TO MANUFACTURERS INSTRUCTIONS.
CUSTOM VINYL GRAPHICS, SUPPLIED AND INSTALLED BY SNACK BAR, GUEST COUNTER, COORDINATE FINAL LOCATION OF GRAPHICS W/
ASTRO CARPET: BROADLOOM GR-1 VINYL GRAPHICS PROVIDE A SMOOTH PAINT FINISH FREE OF
OWNER REDEMPT., ETC. TENANT 11 FLOORING CONTRACTOR SHALL INSTALL FLOOR FINISH CONTINUOUS UNDER UNFIXED
STYLE: L8102 R1 TWEED DEBRIS
CP-3 CARPET PATHS EQUIPMENT AND MILLWORK COUNTERTOPS. FLOOR FINISH SHALL TERMINATE AT MILLWORK
COLOR: 3014/GL6126 PROJECT
BASE OR WALL BASE.
REPEAT: 36"x36"
PAINTER TO PREP WALLS AS REQUIRED TO 12 CARPET SUPPLIED BY OWNER. INSTALLATION AND ALL ACCESSORIES NECESSARY TO INSTALL
DLCOUCH RECYCLED TYPE II
ASTRO CARPET: BROADLOOM
STYLE: L8303 R1 OPT8B
WC-1 VINYL WALLCOVERING
COLOR: 2VRE-04
LOW WALLS AT BILLIARDS PROVIDE A SMOOTH PAINT FINISH FREE OF
DEBRIS
CARPET BY GENERAL CONTRACTOR - REFER TO SPECIFICATION ROUND1 -
CP-4 CARPET ARCADE
COLOR: 7963/CU7963
REPEAT: 36"x36"
13
14
REFER TO A-701 AND DETAILS ON A-501 FOR RS-1 ON COLUMNS AS SHOWN
REFER TO SHEET A-161 FOR CEILING FINISH INFORMATION
PLAZA BONITA
MISC. WALL FINISHES
MISC. FLOORING FINISHES 15 ALL HOLLOW METAL DOORS AND FRAMES TO BE PAINTED WITH ALKYD PAINT (SEMI GLOSS
SHEEN) TO MATCH ADJACENT WALL
MANNINGTON COMMERCIAL; FRIXTION INTERTIA COLOR: SLIDE BRUSHED ALUMINUM., 4'-0" HIGH, START AT TOP OF BASE; 2"
CG-2 CORNER GUARD ALL OUTSIDE GYP BD CORNERS, TYP. REFER TO DETAIL 4/A-501 16 DRY-FALL CEILING PAINT WILL BE APPLIED AFTER NORMAL WORK HOURS AND CLOSELY
34368 CARSON COOPER LEGS, SCREW ATTACHED
MA-1 WALK OFF MAT EXTERIOR ENTRANCE COORDINATED WITH THE GENERAL CONTRACTORS FIELD MANAGER
SIZE: 18"x36" CARSON.COOPER@MANNINGTON.COM 414-335-9448 PLASTIC LUMBER YARD 1/2"x6" HDPE, RADIUSED AT EXPOSED
PATTERN: STAGGERED BILLIARDS - REFER TO WALL FINISH PLAN AND INTERIOR ELEVATIONS. REFER TO 17 PROVIDE A TAPE LINE ON STORAGE ROOM WALLS 18" BELOW THE LOWEST OBSTRUCTION, FP
CR-1 CHAIR RAIL EDGES. LINES ETC.
DETAIL 14/A-501
TANDUS CENTIVA; EVENT SERIES WOOD CRAFTED PLANK: COLOR: DARK GRAY
18 PROVIDE CAUTION TAPE ON FLOOR FOR CLEARANCE IN FRONT OF ELECTRICAL EQUIPMENT -
VT-1 WOOK LOOK VINYL BRUNSWICK ECF2121 TG BOWLERS SEATING MARLITE; FRP PANEL AND TRIM COORDINATE WITH ELECTRICAL PLANS
SIZE: 6"x48" FP-1 FIBERGLASS REINFORCED PANEL STYLE: PEBBLED SURFACE KITCHEN
ARMSTRONG; STANDARD EXCELON; COLOR: P100 WHITE
VINYL COMPOSITION TILE - EMPLOYEE LOUNGE; A/V/; STORAGE;
VT-2 COLOR: 51915 - CHARCOAL; SDATEMA@FLORSTAR.COM 616-204-5540 MARLITE; FRP PANEL AND TRIM
CHARCOAL FACILITY STORAGE; SERVICE AISLE PORTION OF MECHANIC'S ROOM,
SIZE: 12"x12" FP-2 FIBERGLASS REINFORCED PANEL STYLE: PEBBLED SURFACE
JANITORS CLOSET
COLOR: P430N MEDIUM GRAY
DURKAN; HOT AND HEAVY
PATTERN; LINEATE REFERENCE TO PATTERN FROM LONSEAL;
VT-4 LUXURY VINYL TILE - ORANGE SEATING AREA COLUMN WRAP AT BOWLING LANES;
COLOR: 232 BARRED MANUFACTURER RS-1 RESILENT SHEET VINYL STYLE: LONPLATE I REFER TO DETAIL 10/A-501
SIZE: 9"x59" BOWLER SEATING
COLOR: 161 METALLIC GRAY
DURKAN; HOT AND HEAVY AUDIMUTE ACOUSTICAL PANEL;
PATTERN; LINEATE REFERENCE TO PATTERN FROM MEREDITH SCHOLLE SA-1 SOUND-ABSORBING WALL PANEL ECO-C-TEX ACOUSTICAL PANELS PINSETTER SERVICE
VT-5 LUXURY VINYL TILE - BLUE SEATING AREA
COLOR: 656 LINES
SIZE: 9"x59"
MANUFACTURER MEREDITH.SCHOLLE@MOHAWKIND.COM 616-250-5317 FINISH COLOR: NATURAL TENANT
DURKAN; HOT AND HEAVY WS-1 SLATWALL WHITE MELAMINE w/ ALUMINUM INSERT'S REDEMPTION
REFER TO DETAIL 11/A-501. CONTRACTOR TO
ORDER 20% EXTRA SLATWALL TO ENSURE ENOUGH QUANTITY TO COMPLETE THE PROJECT
IMPROVEMENT
PATTERN; LINEATE REFERENCE TO PATTERN FROM MEREDITH SCHOLLE
VT-6 LUXURY VINYL TILE - GRAY SEATING AREA
COLOR: 948 FIGURED MANUFACTURER MEREDITH.SCHOLLE@MOHAWKIND.COM 616-250-5317 PAINT FINSHES
SIZE: 9"x59"
TYP. WALL ABOVE 12'-0" A.F.F. ON ROUND 1
SHERWIN WILLIAMS; EXPOSED CEILING AND STRUCTURE
DURKAN; MATUTO PLUS STONE PT-1 INTERIOR PAINT - DARK GRAY SIDE
COLOR: SW 7067 CITYSCAPE ON LOWER LEVEL
FLAT PAINT
3030 PLAZA BONITA RD, SUITE
COLOR: 915A FROSTBITE STONE MEREDITH SCHOLLE
VT-7 VINYL PLANK
SIZE: 9"x59"
REDEMPTION STORE
MEREDITH.SCHOLLE@MOHAWKIND.COM 616-250-5317 1025
SHERWIN WILLIAMS;
INSTALLATION: CUSTOM, HALF-LAP PT-2 EXTERIOR PAINT - DARK GRAY
COLOR: SW 7076 CYBERSPACE
EXTERIOR ENTRANCE NATIONAL CITY, CA 91950
SHERWIN WILLIAMS; CLIENT
TANDUS CENTIVA; EVENT SERIES WOOD CRAFTED PLANK: PT-3 INTERIOR PAINT BULKHEADS, GUEST COUNTER SEMI GLOSS OVER SNACK BAR AND BAR
VT-8 VINYL PLANK BOWLERS SEATING COLOR: SW 7035 AESTHETIC WHITE
WHITEWASHED ECF2118 TG SIZE: 6"x48"

TARKETT: TANDUS CENTIVA; VICTORY SERIES STYLE: CORAL


PT-4 INTERIOR PAINT - BLUE
SHERWIN WILLIAMS;
COLOR: SW 6965 HYPER BLUE
ARCADE COLUMNS
ALL PAINT SHEENS ARE SATIN/EGGSHELL
UNLESS NOTED OTHERWISE
ROUND1
VT-9 SOLID VINYL TILE
REEF
MALL ENTRY PT-5 INTERIOR PAINT - GREEN
SHERWIN WILLIAMS;
SNACK BAR
ENTERTAINMENT
COLOR: MIST 0068 COLOR: SW 6711 PARAKEET
SIZE: 18"x18"
PT-6 NOT USED
WALL BASE FINISHES SHERWIN WILLIAMS;
PT-7 INTERIOR PAINT - DARK GRAY SIDE OF LANES AT RAMPS
MOHAWK GROUP: C0116 / 63125 COVE BASE, 4" COLOR: 99 COLOR: SW 7069 IRON CORE
RB-1 RUBBER WALL BASE TYPICAL BASO U.N.O
BLACK BROWN SHERWIN WILLIAMS;
PT-8 INTERIOR PAINT OFFICE, SAFE
DALITE; VOLUME 1.0; COLOR: SW 7071 GRAY SCREEN
SCHLUTER DILEX COVE PROFILE - SATIN
WB-1 BULLNOSE TILE COLOR: INTENSITY PEBBLE VL72 JANITOR; RESTROOM ALCOVE SHERWIN WILLIAMS; MECHANIC, PINSETTER SERVICE,
ANODIZED ALUMINUM PT-9 INTERIOR PAINT - LIGHT GRAY
SIZE: 3"x12" COLOR: SW 7017 DORIAN GRAY STORAGE ROOMS
SHERWIN WILLIAMS;
DALITE; QUARRY TEXTURES™ QUARRY TILE; COLOR: ASHEN PT-10 INTERIOR PAINT SEATING AREA
WB-2 COVE QUARRY TILE BASE KITCHEN; SNACK BAR; BAR COLOR: SW 5633 INVENTIVE ORANGE
GRAY - OT03, ABRASIVE GRAIN; SIZE: 5"x6"
SHERWIN WILLIAMS;
PT-11 INTERIOR PAINT OFFICE ACCENT WALL
SCHLUTER SYSTEMS; DILEX COVE; COLOR: SW 6228 REFUGE
WB-3 COVE-SHAPED PROFILE SATIN ANODIZED ALUMINUM; RESTROOMS SHERWIN WILLIAMS;
AHK 1S 100AE PT-12 INTERIOR PAINT - RED 3070 SATURN ST. STE. 200
COLOR: SW 6866 HEARTTHROB
FLOOR TRANSITIONS PT-13 NOT USED BREA, CA 92821
SHERWIN WILLIAMS;
TANDUS METAL EDGE VINYL TO CARPET AND CARPET TO PT-14 INTERIOR PAINT - GRAY ARCADE WALLS
REFER TO GENERAL NOTE #6 REFER COLOR: SW 7065 ARGOS
TR-1 TRANSITION ENGINEERED TILE SPORTS FLOORING) TYPICAL BASO U.N.O
TO DETAIL 15/A-501 SHERWIN WILLIAMS; PAINTED TO PREP WALLS AS REQUIRED TO PROVIDE A SMOOTH PAINT FINISH FREE OF DEBRIS TO
COLOR: STEEL #00179 PT-14* INTERIOR PAINT - GRAY BENEATH WC-1
COLOR: SW 7065 ARGOS ALLOW FOR PROPER INSTALLATION OF VENDOR GRAPHICS
SHERWIN WILLIAMS;
TR-2 TRANSITION SCHLUTER SCHIENE VINYL TO TILE OR CARPET TO TILE PUBLIC AREAS PT-15 INTERIOR PAINT - BLUE OUTSIDE LOW WALLS AT LANES
COLOR: SW 6226 LANGUID BLUE
CONT. BLACK RESILIENT TRANSITION MOULDING (VNYL TO SHERWIN WILLIAMS;
TR-3 TRANSITION NON-PUBLIC AREAS REFER TO GENERAL NOTE #5 PT-16 INTERIOR PAINT - ORANGE PARTY ROOMS
CARPET) COLOR: CHIVALRY COPPER 6353
SHERWIN WILLIAMS;
BLACK TRANSITION STRIP BOWLING LANESS TO BOWLERS JUAN LOEBEL WWW.POLYMERFAB.NET PT-17 INTERIOR PAINT - GRAY BAR
TR-4 TRANSITION REFER TO DETAIL 2/A-501 COLOR: SW 7066 GRAY MATTERS
DETAIL "C" BY POLYMER FABRICATION INC. SEATING 386-673-3012
SHERWIN WILLIAMS;
PT-18 INTERIOR PAINT - EMPLOYEE LOUNGE
COLOR: SW 6220 INTERESTING AQUA
TR-5 TRANSITION MOHAWK GROUP REDUCER - COLOR: 99 BLACK BROWN
SHERWIN WILLIAMS;
PT-19 INTERIOR PAINT - PARTY ROOMS
COLOR: DOVER WHITE 6385
PLASTIC LAMINATE FINISHES
SHERWIN WILLIAMS;
PIONITE; PT-20 INTERIOR PAINT - BLUE PARTY ROOM
COLOR: 6946 SURFER
PL-1 PLASTIC LAMINATE PATTERN: WEDDING CAKE WT790 GUEST COUNTER
TEXTURED / SUEDE SHERWIN WILLIAMS;
PT-21 INTERIOR PAINT - BLUE PARTY ROOM
COLOR: 6958 DYNAMIC BLUE
FORMICA; REDEMPTION CUBBIES,
PL-2 PLASTIC LAMINATE REFER TO DETAIL 10-11/A-502 & 16-18/A-502 SHERWIN WILLIAMS;
COLOR: #7223C-90 NEW WHITE ORIGINAL GOODS SHELF PT-22 INTERIOR PAINT - PURPLE PARTY ROOM
COLOR: 6982 GUTSY GRAPE
WILSONART; PT-23 NOT USED
PL-3 PLASTIC LAMINATE REDEMPTION SHELVES REFER TO DETAIL 12/A-502
COLOR: 6256-419 BRITE BRUSHED NATURAL ALUMINUM SHERWIN WILLIAMS;
PT-24 INTERIOR PAINT DUCTWORK ACCENT
COLOR: 6905 GOLDFINCH
FORMICA; REDEMPTION DISPLAY CASES AND
PL-4 PLASTIC LAMINATE REFER TO DETAILS 13-15/A-502 SHERWIN WILLIAMS;
COLOR: #909-90 COLORE CORE "BLACK" BASE PT-25 INTERIOR PAINT
COLOR: 6909 LEMON TWIST
NEVAMAR;
PL-5 PLASTIC LAMINATE SNACK BAR COUNTER SHERWIN WILLIAMS; RELEASE DATE
PATTERN: CUTTING EDGE WZ2009 ARP PT-26 INTERIOR PAINT - BLUE SEMI GLOSS
COLOR: 6766 MARINER
LAB DESIGNS;
PATTERN: BLACK KRINKLE MATTE SHERWIN WILLIAMS; DATE DESCRIPTION
PL-6 PLASTIC LAMINATE BAR ORIENTATION: VERTICAL PT-27 INTERIOR PAINT - RED SEMI GLOSS
SIZE: 4'x8' COLOR: 6867 FIREWORKS
07-06-23 FOR PERMITS
SHERWIN WILLIAMS;
PIONITE; PT-28 INTERIOR PAINT 07-21-23 FOR BIDS
PL-7 PLASTIC LAMINATE BAR COLOR: 6957 UNDERCOOL
PATTERN: MOON DUST MG115 STONEX
SHERWIN WILLIAMS;
SOLID SURFACE COUNTERTOP FINISHES PT-29 INTERIOR PAINT
COLOR: 7004 SNOWBOUND
FORMICA; PT-30 NOT USED
SS-1 SOLID SURFACE COLOR: 650 - EBONY MOSAIC MENS RESTROOM REFER TO SHEET A-401 AND A-402
PT-31 NOT USED
FINISH: S1 SIZE: 1/2"
PT-32 NOT USED
FORMICA;
SS-2 SOLID SURFACE COLOR: 742 - BLANCO TERRAZZO WOMENS RESTROOM REFER TO SHEET A-401 AND A-402 PT-33 NOT USED
FINISH: S1 SIZE: 1/2"
PT-34 NOT USED
LOW-WALL CAP; BOWLER SEATING
SS-3 SOLID SURFACE TBD REFER TO DETAILS 5/A-501 AND 7/A-501 PT-35 NOT USED
RAIL
SHERWIN WILLIAMS;
WALL TILE FINISHES PT-36 INTERIOR PAINT - YELLOW
COLOR: SW 6682 JUNE DAY
GAME ROOM WALLS
DALTILE; SEMIGLOSS GROUT: MAPEI GROUT COLOR: #27 FOR PRICING AND ASSISTANCE WITH ORDERING,
PLEASE CONTACT: NATIONAL ACCOUNT HELP SHERWIN WILLIAMS;
WT-1 WALL TILE COLOR: ARCTIC WHITE SNACK BAR, KITCHEN "SILVER" VERTICAL STAGGERED PT-37 INTERIOR PAINT - LIGHT GREEN GAME ROOM WALLS
DESK 877-556-5728 COLOR: SW 6709 GLEEFUL
SIZE: 8"x24" PATTERN
National.Accounts@daltile.com PT-38 NOT USED
DALTILE; SEMIGLOSS FOR SPECIAL CONCERNS AND ESCALATIONS, PLEASE
GROUT: MAPEI GROUT COLOR: #27 PT-39 NOT USED
WT-2 WALL TILE COLOR: CHALKBOARD Q180 MENS RESTROOM AT ENTRANCE CONTACT: DONNA APCAR-NATIONAL ACCOUNT
"SILVER"
SIZE: 4"x12" MANAGER
DALTILE; PORTFOLIO 818-303-6911 Donna.apcar@dalitile.com
GROUT: MAPEI GROUT COLOR: #27
WT-3 WALL TILE COLOR: CHARCOAL PF05 MENS; FAMILY RESTROOM
"SILVER"
SIZE: 12"x24"
PROJECT
DALTILE; PORTFOLIO
MENS & FAMILY RESTROOM ACCENT & GROUT: MAPEI GROUT COLOR: #27
WT-4 WALL TILE COLOR: ASH GREY PF05
SINK WALL "SILVER" REFER
SIZE: 12"x24"
2112128GR
DALTILE; CASCADING WATERS MENS SINK WALL ACCENT & ACCENT GROUT: MAPEI GROUT COLOR: #27
WT-5 MOSAIC WALL TILE
COLOR: CHERULEAN SWELL CW45 AT ENTRANCE "SILVER" REFER
DALTILE; FABRIC ART
SHEET
7/25/2023 3:40:46 PM

GROUT: MAPEI GROUT COLOR: #11


WT-6 WALL TILE COLOR: MODERN TEXTILE TAUPE MT52 WOMENS SINK WALL
"SAHARA BEIGE"
SIZE: 12"x24" FINISH KEY AND ROOM
DALTILE; COLOR WHEEL LINEAR SEMI-GLOSS
GROUT: MAPEI GROUT COLOR: #11 FINISH SCHEDULE
WT-7 WALL TILE COLOR: BISCUIT K175 WOMENS RESTROOM AT ENTRANCE
"SAHARA BEIGE"
SIZE: 4"x12"
A-602
FLOOR FINISH LEGEND FLOOR FINISH GENERAL
NOTES
CP-1 CP-6 MA-1 NO. NOTE
VT-5
A. BEFORE STARTING ANY WORK OR ORDERING
MATERIALS; CONTRACTOR SHALL SECURE WRITTEN
CP-2 FT-1 VT-1 VT-6 APPROVAL OF FINAL INTERIOR COLOR SCHEDULE AND PARADIGM DESIGN
WALL ELEVATIONS FROM ARCHITECT. SCOPE OF
PROJECT SHOULD INCLUDE MULTIPLE COLORS AND ARCHITECTS | ENGINEERS
CP-3 FT-2 VT-2 VT-7 TRANSITIONS
B. CARPET CONTRACTOR SHALL CALCULATE YARDAGE
FOR PATTERN REPEAT AND PROVIDE YARDAGE
VT-3 VT-8 NEEDED TO TENANT AT MOST SIX (6) WEEKS PRIOR TO
CP-4 FT-3
SCHEDULED INSTALLATION
C. CONTRACTOR SHALL BE RESPONSIBLE FOR
Grand Rapids | Phoenix | Traverse City
INSTALLATION OF BASE MATERIAL ON EXPOSED
CP-5 FT-4 VT-4 VT-9 www.paradigmae.com
PERIMETER OF ALL MILLWORK
D. PROVIDE FLOOR LEVELING COMPOUND OVER
CONCRETE FLOOR AS REQUIRED AT THE TILE
FLOORING TO ALIGN THE TOP OF THE TILE WITH THE
REFER TO SHEET A-602 FOR ROOM FINISH SCHEDULE AND KEY TOP OF THE CARPET PILE
E. IN AREAS NOT ACCESSED BY PUBLIC (E.G. OFFICE,
STORAGE, BACKROOMS, ETC.) PROVIDE CONT. BLACK
RESILIENT TRANSITION MOULDING AT DISSIMILAR
MATERIALS. COORDINATE SHAPE AND STYLE OF
FIRE TRANSITION PIECE WITH ADJACENT FLOOR FINISH
FT 1 STORAGE UP
STAIR 1
RISER F. ALL PUBLIC AREAS PROVIDE TANDUS METAL EDGE
VT 2 111 TR 5 113 TRANSITION BETWEEN DISSIMILAR MATERIALS
WB 3
MENS S-1 STORAGE G. TILE CONTRACTOR SHALL USE PROPER TRIMS,
RB 1
108 VT 2 112 BULLNOSE, AND COVED BASE. NO TILE WORK SHALL
CP 1 RB 1 END ON AN EXPOSED OUTSIDE CORNER. FAILURE TO
RB 1 CP 3 CORRECT TILE INSTALLATIONS TO COMPLY WILL
TR 1 TR 3 RESULT IN REJECTION OF WORK. ALL WORK MUST BE
FT 1 JANITOR RB 1
PLUSH APPROVED BY THE LOCAL HEALTH DEPARTMENT IN
WB 1 107 PARTY
STORAGE ELECTRICAL FOOD PREPARATION AREAS
ROOM 1
105 VT 2 114 H. CONTRACTOR SHALL BE RESPONSIBLE FOR
FT 1 110
TR 1 NECESSARY FLOOR LEVELING TO MAKE FINISH
RB 1 WB 3

12'-2 1/4"
SURFACE FLUSH WITH ADJACENT SURFACE. THIS
FT 1 WOMENS INCLUDES NECESSARY SLOPED FLOOR TRANSITION TO
FAMILY 109 FLUSH TENANT FINISH SURFACE WITH ADJACENT
PROJECT
WB 3 VT 2
TOILET EXISTING MALL FLOOR FINISH
RB 1
106
CP 3
I. TILE INSTALLATION OVER EXISTING CONSTRUCTION OR
CONTROL JOINTS SHALL INCLUDE INSTALLATION OF AN ROUND1 -
ANTI FRACTURE MEMBRANE INSTALLED OVER JOINT
TR 1 RB 1
J.
PER MANUFACTURERS INSTRUCTIONS
PROVIDE WATERPROOFING MEMBRANE ADJACENT TO
PLAZA BONITA

6'-0"
TR 2 TR 3 FREIGHT

14'-9 3/4"
ELEVATOR ALL WET AREAS. TURN AND EXTEND MEMBRANE EDGE
15'-1"

ELEV-1 6" UP WALL FINISH OR HEIGHT OF CABINET BASE


CP 1 INSTALLED PER MANUFACTURERS INSTRUCTIONS
RB 1 K. FLOORING CONTRACTOR SHALL INSTALL FLOOR FINISH
CONTINUOUS UNDER UNFIXED EQUIPMENT AND
CP 1 PARTY MILLWORK COUNTERTOPS. FLOOR FINISH SHALL
RB 1 ROOM 2 TERMINATE AT MILLWORK BASE OR WALL BASE
PARTY 121 VT 2 L. CARPET SUPPLIED BY OWNER. INSTALLATION AND ALL
CP 3 REDEMPTION
6'-0"

ROOM 4 TR 1 RB 1 ACCESSORIES NECESSARY TO INSTALL CARPET BY


RB 1 TR 1 STORAGE
124 BOWLING BOWLING PINSETTER A.V. GENERAL CONTRACTOR - REFER TO SPECIFICATION

14'-11 1/4"
123 BOWLER'S M. REFER TO A-701 AND DETAILS ON A-501 FOR RS-1 ON
CP 4 APPROACH LANES SERVICE 115
VT 1 SEATING COLUMNS AS SHOWN
36'-0" 6'-0" 22'-3" RB 1 119 118 117
RB 1 120 N. REFER TO SHEET A-161 AND A-162 FOR CEILING FINISH
EXISTING MALL CONCOURSE INFORMATION

42'-5 5/8" +/-


FLOOR TILE ALONG NEW CP 3 VT 2 CP 3 O. ALL HOLLOW METAL DOORS AND FRAMES TO BE
VT 2 RB 1
STOREFRONT WALL TO BE RB 1 RB 1 PAINTED WITH ALKYD PAINT (SEMI GLOSS SHEEN) TO
RB 1 MATCH ADJACENT WALL
REPLACED/REPAIRED AS 6'-0" TR 3
REQUIRED - COORDINATE WITH P. DRY-FALL CEILING PAINT WILL BE APPLIED AFTER
PARTY TR 1 VT 2 NORMAL WORK HOURS AND CLOSELY COORDINATED
LANDLORD
ROOM 3 RB 1 WITH THE GENERAL CONTRACTORS FIELD MANAGER

14'-9"
122 Q. PRIOR TO STARTING FINISH PAINTING, THE
VENDING VT 8 SUBCONTRACTOR WILL VERIFY ALL COLORS AND ALL
124 RB 1
CP 3
CP 4
CP 3
CP 4
CP 1 MECHANIC'S
SHEEN LEVELS WITH THE GENERAL CONTRACTORS
FIELD MANAGER. ONE WEEK PRIOR TO ANY FINISH
TENANT
RB 1 RB 1
RB 1 RB 1 RB 1 116 PAINTING STARTING PROVIDE AN 8'x8' WALL TEST AREA
ONSITE TO VERIFY ALL SHEEN LEVELS WITH THE
IMPROVEMENT
50'-1 3/8"

VT 5 GENERAL CONTRACTORS FIELD MANAGER


RB 1 VT 2
R. PROVIDE A TAPE LINE ON STORAGE ROOM WALLS 18"
RB 1 BELOW THE CEILING - REFER TO ROOM FINISH

11'-7 5/8"
NOT IN CONTRACT LEASELINE SCHEDULE.
TR 3
CP 3 REDEMPTION 3030 PLAZA BONITA RD, SUITE
6'-0"
RB 1 TR 1 STORE
125
UP 1025
FT 2 NATIONAL CITY, CA 91950
WB 2
CLIENT
KITCHEN
128 ROUND1
BAR
CP 1
130 ENTERTAINMENT
RB 1 VT 4 SEATING
VT 5 131
VT 9 MECHANICAL CP 2
36'-1 7/8"

VT 6 MA 1
CP 3 127 TR 2 RB 1
6'-0"

RB 1 RB 1
TR 1 RB 1
TR 2 GUEST VT 2
COUNTER RB 1 TR 2
126

MALL
ENTRANCE
104 CP 1 FT 2 WB 1 SNACK
RB 1 TR 2 BAR
129
7'-0 3/4"

CP 3 RB 1 CP 3 RB 1
CP 1
TR 2
3070 SATURN ST. STE. 200
FT 1
6'-0"

RB 1 BREA, CA 92821
TR 2 TR 1 TR 1
CP 3 11'-6 1/4" 6'-0" 9'-2 1/4" CP 3

6'-0"
RB 1 RB 1

19'-3 1/4" 6'-0" 50'-0 3/8"


UP
58'-0"

STAIR
S-2
CP 4 CP 3 CP 4 CP 4 CP 3 CP 4 CP 3 CP 4 CP 3 CP 4 CP 3 CP 4
RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1
39'-11 1/2"

37'-7 1/8" +/-


EXISTING MALL CONCOURSE
FLOOR TILE ALONG NEW
STOREFRONT WALL TO BE
REPLACED/REPAIRED AS
REQUIRED - COORDINATE WITH
LANDLORD
19'-4 1/4" 6'-0" 63'-0 3/4" 6'-0" 45'-9 1/2" 6'-0" 45'-8 3/4" 6'-0" 25'-5 1/4"
6'-0"
6'-0"

CP 3
6'-0"

6'-0"
RB 1
1'-7 3/4" +/-

6'-0" RELEASE DATE


3'-1" 6'-0" 3'-1"
TR 1 DATE DESCRIPTION
12'-2"

3'-4"
07-06-23 FOR PERMITS
07-21-23 FOR BIDS
VESTIBULE
27'-11 1/4"

CP 1 HIGH
CP 4
101 MA 1 RB 1 RB 1 VALUE EMPLOYEE STORAGE/
RB 1 STORAGE OFFICE LOUNGE LACTATION
137 136 135 134
CP 1
RB 1 VT 2
ELECTRICAL
VT 2 TR 1 RB 1
103 VT 2
TR 1 RB 1
RB 1

PROJECT

N
FIRST FLOOR FINISH PLAN 2112128GR
SCALE: 1" = 10'-0"

SHEET
7/25/2023 3:40:53 PM

FLOOR FINISH PLAN

A-701
FINISH GENERAL NOTES
NO. NOTE

1. BEFORE STARTING ANY WORK OR ORDERING


MATERIALS; CONTRACTOR SHALL SECURE WRITTEN
APPROVAL OF FINAL INTERIOR COLOR SCHEDULE AND
WALL ELEVATIONS FROM ARCHITECT. SCOPE OF
PROJECT SHOULD INCLUDE MULTIPLE COLORS AND
TRANSITIONS. PARADIGM DESIGN
2. CARPET CONTRACTOR SHALL CALCULATE YARDAGE ARCHITECTS | ENGINEERS
FOR PATTERN REPEAT AND PROVIDE YARDAGE
NEEDED TO TENANT AT MOST SIX (6) WEEKS PRIOR TO
SCHEDULED INSTALLATION.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR


INSTALLATION OF BASE MATERIAL ON EXPOSED
PERIMETER OF ALL MILLWORK. Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
4. PROVIDE FLOOR LEVELING COMPOUND OVER
CONCRETE FLOOR AS REQUIRED AT THE TILE
FLOORING TO ALIGN THE TOP OF THE TILE WITH THE
TOP OF THE CARPET PILE.

5. IN AREAS NOT ACCESSED BY PUBLIC (E.G. OFFICE,


STORAGE, BACKROOMS, ETC.) PROVIDE CONT. BLACK
RESILIENT TRANSITION MOULDING AT DISSIMILAR
MATERIALS. COORDINATE SHAPE AND STYLE OF
TRANSITION PIECE WITH ADJACENT FLOOR FINISH.

A-401
PT 14* PT 9
STORAGE
UP PT 9 PT 9
6. ALL PUBLIC AREAS PROVIDE TANDUS METAL EDGE
PT 9 GR 1 TRANSITION BETWEEN DISSIMILAR MATERIALS.
MENS 111 STORAGE
2 108
112 7. TILE CONTRACTOR SHALL USE PROPER TRIMS,
1 BULLNOSE, AND COVER BASE. NO TILE WORK SHALL
PT 9 4 PT 9 END ON AN EXPOSED OUTSIDE CORNER FAILURE TO
PT 25 PT 19 PT 14 CORRECT TILE INSTALLATIONS TO COMPLY WILL
JANITOR A-205 ELECTRICAL
PLUSH RESULT IN REJECTION OF WORK. ALL WORK MUST BE
STORAGE 107 2 114 APPROVED BY THE LOCAL HEALTH DEPARTMENT IN
3
PARTY 3 FOOD PREPARATION AREAS.
105
PT 14 5 PT 14 ROOM 1
A-401 WOMENS
8 FAMILY 110 8. CONTRACTOR SHALL BE RESPONSIBLE FOR PROJECT
TOILET 109
A-401 PT 16 NECESSARY FLOOR LEVELING TO MAKE FINISH
106 4 PT 14* SURFACE FLUSH WITH ADJACENT SURFACE. THIS
7
6
GR 1
PT 14
INCLUDES NECESSARY SLOPED FLOOR TRANSITION TO
FLUSH TENANT FINISH SURFACE WITH ADJACENT
ROUND1 -
PT 36
PT 14* PT 14*
BOWLER'S
SEATING
PINSETTER
SERVICE
PT 9 EXISTING MALL FLOOR FINISH.
PLAZA BONITA
GR 1 GR 1 120 117 9. TILE INSTALLATION OVER EXISTING CONSTRUCTION OR
PT 19 CONTROL JOINTS SHALL INCLUDE INSTALLATION OF AN
7 PARTY ANTI FRACTURE MEMBRANE INSTALLED OVER JOINT
5
2 ROOM 4 8 PER MANUFACTURERS INSTRUCTIONS.
A-204
124 14 PT 9 PT 21
A-202 A-205
13 BOWLING 5 10. PROVIDE WATER PROOFING MEMBRANE ADJACENT TO
PT 19 PT 26 6 APPROACH ALL WET AREAS. TURN AND EXTEND MEMBRANE EDGE
A-205 7 PARTY 119 A-203 6" UP WALL FINISH OR HEIGHT OF CABINET BASE
15 ROOM 2 A.V. INSTALLED PER MANUFACTURERS INSTRUCTIONS.
16 PT 15
PT 14* 121 6 BOWLING 115
PT 20 11. FLOORING CONTRACTOR SHALL INSTALL FLOOR FINISH
PT 20 GR 1 LANES
PT 9 CONTINUOUS UNDER UNFIXED EQUIPMENT AND
118
REDEMPTION MILLWORK COUNTERTOPS. FLOOR FINISH SHALL
GR 1 STORAGE PT 17 TERMINATE AT MILLWORK BASE OR WALL BASE.
PT 14* PT 9
123 GR 1 @ ALL 12. CARPET SUPPLIED BY OWNER. INSTALLATION AND ALL
PARTY PT 19 COLUMNS FRP @ ACCESSORIES NECESSARY TO INSTALL CARPET BY
ROOM 3 PT 12 U.N.O. SINK
PT 37 GENERAL CONTRACTOR - REFER TO SPECIFICATION.
122 9
PT 3 19 12
22 PT 22 13. REFER TO A-701 AND DETAILS ON A-501 FOR RS-1 ON
A-205 COLUMNS AS SHOWN.
6 A-205
PT 37 PT 37 10
PAINT PORTION OF A-204 20 11 14. REFER TO SHEET A-161 FOR CEILING FINISH
DUCTWORK ABOVE
PT 24
21
PT 14*
INFORMATION TENANT
MECHANIC'S
PT 14* GR 1 116 15. ALL HOLLOW METAL DOORS AND FRAMES TO BE IMPROVEMENT
PT 12 REDEMPTION GR 1 PAINTED WITH ALKYD PAINT (SEMI GLOSS SHEEN) TO
STORE PT 9 MATCH ADJACENT WALL
125
FRP 1 16. DRY-WALL CEILING PAINT WILL BE APPLIED AFTER
PT 12 UP PT 14 NORMAL WORK HOURS AND CLOSELY COORDINATED
WITH THE GENERAL CONTRACTORS FIELD MANAGER. 3030 PLAZA BONITA RD, SUITE
1025
2'-6"

2'-6"

PT 12 PT 14 17. PROVIDE A TAPE LINE ON STORAGE ROOM WALLS 18"


BELOW THE CEILING - REFER TO ROOM FINISH NATIONAL CITY, CA 91950
PT 26 12 SCHEDULE.
1 2 GR 1 CLIENT
1 A-601 KITCHEN PT 17
A-204 5 FULL HEIGHT 18. PROVIDE CAUTION TAPE ON FLOOR FOR CLEARANCE IN
A-202 128
WALL, ABOVE FRONT OF ELECTRICAL EQUIPMENT - COORDINATE
A-204
3
CHAIR RAIL WITH ELECTRICAL PLANS ROUND1
WT 1
3 PT 3
4 WC 1
BELOW GR 1
ENTERTAINMENT
MALL A-202
ENTRANCE MECHANICAL WT 1 10
BAR SEATING
104 127 130 131 A-601

FRP 1
4 GR 1
A-202 GUEST WT 1 PT 10 WC 1
PT 26
COUNTER SNACK
2'-6"

2'-6"

PT 12 126 BAR
129 UP
PT 12
PT 15 WC 1 PT 15
3070 SATURN ST. STE. 200
4 1 UP BREA, CA 92821
A-203 A-203
PAINT PORTION OF PT
DUCTWORK ABOVE PT 24 PAINT PORTION OF 2
DUCTWORK ABOVE
A-203

PT 37

PT 24 PT 37

PT 37

PT 37

3
A-203

PT 12

PT 9 EMPLOYEE RELEASE DATE


VESTIBULE
5 PT 37 LOUNGE
PT 37 101 HIGH
PT 14 135 DATE DESCRIPTION
A-202 VALUE STORAGE/
PT 36 STORAGE OFFICE LACTATION 07-06-23 FOR PERMITS
17
137 PT 8 136 PT 11 18 134 07-21-23 FOR BIDS
A-205 PT 9
PT 9

PT 36 PT 18

PROJECT
N
FIRST FLOOR WALL FINISH PLAN
SCALE: 3/32" = 1'-0"
2112128GR
SHEET
7/25/2023 3:41:00 PM

WALL FINISH PLAN

A-702
GENERAL STRUCTURAL NOTES Applies unless noted otherwise on drawings

PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S100.dwg, S100, 2023-07-21 11:14:46 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET

CARUSO TURLEY SCOTT INC GENERAL


consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
STRUCTURAL NOTES
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-100
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S101.dwg, S101, 2023-07-21 11:14:52 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET

CARUSO TURLEY SCOTT INC TYPICAL


consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
DETAILS
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-101
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S201.dwg, S201, 2023-07-21 11:14:57 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET
SCALE: 3/32" = 1'-0"
CARUSO TURLEY SCOTT INC FOUNDATION AND
consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
FLOOR FRAMING
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-201
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S201.dwg, S202, 2023-07-21 11:14:58 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET
SCALE: 3/32" = 1'-0"
CARUSO TURLEY SCOTT INC CEILING AND
consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
SOFFIT FRAMING
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-202
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S301.dwg, S301, 2023-07-21 11:15:02 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET

CARUSO TURLEY SCOTT INC FOUNDATION


consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
DETAILS
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-301
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S302.dwg, S302, 2023-07-21 11:15:06 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET

CARUSO TURLEY SCOTT INC SUSPENDED


consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
FRAMING DETAILS
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-302
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

550 3 Mile NW Suite B


Grand Rapids, MI 49544
(616) 785-5656

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

O F E S S IO N
PR A
D
R A J . HE

L
RE
ND

EN
R E G IS T E
SA

RD

G IN E E R
S 4080
3
07-21-2
ST

L
TA R UC T UR A

IA
S
TE RN
O F C A L IF O

PROJECT

ROUND 1 -
PLAZA BONITA

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821
C:\Users\Jami\Desktop\Jami Work\WORK HERE\DONE\6 JUNE 2023\done 6-30\230210 6-30\230210-S303.dwg, S303, 2023-07-21 11:48:16 AM

RELEASE DATE

DATE DESCRIPTION

05-18-23 FOR PERMITS


07-21-23 FOR BIDS

PROJECT

SHEET

CARUSO TURLEY SCOTT INC FLOOR INFILL


consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
DETAILS
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
S-303
FIRE PROTECTION NOTES
A BUILDING SHALL BE FULLY SPRINKLERED. ENTIRE SYSTEMS SHALL
BE DESIGNED IN ACCORDANCE WITH NFPA 13 LIGHT HAZARD
OCCUPANCY AND MANUFACTURES RECOMMENDATIONS FOR THE
SPRINKLERS USED. STORAGE AND MECHANICAL ROOMS SHALL BE
DESIGNED IN ACCORDANCE WITH NFPA ORDINARY HAZARD.

B HYDRAULIC CALCULATIONS SHALL BE RUN FOR ALL REMOTE AREAS


AND SUBMITTED WITH WORKING DRAWINGS WHICH SHOW
SPRINKLERS, PIPE, INSPECTORS TEST VALVES, AND HANGER
LOCATIONS, PIPE SIZING AND RISER DETAIL. PARADIGM DESIGN
C HYDRAULIC CALCULATIONS SHALL LEAVE A MINIMUM PRESSURE ARCHITECTS | ENGINEERS
CUSHION OF 10% FROM THE AVAILABLE SUPPLY PRESSURE TO THE
SYSTEM PRESSURE REQUIREMENT FOR EACH CALCULATION.

D IT IS THE RESPONSIBILITY OF THE FIRE PROTECTION CONTRACTOR


I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8 TO ARRANGE FOR A FLOW TEST AS CLOSE TO THIS SITE AS
POSSIBLE. THE RESULTS OF THE FLOW TEST SHALL BE INCLUDED
WITH THE SUBMITTALS OF THE HYDRAULIC CALCULATIONS FOR Grand Rapids | Phoenix | Traverse City
REVIEW. www.paradigmae.com
EXISTING SPRINKLER
MENS PARTY RISER TO REMAIN. FPC TO
4..1 4..1 108 ROOM 1 VERIFY AND COORDINATE
110 WITH LANDLORD. E ALL SPRINKLER PIPING AND HEAD PLACEMENT SHALL BE
COORDINATED WITH LIGHTING, DIFFUSERS, ETC. CENTER
A A SPRINKLER HEADS WITHIN CEILING TILES.
STAIR 1 FIRE
STORAGE S-1 STORAGE RISER F PROVIDE A SPRINKLER SYSTEM RISER SCHEMATIC WITH CONTROL
111 113 AND CHECK VALVES, BACKFLOW PREVENTION DEVICES, SUPPLY
112 AND SYSTEM PRESSURE GAUGES, WATER FLOW SWITCHES,
TAMPER SUPERVISING SWITCHES, LOCAL WATERFLOW ALARM
LOCATION, AND SPARE SPRINKLER HEAD CABINET LOCATION.
FEC [NFPA 13 6.9.2, 8.15.1.1,]

JANITOR ELECTRICAL G PROVIDE A LOCAL WATERFLOW ALARM. [NFPA 13 6.9.3]


107 114
PLUSH H SHOW THAT THE SYSTEM IS SUPERVISED PER NFPA 13 8.15.1.1.2
STORAGE AND TITLE 24, PART 2, 903.4: A. PROVIDE TAMPER SWITCHES AT ALL
105 WOMENS CONTROL VALVES. B. PROVIDE A FLOW SWITCH OR ALARM CHECK
109 VALVE AND SPECIFY CONNECTION TO THE GENERAL BUILDING
ALARM (MUST SOUND WITHIN 5 MINUTES OF FLOW). [NFPA 13 6.9.1]

5.1 5.1 I PROVIDE (5) FIVE EXTRA SPRINKLER HEADS OF EACH TYPE IN
BFEC B CABINET NEAR RISER WITH A WRENCH. [NFPA 13 6.2.9]
PROJECT
J THE FIRE DEPARTMENT CONNECTION MUST BE AN APPROVED NH
FAMILY FREIGHT STANDARD, INTERNAL THREADED SWIVEL FITTING, WITH LISTED
TOILET
106
ELEVATOR
ELEV-1
PLUGS OR CAPS. [NFPA 13 6.8]
ROUND1 -
PARTY
PARTY
ROOM 2
K THE MAXIMUM AREA PER RISER IS: LIGHT OR ORDINARY HAZARD ¬
52,000 SQ. FT.; EXTRA HAZARD ¬ 40,000 SQ. FT. PER RISER OR 25,000
FOR PIPE SCHEDULE SYSTEMS. [NFPA 13 8.2.1]
PLAZA BONITA
ROOM 4 121 FE
REDEMPTION
124 STORAGE BOWLING L THE ENTIRE BUILDING MUST BE SPRINKLED. IDENTIFY ALL AREAS
123 BOWLER'S APPROACH A.V. TO BE SPRINKLED.
SEATING 119 BOWLING PINSETTER 115
120 LANES SERVICE M THE ENTIRE SYSTEM MUST BE DRAINABLE. SPRINKLER FEED
118 117 PIPES MUST BE PITCHED FOR DRAINAGE (I.E., TRAPPED PIPING,
DRY PIPE SYSTEMS, LOW POINTS, ETC.). [NFPA 13 8.15.2.2] PROVIDE
AUXILIARY DRAINS FOR TRAPPED PIPING. [NFPA 13 8.15.2.5] ALL
DRAINS MUST DISCHARGE OUTSIDE OR TO A DRAIN CONNECTION.

FEC
C C [NFPA 13 8.15.2.4.4]
6.1 6.1

D W
PARTY N PROVIDE A PRESSURE REDUCING VALVE WHERE THE POTENTIAL
REDEMPTION ROOM 3 EXISTS FOR WATER PRESSURES EXCEEDING 175 PSI. [NFPA 13
STORE 122 8.15.1.2]
125
O REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
VENDING
124 MECHANIC'S
P ALL STATE AND LOCAL AMENDMENTS TO ADOPTED BUILDING CODE
116 SHALL BE ADHERED TO.

MALL
TENANT
24X24 24X48

ENTRANCE
104

CWI
FE
IMPROVEMENT

CWO
D

FE-K
6.2 D 6.2 D

24X48
24X48
7.1 7.1

24X48
24X48
24X48

24X48

24X48

18"X18"X12"

24X48
24X48
3030 PLAZA BONITA RD, SUITE
KITCHEN
1025

34DR
128

24X48
VESTIBULE NATIONAL CITY, CA 91950

24X48
133

24X48
BAR BILLIARDS CLIENT
130

CWI
132

C
MECHANICAL

D
SEATING
ROUND1

TS14BLW

CH
H
CWO
GUEST

D
127 131

D
COUNTER

G
ENTERTAINMENT

D
C R C -63C
G

CH
D
126

D
D C

SC -15-TS

CH
D
D
H
C

SNACK

C R I-12-30-7
D
BAR
8.1 E 8.1 E
129
RC D
C

8.2 8.2 H R

D
C

FEC

FEC
STAIR
S-2
3070 SATURN ST. STE. 200
BREA, CA 92821

CONSULTANT
F F
FEC
9.1 9.1

NOTE: FP CONTRACTOR SHALL PROVIDE A FULLY


SPRINKLERED SYSTEM PER NFPA 13. THE
EXISTING SYSTEM SHALL REMAIN OPERATIONAL
THROUGHOUT CONSTRUCTION. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS. 4801 Henry St. 1751 Barlow St.
THERE SHALL BE NO INTERFERANCE OR Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
TERMINATION OF ANY LIFE SAFETY SYSTEMS FOR F 231-798-2981 F 231-947-1710
ANY TENANT AREAS OR MALL COMMON AREAS. REC #5002

G G

10.1 10.1

HIGH

FEC
VESTIBULE VALUE
STORAGE EMPLOYEE STORAGE/
101
137 OFFICE LOUNGE LACTATION
136 135 134

REF.
RELEASE DATE

STAIR 3 DATE DESCRIPTION


ELECTRICAL
FEC

S-3
103 4-21-23 LANDLORD REVIEW
5-18-23 PERMITS
H H
7-21-23 FOR BIDS

11.1 11.1

I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8

N
FIRE PROTECTION FIRST FLOOR PLAN
SCALE: 3/32" = 1'-0"

PLAN
PROJECT

2112128GR
SHEET
7/21/2023 3:25:07 PM

FIRE PROTECTION PLAN

F-101
PLUMBING GENERAL NOTES
A UTILITIES SHOWN ARE APPROXIMATE LOCATIONS, THEIR
LOCATIONS SHOULD NOT BE CONSIDERED EXACT LOCATIONS
NOR SHOULD THEY BE CONSIDERED AS THE ONLY UTILITIES IN
THE AREA.

B ALL CONCRETE MAINTENANCE PADS SHALL BE INSTALLED BY


CONTRACTOR.

C SLEEVE AND SEAL ALL WALL, FLOOR, AND ROOF PENETRATIONS.

D KEEP AREA CLEAN. REMOVE DEBRIS ON A DAILY BASIS. PARADIGM DESIGN


E INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO
COORDINATE THE EXACT ROUTING AND ELEVATION OF PIPING
ARCHITECTS | ENGINEERS
SYSTEMS. THIS CONTRACTOR SHALL INSTALL PIPING SO AS TO
NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
SYSTEMS.

F PROVIDE ASSE 1070 APPROVED POINT OF USE MIXING VALVE


I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8 FOR ALL HANDWASHING SINKS.
Grand Rapids | Phoenix | Traverse City
1 G PLUMBING CONTRACTOR SHALL COORDINATE WITH OWNERS www.paradigmae.com
P-401 MILL WORK SUPPLIER PRIOR TO ROUGH-IN OF SODA SLEEVES
AND OPEN HUB DRAINS IN THE CONCESSIONS AREA.

4..1 4..1 H INSTALL WATER HAMMER ARRESTERS PER SPEC'S AND


PDI-WH-201.
A A
STAIR 1 I ALL FLOOR DRAINS SHALL BE INSTALLED PER DETAIL ON P-501.
FIRE
MENS STORAGE S-1 RISER
STORAGE J ALL DOMESTIC WATER PIPING SHALL BE INSULATED PER SPECS.
108 111 113
112
K ALL CORE DRILLING BY P.C.
PARTY
ROOM 1 FEC
110
JANITOR
ELECTRICAL
107
114
PLUSH
STORAGE
105 FAMILY
WOMENS PLUMBING PLAN NOTES
TOILET 109
106 LEGEND SYMBOL INDICATOR
5.1 5.1
BFEC B 1 PLUMBING CONTRACTOR SHALL PROVIDE 6" SCHEDULE 40 PVC SODA
3" S FREIGHT SLEEVE WITH LONG SWEEP ELBOWS FROM 3" A.F.F. EXTENDING DOWN TO
PROJECT
ELEVATOR BELOW FLOOR. SLEEVE AND SEAL FLOOR PENETRATIONS. COORDINATE
THE EXACT LOCATIONS WITH SODA FOUNTAIN MANUFACTURERS

PARTY
ELEV-1
RECOMMENDATIONS. TUBING TO SODA HEADS BY VENDOR.
ROUND1 -
4" (E)S
4" (E)S
4" S
3" S 4" (E)S 4" S
ROOM 2
121
4" (E)S 2 SODA RACK, C02 TANKS, BAG-IN-BOX, TUBING TO SODA HEADS,ETC.
PROVIDED BY AND SET IN PLACE BY OTHERS.
PLAZA BONITA
FE
3 1/2"CW DOWN TO BALL VALVE AND BACKFLOW PREVENTER, EQUAL TO
WATTS SERIES 7, EXTEND TO OWNER FURNISHED AND INSTALLED
4" S PARTY CARTRIDGE FILTERS. MOUNT ON WALL AT APROX. 5'-0" A.F.F., EXTEND 1/2"
4" (E)S A.V.
CONNECT NEW SANITARY ROOM 4 FILTERED WATER TO KITCHEN EQUIPMENT.
LINES TO EXISTING
BOWLER'S BOWLING BOWLING 115
124 CONNECT NEW SANITARY LINES 2
6" (E)S SANITARY. P.C. TO VERIFY TO EXISTING SANITARY. P.C. TO
SEATING APPROACH LANES 4 BALL VALVE. INSTALL IN ACCESSIBLE LOCATION.
SIZE, CONDITION, VERIFY SIZE, CONDITION, 120 119 118 P-101
5 CHECK VALVE. INSTALL IN ACCESSIBLE LOCATION.
LOCATION, & INVERT LOCATION, & INVERT ELEVATION. PINSETTER
ELEVATION. SERVICE 6 THERMOSTATIC BALANCING VALVE. MATCH PIPE SIZE. SET TERMPERATURE
INDICATED ON PLANS. INSTALL IN ACCESSIBLE LOCATION.

FEC
C 117 C
6.1 6.1

D W
7 WASTE FROM BELOW TO WCO, FIXTURES, AND VENT UP. SIZES AS NOTED
REDEMPTION PARTY ON PLANS.
2" V 2" VENTS UP IN CHASE.
CONNECT TO EXISTING STORAGE ROOM 3
123 8 SANITARY VENT FROM BELOW, SIZE NOTED ON PLANS.
2" V VENT THROUGH THE ROOF. 122
2" V 2" V 9 P.C. SHALL ROUTE PIPING AS HIGH AS POSSIBLE. ROUTE THROUGH OPEN
2" V WEB JOISTS WHEREVER POSSIBLE. PRIME AND PAINT PIPING IN EXPOSED
2" V AREAS TO MATCH CEILING.
2" V
VENDING 10 FURNISH AND INSTALL BACKFLOW PREVENTOR WITH FUNNEL AND
CONNECT 2" UNDERFLOOR INDIRECT WASTE LINE TO NEAREST FLOOR DRAIN OR FLOOR SINK.
VENTS TO EXISTING. ROUTE 124
MECHANIC'S TERMINATE INDIRECT WASTE AT FLOOR DRAIN WITH AIR GAP.
OVER TO WALL AND UP.
116
11 INDIRECT WASTE FROM KITCHEN EQUIPMENT FURNISHED AND INSTALLED
MALL
ENTRANCE
24X24 24X48
BY P.C.. TERMINATE AT NEAREST FLOOR DRAIN WITH AIR GAP. ROUTE
PIPING BELOW EQUIPMENT AND TIGHT TO WALL WHERE POSSIBLE. P.C.
TENANT
REDEMPTION
104 SHALL FURNISH UNISTRUT WHERE REQUIRED TO MOUNT PIPING.
IMPROVEMENT

CWI
STORE COORDINATE THE EXACT ROUTING WITH CASE WORK SUPPLIER PRIOR TO
125 FE INSTALLATION. REFER TO PLUMBING KITCHEN NOTES SCHEDULE FOR

CWO
D

FE-K
6.2 D 6.2 D SIZES. ALL INDIRECT WASTE PIPING SHALL BE INSTALLED SUCH THAT

24X48
24X48
THERE ARE NO TRIP HAZARDS AND ALL REQUIRED SERVICE ACCESS AND
7.1 7.1 CLEARANCES FOR EQUIPMENT, PIPING, AND VALVES ARE MAINTAINED.

24X48
24X48
24X48
KITCHEN
3030 PLAZA BONITA RD, SUITE

24X48

24X48

18"X18"X12"

24X48
128 24X48
12 CO2 SYSTEM SHALL BE INSTALLED BY ROUND ONE'S CO2 VENDOR (NUCO2)
IN ACCORDANCE WITH NUCO2'S GUIDELINE FOR NEW INSTALLATION OF 1025
4", FCO. LIQUID CARBON DIOXIDE BULK TANK (STANDARD NO. OP-208). BEVERAGE

34DR
NATIONAL CITY, CA 91950

24X48
VESTIBULE SUPPLY LINES IN PUBLIC SPACES SHALL BE ENCLOSED IN STEEL OR PVC

24X48
6" (E)S 133 CONDUIT/CHASE.
13 BEER PURVEYOR TO RUN CO2 LINES FROM TANK IN MECH. ROOM TO CLIENT

24X48
MECHANICAL BAR BILLIARDS POWER PACK BY BEER COOLER.
130

CWI
127 SEATING 132 14 1/2" FILTERED WATER TO ICE MACHINE.
ROUND1

D
TS14BLW

CH
131

H
GUEST CWO
D
15 COORDINATE STUB UP LOCATIONS WITH CASEWORK.

D
COUNTER 4" (E)S
ENTERTAINMENT

D
C R C -63C
G

CH
16 4"S FROM CHASE WALL TO DOWN BELOW GRADE.

D
126

D
17 4"S IN CHASE WALL.
D C

SC -15-TS
D
D
H
C

6" (E)S 18 2"S FROM WALL CARRIER AUXILLARY INLET UP TO URINAL, WCO ABOVE
FIXTURE, AND 2"V UP.
SNACK

C R I-12-30-7
D
BAR
8.1 E 8.1 E
129
RC D

8.2 8.2 H R

D
C

FEC
8

FEC
2 4" GW
P-402
STAIR 3070 SATURN ST. STE. 200
S-2 BREA, CA 92821

CONSULTANT
4" (E)S
F F
FEC (E) FCO. FE
9.1 9.1

4" (E)S 3" S


4", FCO.
4" (E)S

SEE OVERALL CONNECT 3"S TO 3" S 4801 Henry St. 1751 Barlow St.
PLAN P-101 FOR EXISTING Muskegon, MI 49441 Traverse City, MI 49686
4" GW T 231-798-4328 T 231-947-1707
CONTINUATION. SANITARY. P.C. TO F 231-798-2981 F 231-947-1710
FIELD VERIFY REC #5002
LOCATION,
CONDITION, AND
4" (E)GW CAP AND ABANDON INVERT ELEVATION.
3" S
EXISITNG GREASE
WASTE IN PLACE. 2"
G G 8
CONNECT NEW 4" GW LINE TO
CONNECT NEW 2"S LINE EXISTING. P.C. TO VERIFY SIZE,
10.1 10.1 TO EXISTING SANITARY. CONDITION, LOCATION, & INVERT
P.C. TO VERIFY SIZE, ELEVATION.
CONDITION, LOCATION, & AW-1 MSB-1
INVERT ELEVATION. 1/2"H&CW, 2"W, 3" S 1/2"H&CW,
2"V, SEE SPECS 3"W, 2"V.
FEC AND DETAIL.
VESTIBULE 2" S 2" S 7
EMPLOYEE STORAGE/ 2" S
101 C 3" S C
LOUNGE LACTATION EWS-1

W
135 134

REF.
7 1/2"H&CW, 3" S UP TO
1-1/2"W, 1-1/2"V. WCO., AW-1, & RELEASE DATE
HIGH 1 1/2" V
2"V UP.
(E)YCO. VALUE DATE DESCRIPTION
OFFICE

D
STAIR 3 STORAGE
ELECTRICAL
FEC

S-3 136 4-21-23 LANDLORD REVIEW


103 137
4" (E)S 5-18-23 PERMITS
H H 2"S UP TO 3",FCO. 7-21-23 FOR BIDS
EWS-1, AND
1-1/2" V UP. 3",FD-1
W/T.S.
4" (E)GW
11.1 11.1
P.C. TO FIELD VERIFY 3"V UP THROUGH
SIZE, CONDITION, AND CHASE TO ROOF
PIPE ROUTING FROM SAMPLE PORT TERMINATION.
GREASE INTERCEPTOR. EXISTING GREASE INTERCEPTOR TO
REMAIN. P.C. TO FIELD VERIFY SIZE,
CONDITION, AND INVERT ELEVATION OF
INLET AND OUTLETS.

(E)YCO., TYP.
I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8

PROJECT
N
OVERALL SANITARY PLUMBING FIRST FLOOR PLAN
SCALE: 3/32" = 1'-0"

PLAN
2112128GR
SHEET
7/21/2023 3:25:19 PM

OVERALL SANITARY
PLUMBING PLAN
2 ENLARGED MECHANICS ROOM SANITARY PLAN
P-101 SCALE: 1/4" = 1'-0"
P-101
PLUMBING GENERAL NOTES
A UTILITIES SHOWN ARE APPROXIMATE LOCATIONS, THEIR
LOCATIONS SHOULD NOT BE CONSIDERED EXACT LOCATIONS
NOR SHOULD THEY BE CONSIDERED AS THE ONLY UTILITIES IN
THE AREA.

B ALL CONCRETE MAINTENANCE PADS SHALL BE INSTALLED BY


CONTRACTOR.

C SLEEVE AND SEAL ALL WALL, FLOOR, AND ROOF PENETRATIONS.

D KEEP AREA CLEAN. REMOVE DEBRIS ON A DAILY BASIS. PARADIGM DESIGN


E INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO
COORDINATE THE EXACT ROUTING AND ELEVATION OF PIPING ARCHITECTS | ENGINEERS
I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8 SYSTEMS. THIS CONTRACTOR SHALL INSTALL PIPING SO AS TO
NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
SYSTEMS.
FIRE
RISER F PROVIDE ASSE 1070 APPROVED POINT OF USE MIXING VALVE
4..1 4..1 113 FOR ALL HANDWASHING SINKS.
2 1/2" (E) CW Grand Rapids | Phoenix | Traverse City
A A G PLUMBING CONTRACTOR SHALL COORDINATE WITH OWNERS
www.paradigmae.com
MILL WORK SUPPLIER PRIOR TO ROUGH-IN OF SODA SLEEVES
STAIR 1 AND OPEN HUB DRAINS IN THE CONCESSIONS AREA.
MENS CONNECT
STORAGE S-1 STORAGE
2-1/2"CW TO
108 111 112 H INSTALL WATER HAMMER ARRESTERS PER SPEC'S AND
EXISTING CW
PARTY 2 1/2" CW STUB.
PDI-WH-201.
ROOM 1 2 1/2" CW
110 I ALL FLOOR DRAINS SHALL BE INSTALLED PER DETAIL ON P-501.
FEC 9 PROVIDE SHUT-
OFF VALVE IN J ALL DOMESTIC WATER PIPING SHALL BE INSULATED PER SPECS.
JANITOR ACCESSIBLE
LOCATION
107
K ALL CORE DRILLING BY P.C.
PLUSH 1 1/4" CW
STORAGE WOMENS
2
105 FAMILY 109
P-401
TOILET ELECTRICAL
106 114
5.1
BFEC
5.1
B
PLUMBING PLAN NOTES
FREIGHT
ELEVATOR
9
ELEV-1
LEGEND SYMBOL INDICATOR
1 PLUMBING CONTRACTOR SHALL PROVIDE 6" SCHEDULE 40 PVC SODA
1 1/2" CW
SLEEVE WITH LONG SWEEP ELBOWS FROM 3" A.F.F. EXTENDING DOWN TO
BELOW FLOOR. SLEEVE AND SEAL FLOOR PENETRATIONS. COORDINATE PROJECT
THE EXACT LOCATIONS WITH SODA FOUNTAIN MANUFACTURERS
RECOMMENDATIONS. TUBING TO SODA HEADS BY VENDOR.

PARTY REDEMPTION
STORAGE
PARTY
ROOM 2
BOWLING
APPROACH
FE
ROUND1 -
ROOM 4 BOWLER'S 2 SODA RACK, C02 TANKS, BAG-IN-BOX, TUBING TO SODA HEADS,ETC.
124 123 121
SEATING
120
119
BOWLING PINSETTER
A.V.
115
PROVIDED BY AND SET IN PLACE BY OTHERS.
PLAZA BONITA
9 LANES SERVICE 3 1/2"CW DOWN TO BALL VALVE AND BACKFLOW PREVENTER, EQUAL TO
118 117 WATTS SERIES 7, EXTEND TO OWNER FURNISHED AND INSTALLED
CARTRIDGE FILTERS. MOUNT ON WALL AT APROX. 5'-0" A.F.F., EXTEND 1/2"
FILTERED WATER TO KITCHEN EQUIPMENT.

FEC
C C 4 BALL VALVE. INSTALL IN ACCESSIBLE LOCATION.
6.1 6.1

D W
5 CHECK VALVE. INSTALL IN ACCESSIBLE LOCATION.
PARTY 6 THERMOSTATIC BALANCING VALVE. MATCH PIPE SIZE. SET TERMPERATURE
ROOM 3 2 INDICATED ON PLANS. INSTALL IN ACCESSIBLE LOCATION.
122 P-102
7 WASTE FROM BELOW TO WCO, FIXTURES, AND VENT UP. SIZES AS NOTED
ON PLANS.

MECHANIC'S 8 SANITARY VENT FROM BELOW, SIZE NOTED ON PLANS.


VENDING
116 9 P.C. SHALL ROUTE PIPING AS HIGH AS POSSIBLE. ROUTE THROUGH OPEN
124
WEB JOISTS WHEREVER POSSIBLE. PRIME AND PAINT PIPING IN EXPOSED
AREAS TO MATCH CEILING.

MALL 24X24 24X48


10 FURNISH AND INSTALL BACKFLOW PREVENTOR WITH FUNNEL AND
ENTRANCE REDEMPTION INDIRECT WASTE LINE TO NEAREST FLOOR DRAIN OR FLOOR SINK.
104 TERMINATE INDIRECT WASTE AT FLOOR DRAIN WITH AIR GAP.

CWI
STORE
125 3/4" CW FE 11 INDIRECT WASTE FROM KITCHEN EQUIPMENT FURNISHED AND INSTALLED

CWO

FE-K
6.2 D 6.2 D BY P.C.. TERMINATE AT NEAREST FLOOR DRAIN WITH AIR GAP. ROUTE

24X48
TENANT

24X48
PIPING BELOW EQUIPMENT AND TIGHT TO WALL WHERE POSSIBLE. P.C.
7.1 7.1 SHALL FURNISH UNISTRUT WHERE REQUIRED TO MOUNT PIPING.

24X48
COORDINATE THE EXACT ROUTING WITH CASE WORK SUPPLIER PRIOR TO
IMPROVEMENT

24X48
KITCHEN
24X48
INSTALLATION. REFER TO PLUMBING KITCHEN NOTES SCHEDULE FOR

24X48

24X48

18"X18"X12"
SIZES. ALL INDIRECT WASTE PIPING SHALL BE INSTALLED SUCH THAT

24X48
128 24X48

THERE ARE NO TRIP HAZARDS AND ALL REQUIRED SERVICE ACCESS AND
CLEARANCES FOR EQUIPMENT, PIPING, AND VALVES ARE MAINTAINED.

34DR

24X48
VESTIBULE

24X48
133
12 CO2 SYSTEM SHALL BE INSTALLED BY ROUND ONE'S CO2 VENDOR (NUCO2)
3030 PLAZA BONITA RD, SUITE

24X48
MECHANICAL BAR BILLIARDS IN ACCORDANCE WITH NUCO2'S GUIDELINE FOR NEW INSTALLATION OF
130 LIQUID CARBON DIOXIDE BULK TANK (STANDARD NO. OP-208). BEVERAGE 1025

CWI
127 132 SUPPLY LINES IN PUBLIC SPACES SHALL BE ENCLOSED IN STEEL OR PVC

C
NATIONAL CITY, CA 91950

D
SEATING

TS14BLW

CH
CONDUIT/CHASE.

H
CWO
GUEST

D
131

D
COUNTER 13 BEER PURVEYOR TO RUN CO2 LINES FROM TANK IN MECH. ROOM TO

D
POWER PACK BY BEER COOLER.

C R C -63C
G
CLIENT

CH
D
126

D
14 1/2" FILTERED WATER TO ICE MACHINE.

ROUND1
D C

SC -15-TS

CH
D
D
H
C 15 COORDINATE STUB UP LOCATIONS WITH CASEWORK.

SNACK 16 4"S FROM CHASE WALL TO DOWN BELOW GRADE.


ENTERTAINMENT

C R I-12-30-7
D
BAR 17 4"S IN CHASE WALL.
8.1 E 8.1 E
129
C
RC D 18 2"S FROM WALL CARRIER AUXILLARY INLET UP TO URINAL, WCO ABOVE
8.2 8.2 H R

D
C
FIXTURE, AND 2"V UP.
FEC

FEC
1
P-402

STAIR
S-2
8

3070 SATURN ST. STE. 200


F F BREA, CA 92821
FEC SEE OVERALL MSB-1
9.1 9.1 PLAN P102 FOR 1/2"H&CW, TYP.
CONTINUATION. 3"W, 2"V. 5
CONSULTANT
9

1 1/4" CW AW-1
1/2"H&CW, 2"W,
2"V, SEE SPECS
AND DETAIL.
4 1/2" HW (140°)

C 3/4" CW C
TYP. 4

4 1 1/4" CW
1 1/4" HW (140°) 4801 Henry St. 1751 Barlow St.
Muskegon, MI 49441 Traverse City, MI 49686
3/4" CW T 231-798-4328 T 231-947-1707
F 231-798-2981 F 231-947-1710
1 1/4" CW REC #5002
G G 4 1/2" HW (140°)
1 1/4" HW (140°)
5

10.1 10.1 EWS-1 4


1/2"H&CW,
1-1/2"W, 1-1/2"V. DWH-4
EMPLOYEE

FEC
VESTIBULE HIGH OFFICE LOUNGE
101 136 135 STORAGE/
VALUE INSTALL SOLENOID VALVE
LACTATION
STORAGE AT CO2 TANK OUTLET TO
134

REF.
137 INTERLOCK WITH CO2
3/4" CW DOWN TO LAV-3 SYSTEM EMERGENCY
AND 3/8" TO TANKLESS SHUT OFF SWITCH.
POINT OF USE WATER
STAIR 3 HEATER DWH-5. EQUAL TO 12 13
ELECTRICAL
FEC

EEMAX LAVADVANTAGE
S-3
103 MODEL #SPEX4208T. SEE 3/4" CW
DETAIL 19/P-501. 4 MECHANIC'S RELEASE DATE
H H 116
DATE DESCRIPTION
4-21-23 LANDLORD REVIEW
11.1 11.1 5-18-23 PERMITS
7-21-23 FOR BIDS

SEE OVERALL
PLAN P102 FOR
CONTINUATION.

I I.5 J K L L.1M.1 M1 2 3 4 5 6 7 8

N
OVERALL DOMESTIC PLUMBING PLAN
SCALE: 3/32" = 1'-0"

PLAN N
ENLARGED MECHANICS DOMESTIC PLUMBING PLAN
SCALE: 1/4" = 1'-0"

PLAN

PROJECT

2112128GR
SHEET
7/21/2023 3:25:28 PM

OVERALL DOMESTIC
PLUMBING PLAN

P-102
PLUMBING GENERAL NOTES
A UTILITIES SHOWN ARE APPROXIMATE LOCATIONS, THEIR
LOCATIONS SHOULD NOT BE CONSIDERED EXACT LOCATIONS
NOR SHOULD THEY BE CONSIDERED AS THE ONLY UTILITIES IN
THE AREA.
M 1 2 3
B ALL CONCRETE MAINTENANCE PADS SHALL BE INSTALLED BY
CONTRACTOR.

C SLEEVE AND SEAL ALL WALL, FLOOR, AND ROOF PENETRATIONS.


A A
D KEEP AREA CLEAN. REMOVE DEBRIS ON A DAILY BASIS. PARADIGM DESIGN
E INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO ARCHITECTS | ENGINEERS
COORDINATE THE EXACT ROUTING AND ELEVATION OF PIPING
3"V UP IN CHASE SYSTEMS. THIS CONTRACTOR SHALL INSTALL PIPING SO AS TO
TO ROOF NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
TERMINATION SYSTEMS.
MENS
108
F PROVIDE ASSE 1070 APPROVED POINT OF USE MIXING VALVE
FOR ALL HANDWASHING SINKS.
(5)LAV-1 3" V (4)WC-1 Grand Rapids | Phoenix | Traverse City
1/2"H&CW, 2"W 3",FD-1 1"CW, 4"W.
W/T.S. G PLUMBING CONTRACTOR SHALL COORDINATE WITH OWNERS www.paradigmae.com
2",WCO. DN., 1-1/2"V.
(6)UR-1 MILL WORK SUPPLIER PRIOR TO ROUGH-IN OF SODA SLEEVES
3/4"CW, AND OPEN HUB DRAINS IN THE CONCESSIONS AREA.
3",FCO. 3" V 2"W, 2"V. 3" V
3" S 3",WCO. WC-2 H INSTALL WATER HAMMER ARRESTERS PER SPEC'S AND
1"CW, 4"W. PDI-WH-201.
3"
8 2" V 4",WCO.
2" V 2" V 2" V 8 2"V 16 I ALL FLOOR DRAINS SHALL BE INSTALLED PER DETAIL ON P-501.
4" S 4" S
2" S MSB-1 4" S J ALL DOMESTIC WATER PIPING SHALL BE INSULATED PER SPECS.
1-1/2" 8 1/2"H&CW,
3"W, 2"V. 2" V
K ALL CORE DRILLING BY P.C.
1 1/2" V
3" S 17 17 8
8 18 18 18
JANITOR 4",WCO. 4" S
3"
107 2" V
3",FD-1
W/T.S. (8)WC-1
3",WCO.
7
4",WCO. 1"CW, 4"W.
WC-2
PLUMBING PLAN NOTES
4"S UP TO WC, 3" V 1"CW, 4"W.
1 1/2" V WCO., & 3"V UP. 3" V

3" S
LEGEND SYMBOL INDICATOR
1 PLUMBING CONTRACTOR SHALL PROVIDE 6" SCHEDULE 40 PVC SODA PROJECT
SLEEVE WITH LONG SWEEP ELBOWS FROM 3" A.F.F. EXTENDING DOWN TO
WOMENS 3",FD-1 BELOW FLOOR. SLEEVE AND SEAL FLOOR PENETRATIONS. COORDINATE
3" V
LAV-2
1/2"H&CW
3",FD-1
W/T.S.
WC-2
1"CW, 4"W.
109 W/T.S.
(2)WC-1
1"CW, 4"W.
THE EXACT LOCATIONS WITH SODA FOUNTAIN MANUFACTURERS
RECOMMENDATIONS. TUBING TO SODA HEADS BY VENDOR. ROUND1 -
2"W DN.,
1-1/2"V. (6)LAV-1
1/2"H&CW, 2"W
4" S 2 SODA RACK, C02 TANKS, BAG-IN-BOX, TUBING TO SODA HEADS,ETC.
PROVIDED BY AND SET IN PLACE BY OTHERS.
PLAZA BONITA
7 3" S
1 1/2" V DN., 1-1/2"V.
3" S 3" S 1 1/2" V 2",WCO.
3" S 3 1/2"CW DOWN TO BALL VALVE AND BACKFLOW PREVENTER, EQUAL TO
FAMILY 2",WCO. WATTS SERIES 7, EXTEND TO OWNER FURNISHED AND INSTALLED
TOILET CARTRIDGE FILTERS. MOUNT ON WALL AT APROX. 5'-0" A.F.F., EXTEND 1/2"
106 FILTERED WATER TO KITCHEN EQUIPMENT.

4 BALL VALVE. INSTALL IN ACCESSIBLE LOCATION.


BFEC B
5 CHECK VALVE. INSTALL IN ACCESSIBLE LOCATION.

6 THERMOSTATIC BALANCING VALVE. MATCH PIPE SIZE. SET TERMPERATURE


2" S
INDICATED ON PLANS. INSTALL IN ACCESSIBLE LOCATION.
EWC-1 2" S 4" S 4",WCO.
1-1/2" 8 8 8 17
1/2"CW, 16
2"W, 1-1/2"V. 1-1/2" 3" 7 WASTE FROM BELOW TO WCO, FIXTURES, AND VENT UP. SIZES AS NOTED
3" S ON PLANS.
4" S 3" S
8 SANITARY VENT FROM BELOW, SIZE NOTED ON PLANS.
4" S
4" S 9 P.C. SHALL ROUTE PIPING AS HIGH AS POSSIBLE. ROUTE THROUGH OPEN
WEB JOISTS WHEREVER POSSIBLE. PRIME AND PAINT PIPING IN EXPOSED
SEE SHEET P101 AREAS TO MATCH CEILING.
FOR CONTINUATION
SEE SHEET P101 10 FURNISH AND INSTALL BACKFLOW PREVENTOR WITH FUNNEL AND
M 1 2 FOR CONTINUATION 3 INDIRECT WASTE LINE TO NEAREST FLOOR DRAIN OR FLOOR SINK.
TERMINATE INDIRECT WASTE AT FLOOR DRAIN WITH AIR GAP.
1 ENLARGED RESTROOM SANITARY PLANS
INDIRECT WASTE FROM KITCHEN EQUIPMENT FURNISHED AND INSTALLED
P-101 SCALE: 1/4" = 1'-0" 11
BY P.C.. TERMINATE AT NEAREST FLOOR DRAIN WITH AIR GAP. ROUTE
PIPING BELOW EQUIPMENT AND TIGHT TO WALL WHERE POSSIBLE. P.C.
TENANT
SHALL FURNISH UNISTRUT WHERE REQUIRED TO MOUNT PIPING.
COORDINATE THE EXACT ROUTING WITH CASE WORK SUPPLIER PRIOR TO
IMPROVEMENT
INSTALLATION. REFER TO PLUMBING KITCHEN NOTES SCHEDULE FOR
SIZES. ALL INDIRECT WASTE PIPING SHALL BE INSTALLED SUCH THAT
THERE ARE NO TRIP HAZARDS AND ALL REQUIRED SERVICE ACCESS AND
CLEARANCES FOR EQUIPMENT, PIPING, AND VALVES ARE MAINTAINED.

CO2 SYSTEM SHALL BE INSTALLED BY ROUND ONE'S CO2 VENDOR (NUCO2)


3030 PLAZA BONITA RD, SUITE
12
IN ACCORDANCE WITH NUCO2'S GUIDELINE FOR NEW INSTALLATION OF 1025
LIQUID CARBON DIOXIDE BULK TANK (STANDARD NO. OP-208). BEVERAGE
SUPPLY LINES IN PUBLIC SPACES SHALL BE ENCLOSED IN STEEL OR PVC
NATIONAL CITY, CA 91950
CONDUIT/CHASE.
13 BEER PURVEYOR TO RUN CO2 LINES FROM TANK IN MECH. ROOM TO CLIENT
POWER PACK BY BEER COOLER.
14 1/2" FILTERED WATER TO ICE MACHINE.
ROUND1
15 COORDINATE STUB UP LOCATIONS WITH CASEWORK.

16 4"S FROM CHASE WALL TO DOWN BELOW GRADE.


ENTERTAINMENT
17 4"S IN CHASE WALL.

18 2"S FROM WALL CARRIER AUXILLARY INLET UP TO URINAL, WCO ABOVE


FIXTURE, AND 2"V UP.

M 1 2 3

3070 SATURN ST. STE. 200


BREA, CA 92821
A A CONSULTANT

MENS
108
(5)LAV-1 (4)WC-1
1/2"H&CW, 2"W 1"CW, 4"W.
DN., 1-1/2"V.
4801 Henry St. 1751 Barlow St.
(6)UR-1 Muskegon, MI 49441 Traverse City, MI 49686
3/4" CW T 231-798-4328 T 231-947-1707
3/4"CW, WC-2 SEE SHEET
F 231-798-2981 F 231-947-1710
2"W, 2"V. 1"CW, 4"W. P102 FOR
1/2" CW 3/4" CW 3/4" CW REC #5002
CONTINUATION
1 1/4" CW 1 1/2" CW 2" CW
2" CW 4 2" CW
5 4 2 1/2" CW
1/2" HW 3/4" HW 1" HW
6
4 MSB-1 4
125° 1/2"H&CW,
3"W, 2"V.
1/2" HWR JANITOR
5 1" CW 3/4" CW 1 1/4" CW 1" CW 1 1/4" CW 1 1/2" CW 2" CW 2" CW 2" CW
107 DWH-3 4
SEE DETAIL 1 1/4" CW
125° AND SPECS.
6 1/2" HWR WC-2
5 1/2" HW 4
4 1"CW, 4"W.
4 1 1/4" CW
RCP-2
4
(8)WC-1
1"CW, 4"W. RELEASE DATE

1/2" HWR DATE DESCRIPTION


LAV-2 WC-2
1/2"H&CW 1"CW, 4"W. 4 WOMENS 2" CW 4-21-23 LANDLORD REVIEW
2"W DN., 109 1 1/2" CW 2" CW
1-1/2"V. 1" CW 5-18-23 PERMITS
7-21-23 FOR BIDS
(6)LAV-1 125° 6 5
4
FAMILY 1/2" HWR 1/2"H&CW, 2"W
TOILET DN., 1-1/2"V. (2)WC-1 1 1/2" CW
1/2" CW
106 1/2" CW 1"CW, 4"W.
4
4 1/2" HWR

1" HW

B B

EWC-1
1/2"CW, 1" HW 1/2" CW 3/4" CW 1" HW 3/4" HW 1/2" HW 3/4" CW 1 1/2" CW 1 1/2" CW
2"W, 1-1/2"V.

SEE SHEET
P102 FOR 1 1/2" CW
CONTINUATION

M 1 2 3

2 ENLARGED RESTROOM DOMESTIC PLAN


P-102 SCALE: 1/4" = 1'-0"
PROJECT

2112128GR
SHEET
7/21/2023 3:25:31 PM

RESTROOM ENLARGED
PLAN

P-401
2 3
PLUMBING GENERAL NOTES
A UTILITIES SHOWN ARE APPROXIMATE LOCATIONS, THEIR
LOCATIONS SHOULD NOT BE CONSIDERED EXACT LOCATIONS
SEE P102 FOR NOR SHOULD THEY BE CONSIDERED AS THE ONLY UTILITIES IN
P64 1 1/2" CW CONTINUATION
1/2"CW DN. TO SODA 2 THE AREA.
ASSEMBLY.
SEE DETAIL ON 24X24 24X48 B ALL CONCRETE MAINTENANCE PADS SHALL BE INSTALLED BY
SHEET P501. CONTRACTOR.

C SLEEVE AND SEAL ALL WALL, FLOOR, AND ROOF PENETRATIONS.


5 4
P62 D KEEP AREA CLEAN. REMOVE DEBRIS ON A DAILY BASIS. PARADIGM DESIGN

CWI
REDEMPTION 1/2" CW
E INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO
STORE P43.2 5 COORDINATE THE EXACT ROUTING AND ELEVATION OF PIPING ARCHITECTS | ENGINEERS
4
125 3/4" CW SYSTEMS. THIS CONTRACTOR SHALL INSTALL PIPING SO AS TO
3 10 6 125° 3/4" HW (140°) NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF

CWO
D
1 1/2" CW SYSTEMS.
1/2" HWR

FE-K
F PROVIDE ASSE 1070 APPROVED POINT OF USE MIXING VALVE
D D

24X48
24X48
FOR ALL HANDWASHING SINKS.
3/4" HW (140°) Grand Rapids | Phoenix | Traverse City
G PLUMBING CONTRACTOR SHALL COORDINATE WITH OWNERS
www.paradigmae.com
MILL WORK SUPPLIER PRIOR TO ROUGH-IN OF SODA SLEEVES

24X48
AND OPEN HUB DRAINS IN THE CONCESSIONS AREA.

7.2 H INSTALL WATER HAMMER ARRESTERS PER SPEC'S AND


4 PDI-WH-201.
P40

24X48
24X48 I ALL FLOOR DRAINS SHALL BE INSTALLED PER DETAIL ON P-501.
3/4" CW
KITCHEN

24X48

24X48

18"X18"X12"
J ALL DOMESTIC WATER PIPING SHALL BE INSULATED PER SPECS.

24X48
128
DWH-1 & DWH-2 24X48
125° 6 5 P42
SEE DETAIL ON P501
TYP 4 K ALL CORE DRILLING BY P.C.
AND SPEC'S.

1" HW (140°) 3/4" HW (140°)

34DR

24X48
1 1/2" HW (140°)

24X48
1/2" CW 4

1/2" HW (140°) PLUMBING PLAN NOTES


P42
1 1/2" CW
LEGEND SYMBOL INDICATOR

24X48
14

P86 1 PLUMBING CONTRACTOR SHALL PROVIDE 6" SCHEDULE 40 PVC SODA PROJECT
1/2" HWR SLEEVE WITH LONG SWEEP ELBOWS FROM 3" A.F.F. EXTENDING DOWN TO
P87 4 BAR BELOW FLOOR. SLEEVE AND SEAL FLOOR PENETRATIONS. COORDINATE

CWI
RCP-1
130
P13
THE EXACT LOCATIONS WITH SODA FOUNTAIN MANUFACTURERS
ROUND1 -

C
RECOMMENDATIONS. TUBING TO SODA HEADS BY VENDOR.

D
PLAZA BONITA

TS14BLW

CH
1/2" HWR 1/2" CW P43 P18

H
CWO
6 125° 2 SODA RACK, C02 TANKS, BAG-IN-BOX, TUBING TO SODA HEADS,ETC.

D
10 3 P43.2 PROVIDED BY AND SET IN PLACE BY OTHERS.
5

D
1 1/2" HW (140°) P42
1/2"CW DN TO P53.1

G
1 1/2" HW (140°) P17 4 3 1/2"CW DOWN TO BALL VALVE AND BACKFLOW PREVENTER, EQUAL TO
GUEST WATER FILTER.
P54 WATTS SERIES 7, EXTEND TO OWNER FURNISHED AND INSTALLED

D
COUNTER SEE DETAIL. P53 TYP
CARTRIDGE FILTERS. MOUNT ON WALL AT APROX. 5'-0" A.F.F., EXTEND 1/2"

CRC-63C
G

CH
126 FILTERED WATER TO KITCHEN EQUIPMENT.

D
HOLD PIPING TIGHT TO
WALL. COORDINATE BALL VALVE. INSTALL IN ACCESSIBLE LOCATION.
4

G
MECHANICAL

D
WITH CASEWORK.
3/4" CW 3/4" CW
127 1"HW, 3/4" CW, & 1/2" 5 CHECK VALVE. INSTALL IN ACCESSIBLE LOCATION.
4 HWR FROM BELOW TO 6 THERMOSTATIC BALANCING VALVE. MATCH PIPE SIZE. SET TERMPERATURE
1/2" HWR SERVE BAR FIXTURES. INDICATED ON PLANS. INSTALL IN ACCESSIBLE LOCATION.
D C

SC-15-TS

CH
D
D 15
H 4
C 7 WASTE FROM BELOW TO WCO, FIXTURES, AND VENT UP. SIZES AS NOTED
P12 ON PLANS.
1/2" HW (140°)
1/2"CW, HW, HWR 8 SANITARY VENT FROM BELOW, SIZE NOTED ON PLANS.
FOR DISHWASHER 1" HW (140°)
DN. TO SERVE 1/2" HWR 1" HW (140°)
SNACK BAR SINK. 1/2" CW PIPING SEE DETAIL. 9 P.C. SHALL ROUTE PIPING AS HIGH AS POSSIBLE. ROUTE THROUGH OPEN
1"HW, 3/4"CW, &

CRI-12-30-7
WEB JOISTS WHEREVER POSSIBLE. PRIME AND PAINT PIPING IN EXPOSED

D
1/2"HWR DN. TO SERVE
1/2" HWR SNACK UNDERBAR 3-COMP. P19 AREAS TO MATCH CEILING.
1/2" HW (140°) BAR SINK AND HAND SINKS.
129 10 FURNISH AND INSTALL BACKFLOW PREVENTOR WITH FUNNEL AND
E E INDIRECT WASTE LINE TO NEAREST FLOOR DRAIN OR FLOOR SINK.
125° TERMINATE INDIRECT WASTE AT FLOOR DRAIN WITH AIR GAP.
6
INSTALL VALVES
IN ACCESSIBLE 5 11 INDIRECT WASTE FROM KITCHEN EQUIPMENT FURNISHED AND INSTALLED
BY P.C.. TERMINATE AT NEAREST FLOOR DRAIN WITH AIR GAP. ROUTE
TENANT
LOCATION UNDER
COUNTER.
4
C
H
RC
R
D
C
PIPING BELOW EQUIPMENT AND TIGHT TO WALL WHERE POSSIBLE. P.C.
SHALL FURNISH UNISTRUT WHERE REQUIRED TO MOUNT PIPING. IMPROVEMENT
COORDINATE THE EXACT ROUTING WITH CASE WORK SUPPLIER PRIOR TO
INSTALLATION. REFER TO PLUMBING KITCHEN NOTES SCHEDULE FOR
D SIZES. ALL INDIRECT WASTE PIPING SHALL BE INSTALLED SUCH THAT
THERE ARE NO TRIP HAZARDS AND ALL REQUIRED SERVICE ACCESS AND
15 1/2"CW, HW, & HWR CLEARANCES FOR EQUIPMENT, PIPING, AND VALVES ARE MAINTAINED.
FROM BELOW. HOLD PIPING TIGHT TO
P82
WALL. COORDINATE P77
WITH CASEWORK. 3030 PLAZA BONITA RD, SUITE
P78 12 CO2 SYSTEM SHALL BE INSTALLED BY ROUND ONE'S CO2 VENDOR (NUCO2)
IN ACCORDANCE WITH NUCO2'S GUIDELINE FOR NEW INSTALLATION OF
1025
2 3 LIQUID CARBON DIOXIDE BULK TANK (STANDARD NO. OP-208). BEVERAGE NATIONAL CITY, CA 91950
SUPPLY LINES IN PUBLIC SPACES SHALL BE ENCLOSED IN STEEL OR PVC
CONDUIT/CHASE.
1 ENLARGED KITCHEN DOMESTIC PLUMBING PLAN 13 BEER PURVEYOR TO RUN CO2 LINES FROM TANK IN MECH. ROOM TO
CLIENT
P-102 SCALE: 1/4" = 1'-0" POWER PACK BY BEER COOLER.
14 1/2" FILTERED WATER TO ICE MACHINE. ROUND1
15 COORDINATE STUB UP LOCATIONS WITH CASEWORK.
ENTERTAINMENT
16 4"S FROM CHASE WALL TO DOWN BELOW GRADE.
17 4"S IN CHASE WALL.
2 3 2"S FROM WALL CARRIER AUXILLARY INLET UP TO URINAL, WCO ABOVE
18
FIXTURE, AND 2"V UP.

3"S UP TO WCO., 8
2 & 2"V UP.

24X24 24X48

1 COORDINATE PIPES
WITH COLUMN FOOTING.
3",WCO.
CWI

2" V
REDEMPTION 3",FD-3 3" GW 3070 SATURN ST. STE. 200
W/T.S.
STORE 3",WCO.
2" V BREA, CA 92821
3" S
125
2" V 3" V
CWO

3"V UP IN CHASE ABOVE CONSULTANT


D

3"S UP TO FLOOR SINK, 7


TO ROOF TERMINATION.
WCO, & 2"V UP.
FE-K

D KITCHEN D
24X48
24X48

1
128
3" S
3",FD-1
W/T.S.
24X48

3" V
6" SODA SEE P-101 FOR
6" BEER
3",FD-3 CONTINUATION
24X48

24X48 W/T.S. CONNECT 3"S TO


6" SODA 3" GW
EXISTING SANITARY 4801 Henry St. 1751 Barlow St.
4",FCO.
24X48

24X48

Muskegon, MI 49441 Traverse City, MI 49686


18"X18"X12"

BRANCH. P.C. TO FIELD


24X48

T 231-798-4328 T 231-947-1707
3",FD-1 VERIFY LOCATION, F 231-798-2981 F 231-947-1710
W/T.S. 24X48 4" (E)S SIZE, & CONDITION.
3" GW REC #5002

CONNECT 3"S & 4"S TO 4" (E)S


4" (E)S
EXISTING SANITARY
34DR

3" V 7
BRANCH. P.C. TO FIELD 1 1/2" V 2" S 2"S UP TO
24X48

VERIFY LOCATION, WCO, SINK, &


SIZE, & CONDITION. 3" V 1-1/2"V UP.
24X48

7 8
2"S UP TO
2" V 4" S WCO, SINK, & 2"
4" GW 1-1/2"V UP. 6" BEER 3" S

3" S 3",FCO.
24X48

2" 8
BAR
2" V 2" V 2"
4",FCO. 130
4" (E)S 8
CWI

3" S 15 1
3",FD-3 RELEASE DATE
W/T.S. 3",WCO.
C

3",FD-1 3",FD-1 3" GW 3",FD-3


D

W/T.S. W/T.S. 8 2" W/T.S. DATE DESCRIPTION


TS14BLW

CH

3",WCO. 3" GW 3",FD-3


H
CWO

3" GW
4-21-23 LANDLORD REVIEW
D

W/T.S.
2" V
2" S 5-18-23 PERMITS
D

SEE P-101 FOR


CONTINUATION MECHANICAL 3",FD-3 7-21-23 FOR BIDS
G

11
W/T.S. 1 1/2" V 3" GW
D

127 2" S 3",FD-3 3",FD-1


CRC-63C

2" S W/T.S.
G

W/T.S.
CH

3",FD-1
D

W/T.S.
G

15 2" UP TO CLEAN OUT


D

6" SODA
7 IN CABINET, HAND
3" GW 1 1/2" V SINK, & ISLAND
2" V FIXTURE VENT. SEE
D C 2" V 3" S DET. 17/P-501
SC-15-TS

CH

GUEST
D

D
COUNTER H
C
3" GW
1 1/2" V
126 2" 3" GW BELOW
8 8
1-1/2" 2"
8
3",FCO.
CRI-12-30-7

3" GW
D

1 1/2" V 2" S 3" GW


SNACK 3" S
BELOW 15 1
3",FD-1 BAR 3",FD-1 3",FD-3
W/T.S. 6" SODA
129 W/T.S. W/T.S.
E E
3",FCO.

3",FD-3 RC D
C
H W/T.S. R C 4" GW
PROJECT
2" UP TO CLEAN OUT D
IN CABINET, HAND 15 COORDINATE
SINK, & ISLAND PIPES WITH 1 15 SEE P-101 FOR
FIXTURE VENT. SEE
DET. 17/P-501
COLUMN FOOTING.
CONTINUATION 2112128GR
2 3 SHEET
7/21/2023 3:25:37 PM

2 ENLARGED KITCHEN SANITARY PLAN KITCHEN ENLARGED


P-101 SCALE: 1/4" = 1'-0"
PLAN

P-402
FLOOR

ADJUSTABLE FLOOR
MATERIAL FROM EXCAVATION PLACED IN 2" FLOOR CLEAN OUTS CLEANOUT WITH VENT
LAYERS. TAMP TO 98% PROCTOR. MATERIAL TO BE FLUSH WITH NICKEL BRONZE
SHALL BE FREE OF STONES. FLOOR / GRADE.WADE SCORATED TOP.
W-6000-1 NB FLOOR
WADE W-8550-E WCO
INITIAL BACKFILL HAND PLACED AND WADE W-6000-Z W/8480R6-85
MECHANICALLY TAMPED TO 95% PROCTOR IN 6" CLEANOUT TO W-8550-B W/

1'-0" ABOVE
LAYERS. USE MATERIAL FROM EXCAVATION.
MATERIAL SHALL BE FREE OF STONES.
GRADE (TYP.) W-8480C6-1
FLOOR DRAINS OR
FLOOR SINK SHALL BE
PARADIGM DESIGN
WALL CLEANOUT FLOOR DRAIN
TOP OF PIPE FLUSH WITH FLOOR.
CLEAN OUT PLUG. WITH ACCESS ARCHITECTS | ENGINEERS
COVER (TYP.) FLOOR

HAUNCHING CONSISTING OF FINE GRANULAR FILL SANITARY PIPING.


COMPACTED TO 98% PROCTOR.
VARIES
SHAPED SUBGRADE CONSISTING OF FINE
GRANULAR FILL COMPACTED TO 98% PROCTOR. Grand Rapids | Phoenix | Traverse City
"P" TRAP www.paradigmae.com
2'-6"

1 SANITARY PIPE TRENCH DETAIL 2 YARD CLEANOUT DETAIL 3 FLOOR CLEANOUT DETAIL 4 WALL CLEANOUT DETAIL 5 FLOOR DRAIN DETAIL
P-501 NOT TO SCALE P-501 NOT TO SCALE P-501 NOT TO SCALE P-501 NOT TO SCALE P-501 NOT TO SCALE

CHECK VALVES ABOVE CEILING. COORDINATE MOUNTING


PROVIDE ACCESS DOOR AS HEIGHT WITH WASHER AND
REQUIRED IF GYPSUM CEILING MANUFACTURERS

1/2"

1/2"
SYSTEM. INSTALLATION
INSTRUCTIONS.
ZURN MODEL 460XL ANTI-SIPHON WHITE POWDER COATED
H&CW DOWN IN WALL ANTI-SPILL VACUUM BREAKER STEEL WASHING MACHINE
ASSEMBLY MOUNTED OVER SERVICE WASH RINSE STERILE. BOX WITH QUARTER TURN GOOSENECK FAUCET
SINK FOR CHEM. FEED SYSTEM BY BASIN BASIN BASIN TOP MOUNTED BALL VALVES FOOD SERVICE HAND
MOP HOLDER 1/2" AND 2"PVC CENTER DRAIN. SINK FURNISHED BY
OWNER.
MOUNTED 5'-0" TRANSITION TO 2"W. AT BOX. KITCHEN EQ. SUPPLIER,
ABOVE FLOOR. REFER TO SPECIFICATIONS. INSTALLED BY P.C.
SOAP

2"V.
2" TYP.
DISPENSER
1/2" BY OWNER. CHEMICAL FEED SYSTEM SHALL BE PROJECT
INSTALLED DIRECTLY OVER MOP PROVIDE 1" AIR GAP
HOSE BRACKET MOUNTED 18" SINK. G.C. TO COORDINATE AND

V
ABOVE FINISHED FLOOR. VERIFY CORRECT POSITION. FLOOR SINK
ROUND1 -

24"
FLOOR WATTS OR APPROVED EQUAL
S.S. WALL GUARD FURNISHED 120° F HW MMV THERMOSTATIC MIXING
WITH MSB-1.
TRAP
CW
VALVE, ASSE 1070 COMPLIENT
WITH INTEGRAL STOP, CHECKS
AND WALL MOUNTING FLANGE.
PLAZA BONITA
24"x24"x10" SERVICE SINK, 1. PIPING SHOWN DIAGRAMMATIC FOR CLARIFICATION. 2"W.
MSB-1. SEE PLANS FOR ROUTING AND SPECIFICATIONS FOR
SEAL WATERTIGHT ON ALL
PIPING MATERIALS.
SIDES WITH CAULK.
WATER SUPPLY
FLOOR. OFFSET PIPING TO BOX TO ANGLE STOP (TYP)
2" SAN. RISER. 1/2" HW

2"W.
DN TO SAN. UNDERFLOOR.
FLOOR. 1/2" CW
REMOVABLE STAINLESS
STEEL
COMBINATION DOME
STRAINER
AND LINT BASKET.

9 HAND SINK MIXING VALVE DETAIL


6 MOP SINK DETAIL 7 TRIPLE POT SINK DETAIL 8 WASHING MACHINE OUTLET BOX DETAIL P-501 NOT TO SCALE

P-501 NOT TO SCALE


P-501 NOT TO SCALE P-501 NOT TO SCALE

1/2" BYPASS SERIES 9D-M2 DUAL CHECK VALVES


WITH INTERMEDIATE ATMOSPHERIC BALL VALVES BELOW

1. PIPING SHOWN DIAGRAMMATIC FOR CLARIFICATION.


FURNISH
ESCUTCHEON
1/2" CW VENT, 1/2" SIZE. SINK. (TYP)
TENANT
1/2" CW
SEE PLANS FOR ROUTING AND SPECIFICATIONS FOR
PIPING MATERIALS. 1/2" BY-PASS.
AT WALL
PENETRATION UNION BRAIDED STAINLESS STEEL FLEXIBLE MIXING TEE WITH INTEGRAL VACUUM 1/2" BY-PASS. IMPROVEMENT

1/2"
CONNECTION TO ICE MACHINE PER BREAKER AND PRE-RINSE FURNISHED BY ICE MACH. (SELF SERVE)
(TYP) 1/2"
BALL VALVE UNION MANUFACTURERS RECOMMENDATIONS. OTHERS, INSTALLED BY P.C.
(TYP.) BALL VALVE (TYP)
DUAL CHECK VALVE WITH INSULATE ALL EXPOSED PIPING. FILTER, FOOD SERVICE 1/2" FLEX. TO ICE
ATMOSPHERIC VENT, EQUAL ICE MACHINES FURNISHED AND SET
1/2" IN PLACE BY OTHERS. ALL PIPING, ITEM KE-43.2. VERIFY EXACT MACHINE AT SELF
CW TO WATTS 3/8" SIZE, MODEL TWIN WATER FILTRATION SYSTEM QUANTITY TO INSTALL IN 1/2" PEX OR SERVE. VERIFY
SD-3. (TYP.) WITH SCALE AND CORROSION CONNECTIONS, AND ASSOCIATED
PARALLEL. TYPE "K" CONN. AT UNIT.
3030 PLAZA BONITA RD, SUITE
INHIBITING MEDIA FURNISHED BY VALVES AND FITTINGS BY P.C.
EQUIPMENT SUPPLIER, INSTALLED
COPPER TUBING. 1025
DUAL CHECK VALVE WITH
1/2" TYP. BY P.C. ATMOSPHERIC VENT, EQUAL 6" PVC SLEEVE.
NATIONAL CITY, CA 91950
1/2"
INSTALLED BY P.C.. VERIFY EXACT ICE MACHINES AND REMOTE TO WATTS 1/2" SIZE, MODEL
BALL VALVE. (TYP.) 1/2"
ROUGH-IN REQUIREMENTS AND QUANTITY, CONDENSERS FURNISHED 9D-M2. (TYP.) CLIENT
INSTALL FILTERS IN PARALLEL. BY OWNER, INSTALLED BY
M.C. REFERIGERANT PIPING

REDUCER / INCREASER, (TYP.).


EXTENSION DOWN TO SODA
EQUIPMENT BY SODA
BACK FLOW PREVENTOR AIR
GAP, FUNNEL AND
FROM ICE MACHINES TO
REMOTE CONDENSERS ON
EXTEND TUBING INDIRECT FROM
ATMOSPHERIC VENT CONNECTION TO
ROUND1
DISCHARGE LINE TO FLOOR
P.C. SHALL COORDINATE
EQUIPMENT SUPPLIER.
SINK.
ROOF SHALL BE FURNISHED
AND INSTALLED BY M.C.
FUNNEL
OR CONTINUOUS TRAY UNDER ALL CHECK
1. PIPING SHOWN DIAGRAMMATIC FOR CLARIFICATION.
SEE PLANS FOR ROUTING AND SPECIFICATIONS FOR
ENTERTAINMENT
THE EXACT QUAN. OF REFER TO MECHANICAL VALVES. EXTEND 3/4" DOWN TO NEAREST
SODA CONNECTIONS. PLANS. PIPING MATERIALS.
EXTEND TUBING INDIRECT FROM INDIRECT WASTE FROM ICE MACHINE FLOOR DRAIN OR MOP SINK.
ATMOSPHERIC VENT CONNECTION TO FOR PRICING FIGURE: TO FLOOR DRAIN WITH AIR GAP.
FUNNEL OR CONTINUOUS TRAY (8) TOTAL FOR BAR AND
UNDER ALL CHECK VALVES. EXTEND SELF SERVE SODA DISP..
FLOOR SINK
1/2" DOWN TO NEAREST FLOOR DRAIN
OR FLOOR SINK.
FLOOR
12 PRE RINSE ASSEMBLY 13 REFRESH STATION ICE MACHINE DETAIL
P-501 NOT TO SCALE P-501 NOT TO SCALE
10 SODA RACK DETAIL
P-501 NOT TO SCALE
11 ICE MACHINE DETAIL 1 1/2" CW
P-501 NOT TO SCALE BALL VALVE (TYP)
CHECK VALVE (TYP)
FLASH AND SEAL ENTIRE VENTING FURNISHED AND 1 1/2"
ROOF PENETRATION INSTALLED BY M.C. UNDER THE MECH.
1/2"HWR
"WATTS" 008QTS ANTI-SIPHON VACUUM BREAKER SERVING BOOSTER HEATER AND AS REQUIRED UTILIZE PERMIT AND LICENSING. NOTE: CONCENTRIC BALANCING VALVE (TYP.) 3070 SATURN ST. STE. 200
ANTI-SPILL VACUUM BREAKER RINSE AID. ALL AN INTEGRAL PART OF DISHMACHINE. "PATE" PIPE SEAL. VENT KIT FURNISHED BY P.C., INSTALLED BY
MOUNTED ABOVE CHEM. FEED VERIFY VACUUM BREAKER MEETS ALL STATE AND THE M.C.. P.C. SHALL COORDINATE WITH THE M.C..
BREA, CA 92821

1 1/2"
SYSTEM. LOCAL PLUMBING CODES AND LOCAL CROSSCONNECT REFER TO MECHANICAL PLANS
REGULATIONS. 1/2"HWR
CONSULTANT
THERMAL EXPANSION TANK. EQUAL 14 1-1/2" 140°
UNION AND PIPING TO 1 1/2" 0°
TO "AMTROL INC." THERM-X-TROL HW TO
CHEMICAL FEED BY P.C. COMMERCIAL DISHWASHER. MODEL NO. ST-12 WITH A 150 PSIG FIXTURES..

1 1/2"
P.C. SHALL VERIFY ALL CONN. MAX. WORKING PRESSURE, 4.4 GAL

1 1/2"

1 1/2"
LOCATIONS AND SIZES. TOTAL VOLUME. 1 1/2"
BALL VALVE, TYP. EXTEND VENT AS
HIGH AS POSSIBLE

140°
1/2" CW VACUUM BREAKER 1 1/4" GAS TO UNIT WITH BALL VALVE (TYP) 45°
PER CODE. 3" SCHEDULE GAS COCK AND DIRT LEG.. 45°
CHEMICAL FEED 40 CPVC (TYP.) RECIRC. PUMP RCP-1
DISPENSER BY OWNER. SEE PLANS FOR SIZE THERMOMETER
EQUAL TO BELL & GOSSETT MODEL 1 1/2" V
CHECK VALVE. THERMAL EXPANSION ECOCIRC e3-6, 1.0 GPM AT 6' HEAD, 120V-1∅,
WATER INLET. TANK. EQUAL TO FURNISH PUMP WITH B&G MODEL 4801 Henry St. 1751 Barlow St.
"AMTROL INC." THERM-X- ECOCIRC ECM CIRCULATION TIMER. 1-1/2"S TO Muskegon, MI 49441 Traverse City, MI 49686
UNION (TYP.) ISLAND
FLEX. HOSE FURNISHED DETERGENT INLET PIPE BY VENDOR. COLD WATER TROL MODEL NO. ST-5. MOUNT AT APPROX. 48" A.F.F. T 231-798-4328 T 231-947-1707
HANDSINK F 231-798-2981 F 231-947-1710
WITH DISHWASHER. REC #5002
SEE PLANS FOR SIZE 1 1/2" V
3/4" 140° HW
CLEANOUT IN
RELIEF VALVE PER CABINET
1-1/2" DRAIN HOSE. HOT WATER TO FIXTURES. LOCAL CODE (TYP.)
1/2" CW 2" S
AIR GAP. ELEC. WATER HEATER DWH-3 & DWH-4
T
RELIEF VALVE PER SEE SCHEDULE & SPECS WTR. HEATER
FLOOR SINK.
BACKFLOW PREVENTER, LOCAL CODE. DWH-1& DWH-2
HOSE BIBB & DRAIN VALVE.
LEAD FREE, EQUAL TO FLOOR. SEE SCHEDULE & DRAIN VALVE
WATTS LF009, 1/2" SIZE. GALV. DRIP PAN SPEC'S. 1-1/2" UNDERFLOOR
PER CODE. FOOT VENT SLOPED
* WASTE WATER TEMPERING 3/4" CONDENSATE, EXTEND TO FLOOR DRAIN. UP TO NEAREST
ASSEMBLY. EQUAL TO COOL NEUTRALIZER (NOT SHOWN) FURNISHED WITH WALL WITH
DRAIN FLOW, MODEL DTV
3/4" TO MOP SINK WATER HEATER. CLEANOUT
120-UG. OR DISH MACHINE
ANCHOR WITH S.S. OR FLOOR DRAIN
OPTION "DRAIN QUENCH
UNISTRUT TO MAINTAIN AIR SEAL CONN. TO PAN. BALL VALVES (TYP.) 3 1/2" CONC. OR FIBERGLASS PAD BY P.C..
ASSEMBLY". INSTALL PER
MFG'S RECOMMENDATIONS. GAP.
NOTES: DRAIN VALVE EXTEND RELIEF VALVE PIPING AND TERMINATE
INDIRECT AT FLOOR DRAIN
RELEASE DATE
A. UTILITIES ARE SHOWN FOR A JACKSON DYNATEMP SERIES DOOR-TYPE DISHMACHINE AND ARE SUBJECT TO CHANGE. P.C. UNIONS (TYPICAL)
WTR. HEATER VENT/COMB.
SHALL CAREFULLY FOLLOW ALL INSTALLATION REQUIREMENTS AND CODES. WALL SHELF AND BRACKET FURNISHED WITH WATER HEATER OR
B. INSTALL ALL RPZ'S, VALVES, ECT. IN A SERVICEABLE LOCATION, FIELD VERIFY ALL LOCATIONS. DATE DESCRIPTION
BUILT IN FIELD, PRIME AND PAINT TO PREVENT RUSTING.
C. ITEMS MARKED WITH AN *... P.C. SHALL INCLUDE IN THEIR BID A DEDUCTIVE ALTERNATE TO OMIT THE INDIVIDUAL COMPONENT.
PRIOR TO INSTALLATION THE P.C. SHALL VERIFY THE EXACT MODEL TO BE INSTALLED. IF ANY OF THESE COMPONENTS ARE 17 ISLAND VENT DETAIL 4-21-23 LANDLORD REVIEW
FOUND TO BE FURNISHED WITH OR INTEGRAL TO THE UNIT THEN THE COST OF THE COMPONENT SHALL BE CREDITED. IF
EXTERNAL TO THE UNIT THEN INSTALLATION SHALL REMAIN THE RESPONSIBILITY OF THE P.C. 15 DWH-3 & 4 ELECTRIC WATER HEATER DETAIL 16 WATER HEATER DETAIL P-501 NOT TO SCALE 5-18-23 PERMITS
NOT TO SCALE P-501 NOT TO SCALE 7-21-23 FOR BIDS
P-501
14 DISHWASHER PIPING DETAIL
P-501 NOT TO SCALE

WATER PIPING
TO FIXTURE

PIPE HANGER W/
SEE PLANS FOR ROD TO
PIPE SIZE. STRUCTURE SEE PLANS FOR
INSTANTANEOUS ELECTRIC

CW
HW
PIPE SIZE.
WATER HEATER MOUNTED
ON WALL. EQUAL TO EEMAX FLOW REGULATOR
LAVADVANTAGE MODEL
CLEVIS RING TYPE #SPEX4208T.
COLD WATER
PIPE HANGER. SUPPLY W/ STOP

PIPE HANGER PIPE HANGER W/


WTR. HEATER
W/ ROD TO ROD TO
INSULATION DWH-5
STRUCTURE. STRUCTURE
HIGH DENSITY ELECTRIC JUNCTION BOX BY
CW ELECTRIC CONTRACTOR
INSULATION INSULATION

18 GA PIPE SHIELD MIN. SHUT-OFF VALVE


12" LONG W/ FLARED SEAL INSULATION JACKET
BLOCKING INSERT TO
PREVENT CRUSHING AT HANGER PENETRATION.
INSULATION.
PROJECT

NOTE: ABOVE DETAIL


2-1/2" & LARGER PIPE.
NOTE: ABOVE DETAIL
2-1/2" & LARGER PIPE.
NOTE: ABOVE DETAIL
2" & SMALLER PIPE.
WIRING BY PLUMBING CONTRACTOR 2112128GR
SHEET
7/21/2023 3:25:38 PM

18 PIPE HANGER DETAIL 19 INSTANTANEOUS WATER HEATER DETAIL


P-501 NOT TO SCALE P-501 NOT TO SCALE PLUMBING DETAILS

P-501
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

2" V
2" V
Grand Rapids | Phoenix | Traverse City
2" V www.paradigmae.com

2" V
3"V UP IN CHASE ABOVE
TO ROOF TERMINATION.

1 1/2" V

2" V
2" V
2" V
2" V

1 1/2" V

3" V
3" V
3" V

2" V
2" V

2" V

2" V
1 1/2" V
2" V
3" V

2" V

1 1/2" V
PROJECT

1 1/2" V

2" V
2" V
ROUND1 -

2" V
3",FCO.
PLAZA BONITA
3",FD-3 3",FD-1 SEE P-101 FOR
2" UP TO CLEAN OUT W/T.S. CONTINUATION
W/T.S.
IN CABINET, HAND
SINK, & ISLAND 2" S
FIXTURE VENT. SEE 3",FD-3 3",WCO.
DET. 17/P-501 W/T.S.
3",FD-1
W/T.S.

3" GW 3",WCO.
3",FD-1 2" S 4" (E)S
W/T.S.
3" S
2" S
3",FD-1
3",FD-3
W/T.S.
W/T.S.
3",WCO.
3" S
3",FCO. 3" GW
3",FD-3 4",FCO.
3" S W/T.S.
3",FD-1 4",FCO.
4" S 6" BEER
W/T.S. 3" GW
6" SODA 3",FD-1 3",FD-3
W/T.S. W/T.S.
4" GW
4" GW

4" GW 3" S
6" SODA
TENANT
3",FD-3
W/T.S. 3" S
3",FCO.
2" S 6" SODA IMPROVEMENT
6" SODA

3",FD-1 3" GW 3",WCO.


2" S W/T.S. 3030 PLAZA BONITA RD, SUITE
2" UP TO CLEAN OUT 3" GW
IN CABINET, HAND 3",FD-3 3" GW
3",FD-3 6" BEER 1025
SINK, & ISLAND W/T.S. 4" (E)S
FIXTURE VENT. SEE
W/T.S. 2" S NATIONAL CITY, CA 91950
3" S
DET. 17/P-501 3",FD-1 CONNECT 3"S & 4"S TO
W/T.S. EXISTING SANITARY CLIENT
3"V UP IN CHASE
BRANCH. P.C. TO FIELD
3" V

TO ROOF 3",FD-3
W/T.S. VERIFY LOCATION,
TERMINATION
SIZE, & CONDITION.
ROUND1
CONNECT 3"S TO
1 1/2" V EXISTING SANITARY
BRANCH. P.C. TO FIELD
ENTERTAINMENT
1 1/2" V
1 1/2" V

4" (E)S VERIFY LOCATION,


SIZE, & CONDITION.
3" V SEE P-101 FOR
2" V
CONTINUATION
1 1/2" V

2" V

3" V
KITCHEN SANITARY RISER DIAGRAM
1 1/2" V

3" V
3" V

3" V

2" V
2" V
2" V
1 1/2" V

2" V

3070 SATURN ST. STE. 200


BREA, CA 92821
2" V

CONSULTANT
2" V

3" V
2" V

2" V
1 1/2" V

(5)LAV-1
1/2"H&CW, 2"W 1 1/2" V 4801 Henry St. 1751 Barlow St.
DN., 1-1/2"V. Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
1 1/2" V

F 231-798-2981 F 231-947-1710
3" V

REC #5002
2",WCO.

LAV-2
1/2"H&CW
2"W DN., 2" S
1-1/2"V.
3",WCO. MSB-1
3" V

3",FD-1 2",WCO.
1/2"H&CW, 3",FCO.
W/T.S.
4"S UP TO WC, 3"W, 2"V.
3" S WCO., & 3"V UP.
4",WCO.
3" S
3",FD-1
W/T.S.
(6)UR-1
3/4"CW,
2"W, 2"V.
FIXTURE UNIT CALCULATION
2",WCO. LOAD VALUES (in wsfu's) DRAINAGE LOAD
EWC-1 WC-2 ROOM QTY PLUMBING FIXTURE HW CW Trap Size Indirect RELEASE DATE
1/2"CW, 1"CW, 4"W. Hot Cold Combined Total DFU / fixture Total Grease
2"W, 1-1/2"V.
3" S 1 3-COMP. SINK/pre-rinse 1/2" 1/2" 3 3 4.0 4 3" Y 6 6 Y DATE DESCRIPTION
4" S 4",WCO. 4" S
1 DISHWASHER 3/4" 1.5 1.5 1.5 3" Y 6 6 Y 5-18-23 PERMITS
3",WCO.
1 WORKTABLE SINK 1/2" 1/2" 3 3 4.0 4 3" Y 4 4 Y 7-21-23 FOR BIDS
3" S 3",FD-1 3 HAND SINK 1/2" 1/2" 1.5 1.5 2.0 6 1-1/2" N 1 3 N
3" S W/T.S.
KITCHEN 1 DISHTABLE SINK 1/2" 1/2" 3 3 4.0 4 3" Y 4 4 Y
1 MOP SINK 1/2" 1/2" 2.25 2.25 3.0 3 3" N 2 2 Y
(6)LAV-1 (4)WC-1
1 SODA ASSEMBLY - 1/2" 0.5 0.5 0.5 3" Y 1 1 N
2",WCO. 1/2"H&CW, 2"W 1"CW, 4"W. 1 MOP SINK 3/4" 3/4" 2.25 2.25 3.0 3 3" N 3 3 Y
DN., 1-1/2"V.
3" S 3" S 1 ICE MAKER - 1/2" 0.5 0.5 0.5 3" Y 1 1 N
3",FD-1
W/T.S. SNACK BAR 1 HAND SINK 1/2" 1/2" 1.5 1.5 2.0 2 1-1/2" N 1 1 N
WC-2
1 UNDERBAR 3-COMP.... 1/2" 1/2" 3 3 4.0 4 3" Y 6 6 Y
(8)WC-1 1"CW, 4"W. BAR 1 UNDERBAR HAND SINK 1/2" 1/2" 1.5 1.5 2.0 2 1-1/2" N 1 1 N
1"CW, 4"W.
2" S 1 BLENDER STATION SINK 1/2" 1/2" 1.5 1.5 2.0 2 1-1/2" Y 2 2 Y
4" S
4",WCO. 1 WASHING MACHINE 1/2" 1/2" 1 1 1.4 1.4 2" N 3 3 N
SEE SHEET P101 MECHANICS
FOR CONTINUATION 3" S
2",WCO. 1 EYEWASH 1/2" 1/2" 0.5 0.5 0.7 0.7 1-1/2" N 1 1 N
4" S RM.
2" S
1 MOP SINK 1/2" 1/2" 2.25 2.25 3.0 3 3" N 3 3 N
WC-2
16 FLUSH VALVE TOILETS - 1" 5 5.0 80 4" N 4 64 N
(2)WC-1 1"CW, 4"W. RESTROOMS 6 URINALS - 3/4" 4 4.0 24 2" N 2 12 N
1"CW, 4"W.
11 LAVATORIES 1/2" 1/2" 1.5 1.5 2.0 22 1-1/2" N 1 11 N
4" S JANITOR 1 MOP SINK 3/4" 3/4" 2.25 2.25 3.0 3 3" N 3 3 N
FAMILY 1 FLUSH VALVE TOILETS - 1" 5 5.0 5 4" N 4 4 N
4",WCO.
SEE SHEET P101
4" S RESTROOM 1 LAVATORIES 1/2" 1/2" 1.5 1.5 2.0 2 1-1/2" N 1 1 N PROJECT
FOR CONTINUATION ALCOVE 1 DRINKING FOUNTAIN - 1/2" 0.25 0.25 0.25 2" N 0.5 0.5 N
EMPLOYEE... 1 HAND SINK 1/2" 1/2" 1.5 1.5 2.0 2 1-1/2" N 1 1 N 2112128GR
TOTAL 179.85 TOTAL 143.5
Demand Est. 85 GREASE TOTAL 33
SHEET
Water Service Size 2-1/2" SANITARY TOTAL 110.5
7/21/2023 3:25:43 PM

RESTROOM SANITARY RISER DIAGRAM


PLUMBING SANITARY
RISER DIAGRAM

P-601
KITCHEN EQUIPMENT SCHEDULE
INDIRECT DIRECT
ITEM NO. DESCRIPTION CW HW HW TEMP BFP COMMENTS
WASTE WASTE

FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY PARADIGM DESIGN


WALK-IN BEER
1" TO F.S. P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P7.2 COOLER COIL - - - N/A AIR GAP ARCHITECTS | ENGINEERS
W/ AIR GAP INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
CONDENSATE
DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.

FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY


UNDERBAR P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND Grand Rapids | Phoenix | Traverse City
P12 1/2" 1/2" 120º N/A 1-1/2" AIR GAP
HAND SINK INSTALLED BY P.C.. P.C. SHALL PROVIDE 1070 POINT OF USE www.paradigmae.com

MIXING VALVE. REFER TO HAND SINK MIXING VALVE DETAIL...

FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY


1/2"CW, HW, HWR 1-1/2" TO
DN. TO SERVE 1/2" HWR 1/2" HWR P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
SNACK BAR SINK. P13 UNDERBAR SINK 1/2" 1/2" 140º F.S. W/ AIR N/A AIR GAP
INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
GAP
1/2" HW (140°) DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.
1 1/2" HW (140°)
P82
1/2" CW
3/4" HW (140°) FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
FOR DISHWASHER UNDERBAR 3 (3) 1-1/2"
PIPING SEE DETAIL. 1 1/2" HW (140°) P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P17 COMP SINK & 1/2" 1/2" 140º TO F.S. W/ N/A AIR GAP
DWH-1 & DWH-2 INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
FAUCET AIR GAP

1/2" HWR
1 1/2" HW (140°)
1/2" HWR SEE DETAIL ON P501 DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.

1/2" CW
1/2"CW, HW, & HWR AND SPEC'S.
1/2"CW DN TO
FROM BELOW.
WATER FILTER.
SEE DETAIL. FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
DRAIN PER
1" HW (140°) P43.2 P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
1 1/2" HW (140°) P18 BEER TOWER - - - MFR TO F.S. N/A AIR GAP
1/2" HW (140°) INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
1"HW, 3/4"CW, &
1/2" HWR 1 1/2" CW RCP-1 W/ AIR GAP
1/2"HWR DN. TO SERVE P43 DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP. PROJECT
UNDERBAR 3-COMP. 1/2" CW
SINK AND HAND SINKS. 1" CW

3/4" CW 1/2" HWR


1/2" HWR
1/2"CW DN. TO SODA 1/2" TO F.S.
FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
ROUND1 -

1/2" HW (140°)
P19 ICE BIN - - - N/A AIR GAP
PLAZA BONITA

1/2" CW
1" HW (140°) P53 ASSEMBLY.
P54 SEE DETAIL ON W/ AIR GAP INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
P53.1 SHEET P501.

1/2" CW
DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.
1/2" HWR

3/4" CW
P42
1 1/2" CW P43.2
P86 FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
1-1/2" TO
P87 WORK TABLE W/ P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
3/4" CW
P62 P40 1/2" 1/2" 140º F.S. W/ AIR N/A AIR GAP
PREP SINK INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
GAP
DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.

3/4" HW (140°)

3/4" HW (140°)
1/2" CW
1" HW (140°)

1/2" HWR
1/2" CW
1/2" HW (140°) P42 1 1/2" CW
FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY

1/2" CW
P12
P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
1/2" HWR 3/4" CW P42 P42 HAND SINK 1/2" 1/2" 120º N/A 1-1/2" INTEGRAL
INSTALLED BY P.C.. P.C. SHALL PROVIDE 1070 POINT OF USE
3/4" HW (140°)

1/2" HW (140°)
1/2" HW (140°) P64
1" HW (140°) MIXING VALVE. REFER TO HAND SINK MIXING VALVE DETAIL...
P40
1"HW, 3/4" CW, & 1/2" P13
1/2" HWR SEE P102 FOR FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
HWR FROM BELOW TO
CONTINUATION 1/2" DRAIN PER
SERVE BAR FIXTURES. P17 ICEMAKER W/ P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P43 FILTERED - - MFR. TO F.S. N/A AIR GAP
HOLD PIPING TIGHT TO BIN INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
WALL. COORDINATE WATER W/ AIR GAP
WITH CASEWORK. DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP. TENANT
IMPROVEMENT
DUAL CHECK FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
WATER FILTER W/ P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P43.2 1/2" - - N/A N/A
ASSEMBLY ATMOSPHE INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
KITCHEN DOMESTIC WATER RISER DIAGRAM RIC VENT ATMOSPHERIC VENT TO FLOOR SINK WITH AIR GAP.
3030 PLAZA BONITA RD, SUITE
1025
SOILED AIR GAP & FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY NATIONAL CITY, CA 91950
1-1/2" TO
DISHTABLE & INTEGRAL P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P53 & P53.1 1/2" 1/2" 140º F.S. W/ AIR N/A CLIENT
PRE-RINSE CHECK INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
GAP
FAUCET VALVES DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.
ROUND1
1/2" TO
FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY ENTERTAINMENT
DISHWASHER, 2" TO F.S. P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P54 DRAIN 3/4" 140º N/A AIR GAP
DOOR TYPE W/ AIR GAP INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
COOLER
DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.

1/2" FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY


P62 BAG-IN-BOX FILTERED - - N/A N/A N/A P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
WATER INSTALLED BY P.C

AIR GAP & FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY


MOP SINK & 3070 SATURN ST. STE. 200
P64 & P64.1 1/2" 1/2" 140º N/A 3" VACUUM P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
SERVICE FAUCET BREA, CA 92821
BREAKER INSTALLED BY P.C.. REFER TO MOP SINK DETAIL (P501).
1/2" CW
CONSULTANT
1/2" HWR
FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
1/2" DRAIN PER
(5)LAV-1 ICE CUBER FOR P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
1/2"H&CW, 2"W P77 FILTERED - - MFR TO F.S. N/A AIR GAP
DN., 1-1/2"V. P78 INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
WATER W/ AIR GAP
1/2" HWR
1" CW DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.
1/2" CW
1/2" HWR

3/4" CW
1/2" CW

FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY


DRAIN PER
SODA P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
3/4" CW P78 - - - MFR TO F.S. N/A AIR GAP
DISPENSER INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM 4801 Henry St. 1751 Barlow St.
1/2" HW W/ AIR GAP Muskegon, MI 49441 Traverse City, MI 49686
1 1/4" HW

DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP. T 231-798-4328


F 231-798-2981
T 231-947-1707
F 231-947-1710
1/2" HW

REC #5002
1" CW
1/2" HWR
1/2" CW

LAV-2
1/2"H&CW RCP-2 1" HW
FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
2"W DN., MSB-1
1-1/2"V. P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
1/2"H&CW, P82 HAND SINK 1/2" 1/2" 120º N/A 1-1/2" INTEGRAL
3"W, 2"V. INSTALLED BY P.C.. P.C. SHALL PROVIDE 1070 POINT OF USE
MIXING VALVE. REFER TO HAND SINK MIXING VALVE DETAIL...

WC-2 (6)UR-1
1/2" HWR AIR GAP & FURNISHED BY KITCHEN EQUIPMENT SUPPLIER, INSTALLED BY
1"CW, 4"W. 3/4"CW, (3) 1-1/2"
3/4" CW 2"W, 2"V. 3 COMP SINK & INTEGRAL P.C. ALL ASSOCIATED PIPING, VALVES, ETC, FURNISHED AND
P86 & P87 1/2" 1/2" 140º TO F.S. W/ N/A
1 1/4" CW FAUCET CHECK INSTALLED BY P.C.. P.C. SHALL ROUTE INDIRECT WASTE FROM
DWH-3 1" HW AIR GAP
SEE DETAIL 1 1/4" CW VALVES DRAIN CONNECTION TO FLOOR SINK WITH AIR GAP.
AND SPECS.
1 1/2" CW
EWC-1
1/2"CW, 1" CW
NOTES: RELEASE DATE
2"W, 1-1/2"V. 1 1/2" CW 1. ALL FOOD SERVICE EQUIPMENT, I.E. EQUIPMENT NOTED WITH A "ITEM NUMBER" SHALL BE FURNISHED, INSTALLED AND / OR SET IN PLACE BY THE FOOD SERVICE
1 1/4" CW DATE DESCRIPTION
CONTRACTOR. IN GENERAL THE TRIMS, WASTE BASKETS, TAILPIECE, THREADED CONNECTIONS OR NIPPLES ARE FURNISHED WITH THIS EQUIPMENT. P.C. SHALL COORDINATE
2 1/2" CW 5-18-23 PERMITS
1 1/2" CW WITH THE FOOD SERVICE CONTRACTOR FOR EXACT SIZES, CONNECTION TYPES, LOCATIONS ETC..
7-21-23 FOR BIDS
(6)LAV-1
1/2"H&CW, 2"W
(4)WC-1
1"CW, 4"W.
THE P.C. SHALL FURNISH AND INSTALL THE FOLLOWING AS APPROPRIATE FOR THE FIXTURE OR APPLIANCE. KEYED WHEEL HANDLE STOPS, WALL ESCUTCHEONS, CHROME PLATED
DN., 1-1/2"V. BRASS P-TRAP AT HAND SINKS, COPPER TUBING FROM 3-COMP., WORK SINKS, DISH. MACH., ETC. THAT TERMINATE WITH AN AIR GAP AT THE FLOOR SINK, PEX TUBING WITH
2" CW

(8)WC-1 STAINLESS STEEL CLAMPS FROM MISC. APPLIANCES. PROVIDE STAINLESS STEEL BRAIDED WATER SUPPLIES TO FIXTURES OR APPLIANCES.
2" CW

125°
1/2" HWR

1"CW, 4"W.
1/2" CW
2" CW SEE SHEET
P102 FOR
3/4" CW 2" CW
CONTINUATION
1" HW GAS WATER HEATER SCHEDULE
1 1/2" CW

WC-2
(2)WC-1 1"CW, 4"W.
3/4" HW 1"CW, 4"W. TAG SERVICE MBH/HR RECOVERY RATE - THERMAL BASIS OF DESIGN REMARKS
1 1/2" CW
3/4" CW GPH @ 100° RISE EFFICIENCY
1/2" HW
WC-2 DWH-1 AND KITCHEN 150 175 96% LOCHINVAR SHIELD SWR150N REFER TO DETAIL 16 ON SHEET P-501 AND SPECIFICATION SECTION
1"CW, 4"W. DWH-2 22 3400 FOR ADDITIONAL REQUIREMENTS.

SEE SHEET
P102 FOR
CONTINUATION
ELECTRIC WATER HEATER SCHEDULE
TAG SERVICE KW VOLTAGE/P RECOVERY TANK CAPACITY, BASIS OF DESIGN REMARKS
RESTROOM DOMESTIC WATER RISER DIAGRAM HASE RATE - GPH @
100° RISE
GALLONS

DWH-3 RESTROOMS 24 480/3PH 98 40 LOCHINVAR COMPACT ASME HI-POWER REFER TO DETAIL 15 ON SHEET P-501 AND SPECIFICATION SECTION 22 3400
MODEL LCA-40X24 FOR ADDITIONAL REQUIREMENTS.
DWH-4 MECHANICS 24 480/3PH 98 40 LOCHINVAR COMPACT ASME HI-POWER REFER TO DETAIL 15 ON SHEET P-501 AND SPECIFICATION SECTION 22 3400 PROJECT
ROOM MODEL LCA-40X24 FOR ADDITIONAL REQUIREMENTS.
DWH-5 EMPLOYEE 4.1 208/1PH -- -- EEMAX LAVADVANTAGE SPEX4208T REFER TO DETAIL 19 ON SHEET P-501 AND SPECIFICATION SECTION 22 3400
LOUNGE FOR ADDITIONAL REQUIREMENTS.
2112128GR
SHEET
PUMP SCHEDULE
7/21/2023 3:25:46 PM

TAG SERVICE FLOW


GPM
HEAD
PRESSURE
ELECTRICAL BASIS OF DESIGN REMARKS
PLUMBING DOMESTIC
FEET
WATER RISER DIAGRAM
RCP-1 KITCHEN 1 9 120V, 5-28W BELL & GOSSETT ECOCIRC e3-6, LEAD FREE ECM FURNISH PUMP WITH B&G MODEL ECOCIRC ECM CIRCULATION TIMER. MOUNT AT
CIRCULATOR APPROX. 48" A.F.F.
RCP-2 RESTROOMS 1 9 120V, 5-28W BELL & GOSSETT ECOCIRC e3-6, LEAD FREE ECM
CIRCULATOR
FURNISH PUMP WITH B&G MODEL ECOCIRC ECM CIRCULATION TIMER. MOUNT AT
APPROX. 48" A.F.F.
P-602
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

CLIENT

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

CONSULTANT

4801 Henry St. 1751 Barlow St.


Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
F 231-798-2981 F 231-947-1710
REC #5002

RELEASE DATE

DATE DESCRIPTION
5-18-23 PERMITS
7-21-23 FOR BIDS

PROJECT

2112128GR
SHEET
7/21/2023 3:25:46 PM

PLUMBING COMPLIANCE
FORMS

P-603
PARADIGM DESIGN
MECHANICAL GENERAL NOTES
ARCHITECTS | ENGINEERS
A ALL WORK SHALL BE INSTALLED PER LOCAL, STATE, & FEDERAL CODES, RULES, ORDINANCES, AND REGULATIONS.

B REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

C ALL DUCT AND EQUIPMENT ELEVATIONS NOTED ON PLANS MEASURED FROM F.F. TO BOTTOM OF DUCT/EQUPMENT UNLESS
OTHERWISE NOTED.
D ALL DUCTWORK SHALL BE INSULATED ACCORDING TO WRITTEN SPECIFICATIONS UNLESS OTHERWISE NOTED.
Grand Rapids | Phoenix | Traverse City
E ALL DUCTWORK BEHIND GRILLES AND DIFFUSERS CONNECTIONS SHALL BE PAINTED FLAT BLACK. PAINT INSIDE OF DUCT
CONNECTIONS 2'-0" UP STREAM OF FIRST 90 DEGREE ELBOW. www.paradigmae.com
2 3
F ALL WORK SHOWN ON THIS PLAN TO BE COORDINATED WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
INSTALLATION.
G FIELD VERIFY THERMOSTAT AND SENSOR LOCATIONS WITH OWNER. INSTALL SENSORS AT A HEIGHT OF ±4'-0" A.F.F..
COORDINATE MECHANICAL SENSOR LOCATIONS WITH OTHER TRADES, INSTALL SENSORS ±6"-1'0" ABOVE LIGHTING
CONTROLS WHEN INSTALLED IN SIMILAR LOCATIONS.

H ALL DUCT DIMENSIONS ARE INSIDE DIMENSIONS.

I INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO COORDINATE THE EXACT ROUTING AND ELEVATION OF DUCTING
SYSTEMS. THIS CONTRACTOR SHALL INSTALL DUCTING SO AS TO NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF

MATCH LINE - SEE SHEET M-104


SYSTEMS.

J ALL RECTANGULAR RETURN DUCTWORK SHALL HAVE 1" INTERNAL LINER, REFER TO SPECIFICATIONS.

K ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTS SHALL HAVE A BALANCING DAMPER NEAR MAIN. (INDIVIDUAL BRANCH
DAMPERS NOT SHOWN ON PLANS)

L ALL SUPPLY, RETURN AND EXHAUST DUCT ELBOWS SHALL BE SMOOTH RADIUS ELBOWS WITH THE INSIDE RADIUS SAME AS
I I.5 J K L L.1 M.1 M 1 WIDTH OF DUCT UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. ALL 90° MITERED ELBOWS SHALL HAVE
TURNING VANES.

M EXHAUST TERMINATIONS, PLUMBING VENTS, ETC. SHALL BE A MINIMUM OF 3FT. VERTICAL CLEARANCE ABOVE OR MINIMUM
OF 10FT. HORIZONTAL CLEARANCE FROM FENESTRATION OR EQUIPMENT OUTDOOR AIR INTAKES.

N ALL SERVICEABLE MECHANICAL EQUIPMENT INSTALLED ON ROOF SHALL BE INSTALLED A MINIMUM OF 10FT FROM ROOF
EDGE OR HAVE GUARD RAIL AS REQUIRED BY CODE. MAINTAIN MANUFACTURER RECOMMENDED CLEARANCES. PROJECT
4.1 4.1
RTU-3 10 O PAINT ALL VISIBLE GAS PIPING TO MATCH ADJACENT SURFACE. ALL GAS PIPING ROUTED ON ROOF SHALL BE PAINTED
YELLOW.
A A
P ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE LOWER
ROUND1 -
LEVEL SHALL BE BLACK IN COLOR UNLESS OTHERWISE NOTED. ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND
MENS
108
10 RTU-1
"B" - SA
"E" - EA
580 CFM
10"x10" NK
STORAGE
111
GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE UPPER LEVEL SHALL BE WHITE IN COLOR UNLESS OTHERWISE
NOTED. DIFFUSERS / GRILLES SHALL BE ORDERED WITH FINISH SPECIFIED IN ASSOCIATED SCHEDULE. MECHANICAL
PLAZA BONITA
"B" - SA CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED DUCTWORK SPECIFIED TO BE PAINTED FOR PREPARATION OF
385 CFM
250 CFM PAINTING BY PAINTING CONTRACTOR. ALL OILS, DUST AND DEBRIS SHALL BE REMOVED FROM SURFACES REQUIRING
10"ø NK PAINTING. OBTAIN WRITTEN APPROVAL FROM MANUFACTURER BEFORE PAINTING DUCT WRAP INSUALTION. UL LISTING MUST
"E" - EA 6"ø NK
42"x36" AL RA NOT BE COVERED. PAINTING MUST OCCUR AFTER ROUGH DUCT INSPECTION. FIRE-WRAPPED GREASE DUCTS SHALL NOT BE
150 CFM

S
TO PAINTED.

44"x36" AL RA
6"x6" NK 10"ø SA
VAV-3-9
VAV-3-9 VAV-3-4

44"x28" SA
JANITOR "E" - TA Q COORDINATE ALL ROOF PENETRATIONS WITH LANDLORD. ALL ROOF PENETRATIONS SHALL BE PERFORMED BY THE
"C" - SA 36"x6" TA

10"ø SA
700 CFM LANDLORD'S ROOFING CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
50 CFM
VAV-3-10 4"ø NK
107 18"x10" NK "I" - TA
10"x8" SA 700 CFM R ALL MECHANICAL DUCTS AND PIPING PENETRATING RATED ASSEMBLIES SHALL BE SEALED AND FIRE-STOPPED TO COMPLY
8"x8" SA
30"x8" NK WITH LOCAL REGULATIONS. FOR REFERENCE, SHAFT WALL CONSTRUCTION IS 1-HR RATED FOR DUCTS ROUTED DOWN TO

8"ø SA
MTD AT 14'0" LOWER LEVEL, DUCT PENETRATIONS INTO AND OUT OF SHAFTS SHALL BE SEALED AND FIRE STOPPED ACCORDINGLY PER
2 A.F.F.
6"ø SA PARTY CODE REQUIREMENTS.
ROOM 1

BOD: 15' - 6"


PLUSH "B" - SA S ALL FLEX DUCTS SHALL TRANSITION FROM ROUND METAL DUCT TO SAME SIZE FLEX DUCT. PROVIDE PREFORMED 90°
WOMENS "E" - EA 110 TRANSITION ELBOW FOR FLEX DUCT CONNECTION INTO SUPPLY DIFFUSER INLET. 5'0" MAXIMUM LENGTH FOR EACH
STORAGE 420 CFM
"B" - SA "E" - EA 109 600 CFM "B" - SA INDIVIDUAL RUN OF FLEX DUCT.
10"ø NK

8"x8" EA
105 70 CFM 100 CFM 10"x10" NK 200 CFM "B" - SA
6"ø NK 6"x6" NK 6"ø NK 250 CFM TO T TEST AND BALANCE CONTRACTOR SHALL BE BROWARD COUNTY CERTIFIED.
TO (2) "I" - TA 6"ø NK
FAMILY VAV-3-4

44"x30" SA
U FIELD VERIFY THAT ALL MECHANICAL WORK COMPLETED BY THE LANDLORD AS PART OF THE SHELL PACKAGE MATCHES
VAV-3-10 300 CFM 8"x8" EA BOD: 13' - 9"
TOILET TO CONDITIONS SHOWN ON PLANS. TENANT MECHANICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND
5.1 S 5.1 28"x8" EA

S
24"x6" NK ENGINEER IF IT IS DETERMINED THAT MECHANICAL WORK BY THE LANDLORD DEVIATES SUBSTANTIALLY FROM PLANS.
106 2
VAV-3-5
BFEC B
24"x6" TA
90"x34" RA OPENING S
IN TOP OF 44"x36" "E" - TA "A" - SA
VAV-3-5
"A" - SA AL RA DUCT. COVER 700 CFM 100 CFM VAV-3-8 TENANT

BOD: 10' - 11"


1000 CFM WITH GALVANIZED "B" - SA "B" - SA "E" - TA
18"x10" NK 6"x6" NK
24"x12" NK WWM. 250 CFM 12"ø SA 250 CFM 700 CFM "I" - TA
MTD AT 45° "A" - SA
1500 CFM
6"ø NK 6"ø NK 18"x10" NK 600 CFM MECHANICAL PLAN NOTES IMPROVEMENT
36"x10" NK
"I" - TA VAV-3-7 14"x14" SA 30"x8" NK

44"x26" SA

18"x12" SA
700 CFM 8"ø SA 8"x10" SA MTD AT 14'0"
8"ø SA LEGEND SYMBOL INDICATOR
BOD: 11' - 7"
MTD AT 45° 30"x8" NK A.F.F.
MTD AT 14'0" 8"x10" SA
30"x14" SA

28"x8" EA
A.F.F. "A" - SA PARTY 1 CONTROL DISPLAY FOR CENTRALIZED CONTROL OF RTU-1, 2, 3, 4, 5, & 6 SHALL BE LOCATED IN A.V. 115, SEE ROOFTOP UNIT SCHEDULE.
125 CFM ROOM 2

8"ø SA
PARTY 6"x6" NK 2 DOOR(S) TO SPACE SHALL BE UNDERCUT A MINIMUM OF 1" TO ALLOW RETURN / EXHAUST AIRFLOW, SEE ARCHITECTURAL PLANS. 3030 PLAZA BONITA RD, SUITE

14"x14" SA
28"x12" SA 121
ROOM 4
M.C. SHALL PROVIDE FIXED CO2 GAS DETECTION SYSTEM EQUAL TO MODEL #RAD-0102. FURNISH AND INSTALL PER THE MFG. 1025
124 "B" - SA "B" - SA
RECOMMENDATION AND IN ACCORDANCE WITH NFPA-55 AND CALIFORNIA FIRE CODE 2022 SECTION 5307.3.2.. FURNISH UNIT WITH
REDEMPTION 200 CFM 250 CFM
3 ADDITIONAL DISPLAY AND VISUAL ALARM MOUNTED OUTSIDE ROOM WITH LOCKABLE PLEXIGLAS COVER OVER ALARM, SIGNAGE MOUNTED
NATIONAL CITY, CA 91950
"A" - SA 6"ø NK 6"ø NK
"A" - SA STORAGE VAV-3-1 ON DOOR INTO ROOM, CO2 SYSTEM EMERGENCY SHUTOFF SWITCH INTERLOCKED WITH SOLENOID VALVE AT CO2 TANK OUTLET, AND EF-2

44"x22" SA
1500 CFM "A" - SA
1500 CFM 123 MANUAL SHUTOFF SWITCH.
36"x10" NK 1500 CFM "B" - SA "B" - SA
MTD AT 45° 36"x10" NK 36"x10" NK 38"x14" SA
250 CFM 200 CFM
MTD AT 45° MTD AT 45° ROUTE REFRIGERANT LINES FROM ACCU-1 OVER ON ROOF TO PIPE CURB, DOWN THRU ROOF INTO CHASE AND DOWN TO ROUND 1 SPACE,
ROUND1

44"x24" SA
6"ø NK 6"ø NK "A" - SA

S
125 CFM 4 AND OVER TO ASSOCIATED INDOOR UNIT A/C-1 IN A/V 126. COVER REFRIGERANT PIPE INSULATION WITH UV RESISTANT PVC JACKET OR

S
TO PAINT WITH UV RESISTANT PVC COATING.
6"x6" NK S TO
VAV-3-7
VAV-3-6 ENTERTAINMENT
C BOD: 13' - 9" C 5 PIPE CURB EQUAL TO PATE MODEL #PCC WITH CAP COLLAR AND BOOT FITTING PACKAGE.
6.1 6.1 "A" - SA
TO
32"x20" SA

125 CFM
S 6"x6" NK
RTU-1 3"Ø COMBUSTION AIR INTAKE AND 3"Ø FLUE EXHAUST VENT UP FROM WATER HEATER AND UP THRU ROOF TO ROOF CONCENTRIC

10"x8" SA
VAV-3-6

18"x12" SA
"B" - SA
6 TERMINATION. FLASH AND SEAL AS REQUIRED. SEE PLUMBING PLANS AND SPECIFICATIONS.
"A" - SA "A" - SA 250 CFM PARTY "B" - SA

28"x22" SA
1500 CFM 1500 CFM 44"x24" SA 8"ø NK 250 CFM "E" - TA
ROOM 3
36"x10" NK 36"x10" NK 6"ø NK 700 CFM 7 CLOTHES DRYER TO BE DUCTLESS MODEL. NO DRYER VENTING REQUIRED.
122

12"x12" SA
MTD AT 45° MTD AT 45° 10"ø SA 18"x10" NK

18"x18" TA "B" - SA NEW RTU TO BE INSTALLED ON CURB ADAPTER. SEE ROOFTOP UNIT SCHEDULE FOR ADDITIONAL REQUIREMENTS. RECONNECT EXISTING
200 CFM "B" - SA 8 GAS PIPING AND CONDENSATE. VERIFY GAS PIPE SIZE IS ADQEUATE FOR NEW RTU HEATING LOAD.
"B" - SA VENDING
BOD: 11' - 4"

6"ø NK 250 CFM


250 CFM TO "A" - SA

S
125 CFM 6"ø NK 124
8"ø NK VAV-3-8
6"x6" NK 9 NEW RTU TO BE INSTALLED ON EXISTING CURB. RECONNECT EXISTING GAS PIPING AND CONDENSATE.
14"ø SA
10"ø SA

MATCH LINE - SEE SHEET M-104


44"x24" SA

14"ø SA
44"x22" SA
(2) "I" - TA VAV-3-2 CONNECT NEW SA AND RA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT
"A" - SA REDEMPTION
600 CFM 10 TRANSITION AND MODIFY EXISTING DUCTOWRK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION.
3070 SATURN ST. STE. 200
"A" - SA "B" - SA 18"x18" NK 1-1/2" G
1500 CFM BREA, CA 92821
44"x22" SA

1500 CFM STORE 250 CFM


36"x10" NK 24X24 24X48

125
30"x20" SA

36"x10" NK MTD AT 45° 8"ø NK

32"x8" SA
MTD AT 45° VAV-3-3 CONNECT NEW SA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT TRANSITION
CONSULTANT
6.8 6.8 11 AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION. EXISTING RA TO REMAIN

CWI
"B" - SA
KITCHEN 600 CFM WITH GALVANIZED WWM.
BOD: 11' - 2" 128 12"ø NK

CWO
BOD: 11' - 3"

D
10"ø SA "B" - SA

FE-K
6.9 D 6.9 D EXHAUST DUCT FROM EF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE THROUGH EXISTING CHASE.
600 CFM

(2) 3" INTAKE & VENT

24X48
24X48
12 TRANSITION TO 28"x8" EA AND ROUTE OVER AT 13'9" A.F.F..
BOD: 11' - 7" 12"ø NK
7.1 7.1

24X48
(2) 3" INTAKE

1-1/2" G
30"x14" SA

EXHAUST DUCT INTAKE FROM EF-2 12"x12" EA ROUTED OVER AT 10'0" A.F.F.. ROUTE OVER TO CO2 TANK AND ROUTE DOWN TO 3-1/4" A.F.F..
13 EXHAUST OUTLET AT 12"x12" EA ROUTED OVER AT 10'0" A.F.F. TO EQUAL OR GREENHECK MODEL #BVE128 MOUNTED AT 10'0" A.F.F..

24X48
"B" - SA
EXHAUST SYSTEM TO BE INSTALLED TO MEET CALIFORNIA FIRE CODE SECTION 5004.3.1 SYSTEM REQUIREMENTS. SEE DETAIL 15/M501.

& VENT

16"ø GD
250 CFM 17

24X48

24X48

1 8"X1 8"X1 2"

24X48
8"ø NK
"A" - SA "A" - SA TO EXHAUST CONDENSATE DUCT FROM KEF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE. TRANSITION
MALL 44"x22" SA "B" - SA
1500 CFM 1500 CFM BOD: 14' - 2" 1-1/4" G TO 600 CFM
10"ø GD
VAV-3-3 "B" - SA 14 TO 14" EA GD AND ROUTE OVER AT 12'6" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED ACORDING TO IMC SECTION 506
1N ENTRANCE 36"x10" NK 36"x10" NK 1N S FOR EXHAUST SYSTEMS SERVING TYPE I HOODS, SEE KITCHEN HOOD DETAIL FOR ADDITIONAL REQUIREMENTS. 4801 Henry St. 1751 Barlow St.

34DR
DWH-1 & DWH-2 12"ø NK 300 CFM Muskegon, MI 49441 Traverse City, MI 49686

24X48
104 MTD AT 45° MTD AT 45° 8"ø NK T 231-798-4328 T 231-947-1707

24X48

28"x8" SA
STAINLESS STEEL EXHAUST DUCT FROM KEF-2 ON ROOF ROUTED THROUGH EXISTING CHASE INTO ROUND 1 SPACE. TRANSITION FROM F 231-798-2981 F 231-947-1710
BOD: 14' - 2" 10"ø GD KEF-2 TO 14" R S/S EA AND ROUTE THROUGH CHASE, THEN OVER AT 14'2" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED REC #5002
6 15 ACORDING TO IMC SECTION 506 FOR EXHAUST SYSTEMS SERVING TYPE II HOODS AND SEALED WATER TIGHT. REFER TO FOORD SERVICE
BAR

24X48
14"ø GD
"B" - SA "B" - SA EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.
"B" - SA 130
125 CFM 300 CFM MECHANICAL 600 CFM

CWI
6"ø NK 8"ø NK 127 12"ø NK

C
KITCHEN AND DISHWAHSER HOODS, HOOD FIRE SUPPRESSION SYSTEM, EXHAUST FANS, AND ALL ASSOCIATED EQUIPMENT ARE

D
3-WAY 8"ø SA

TS14BLW

CH
16 16 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER UNLESS NOTED OTHERWISE, INSTALLED AND DUCTED BY MECHANICAL CONTRACTOR.

H
CWO
REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.
HOOD-2

G
MATCH LINE - SEE SHEET M-102 MATCH LINE - SEE SHEET M-102

D
(2) "F" - TA

CRC-63C
G

CH
24"x6" TA

D
300 CFM 16 COOLER EVAPORATOR, CONDENSING UNIT, AND ASSOCIATED REFRIGERANT PIPING FURNISHED BY FOOD SERVICE EQUIPMENT

D
24"x6" NK 10"ø GD 16 17 CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. M.C. SHALL VERIFY EQUIPMENT LOCATIONS WITH FOOD SERVICE EQUIPMENT
ABOVE DOOR SUPPLIER. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

18 SEE DETAIL 15/M501 FOR OVERSIZE GRILLE CONSTUCTION.

RELEASE DATE
I I.5 K L L.1 M.1 M 1 2 3
DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

N
MECHANICAL FIRST FLOOR PLAN 'A'
SCALE: 1/8" = 1'-0"

PLAN

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:21:25 PM

MECHANICAL FIRST
FLOOR PLAN 'A'

M-101
KEY PLAN
PARADIGM DESIGN
MECHANICAL GENERAL NOTES
ARCHITECTS | ENGINEERS
A ALL WORK SHALL BE INSTALLED PER LOCAL, STATE, & FEDERAL CODES, RULES, ORDINANCES, AND REGULATIONS.

B REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

C ALL DUCT AND EQUIPMENT ELEVATIONS NOTED ON PLANS MEASURED FROM F.F. TO BOTTOM OF DUCT/EQUPMENT UNLESS
OTHERWISE NOTED.
D ALL DUCTWORK SHALL BE INSULATED ACCORDING TO WRITTEN SPECIFICATIONS UNLESS OTHERWISE NOTED.
Grand Rapids | Phoenix | Traverse City
E ALL DUCTWORK BEHIND GRILLES AND DIFFUSERS CONNECTIONS SHALL BE PAINTED FLAT BLACK. PAINT INSIDE OF DUCT
CONNECTIONS 2'-0" UP STREAM OF FIRST 90 DEGREE ELBOW. www.paradigmae.com

F ALL WORK SHOWN ON THIS PLAN TO BE COORDINATED WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
INSTALLATION.
G FIELD VERIFY THERMOSTAT AND SENSOR LOCATIONS WITH OWNER. INSTALL SENSORS AT A HEIGHT OF ±4'-0" A.F.F..
COORDINATE MECHANICAL SENSOR LOCATIONS WITH OTHER TRADES, INSTALL SENSORS ±6"-1'0" ABOVE LIGHTING
CONTROLS WHEN INSTALLED IN SIMILAR LOCATIONS.

H ALL DUCT DIMENSIONS ARE INSIDE DIMENSIONS.

I INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO COORDINATE THE EXACT ROUTING AND ELEVATION OF DUCTING
SYSTEMS. THIS CONTRACTOR SHALL INSTALL DUCTING SO AS TO NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
I I.5 J K L L.1 M.1 M 1 2 3 SYSTEMS.

J ALL RECTANGULAR RETURN DUCTWORK SHALL HAVE 1" INTERNAL LINER, REFER TO SPECIFICATIONS.

K ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTS SHALL HAVE A BALANCING DAMPER NEAR MAIN. (INDIVIDUAL BRANCH
DAMPERS NOT SHOWN ON PLANS)

L ALL SUPPLY, RETURN AND EXHAUST DUCT ELBOWS SHALL BE SMOOTH RADIUS ELBOWS WITH THE INSIDE RADIUS SAME AS
WIDTH OF DUCT UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. ALL 90° MITERED ELBOWS SHALL HAVE

24X48
14"ø GD
TURNING VANES.
MECHANICAL

CWI
M EXHAUST TERMINATIONS, PLUMBING VENTS, ETC. SHALL BE A MINIMUM OF 3FT. VERTICAL CLEARANCE ABOVE OR MINIMUM
127

C
OF 10FT. HORIZONTAL CLEARANCE FROM FENESTRATION OR EQUIPMENT OUTDOOR AIR INTAKES.

D
8"ø SA

TS14BLW

CH
16

H
CWO
MATCH LINE - SEE SHEET M-101 MATCH LINE - SEE SHEET M-101 N ALL SERVICEABLE MECHANICAL EQUIPMENT INSTALLED ON ROOF SHALL BE INSTALLED A MINIMUM OF 10FT FROM ROOF
HOOD-2 EDGE OR HAVE GUARD RAIL AS REQUIRED BY CODE. MAINTAIN MANUFACTURER RECOMMENDED CLEARANCES. PROJECT

D
(2) "F" - TA

CRC-63C
G

CH
24"x6" TA O PAINT ALL VISIBLE GAS PIPING TO MATCH ADJACENT SURFACE. ALL GAS PIPING ROUTED ON ROOF SHALL BE PAINTED

D
300 CFM 16
BOD: 14' - 2" HOOD-3 YELLOW.
ROUND1 -

D
24"x6" NK 10"ø GD 16 "B" - SA
ABOVE DOOR
2N 2N D C 300 CFM P ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE LOWER

SC-1 5 -TS
S

CH
D
TO D
HOOD-1 8"ø NK LEVEL SHALL BE BLACK IN COLOR UNLESS OTHERWISE NOTED. ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND
PLAZA BONITA
H
C
VAV-3-2 "B" - SA GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE UPPER LEVEL SHALL BE WHITE IN COLOR UNLESS OTHERWISE
125 CFM 2 NOTED. DIFFUSERS / GRILLES SHALL BE ORDERED WITH FINISH SPECIFIED IN ASSOCIATED SCHEDULE. MECHANICAL
GUEST 6"ø NK M1002
8"ø SA CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED DUCTWORK SPECIFIED TO BE PAINTED FOR PREPARATION OF

CRI- 12 -3 0- 7
COUNTER

D
24"x8" SA PAINTING BY PAINTING CONTRACTOR. ALL OILS, DUST AND DEBRIS SHALL BE REMOVED FROM SURFACES REQUIRING
"B" - SA
126 200 CFM PAINTING. OBTAIN WRITTEN APPROVAL FROM MANUFACTURER BEFORE PAINTING DUCT WRAP INSUALTION. UL LISTING MUST
8.1 E 8.1 SNACK E NOT BE COVERED. PAINTING MUST OCCUR AFTER ROUGH DUCT INSPECTION. FIRE-WRAPPED GREASE DUCTS SHALL NOT BE
6"ø NK
BAR PAINTED.
72"x36" RA DUCT RC D
OPENING TO BE H 129 C
C
R
8.2 "A" - SA BOD: 12' - 6" 8.2
1250 CFM COVERED WITH D Q COORDINATE ALL ROOF PENETRATIONS WITH LANDLORD. ALL ROOF PENETRATIONS SHALL BE PERFORMED BY THE
FEC GALVANIZED WWM. LANDLORD'S ROOFING CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
24"x12" NK "B" - SA "B" - SA
600 CFM 600 CFM

MATCH LINE - SEE SHEET M-103


MTD AT 45°
8.3 8.3 R ALL MECHANICAL DUCTS AND PIPING PENETRATING RATED ASSEMBLIES SHALL BE SEALED AND FIRE-STOPPED TO COMPLY
RTU-5 11 14"ø NK 14"ø NK
TO S BOD: 11' - 6" WITH LOCAL REGULATIONS. FOR REFERENCE, SHAFT WALL CONSTRUCTION IS 1-HR RATED FOR DUCTS ROUTED DOWN TO
LOWER LEVEL, DUCT PENETRATIONS INTO AND OUT OF SHAFTS SHALL BE SEALED AND FIRE STOPPED ACCORDINGLY PER
RTU-5 CODE REQUIREMENTS.
36"x14" SA 36"x16" SA
S ALL FLEX DUCTS SHALL TRANSITION FROM ROUND METAL DUCT TO SAME SIZE FLEX DUCT. PROVIDE PREFORMED 90°
TRANSITION ELBOW FOR FLEX DUCT CONNECTION INTO SUPPLY DIFFUSER INLET. 5'0" MAXIMUM LENGTH FOR EACH
INDIVIDUAL RUN OF FLEX DUCT.
BOD: 11' - 7"
"A" - SA T TEST AND BALANCE CONTRACTOR SHALL BE BROWARD COUNTY CERTIFIED.
1000 CFM
24"x12" NK U FIELD VERIFY THAT ALL MECHANICAL WORK COMPLETED BY THE LANDLORD AS PART OF THE SHELL PACKAGE MATCHES
"A" - SA CONDITIONS SHOWN ON PLANS. TENANT MECHANICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND
MTD AT 45°
1250 CFM ENGINEER IF IT IS DETERMINED THAT MECHANICAL WORK BY THE LANDLORD DEVIATES SUBSTANTIALLY FROM PLANS.
24"x12" NK
MTD AT 45°

"A" - SA "A" - SA

36"x16" SA
500 CFM
24"x6" NK
500 CFM
24"x6" NK TENANT
MTD AT 45° MTD AT 45°
F F MECHANICAL PLAN NOTES IMPROVEMENT
FEC
9.1 9.1 LEGEND SYMBOL INDICATOR
"A" - SA 1 CONTROL DISPLAY FOR CENTRALIZED CONTROL OF RTU-1, 2, 3, 4, 5, & 6 SHALL BE LOCATED IN A.V. 115, SEE ROOFTOP UNIT SCHEDULE.
1250 CFM
24"x12" NK
"A"-SA
2 DOOR(S) TO SPACE SHALL BE UNDERCUT A MINIMUM OF 1" TO ALLOW RETURN / EXHAUST AIRFLOW, SEE ARCHITECTURAL PLANS. 3030 PLAZA BONITA RD, SUITE
MTD AT 45°
1025
28"x14" SA

1000 CFM M.C. SHALL PROVIDE FIXED CO2 GAS DETECTION SYSTEM EQUAL TO MODEL #RAD-0102. FURNISH AND INSTALL PER THE MFG.
24"x12" NK RECOMMENDATION AND IN ACCORDANCE WITH NFPA-55 AND CALIFORNIA FIRE CODE 2022 SECTION 5307.3.2.. FURNISH UNIT WITH
"A" - SA MTD AT 45° 3 ADDITIONAL DISPLAY AND VISUAL ALARM MOUNTED OUTSIDE ROOM WITH LOCKABLE PLEXIGLAS COVER OVER ALARM, SIGNAGE MOUNTED
NATIONAL CITY, CA 91950
"A" - SA 500 CFM
500 CFM ON DOOR INTO ROOM, CO2 SYSTEM EMERGENCY SHUTOFF SWITCH INTERLOCKED WITH SOLENOID VALVE AT CO2 TANK OUTLET, AND EF-2
24"x6" NK MANUAL SHUTOFF SWITCH.
24"x6" NK MTD AT 45°
MTD AT 45°

44"x28" SA
4
ROUTE REFRIGERANT LINES FROM ACCU-1 OVER ON ROOF TO PIPE CURB, DOWN THRU ROOF INTO CHASE AND DOWN TO ROUND 1 SPACE,
AND OVER TO ASSOCIATED INDOOR UNIT A/C-1 IN A/V 126. COVER REFRIGERANT PIPE INSULATION WITH UV RESISTANT PVC JACKET OR ROUND1

28"x14" SA
"A" - SA
PAINT WITH UV RESISTANT PVC COATING.
1250 CFM
24"x12" NK "A"-SA
1000 CFM
ENTERTAINMENT
MTD AT 45°
24"x12" NK 5 PIPE CURB EQUAL TO PATE MODEL #PCC WITH CAP COLLAR AND BOOT FITTING PACKAGE.
MTD AT 45°

"A" - SA 3"Ø COMBUSTION AIR INTAKE AND 3"Ø FLUE EXHAUST VENT UP FROM WATER HEATER AND UP THRU ROOF TO ROOF CONCENTRIC
"A" - SA 6 TERMINATION. FLASH AND SEAL AS REQUIRED. SEE PLUMBING PLANS AND SPECIFICATIONS.
500 CFM 500 CFM
24"x6" NK 24"x6" NK
MTD AT 45° MTD AT 45°
G G 7 CLOTHES DRYER TO BE DUCTLESS MODEL. NO DRYER VENTING REQUIRED.
BOD: 11' - 7"

BOD: 11' - 6"


"A" - SA
1250 CFM "A"-SA
24"x12" NK 1000 CFM NEW RTU TO BE INSTALLED ON CURB ADAPTER. SEE ROOFTOP UNIT SCHEDULE FOR ADDITIONAL REQUIREMENTS. RECONNECT EXISTING
10.1 10.1 MTD AT 45° 24"x12" NK 8 GAS PIPING AND CONDENSATE. VERIFY GAS PIPE SIZE IS ADQEUATE FOR NEW RTU HEATING LOAD.
MTD AT 45°

9 NEW RTU TO BE INSTALLED ON EXISTING CURB. RECONNECT EXISTING GAS PIPING AND CONDENSATE.
16"x14" SA

44"x28" SA
CONNECT NEW SA AND RA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT
10 3070 SATURN ST. STE. 200
26"x14" SA

TRANSITION AND MODIFY EXISTING DUCTOWRK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION.
BREA, CA 92821
"A" - SA BOD: 12' - 0"
1250 CFM CONNECT NEW SA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT TRANSITION
"A" - SA "A" - SA
11 AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION. EXISTING RA TO REMAIN
CONSULTANT
500 CFM 24"x12" NK 60"x52" RA OPENING
500 CFM WITH GALVANIZED WWM.
24"x6" NK MTD AT 45° IN TOP OF 72"x24"
24"x6" NK
MTD AT 45° AL RA DUCT. COVER
MTD AT 45°
WITH GALVANIZED
WWM. EXHAUST DUCT FROM EF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE THROUGH EXISTING CHASE.
12 TRANSITION TO 28"x8" EA AND ROUTE OVER AT 13'9" A.F.F..
FEC

72"x24" AL RA
EXHAUST DUCT INTAKE FROM EF-2 12"x12" EA ROUTED OVER AT 10'0" A.F.F.. ROUTE OVER TO CO2 TANK AND ROUTE DOWN TO 3-1/4" A.F.F..
13 EXHAUST OUTLET AT 12"x12" EA ROUTED OVER AT 10'0" A.F.F. TO EQUAL OR GREENHECK MODEL #BVE128 MOUNTED AT 10'0" A.F.F..
10 RTU-2 EXHAUST SYSTEM TO BE INSTALLED TO MEET CALIFORNIA FIRE CODE SECTION 5004.3.1 SYSTEM REQUIREMENTS. SEE DETAIL 15/M501.
H H EXHAUST CONDENSATE DUCT FROM KEF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE. TRANSITION
14 TO 14" EA GD AND ROUTE OVER AT 12'6" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED ACORDING TO IMC SECTION 506
FOR EXHAUST SYSTEMS SERVING TYPE I HOODS, SEE KITCHEN HOOD DETAIL FOR ADDITIONAL REQUIREMENTS. 4801 Henry St. 1751 Barlow St.
Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
STAINLESS STEEL EXHAUST DUCT FROM KEF-2 ON ROOF ROUTED THROUGH EXISTING CHASE INTO ROUND 1 SPACE. TRANSITION FROM F 231-798-2981 F 231-947-1710
KEF-2 TO 14" R S/S EA AND ROUTE THROUGH CHASE, THEN OVER AT 14'2" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED REC #5002
11.1 11.1 15 ACORDING TO IMC SECTION 506 FOR EXHAUST SYSTEMS SERVING TYPE II HOODS AND SEALED WATER TIGHT. REFER TO FOORD SERVICE
EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

KITCHEN AND DISHWAHSER HOODS, HOOD FIRE SUPPRESSION SYSTEM, EXHAUST FANS, AND ALL ASSOCIATED EQUIPMENT ARE
16 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER UNLESS NOTED OTHERWISE, INSTALLED AND DUCTED BY MECHANICAL CONTRACTOR.
REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

COOLER EVAPORATOR, CONDENSING UNIT, AND ASSOCIATED REFRIGERANT PIPING FURNISHED BY FOOD SERVICE EQUIPMENT
17 CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. M.C. SHALL VERIFY EQUIPMENT LOCATIONS WITH FOOD SERVICE EQUIPMENT
SUPPLIER. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

MATCH LINE - SEE SHEET M-103


18 SEE DETAIL 15/M501 FOR OVERSIZE GRILLE CONSTUCTION.

I I.5 K L L.1 M.1 M 1 2 3 RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

N
MECHANICAL FIRST FLOOR PLAN 'B'
SCALE: 1/8" = 1'-0"

PLAN

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:21:28 PM

MECHANICAL FIRST
FLOOR PLAN 'B'

M-102
KEY PLAN
PARADIGM DESIGN
MECHANICAL GENERAL NOTES
ARCHITECTS | ENGINEERS
A ALL WORK SHALL BE INSTALLED PER LOCAL, STATE, & FEDERAL CODES, RULES, ORDINANCES, AND REGULATIONS.

B REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

C ALL DUCT AND EQUIPMENT ELEVATIONS NOTED ON PLANS MEASURED FROM F.F. TO BOTTOM OF DUCT/EQUPMENT UNLESS
OTHERWISE NOTED.
D ALL DUCTWORK SHALL BE INSULATED ACCORDING TO WRITTEN SPECIFICATIONS UNLESS OTHERWISE NOTED.
Grand Rapids | Phoenix | Traverse City
E ALL DUCTWORK BEHIND GRILLES AND DIFFUSERS CONNECTIONS SHALL BE PAINTED FLAT BLACK. PAINT INSIDE OF DUCT
CONNECTIONS 2'-0" UP STREAM OF FIRST 90 DEGREE ELBOW. www.paradigmae.com

F ALL WORK SHOWN ON THIS PLAN TO BE COORDINATED WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
INSTALLATION.
G FIELD VERIFY THERMOSTAT AND SENSOR LOCATIONS WITH OWNER. INSTALL SENSORS AT A HEIGHT OF ±4'-0" A.F.F..
4 5 6 7 8 COORDINATE MECHANICAL SENSOR LOCATIONS WITH OTHER TRADES, INSTALL SENSORS ±6"-1'0" ABOVE LIGHTING
CONTROLS WHEN INSTALLED IN SIMILAR LOCATIONS.

H ALL DUCT DIMENSIONS ARE INSIDE DIMENSIONS.

I INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO COORDINATE THE EXACT ROUTING AND ELEVATION OF DUCTING
SYSTEMS. THIS CONTRACTOR SHALL INSTALL DUCTING SO AS TO NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
SYSTEMS.

24X48
J ALL RECTANGULAR RETURN DUCTWORK SHALL HAVE 1" INTERNAL LINER, REFER TO SPECIFICATIONS.

BILLIARDS VESTIBULE K ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTS SHALL HAVE A BALANCING DAMPER NEAR MAIN. (INDIVIDUAL BRANCH
132 133 DAMPERS NOT SHOWN ON PLANS)

14"ø SA
D
TS14BLW

CH
MATCH LINE - SEE SHEET M-104 MATCH LINE - SEE SHEET M-104 L ALL SUPPLY, RETURN AND EXHAUST DUCT ELBOWS SHALL BE SMOOTH RADIUS ELBOWS WITH THE INSIDE RADIUS SAME AS
WIDTH OF DUCT UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. ALL 90° MITERED ELBOWS SHALL HAVE
"A"-SA "A"-SA "E" - TA TURNING VANES.

D
CRC-63C

CH
650 CFM 650 CFM 1200 CFM

D
24"x12" NK 24"x12" NK M EXHAUST TERMINATIONS, PLUMBING VENTS, ETC. SHALL BE A MINIMUM OF 3FT. VERTICAL CLEARANCE ABOVE OR MINIMUM

D
20"x20" NK
"B" - SA MTD AT 45° MTD AT 45° OF 10FT. HORIZONTAL CLEARANCE FROM FENESTRATION OR EQUIPMENT OUTDOOR AIR INTAKES.
300 CFM

SC-1 5 -TS

CH
D
8"ø NK 18"ø SA 18"ø SA N ALL SERVICEABLE MECHANICAL EQUIPMENT INSTALLED ON ROOF SHALL BE INSTALLED A MINIMUM OF 10FT FROM ROOF
EDGE OR HAVE GUARD RAIL AS REQUIRED BY CODE. MAINTAIN MANUFACTURER RECOMMENDED CLEARANCES. PROJECT
2
M1002
VAV-4-6 O PAINT ALL VISIBLE GAS PIPING TO MATCH ADJACENT SURFACE. ALL GAS PIPING ROUTED ON ROOF SHALL BE PAINTED
CRI- 12 -3 0- 7
"B" - SA
D YELLOW.

E
"B" - SA
200 CFM
6"ø NK
600 CFM
14"ø NK
E P ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE LOWER
ROUND1 -
LEVEL SHALL BE BLACK IN COLOR UNLESS OTHERWISE NOTED. ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND
GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE UPPER LEVEL SHALL BE WHITE IN COLOR UNLESS OTHERWISE
NOTED. DIFFUSERS / GRILLES SHALL BE ORDERED WITH FINISH SPECIFIED IN ASSOCIATED SCHEDULE. MECHANICAL
PLAZA BONITA
CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED DUCTWORK SPECIFIED TO BE PAINTED FOR PREPARATION OF
PAINTING BY PAINTING CONTRACTOR. ALL OILS, DUST AND DEBRIS SHALL BE REMOVED FROM SURFACES REQUIRING

22"x22" SA
MATCH LINE - SEE SHEET M-102

"I" - TA PAINTING. OBTAIN WRITTEN APPROVAL FROM MANUFACTURER BEFORE PAINTING DUCT WRAP INSUALTION. UL LISTING MUST
1200 CFM NOT BE COVERED. PAINTING MUST OCCUR AFTER ROUGH DUCT INSPECTION. FIRE-WRAPPED GREASE DUCTS SHALL NOT BE

FEC
36"x18" NK PAINTED.
ABOVE DOOR
Q COORDINATE ALL ROOF PENETRATIONS WITH LANDLORD. ALL ROOF PENETRATIONS SHALL BE PERFORMED BY THE
LANDLORD'S ROOFING CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.

22"x22" SA R ALL MECHANICAL DUCTS AND PIPING PENETRATING RATED ASSEMBLIES SHALL BE SEALED AND FIRE-STOPPED TO COMPLY
(2) "A"-SA (2) "A"-SA (2) "A"-SA "A"-SA (2) "A"-SA WITH LOCAL REGULATIONS. FOR REFERENCE, SHAFT WALL CONSTRUCTION IS 1-HR RATED FOR DUCTS ROUTED DOWN TO
1000 CFM 1000 CFM 1000 CFM 1000 CFM 1000 CFM LOWER LEVEL, DUCT PENETRATIONS INTO AND OUT OF SHAFTS SHALL BE SEALED AND FIRE STOPPED ACCORDINGLY PER
24"x12" NK 24"x12" NK 24"x12" NK 24"x12" NK 24"x12" NK
STAIR CODE REQUIREMENTS.

14"ø SA
MTD AT 45° MTD AT 45° MTD AT 45° MTD AT 45° MTD AT 45° S-2
S ALL FLEX DUCTS SHALL TRANSITION FROM ROUND METAL DUCT TO SAME SIZE FLEX DUCT. PROVIDE PREFORMED 90°
TRANSITION ELBOW FOR FLEX DUCT CONNECTION INTO SUPPLY DIFFUSER INLET. 5'0" MAXIMUM LENGTH FOR EACH
INDIVIDUAL RUN OF FLEX DUCT.

BOD: 12' - 10"


VAV-4-7 T TEST AND BALANCE CONTRACTOR SHALL BE BROWARD COUNTY CERTIFIED.
44"x18" SA 26"x18" SA
U FIELD VERIFY THAT ALL MECHANICAL WORK COMPLETED BY THE LANDLORD AS PART OF THE SHELL PACKAGE MATCHES
S CONDITIONS SHOWN ON PLANS. TENANT MECHANICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND
TO ENGINEER IF IT IS DETERMINED THAT MECHANICAL WORK BY THE LANDLORD DEVIATES SUBSTANTIALLY FROM PLANS.

F
VAV-4-7 F
S TO

18"x18" SA
RTU-2
TENANT

20"ø SA
"A"-SA
"A" - SA
825 CFM MECHANICAL PLAN NOTES IMPROVEMENT
24"x10" NK
1000 CFM MTD AT 45°
24"x12" NK LEGEND SYMBOL INDICATOR
MTD AT 45°
"A" - SA 1 CONTROL DISPLAY FOR CENTRALIZED CONTROL OF RTU-1, 2, 3, 4, 5, & 6 SHALL BE LOCATED IN A.V. 115, SEE ROOFTOP UNIT SCHEDULE.

BOD: 12' - 7"


800 CFM
24"x10" NK 2 DOOR(S) TO SPACE SHALL BE UNDERCUT A MINIMUM OF 1" TO ALLOW RETURN / EXHAUST AIRFLOW, SEE ARCHITECTURAL PLANS. 3030 PLAZA BONITA RD, SUITE
44"x28" SA

MTD AT 45°
M.C. SHALL PROVIDE FIXED CO2 GAS DETECTION SYSTEM EQUAL TO MODEL #RAD-0102. FURNISH AND INSTALL PER THE MFG. 1025
RECOMMENDATION AND IN ACCORDANCE WITH NFPA-55 AND CALIFORNIA FIRE CODE 2022 SECTION 5307.3.2.. FURNISH UNIT WITH NATIONAL CITY, CA 91950
3 ADDITIONAL DISPLAY AND VISUAL ALARM MOUNTED OUTSIDE ROOM WITH LOCKABLE PLEXIGLAS COVER OVER ALARM, SIGNAGE MOUNTED
"A" - SA ON DOOR INTO ROOM, CO2 SYSTEM EMERGENCY SHUTOFF SWITCH INTERLOCKED WITH SOLENOID VALVE AT CO2 TANK OUTLET, AND EF-2
"A"-SA
825 CFM MANUAL SHUTOFF SWITCH.
1000 CFM
24"x10" NK
24"x12" NK
MTD AT 45°
MTD AT 45°
4
ROUTE REFRIGERANT LINES FROM ACCU-1 OVER ON ROOF TO PIPE CURB, DOWN THRU ROOF INTO CHASE AND DOWN TO ROUND 1 SPACE,
AND OVER TO ASSOCIATED INDOOR UNIT A/C-1 IN A/V 126. COVER REFRIGERANT PIPE INSULATION WITH UV RESISTANT PVC JACKET OR ROUND1
PAINT WITH UV RESISTANT PVC COATING.
6"ø SA BOD: 13' - 5" ENTERTAINMENT
16"ø SA 20"ø SA
5 PIPE CURB EQUAL TO PATE MODEL #PCC WITH CAP COLLAR AND BOOT FITTING PACKAGE.
G G
BOD: 11' - 6"

"I" - TA 3"Ø COMBUSTION AIR INTAKE AND 3"Ø FLUE EXHAUST VENT UP FROM WATER HEATER AND UP THRU ROOF TO ROOF CONCENTRIC

10"ø SA
"I" - TA 6

8"ø SA
2050 CFM TERMINATION. FLASH AND SEAL AS REQUIRED. SEE PLUMBING PLANS AND SPECIFICATIONS.
1200 CFM 28"x28" NK
36"x18" NK 8"ø SA
"A"-SA
1000 CFM ABOVE DOOR
24"x12" NK 7 CLOTHES DRYER TO BE DUCTLESS MODEL. NO DRYER VENTING REQUIRED.
MTD AT 45° "E" - TA
VAV-4-4 VAV-4-3
44"x28" SA

TO 2050 CFM
"B" - SA NEW RTU TO BE INSTALLED ON CURB ADAPTER. SEE ROOFTOP UNIT SCHEDULE FOR ADDITIONAL REQUIREMENTS. RECONNECT EXISTING
FEC

VAV-4-1 22"x22" NK "B" - SA EMPLOYEE 150 CFM 8 GAS PIPING AND CONDENSATE. VERIFY GAS PIPE SIZE IS ADQEUATE FOR NEW RTU HEATING LOAD.
"B" - SA VAV-4-1 "A" - SA TO "B" - SA 250 CFM LOUNGE

S
6"ø NK
S

"B" - SA 600 CFM 200 CFM 250 CFM 8"ø NK

REF. 10"ø SA
600 CFM "E" - TA VESTIBULE VAV-4-4 135
14"ø NK 6"x8" NK 8"ø NK
14"ø NK 1200 CFM 101 9 NEW RTU TO BE INSTALLED ON EXISTING CURB. RECONNECT EXISTING GAS PIPING AND CONDENSATE.
20"x20" NK HIGH

10"x10" SA
TO VALUE
VAV-4-2 STORAGE CONNECT NEW SA AND RA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT
8"ø SA STORAGE/ 10 TRANSITION AND MODIFY EXISTING DUCTOWRK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION.
3070 SATURN ST. STE. 200
S 137 LACTATION
"A" - SA
"B" - SA BREA, CA 92821
250 CFM 134
2 100 CFM "A" - SA 8"ø NK

S
6"x6" NK CONNECT NEW SA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT TRANSITION
200 CFM
(2) "I" - TA OFFICE TO "B" - SA
11 AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION. EXISTING RA TO REMAIN
CONSULTANT
MTD ON BOD
VAV-4-2 6"x8" NK
400 CFM 136
VAV-4-3 "B" - SA 150 CFM WITH GALVANIZED WWM.
STAIR 3 36"x6" TA 36"x6" NK 250 CFM 6"ø NK
ELECTRICAL 8"ø NK
S-3 ABOVE DOOR 24"x6" TA
103 EXHAUST DUCT FROM EF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE THROUGH EXISTING CHASE.
H H 12 TRANSITION TO 28"x8" EA AND ROUTE OVER AT 13'9" A.F.F..
(2) "F" - TA
300 CFM
24"x6" NK EXHAUST DUCT INTAKE FROM EF-2 12"x12" EA ROUTED OVER AT 10'0" A.F.F.. ROUTE OVER TO CO2 TANK AND ROUTE DOWN TO 3-1/4" A.F.F..
ABOVE DOOR 13 EXHAUST OUTLET AT 12"x12" EA ROUTED OVER AT 10'0" A.F.F. TO EQUAL OR GREENHECK MODEL #BVE128 MOUNTED AT 10'0" A.F.F..
EXHAUST SYSTEM TO BE INSTALLED TO MEET CALIFORNIA FIRE CODE SECTION 5004.3.1 SYSTEM REQUIREMENTS. SEE DETAIL 15/M501.

EXHAUST CONDENSATE DUCT FROM KEF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE. TRANSITION
14 TO 14" EA GD AND ROUTE OVER AT 12'6" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED ACORDING TO IMC SECTION 506
FOR EXHAUST SYSTEMS SERVING TYPE I HOODS, SEE KITCHEN HOOD DETAIL FOR ADDITIONAL REQUIREMENTS. 4801 Henry St. 1751 Barlow St.
Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
MATCH LINE - SEE SHEET M-102

STAINLESS STEEL EXHAUST DUCT FROM KEF-2 ON ROOF ROUTED THROUGH EXISTING CHASE INTO ROUND 1 SPACE. TRANSITION FROM F 231-798-2981 F 231-947-1710
KEF-2 TO 14" R S/S EA AND ROUTE THROUGH CHASE, THEN OVER AT 14'2" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED REC #5002
15 ACORDING TO IMC SECTION 506 FOR EXHAUST SYSTEMS SERVING TYPE II HOODS AND SEALED WATER TIGHT. REFER TO FOORD SERVICE
EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

KITCHEN AND DISHWAHSER HOODS, HOOD FIRE SUPPRESSION SYSTEM, EXHAUST FANS, AND ALL ASSOCIATED EQUIPMENT ARE
16 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER UNLESS NOTED OTHERWISE, INSTALLED AND DUCTED BY MECHANICAL CONTRACTOR.
REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

COOLER EVAPORATOR, CONDENSING UNIT, AND ASSOCIATED REFRIGERANT PIPING FURNISHED BY FOOD SERVICE EQUIPMENT
17 CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. M.C. SHALL VERIFY EQUIPMENT LOCATIONS WITH FOOD SERVICE EQUIPMENT
SUPPLIER. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.
4 7 8

18 SEE DETAIL 15/M501 FOR OVERSIZE GRILLE CONSTUCTION.

RELEASE DATE

5 6 DATE DESCRIPTION
05-18-23 Permits

N
MECHANICAL FIRST FLOOR PLAN 'C' 07-21-23 Bids
SCALE: 1/8" = 1'-0"

PLAN

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:21:31 PM

MECHANICAL FIRST
FLOOR PLAN 'C'

M-103
KEY PLAN
PARADIGM DESIGN
MECHANICAL GENERAL NOTES
ARCHITECTS | ENGINEERS
A ALL WORK SHALL BE INSTALLED PER LOCAL, STATE, & FEDERAL CODES, RULES, ORDINANCES, AND REGULATIONS.

B REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

C ALL DUCT AND EQUIPMENT ELEVATIONS NOTED ON PLANS MEASURED FROM F.F. TO BOTTOM OF DUCT/EQUPMENT UNLESS
OTHERWISE NOTED.
D ALL DUCTWORK SHALL BE INSULATED ACCORDING TO WRITTEN SPECIFICATIONS UNLESS OTHERWISE NOTED.
Grand Rapids | Phoenix | Traverse City
E ALL DUCTWORK BEHIND GRILLES AND DIFFUSERS CONNECTIONS SHALL BE PAINTED FLAT BLACK. PAINT INSIDE OF DUCT
CONNECTIONS 2'-0" UP STREAM OF FIRST 90 DEGREE ELBOW. www.paradigmae.com

F ALL WORK SHOWN ON THIS PLAN TO BE COORDINATED WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
INSTALLATION.
G FIELD VERIFY THERMOSTAT AND SENSOR LOCATIONS WITH OWNER. INSTALL SENSORS AT A HEIGHT OF ±4'-0" A.F.F..
COORDINATE MECHANICAL SENSOR LOCATIONS WITH OTHER TRADES, INSTALL SENSORS ±6"-1'0" ABOVE LIGHTING
CONTROLS WHEN INSTALLED IN SIMILAR LOCATIONS.

H ALL DUCT DIMENSIONS ARE INSIDE DIMENSIONS.

I INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO COORDINATE THE EXACT ROUTING AND ELEVATION OF DUCTING
SYSTEMS. THIS CONTRACTOR SHALL INSTALL DUCTING SO AS TO NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
SYSTEMS.

MATCH LINE - SEE SHEET M-101


J ALL RECTANGULAR RETURN DUCTWORK SHALL HAVE 1" INTERNAL LINER, REFER TO SPECIFICATIONS.

K ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTS SHALL HAVE A BALANCING DAMPER NEAR MAIN. (INDIVIDUAL BRANCH
DAMPERS NOT SHOWN ON PLANS)
4 5 6 7 8
L ALL SUPPLY, RETURN AND EXHAUST DUCT ELBOWS SHALL BE SMOOTH RADIUS ELBOWS WITH THE INSIDE RADIUS SAME AS
WIDTH OF DUCT UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. ALL 90° MITERED ELBOWS SHALL HAVE
TURNING VANES.

M EXHAUST TERMINATIONS, PLUMBING VENTS, ETC. SHALL BE A MINIMUM OF 3FT. VERTICAL CLEARANCE ABOVE OR MINIMUM
OF 10FT. HORIZONTAL CLEARANCE FROM FENESTRATION OR EQUIPMENT OUTDOOR AIR INTAKES.

N ALL SERVICEABLE MECHANICAL EQUIPMENT INSTALLED ON ROOF SHALL BE INSTALLED A MINIMUM OF 10FT FROM ROOF
10 EDGE OR HAVE GUARD RAIL AS REQUIRED BY CODE. MAINTAIN MANUFACTURER RECOMMENDED CLEARANCES. PROJECT
A A O PAINT ALL VISIBLE GAS PIPING TO MATCH ADJACENT SURFACE. ALL GAS PIPING ROUTED ON ROOF SHALL BE PAINTED
YELLOW.

STORAGE (2) "I" - TA


"A" - SA
125 CFM
"A" - SA
100 CFM STAIR 1 STORAGE "A" - SA "A" - SA FIRE P ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE LOWER
ROUND1 -
400 CFM 6"x6" NK S-1 100 CFM 100 CFM RISER LEVEL SHALL BE BLACK IN COLOR UNLESS OTHERWISE NOTED. ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND
111
36"x6" NK
6"x6" NK
TO 8"x10" SA
112
6"x6" NK 6"x6" NK 113 GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE UPPER LEVEL SHALL BE WHITE IN COLOR UNLESS OTHERWISE
PLAZA BONITA

S
NOTED. DIFFUSERS / GRILLES SHALL BE ORDERED WITH FINISH SPECIFIED IN ASSOCIATED SCHEDULE. MECHANICAL
"A" - SA 8"x8" SA "A" - SA 8"x10" SA VAV-6-6 BOD: 11' - 7" "A" - SA CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED DUCTWORK SPECIFIED TO BE PAINTED FOR PREPARATION OF
42"x36" AL RA 100 CFM "A" - SA "A" - SA "A" - SA
125 CFM 50 CFM PAINTING BY PAINTING CONTRACTOR. ALL OILS, DUST AND DEBRIS SHALL BE REMOVED FROM SURFACES REQUIRING
6"x6" NK 100 CFM 100 CFM 125 CFM
6"x6" NK VAV-6-6 BOD: 13' - 1" 6"x6" NK 6"x6" NK
6"x6" NK
S 6"x6" NK
PAINTING. OBTAIN WRITTEN APPROVAL FROM MANUFACTURER BEFORE PAINTING DUCT WRAP INSUALTION. UL LISTING MUST
36"x6" TA TO NOT BE COVERED. PAINTING MUST OCCUR AFTER ROUGH DUCT INSPECTION. FIRE-WRAPPED GREASE DUCTS SHALL NOT BE
"E" - TA FEC 12"x10" TA 6"ø SA
VAV-6-1 VAV-6-1 PAINTED.
80"x36" RA OPENING IN
36"x6" TA 8"ø SA
700 CFM TOP OF 42"x36" AL RA
18"x10" NK "I" - TA DUCT. COVER WITH
16"x18" SA 16"x18" SA 14"ø SA 22"x20" SA
ELECTRICAL Q COORDINATE ALL ROOF PENETRATIONS WITH LANDLORD. ALL ROOF PENETRATIONS SHALL BE PERFORMED BY THE
700 CFM GALVANIZED WWM. 114 LANDLORD'S ROOFING CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
30"x8" NK
(2) "I" - TA
MTD AT 14'0"
A.F.F.
200 CFM (2) "I" - TA VAV-6-4 "A" - SA R ALL MECHANICAL DUCTS AND PIPING PENETRATING RATED ASSEMBLIES SHALL BE SEALED AND FIRE-STOPPED TO COMPLY
PARTY WITH LOCAL REGULATIONS. FOR REFERENCE, SHAFT WALL CONSTRUCTION IS 1-HR RATED FOR DUCTS ROUTED DOWN TO

16"x18" SA
12"x10" NK 400 CFM 125 CFM

8"x8" SA
"B" - SA LOWER LEVEL, DUCT PENETRATIONS INTO AND OUT OF SHAFTS SHALL BE SEALED AND FIRE STOPPED ACCORDINGLY PER
ROOM 1 BOD: 12' - 0" ABOVE DOOR 36"x6" NK 6"x6" NK
575 CFM CODE REQUIREMENTS.
110 ABOVE DOOR
"B" - SA 12"ø NK
600 CFM S ALL FLEX DUCTS SHALL TRANSITION FROM ROUND METAL DUCT TO SAME SIZE FLEX DUCT. PROVIDE PREFORMED 90°
"B" - SA TRANSITION ELBOW FOR FLEX DUCT CONNECTION INTO SUPPLY DIFFUSER INLET. 5'0" MAXIMUM LENGTH FOR EACH
12"ø NK "A" - SA
250 CFM TO INDIVIDUAL RUN OF FLEX DUCT.
6"ø NK 100 CFM
VAV-3-4 6"x6" NK T TEST AND BALANCE CONTRACTOR SHALL BE BROWARD COUNTY CERTIFIED.
TO
S

U FIELD VERIFY THAT ALL MECHANICAL WORK COMPLETED BY THE LANDLORD AS PART OF THE SHELL PACKAGE MATCHES
VAV-3-5 CONDITIONS SHOWN ON PLANS. TENANT MECHANICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND
B TO B

S
ENGINEER IF IT IS DETERMINED THAT MECHANICAL WORK BY THE LANDLORD DEVIATES SUBSTANTIALLY FROM PLANS.
S "A" - SA VAV-6-4
1075 CFM FREIGHT
30"x8" NK ELEVATOR
MTD AT 45° "A" - SA

22"x20" SA
ELEV-1
"I" - TA 100 CFM
TENANT

8"x8" SA
16"x14" SA
"B" - SA 6"x6" NK
600 CFM
"B" - SA 575 CFM
30"x8" NK
600 CFM 12"ø NK (2) "I" - TA MECHANICAL PLAN NOTES IMPROVEMENT
18"x12" SA

MTD AT 14'0"
12"ø NK 450 CFM

S
A.F.F.
30"x8" NK
LEGEND SYMBOL INDICATOR
28"x8" EA

"A" - SA TO ABOVE DOOR


1075 CFM
BOWLING VAV-6-2
30"x8" NK APPROACH FE 1 CONTROL DISPLAY FOR CENTRALIZED CONTROL OF RTU-1, 2, 3, 4, 5, & 6 SHALL BE LOCATED IN A.V. 115, SEE ROOFTOP UNIT SCHEDULE.
MTD AT 45° 119 TO 30"x8" TA
"B" - SA
A/C-1
2
A/C-1 2 DOOR(S) TO SPACE SHALL BE UNDERCUT A MINIMUM OF 1" TO ALLOW RETURN / EXHAUST AIRFLOW, SEE ARCHITECTURAL PLANS. 3030 PLAZA BONITA RD, SUITE
PINSETTER A.V.
250 CFM
(2) "I" - TA SERVICE 115 M.C. SHALL PROVIDE FIXED CO2 GAS DETECTION SYSTEM EQUAL TO MODEL #RAD-0102. FURNISH AND INSTALL PER THE MFG. 1025
6"ø NK "A" - SA RECOMMENDATION AND IN ACCORDANCE WITH NFPA-55 AND CALIFORNIA FIRE CODE 2022 SECTION 5307.3.2.. FURNISH UNIT WITH
"B" - SA 600 CFM NATIONAL CITY, CA 91950

24"x22" SA

T
600 CFM BOWLING 117 150 CFM 3 ADDITIONAL DISPLAY AND VISUAL ALARM MOUNTED OUTSIDE ROOM WITH LOCKABLE PLEXIGLAS COVER OVER ALARM, SIGNAGE MOUNTED
TO 18"x18" NK "B" - SA 6"x6" NK EF-2 13
12"ø NK LANES ABOVE DOOR ON DOOR INTO ROOM, CO2 SYSTEM EMERGENCY SHUTOFF SWITCH INTERLOCKED WITH SOLENOID VALVE AT CO2 TANK OUTLET, AND EF-2
VAV-3-1 575 CFM MANUAL SHUTOFF SWITCH.
118 12"ø NK VAV-6-2 TO
18"x18" TA
S

BOWLER'S VAV-6-3
S TO
VAV-3-6
SEATING
(2) "E"-RA
10500 CFM TOTAL 18"x18" TA
S "A" - SA
300 CFM
4
ROUTE REFRIGERANT LINES FROM ACCU-1 OVER ON ROOF TO PIPE CURB, DOWN THRU ROOF INTO CHASE AND DOWN TO ROUND 1 SPACE,
AND OVER TO ASSOCIATED INDOOR UNIT A/C-1 IN A/V 126. COVER REFRIGERANT PIPE INSULATION WITH UV RESISTANT PVC JACKET OR ROUND1
120 10"x8" SA PAINT WITH UV RESISTANT PVC COATING.
24"x48" NK 12"x6" NK ENTERTAINMENT
FEC

C BOD: 13' - 9" MTD AT 45° C

W
(2) "I" - TA 44"x22" RA 12"x12" SA 5 PIPE CURB EQUAL TO PATE MODEL #PCC WITH CAP COLLAR AND BOOT FITTING PACKAGE.
28"x8" EA 600 CFM
BRICK VENT
18"x18" NK VAV-6-3

D
18"x12" SA

7 GREENHECK
ABOVE DOOR
12 MODEL #BVE128
10"x14" SA

"A" - SA 3"Ø COMBUSTION AIR INTAKE AND 3"Ø FLUE EXHAUST VENT UP FROM WATER HEATER AND UP THRU ROOF TO ROOF CONCENTRIC
1075 CFM "B" - SA RTU-6 10 MOUNTED AT 6
"E" - TA 600 CFM
BOD: 12' - 5" 36"x26" SA TERMINATION. FLASH AND SEAL AS REQUIRED. SEE PLUMBING PLANS AND SPECIFICATIONS.
30"x8" NK 10'0" A.F.F.
700 CFM
MTD AT 45° 12"ø NK MECHANIC'S
18"x10" NK 12"x12" EA 116
"I" - TA
7 CLOTHES DRYER TO BE DUCTLESS MODEL. NO DRYER VENTING REQUIRED.
600 CFM
30"x8" NK BOD: 12' - 5"
VENDING 48"x20" RA
MTD AT 14'0" "B" - SA NEW RTU TO BE INSTALLED ON CURB ADAPTER. SEE ROOFTOP UNIT SCHEDULE FOR ADDITIONAL REQUIREMENTS. RECONNECT EXISTING
124 A.F.F. 575 CFM 8 GAS PIPING AND CONDENSATE. VERIFY GAS PIPE SIZE IS ADQEUATE FOR NEW RTU HEATING LOAD.
"A" - SA 12"ø NK RTU-4 10

24"x16" SA
1050 CFM "B" - SA
30"x8" NK 600 CFM BOD: 12' - 8" "F" - EA
36"x24" SA 365 CFM 9 NEW RTU TO BE INSTALLED ON EXISTING CURB. RECONNECT EXISTING GAS PIPING AND CONDENSATE.
MTD AT 45° 12"ø NK

BOD: 13' - 0 1/2"


CO2 12"x8" NK
MTD AT BOD
MATCH LINE - SEE SHEET M-101

1-1/2" G "A" - SA "A" - SA "A" - SA "A" - SA 1-1/2" G

48"x20" RA
3-1/4" A.F.F. CONNECT NEW SA AND RA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT
1175 CFM 1150 CFM 1150 CFM 1150 CFM (2) "I" - RA 10 TRANSITION AND MODIFY EXISTING DUCTOWRK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION.
3070 SATURN ST. STE. 200
24"x12" NK 24"x12" NK 24"x12" NK 24"x12" NK VAV-6-5 12000 CFM 3 BREA, CA 92821
32"x8" SA

MTD AT 45° MTD AT 45° MTD AT 45° MTD AT 45° 48"x36" & 36"x36"
NK JOINED TO CONNECT TO
CONNECT NEW SA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT TRANSITION
16"x16" SA 26"x16" SA MTD AT 11'6" EXISTING GAS PIPING.
11 AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION. EXISTING RA TO REMAIN
CONSULTANT
A.F.F. FE ROUTE OVER AS HIGH
S AS POSSIBLE. WITH GALVANIZED WWM.
D D
S TO TO S VAV-4-5 EXHAUST DUCT FROM EF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE THROUGH EXISTING CHASE.
TO 12
24X48

VAV-4-6 VAV-6-5 14"ø SA VAV-4-8 TRANSITION TO 28"x8" EA AND ROUTE OVER AT 13'9" A.F.F..

S
TO 18 EXHAUST DUCT INTAKE FROM EF-2 12"x12" EA ROUTED OVER AT 10'0" A.F.F.. ROUTE OVER TO CO2 TANK AND ROUTE DOWN TO 3-1/4" A.F.F..
VAV-4-5 13 EXHAUST OUTLET AT 12"x12" EA ROUTED OVER AT 10'0" A.F.F. TO EQUAL OR GREENHECK MODEL #BVE128 MOUNTED AT 10'0" A.F.F..

36"x24" SA
24X48

"A" - SA "A" - SA "A" - SA


425 CFM 425 CFM EXHAUST SYSTEM TO BE INSTALLED TO MEET CALIFORNIA FIRE CODE SECTION 5004.3.1 SYSTEM REQUIREMENTS. SEE DETAIL 15/M501.
450 CFM
"B" - SA 24"x12" NK 24"x12" NK 24"x12" NK
300 CFM MTD AT 45° MTD AT 45° EXHAUST CONDENSATE DUCT FROM KEF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE. TRANSITION
SEATING MTD AT 45°
24X48

8"ø NK 14 TO 14" EA GD AND ROUTE OVER AT 12'6" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED ACORDING TO IMC SECTION 506
131 FOR EXHAUST SYSTEMS SERVING TYPE I HOODS, SEE KITCHEN HOOD DETAIL FOR ADDITIONAL REQUIREMENTS. 4801 Henry St. 1751 Barlow St.
28"x8" SA

Muskegon, MI 49441 Traverse City, MI 49686


VAV-4-8 T 231-798-4328 T 231-947-1707
STAINLESS STEEL EXHAUST DUCT FROM KEF-2 ON ROOF ROUTED THROUGH EXISTING CHASE INTO ROUND 1 SPACE. TRANSITION FROM F 231-798-2981 F 231-947-1710
BAR
24X48

"B" - SA KEF-2 TO 14" R S/S EA AND ROUTE THROUGH CHASE, THEN OVER AT 14'2" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED REC #5002
130 600 CFM 15 ACORDING TO IMC SECTION 506 FOR EXHAUST SYSTEMS SERVING TYPE II HOODS AND SEALED WATER TIGHT. REFER TO FOORD SERVICE
BILLIARDS 14"ø NK VESTIBULE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.
132 133

14"ø SA
D
TS14BLW

CH

KITCHEN AND DISHWAHSER HOODS, HOOD FIRE SUPPRESSION SYSTEM, EXHAUST FANS, AND ALL ASSOCIATED EQUIPMENT ARE
16 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER UNLESS NOTED OTHERWISE, INSTALLED AND DUCTED BY MECHANICAL CONTRACTOR.
MATCH LINE - SEE SHEET M-103 MATCH LINE - SEE SHEET M-103 REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.
D
CRC-63C

CH
D

COOLER EVAPORATOR, CONDENSING UNIT, AND ASSOCIATED REFRIGERANT PIPING FURNISHED BY FOOD SERVICE EQUIPMENT
17 CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. M.C. SHALL VERIFY EQUIPMENT LOCATIONS WITH FOOD SERVICE EQUIPMENT
SUPPLIER. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

18 SEE DETAIL 15/M501 FOR OVERSIZE GRILLE CONSTUCTION.

4 5 6 7 8
RELEASE DATE

DATE DESCRIPTION

N
MECHANICAL FIRST FLOOR PLAN 'D' 05-18-23 Permits
SCALE: 1/8" = 1'-0" 07-21-23 Bids
PLAN

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:21:43 PM

MECHANICAL FIRST
FLOOR PLAN 'D'

M-104
KEY PLAN
PARADIGM DESIGN
MECHANICAL GENERAL NOTES
ARCHITECTS | ENGINEERS
A ALL WORK SHALL BE INSTALLED PER LOCAL, STATE, & FEDERAL CODES, RULES, ORDINANCES, AND REGULATIONS.
L.1M.1 M B REFER TO WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

C ALL DUCT AND EQUIPMENT ELEVATIONS NOTED ON PLANS MEASURED FROM F.F. TO BOTTOM OF DUCT/EQUPMENT UNLESS
OTHERWISE NOTED.
D ALL DUCTWORK SHALL BE INSULATED ACCORDING TO WRITTEN SPECIFICATIONS UNLESS OTHERWISE NOTED.
4.1
4..1 4.1
4..1 Grand Rapids | Phoenix | Traverse City
E ALL DUCTWORK BEHIND GRILLES AND DIFFUSERS CONNECTIONS SHALL BE PAINTED FLAT BLACK. PAINT INSIDE OF DUCT
CONNECTIONS 2'-0" UP STREAM OF FIRST 90 DEGREE ELBOW. www.paradigmae.com

F ALL WORK SHOWN ON THIS PLAN TO BE COORDINATED WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
INSTALLATION.
G FIELD VERIFY THERMOSTAT AND SENSOR LOCATIONS WITH OWNER. INSTALL SENSORS AT A HEIGHT OF ±4'-0" A.F.F..
COORDINATE MECHANICAL SENSOR LOCATIONS WITH OTHER TRADES, INSTALL SENSORS ±6"-1'0" ABOVE LIGHTING
CONTROLS WHEN INSTALLED IN SIMILAR LOCATIONS.

H ALL DUCT DIMENSIONS ARE INSIDE DIMENSIONS.

I INSTALLING CONTRACTOR SHALL USE EXTREME CAUTION TO COORDINATE THE EXACT ROUTING AND ELEVATION OF DUCTING
SYSTEMS. THIS CONTRACTOR SHALL INSTALL DUCTING SO AS TO NOT INTERFERE WITH THE REMOVAL AND/OR SERVICING OF
SYSTEMS.

J ALL RECTANGULAR RETURN DUCTWORK SHALL HAVE 1" INTERNAL LINER, REFER TO SPECIFICATIONS.

K ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTS SHALL HAVE A BALANCING DAMPER NEAR MAIN. (INDIVIDUAL BRANCH
DAMPERS NOT SHOWN ON PLANS)

L ALL SUPPLY, RETURN AND EXHAUST DUCT ELBOWS SHALL BE SMOOTH RADIUS ELBOWS WITH THE INSIDE RADIUS SAME AS
WIDTH OF DUCT UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. ALL 90° MITERED ELBOWS SHALL HAVE
5.1 5.1 TURNING VANES.

M EXHAUST TERMINATIONS, PLUMBING VENTS, ETC. SHALL BE A MINIMUM OF 3FT. VERTICAL CLEARANCE ABOVE OR MINIMUM
OF 10FT. HORIZONTAL CLEARANCE FROM FENESTRATION OR EQUIPMENT OUTDOOR AIR INTAKES.

N ALL SERVICEABLE MECHANICAL EQUIPMENT INSTALLED ON ROOF SHALL BE INSTALLED A MINIMUM OF 10FT FROM ROOF
EDGE OR HAVE GUARD RAIL AS REQUIRED BY CODE. MAINTAIN MANUFACTURER RECOMMENDED CLEARANCES. PROJECT
O PAINT ALL VISIBLE GAS PIPING TO MATCH ADJACENT SURFACE. ALL GAS PIPING ROUTED ON ROOF SHALL BE PAINTED
YELLOW.

P ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE LOWER
ROUND1 -
LEVEL SHALL BE BLACK IN COLOR UNLESS OTHERWISE NOTED. ALL EXPOSED DUCTWORK, DIFFUSERS / GRILLES, AND
4 5 ACCU-1
GENERAL HVAC LOCATED IN OPEN CEILING AREAS IN THE UPPER LEVEL SHALL BE WHITE IN COLOR UNLESS OTHERWISE
NOTED. DIFFUSERS / GRILLES SHALL BE ORDERED WITH FINISH SPECIFIED IN ASSOCIATED SCHEDULE. MECHANICAL
PLAZA BONITA
CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED DUCTWORK SPECIFIED TO BE PAINTED FOR PREPARATION OF
PAINTING BY PAINTING CONTRACTOR. ALL OILS, DUST AND DEBRIS SHALL BE REMOVED FROM SURFACES REQUIRING
PAINTING. OBTAIN WRITTEN APPROVAL FROM MANUFACTURER BEFORE PAINTING DUCT WRAP INSUALTION. UL LISTING MUST
NOT BE COVERED. PAINTING MUST OCCUR AFTER ROUGH DUCT INSPECTION. FIRE-WRAPPED GREASE DUCTS SHALL NOT BE
PAINTED.
12
EF-1 Q COORDINATE ALL ROOF PENETRATIONS WITH LANDLORD. ALL ROOF PENETRATIONS SHALL BE PERFORMED BY THE
6.1 6.1 LANDLORD'S ROOFING CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.

R ALL MECHANICAL DUCTS AND PIPING PENETRATING RATED ASSEMBLIES SHALL BE SEALED AND FIRE-STOPPED TO COMPLY
WITH LOCAL REGULATIONS. FOR REFERENCE, SHAFT WALL CONSTRUCTION IS 1-HR RATED FOR DUCTS ROUTED DOWN TO
LOWER LEVEL, DUCT PENETRATIONS INTO AND OUT OF SHAFTS SHALL BE SEALED AND FIRE STOPPED ACCORDINGLY PER
CODE REQUIREMENTS.

S ALL FLEX DUCTS SHALL TRANSITION FROM ROUND METAL DUCT TO SAME SIZE FLEX DUCT. PROVIDE PREFORMED 90°
TRANSITION ELBOW FOR FLEX DUCT CONNECTION INTO SUPPLY DIFFUSER INLET. 5'0" MAXIMUM LENGTH FOR EACH
INDIVIDUAL RUN OF FLEX DUCT.
T TEST AND BALANCE CONTRACTOR SHALL BE BROWARD COUNTY CERTIFIED.

U FIELD VERIFY THAT ALL MECHANICAL WORK COMPLETED BY THE LANDLORD AS PART OF THE SHELL PACKAGE MATCHES
CONDITIONS SHOWN ON PLANS. TENANT MECHANICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND

4'-2"
RTU-1

4'-7"
9
9 RTU-3 EX 2" G FROM BELOW
ENGINEER IF IT IS DETERMINED THAT MECHANICAL WORK BY THE LANDLORD DEVIATES SUBSTANTIALLY FROM PLANS.

6.8 6.8 14 KEF-1


EX 1" G
6 R
6.9
6.2 6.9
6.2
8
TENANT

EX 2" G
RTU-6
7.1 7.1
3'-8"
MECHANICAL PLAN NOTES IMPROVEMENT
15 KEF-2 EX 1" G
R 2'-3 15/16"
LEGEND SYMBOL INDICATOR

EX 1" G
1N 1N R 1 CONTROL DISPLAY FOR CENTRALIZED CONTROL OF RTU-1, 2, 3, 4, 5, & 6 SHALL BE LOCATED IN A.V. 115, SEE ROOFTOP UNIT SCHEDULE.

EX 1-1/2" G 2 DOOR(S) TO SPACE SHALL BE UNDERCUT A MINIMUM OF 1" TO ALLOW RETURN / EXHAUST AIRFLOW, SEE ARCHITECTURAL PLANS. 3030 PLAZA BONITA RD, SUITE
M.C. SHALL PROVIDE FIXED CO2 GAS DETECTION SYSTEM EQUAL TO MODEL #RAD-0102. FURNISH AND INSTALL PER THE MFG. 1025

EX 1-1/2" G
RECOMMENDATION AND IN ACCORDANCE WITH NFPA-55 AND CALIFORNIA FIRE CODE 2022 SECTION 5307.3.2.. FURNISH UNIT WITH NATIONAL CITY, CA 91950
3 ADDITIONAL DISPLAY AND VISUAL ALARM MOUNTED OUTSIDE ROOM WITH LOCKABLE PLEXIGLAS COVER OVER ALARM, SIGNAGE MOUNTED
9 RTU-2 ON DOOR INTO ROOM, CO2 SYSTEM EMERGENCY SHUTOFF SWITCH INTERLOCKED WITH SOLENOID VALVE AT CO2 TANK OUTLET, AND EF-2
MANUAL SHUTOFF SWITCH.
8 RTU-4
ROUTE REFRIGERANT LINES FROM ACCU-1 OVER ON ROOF TO PIPE CURB, DOWN THRU ROOF INTO CHASE AND DOWN TO ROUND 1 SPACE,
ROUND1

EX 3/4" G
2N 2N 4 AND OVER TO ASSOCIATED INDOOR UNIT A/C-1 IN A/V 126. COVER REFRIGERANT PIPE INSULATION WITH UV RESISTANT PVC JACKET OR
PAINT WITH UV RESISTANT PVC COATING.
ENTERTAINMENT
8 RTU-5 5 PIPE CURB EQUAL TO PATE MODEL #PCC WITH CAP COLLAR AND BOOT FITTING PACKAGE.
8.1 8.1 EX 1" G 3'-2"
2'-5" R
R
8.2 8.2 3"Ø COMBUSTION AIR INTAKE AND 3"Ø FLUE EXHAUST VENT UP FROM WATER HEATER AND UP THRU ROOF TO ROOF CONCENTRIC
6

EX 1" G
2'-7 1/2" TERMINATION. FLASH AND SEAL AS REQUIRED. SEE PLUMBING PLANS AND SPECIFICATIONS.
R EX 3/4" G

2'-5 5/32"
8.3 8.3

3'-8"
7 CLOTHES DRYER TO BE DUCTLESS MODEL. NO DRYER VENTING REQUIRED.

NEW RTU TO BE INSTALLED ON CURB ADAPTER. SEE ROOFTOP UNIT SCHEDULE FOR ADDITIONAL REQUIREMENTS. RECONNECT EXISTING
8 GAS PIPING AND CONDENSATE. VERIFY GAS PIPE SIZE IS ADQEUATE FOR NEW RTU HEATING LOAD.

9 NEW RTU TO BE INSTALLED ON EXISTING CURB. RECONNECT EXISTING GAS PIPING AND CONDENSATE.

CONNECT NEW SA AND RA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT
10 TRANSITION AND MODIFY EXISTING DUCTOWRK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION.
3070 SATURN ST. STE. 200
BREA, CA 92821
CONNECT NEW SA TO EXISTING SA AND RA DROPS. ROUTE OVER TO TAGGED HEIGHT AT DROPS. COORDINATE ANGLE OF DUCT TRANSITION
9.1 9.1 11 AND MODIFY EXISTING DUCTWORK AS REQUIRED TO ALLOW FOR HORIZONTAL ROUTING AT SPECIFIED ELEVATION. EXISTING RA TO REMAIN
CONSULTANT
WITH GALVANIZED WWM.

EXHAUST DUCT FROM EF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE THROUGH EXISTING CHASE.
12 TRANSITION TO 28"x8" EA AND ROUTE OVER AT 13'9" A.F.F..

EXHAUST DUCT INTAKE FROM EF-2 12"x12" EA ROUTED OVER AT 10'0" A.F.F.. ROUTE OVER TO CO2 TANK AND ROUTE DOWN TO 3-1/4" A.F.F..
13 EXHAUST OUTLET AT 12"x12" EA ROUTED OVER AT 10'0" A.F.F. TO EQUAL OR GREENHECK MODEL #BVE128 MOUNTED AT 10'0" A.F.F..
EXHAUST SYSTEM TO BE INSTALLED TO MEET CALIFORNIA FIRE CODE SECTION 5004.3.1 SYSTEM REQUIREMENTS. SEE DETAIL 15/M501.

EXHAUST CONDENSATE DUCT FROM KEF-1 ON ROOF ROUTED FROM EXHAUST FAN DUCT CONNECTION INTO ROUND 1 SPACE. TRANSITION
14 TO 14" EA GD AND ROUTE OVER AT 12'6" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED ACORDING TO IMC SECTION 506
FOR EXHAUST SYSTEMS SERVING TYPE I HOODS, SEE KITCHEN HOOD DETAIL FOR ADDITIONAL REQUIREMENTS. 4801 Henry St. 1751 Barlow St.
Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
STAINLESS STEEL EXHAUST DUCT FROM KEF-2 ON ROOF ROUTED THROUGH EXISTING CHASE INTO ROUND 1 SPACE. TRANSITION FROM F 231-798-2981 F 231-947-1710
KEF-2 TO 14" R S/S EA AND ROUTE THROUGH CHASE, THEN OVER AT 14'2" A.F.F.. EXHAUST DUCT SHALL BE CONSTRUCTED AND INSTALLED REC #5002
15 ACORDING TO IMC SECTION 506 FOR EXHAUST SYSTEMS SERVING TYPE II HOODS AND SEALED WATER TIGHT. REFER TO FOORD SERVICE
EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

10.1 10.1 KITCHEN AND DISHWAHSER HOODS, HOOD FIRE SUPPRESSION SYSTEM, EXHAUST FANS, AND ALL ASSOCIATED EQUIPMENT ARE
16 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER UNLESS NOTED OTHERWISE, INSTALLED AND DUCTED BY MECHANICAL CONTRACTOR.
REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

COOLER EVAPORATOR, CONDENSING UNIT, AND ASSOCIATED REFRIGERANT PIPING FURNISHED BY FOOD SERVICE EQUIPMENT
17 CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. M.C. SHALL VERIFY EQUIPMENT LOCATIONS WITH FOOD SERVICE EQUIPMENT
SUPPLIER. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS.

18 SEE DETAIL 15/M501 FOR OVERSIZE GRILLE CONSTUCTION.

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids
11.1 11.1

L.1M.1 M

N
MECHANICAL ROOF PLAN
SCALE: 3/32" = 1'-0"

PLAN
PROJECT

2112128GR
SHEET
7/21/2023 3:51:51 PM

MECHANICAL ROOF PLAN

M-105
HURRICANE HOLD DOWN CLIPS
WITH 16 GAUGE STIFFNERS
WIDTH WELDED TO ROOF CURB BY CURB CURB - SHALL BE PARADIGM DESIGN
MANUFACTURER @ 2'-0" CENTERS WELDED CONTINUOUS
EXHAUST FAN, SEE SCHED. MIN. (2) STRAPS PER SIDE. TO EXHAUST DUCT ARCHITECTS | ENGINEERS

DEPTH
NEOPRENE GASKET.
D

W W FLASHING AND
COUNTER FLASHING. EA DUCT
THROUGH ROOF
INSULATED ROOF CURB.
SUSPEND DRIP PAN SECURE TIE DOWN STRAPS TO
MEMBRANE ROOFING. FROM STRUCTURE AS CURB WITH (2) #14 TEK SCREWS
Grand Rapids | Phoenix | Traverse City
REQUIRED. www.paradigmae.com
5/16" SELF DRILLING SCREW ON ENCLOSE IN INDIVIDUAL FIRE
EACH SIDE AT CENTER OF UNIT. SECURE HOLD DOWN SECURE HOLD DOWN TO UNIT RATED SHAFT ENCLOSURE OR
L
MAXIMUM 8" FASTENER SPACING. TO CURB WITH (8) # WITH (4) #10x1/2" TEK SCREWS GREASE DUCT FIRE WRAP WITH UL
R1

FRONT VIEW SIDE VIEW 10x1/2" TEK SCREWS


USE ADDITIONAL FASTENERS TO APPROVED DUCT INSULATION.
SATISFY. CENTER FASTENERS 24"x24"x3" DEEP FIRE RESISTANCE RATING NOT
ON FLANGE. DRIP PAN (ONLY LESS THAN HIGHEST RATED
TYPICAL ELBOW IF SPECIFIED) PENETRATION AND NOT LESS
ROOF DECK. WOOD BLOCKING
G2 GREASE GUARD ROOFTOP
R2

BY MECH. CONTR. THAN 1 HOUR RATING AS


45° REQUIRED BY CODE. DEFENSE SYSTEM INSTALLED ON
STRUCTURAL ANGLE SUPPORT ROOF AROUND EXHAUST FAN CURBS,
NOTES:
BY STRUCTURAL TRADES. REFER TO FOOD SERVICE EQUIPMENT
16 GAUGE CURB TIE DOWN
NOTES: 16 GA. OR 18 GA. S/S SUPPLIER. PLANS.
45° 1. ALL SQUARE OR RECTANGULAR ELBOWS SHALL HAVE ONE OF THE TWO STRAPS @ 2'-0" CENTERS
TYPES OF TURNING VANES SHOWN. SINGLE VANE ELBOWS WILL NOT BE BACKDRAFT MIN. (2) STRAPS PER SIDE EXHAUST GREASE DUCT
PERMITTED ONLY ON RADIUS ELBOWS FOR ALL DUCTS LESS THAN 12" DAMPER. ROOF JOIST. 1. ALL PRODUCTS SHALL BE CONTINUOUSLY WELDED
WIDE. APPROVED FOR USE WITHIN AS REQUIRED BY CODE.
ACOUSTICALLY LINED HURRICANE AREAS.
DIMENSIONS: DUCT DROP.
W = 1.14" 2. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS REQUIRED.
ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR EXHAUST EXHAUST AIR DUCT 2. DOWNBLAST EXHAUST FAN COORDINATE HOOD
D = 2.125" SECURE TIE DOWN STRAPS TO
OR RETURN DUCT MAY BE MADE RADIUS ELBOWS PROVIDED SPACE PERMITS SEE PLANS FOR SIZES. SHOWN. DETAIL SIMILAR FOR SUPPORT REQUIREMENTS
R1 = 1.00" ANGLE WITH (2) #14 TEK
RADIUS INSTALLATION. UPBLAST EXHAUST FAN. WITH KITCHEN EQUIPMENT
R2 = 2.00" SCREWS
SUPPLIER AND STRUCTURAL
3. ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR SUPPLY DUCT ENGINEER.
MAY BE MADE RADIUS ELBOWS PROVIDED SPACE PERMITS RADIUS INSTALLATION, ANGLE IRON FRAMING
* SMALL DOUBLE VANE ELBOW. AND/OR THERE IS NOT AN OUTLET OR TAKEOFF WITHIN 5 DIAMETERS OF THE
BY GENERAL CONTRACTOR.
USE FOR ELBOWS UP TO 36" DOWNSTREAM SIDE OF THE ELBOW.
IN WIDTH AND/OR DEPTH. EXHAUST HOOD
PROJECT
2 ROOF EXHAUST FAN DETAIL
M-501 NOT TO SCALE

1 SQUARE OR RECTANGULAR ELBOW WITH TURNING VANES


ROUND1 -
M-501 NOT TO SCALE
PLAZA BONITA
INSULATED DUCTWORK BY
1" THICK, FIBERGLASS MECH. CONTR.
ELBOW, SUSPEND
FROM STRUCTURE.

12"x NECK SIZE


HOLD DOWN CLAMP ENLARGED RTU CURB DETAIL
NO SCALE
NECK SIZE 18" MIN.

FACTORY INSTALLED ECONOMIZER

1"
MECH. CONTR. SHALL OPEN UP
S OFFSET DUCTWORK AS REQUIRED ECONOMIZER PER MANUFACTORY
NE
. LI NOTES
:

3"
TO RUN THRU WEB OF JOIST ROOF TOP A.C. UNIT INSTRUCTIONS.
F RIG GIRDER FIELD VERIFY CONDITION
E
S S-R OFFSET BOTH DUCTS EQUALLY 1. ALL FLASHING AT ROOF PENETRATION TO BE IN ACCORDANCE WITH ROOF MEMBRANE MANUFACTURER AND ARCHITECTURAL
R LE CLG. ROOF CURB INSULATION SPECIFICATION.
1/4" THICK RUBBER MAT 3' 0 PAINT INSIDE FLAT BLACK FURNISHED AND INSTALLED
BY MECH. CONTR.
2. MAINTAIN CODE REQUIRED 10'-0" MINIMUM SEPARATION EQUIPMENT OUTDOOR AIR INTAKES AND HOOD EXHAUST FANS.
NOTE: MAY USE IN LIEU OF PILLOW
ROOF CURB FURNISHED BY OWNER. EXHAUST FANS SHALL BE A MINIMUM OF 10'-0" FROM EDGE OF WALL.
BLOCK PIPESTAND NOTED ON SHEET RUBBER SUPPORT WITH 14
M-107 IF APPROVED BY MIKE BLECHER GAUGE GALVANIZED STEEL ASSEMBLED AND INSTALLED BY MECH.
3. SLOPE ALL HORIZONTAL GREASE DUCTS A MINIMUM OF 1/4" PER FOOT BACK TOWARDS THE HOOD.
AND THE LANDLORD'S ROOFING
CONTRACTOR.
CHANNEL. EQUAL TO MI-
FAB C SERIES 6 RETURN AIR GRILLE BOOT DETAIL ROOF
CONTR.
SEE CURB DETAIL, THIS SHEET.
M-501 NOT TO SCALE 4. PROVIDE GREASE DUCT CLEANOUTS AND ACCESS PANELS AS REQUIRED BY CODE IN ACCORDANCE WITH IMC SECTION 506.
PROVDE SIGN AT EACH ACCESS PANEL STATING "ACCESS PANEL - DO NOT OBSRUCT" PER NFPA-96.
TENANT
CANVAS CONNECTION
5. PRIOR TO THE USE OR CONCEALMENT OF ANY PORTION OF A GREASE DUCT SYSTEM, A LEAKAGE TEST SHALL BE
IMPROVEMENT
5 REFRIGERANT PIPING SUPPORT DETAIL STEEL BEAM
INTERNALLY INSULATE REFER TO
PERFORMED IN THE PRESENCE OF THE CODE OFFICIAL.
M-501 NOT TO SCALE
SPECS. 6. GREASE DUCT SYSTEMS AND EXHAUST EQUIPMENT SERVING A TYPE I HOOD SHALL HAVE CLEARANCES TO COMBUSTIBLES
JOIST AS REQUIRED BY NFPA.

PIPE REDUCER FROM BRANCH


7. REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS. 3030 PLAZA BONITA RD, SUITE
PIPE SIZE TO UNIT CONNECTION 1025
SUPPORT SCHEDULE SIZE. PROVIDE AT UNIT.
GAS LINE TO UNIT NATIONAL CITY, CA 91950
6" PIPE SUPPORT
EQUAL TO MIRO, MODEL 6-RHA-12 3 ROOF CURB DETAIL 4 KITCHEN HOOD DETAIL
UNION M-501 NOT TO SCALE M-501 NOT TO SCALE
4" PIPE SUPPORT
EQUAL TO MIRO, MODEL 5-RHA-7 GAS COCK
DIRT LEG ROUND1
NOTE: OMIT DIRT LEG AT
1 1/2"-3" PIPE SUPPORT
EQUAL TO MIRO, MODEL 3-R-2
EXTERIOR OF THE BUILDING. ENTERTAINMENT
1/2"-1 1/4" PIPE SUPPORT
EQUAL TO MIRO, MODEL 3-R-2

ALL MODELS OF SUPPORTS SHALL BE FURNISHED STAINLESS CLAMP BY


WITH THE OPTIONAL STRAPS OVER THE PIPE AND PORTALS PLUS.
BOLTED TO SUPPORT. ALL METAL SHALL BE OF OW PORTALS PLUS KORAD
FL EPDM RUBBER PIPE
STAINLESS STEEL CONSTRUCTION. A IR LAMINATED
PIPE ABS PIPE PORTAL COVER. PORTAL CAP.
PIPE NOTE:
SUPPORTS SHALL BE FURNISHED AS THE
7 GAS CONNECTION DETAIL GASKETED FASTENERS
M-501 NOT TO SCALE
MANUFACTURERS STANDARD. ADJUST HEIGHT AS MIN.
REQUIRED FOR SITE CONDITIONS. TWO PER SIDE
FASTENERS MULTI-PLY MEMBRANE
APPROXIMATELY 8" BASE FLASHING (8" MIN.
PIPING SUPPORT FOR ALL PIPING O.C. HEIGHT). FEATHERED AT
RUNNING ON ROOF MIRO INDUSTRIES.
FIELD OF ROOF.
60 MIL UNCURED RUBBER FLASHING OR PORTALS PLUS
MFG'S. OPTIONAL SUPPORT PAD. PIPE
PORTAL CURB CANT
STYLE RC-2A (14" 3070 SATURN ST. STE. 200
HIGH). BREA, CA 92821

.
CONSULTANT
SUPPLY AIR MAIN IN
)M
DUCTWORK ( D2
RS
ETE
IAM
TD
8 PIPE ON ROOF DETAIL 4 DU
C ROOF DECK
M-501 NOT TO SCALE FASTEN PER ARCHITECT MULTI-PLY BUILT-UP ROOF
AIR REQUIREMENTS MEMBRANE
FL
OW LOOSE BATT INSULATION
INSULATION
GALVANIZED DUCT AND SUPPORT PIPES FROM
INSULATION AS SPECIFIED STRUCTURE
ON PLANS 4801 Henry St. 1751 Barlow St.
BRANCH DUCTWORK. Muskegon, MI 49441 Traverse City, MI 49686
3/8" CADMIUM PLATED T 231-798-4328 T 231-947-1707
THREADED ROD. SECURE F 231-798-2981 F 231-947-1710
TO STRUCTURE (2 TYP). 10 PIPE THROUGH ROOF DETAIL REC #5002

M-501 NOT TO SCALE


D1

D2 AIR
OW FL
FL 45° LEAD-IN. OW
A IR
VOLUME DAMPER

NOTE:
D1 NOT LESS THAN D2.

TWO HEAVY HEX NUTS, BACK


9 BRANCH CONNECTION DETAIL
M-501 NOT TO SCALE
TO BACK WITH WASHER (TYP
EACH CONNECTION) DIELECTRIC UNION
RELEASE DATE
AS
2" x 2" x 1/8" MIN REQUIRED DATE DESCRIPTION
(GALVANIZED) OPEN FOR DRAWTHRU
NOTES:
BOTTOM CORE OF TRUSS, 05-18-23 Permits
FOR BLOWTHRU PROVIDE 1 1/2" x 1 1/2" x 1/8" STEEL
1. CONTRACTOR SHALL VERIFY ALLOWABLE LOAD FOR EACH TRAPEZE HANGER PER THREADED CLEANOUT TYPICAL. 07-21-23 Bids
SMACNA HVAC DUCT CONSTRUCTION STANDARDS. ANGLE, TYPICAL.
FITTING WITH PLUG.
RTU OR 3/8" THREADED ROD,
2. CONTRACTOR MAY SUBSTITUTE STRAP HANGERS ON DUCTS LESS THAN 36" WIDE. AHU TYPICAL. VIBRATION ISOLATOR, TYPICAL.
DRAIN
PAN

11 RECTANGULAR DUCT TRAPEZE HANGER


B

NOT TO SCALE M.C. SHALL FURNISH AND


M-501 INSTALL 8x8 CONCRETE
PAVER BELOW CONDENSATE
TERMINATIONS ON ROOF.
A

TURN DOWN INLINE FAN.


1"MIN.
PRIMARY SUPPLY AIR/OUTSIDE AIR
RETURN/EXHAUST AIR
BLOWTHRU
PROVIDE SUPPORT A = GREATER OF 4" OR 1/2" PLUS AHU TOTAL FLEXIBLE CONNECTIONS ACOUSTICALLY LINED DUCT
45° AS REQUIRED. PRESSURE IN INCHES-WC. TYPICAL. MIN. 10 FT. BEFORE AND
AFTER EXHAUST FAN, SEE
DUCT TRANSITION, PLAN FOR SIZE, TYPICAL.
DRAWTHRU
D

B = GREATER OF 2" OR 1/2" PLUS AHU TOTAL TYPICAL.


PRESSURE IN INCHES-WC

DIMENSIONS: BALANCING DAMPER


(REQ'D IF BRANCH
D = 6"
SERVES A SINGLE AIR
DISTRIBUTION DEVICE)
13 UNIT COOLING COIL CONDENSATE DRAIN DETAIL 14 INLINE EXHAUST FAN DETAIL
M-501 NOT TO SCALE M-501 NOT TO SCALE PROJECT
BRANCH DUCT
15 OVERSIZE GRILLE CONSTRUCTION DETAIL
M-501 NOT TO SCALE 2112128GR
SHEET
7/21/2023 3:51:53 PM

MECHANICAL DETAILS
12 RECTANGULAR BRANCH DUCT DETAIL
M-501 NOT TO SCALE

M-501
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

ROOFTOP UNIT SCHEDULE EXHAUST FAN SCHEDULE


SUPPLY FAN COOLING (DX) HEATING (NATURAL GAS) SYMBOL CFM ESP RPM SONES BDD/CURB H.P. VOLTAGE WEIGHT REMARKS Grand Rapids | Phoenix | Traverse City
MINIMUM ENHANCED UNIT
SYMBOL MIN. MOTOR NOM. INPUT/OUTPUT VOLTAGE MCA MOCP CURB REMARKS EF-1 1400 0.5 1087 8.4 YES/YES 1/2 115 V / 1 PH 73 GREENHECK MODEL #G-140-VG. www.paradigmae.com
CFM ESP AMBIENT EDB EWB LDB LWB EER EAT LAT OA CFM DEHUMID. WEIGHT
CFM HP TONS MBH EF-2 400 0.3 1430 6.4 YES/NO 1/10 115 V / 1 PH 49 GREENHECK MODEL #SQ-90-VG.
RTU-1 16000 6000 1.0" 15.0 50.0 95.0 78.4 65.4 56.6 54.8 10.3 400 / 324 60.1 95.0 6000 460 V / 3 PH 126.0 150A NO EXISTING 6197 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC600C4L. KEF-1 2724 1.6 1250 16.9 YES/YES 2 208 V / 1 PH 150 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER. INSTALLED BY MECHANICAL CONTRACTOR.
RTU-2 16000 6000 1.0" 15.0 50.0 95.0 78.6 65.5 56.7 54.9 10.3 400 / 324 59.6 95.0 6000 460 V / 3 PH 126.0 150A NO EXISTING 6197 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC600C4L. KEF-2 525 0.4 1149 9.3 YES/YES 1/3 115 V / 1 PH 68 FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER. INSTALLED BY MECHANICAL CONTRACTOR.
RTU-3 15000 6000 1.25" 15.0 50.0 95.0 76.8 65.5 56.0 54.3 10.3 400 / 324 59.6 95.0 6000 460 V / 3 PH 126.0 150A NO EXISTING 6197 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC600C4L. NOTES:
RTU-4 10500 4200 1.25" 10.0 27.5 95.0 78.6 65.5 57.2 55.7 10.8 350 / 284 59.6 95.0 4200 460 V / 3 PH 82.0 100A NO ADAPTER 4738 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC330C4L. 1. EF-1 & 2 SHALL OPERATE CONTINUOUSLY DURING BUILDING OCCUPIED TIMES.
RTU-5 12000 4800 1.0" 15.0 40.0 95.0 78.4 65.4 55.5 53.9 11.1 400 / 324 60.1 95.0 4800 460 V / 3 PH 106.0 125A NO ADAPTER 5926 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC480C4L. 2. FOR EXHAUST FANS KEF-1, & 2, REFER TO FOOD SERVICE EQUIPMENT PLANS FOR EQUIPMENT SPECIFICATIONS AND ADDITIONAL REQUIREMENTS. KEF-1, & 2 SHALL BE INTERCONNECTED WITH KITCHEN
RTU-6 10500 3600 1.25" 10.0 27.5 95.0 77.5 64.8 56.5 54.9 10.8 350 / 284 62.7 95.0 3600 460 V / 3 PH 82.0 100A NO ADAPTER 4738 EQUAL TO TRANE PACKAGED ROOFTOP MODEL #YDC330C4L. HOOD CONTROL PANEL AND SHALL BE AUTOMATICALLY CONTROLLED TO OPERATE SIMULTANEOUSLY WITH THE OPERATION OF THE KITCHEN EXHAUST SYSTEM, REFER TO FOOD SERVICE EQUIPMENT
NOTES: PLANS AND ELECTRICAL PLANS.
1. ROOFTOP UNITS , ASSOCIATED GAS PIPING, CONDENSATE PIPING, SPECIFIED OPTIONS AND ACCESSORIES, ROOFTOP UNIT STARTUP AND CONTROLS AND ASSOCIATED CABLES, WIRING, ETC. PROVIDED AND INSTALLED BY TENANT. ROOFTOP UNIT STARTUP AND CONTROLS 3. ROOF CURBS AND EQUIPMENT TIE-DOWNS SHALL MEET ALL APPLICABLE WIND RESISTANCE CODE REQUIREMENTS.
AND ASSOCIATED CABLES, WIRING, ETC. PROVIDED AND INSTALLED BY TENANT. TENANT MC SHALL FIELD VERIFY THAT ROOFTOP UNIT SUPPLY AND RETURN DUCT LOCATIONS, ORIENTATIONS, ETC. PRIOR TO PURCHASING UNITS AND CURBS.
2. ALL RTU'S SHALL BE PROVIDED WITH FACTORY MOUNTED SMOKE DETECTOR IN SUPPLY AIR, WIRED TO FIRE ALARMS SYSTEM BY ELECTRICAL CONTRACTOR.
3. RTU-1, 2, & 5 SHALL BE SINGLE-ZONE VAV UNITS AND SHALL BE PROVIDED WITH FACTORY VFD AND BACNET CARD BY TENNANT. RTU- 3, 4, & 6 SHALL BE TRUE VAV UNIT AND SHALL BE PROVIDED WITH FACTORY VFD AND BACNET CARD BY TENNANT.
4. TENANT MECHANICAL CONTRACTOR SHALL PROVIDE TRANE CONTROL PANEL MODEL TRACER SC AND ASSOCIATED TRANE 10" CONTROL DISPLAY TO ALLOW FOR MONITORING, PROGRAMING, AND CONTROLS INTEGRATION OF ALL ROOFTOP UNIT. ANY ALTERNATIVE
CONTROL SYSTEMS MUST BE APPROVED BY TENANT ENGINEER. LOCATE CONTROL PANEL IN STORAGE AND CONTROL DISPLAY IN OFFICE. RTU-1, 2, 3, 4, 5, & 6 SHALL BE PROVIDED WITH REMOTE TEMPERATURE SENSOR LOCATED IN ASSOCIATED ZONE FOR EACH UNIT BY GRILLE AND DIFFUSER SCHEDULE
TENANT. REFER TO VARIABLE AIR VOLUME BOX SCHEDULE FOR RTU-3, 4 & 6 ZONE CONTROL DEVICE REQUIREMENTS. TYPE DESCRIPTION
PROJECT
5. ALL RTU'S SHALL BE PROVIDED WITH FACTORY DEMAND CONTROL VENTILATION INTERLOCKED TO CO2 SENSOR LOCATED IN COMMON RA DUCT FOR EACH UNIT. SURFACE MOUNTED SUPPLY AIR DIFFUSER. ALL ALUMINUM CONSTRUCTION. TWO SETS OF ADJUSTABLE BLADES AT 3/4" SPACING, FRONT
6. ALL RTU'S SHALL BE PROVIDED WITH REFERENCE ENTHALPY ECONOMIZER WITH ULTRA-LOW LEAK DAMPERS AND FAULT DETECTION AND DIAGNOSIS. OUTSIDE AIR/ECONOMIZER DAMPERS TO BE OPPOSED BLADE DAMPER TYPE.
7. ALL RTU'S SHALL BE PROVIDED WITH FACTORY 100% POWER EXHAUST WITH ULTRA-LOW LEAD EXHAUST DAMPERS.
"A" SET PARALLEL TO THE LONG DIMENSION, BACK PARALLEL TO THE SHORT DIMENSION, OPPOSED BLADE DAMPER. NECK SIZE AS NOTED ON
PLAN. FINISH SHALL BE BLACK OR AS SPECIFIED BY ARCHITECT. EQUAL TO TITUS 300FL.
ROUND1 -
8. ALL RTU'S SHALL BE PROVIDED WITH FACTORY MOUNTED AND POWERED CONVENIENCE OUTLET WITH NON-FUSED DISCONNECT.
9. RTU-4, 5, & 6 SHALL BE PROVIDED WITH INSULATED CURB ADAPTER AND RTU-1, 2, & 3 SHALL REUSE AND BE INSTALLED ON EXISTING ROOF CURB, FIELD VERIFY DIMENSIONS OF EXISTING ROOF CURB TO CONFIRM COMPATIBILITY WITH NEW UNITS PRIOR TO BIDDING. CEILING SUPPLY AIR DIFFUSER FOR MOUNTING IN T'BAR BORDER TYPE 3. 24X24 FACE, NECK SIZE AS NOTED ON PLAN. ALL STEEL
PLAZA BONITA
RTU-6 CURB ADAPTER SHALL SHIFT UNIT OVER TO ALLOW FOR MINIMUM 3'0" CLEARANCE. "B" CONSTRUCTION, ADJUSTABLE HORIZONTAL AND VERTICAL DISCHARGE, 4-WAY FLOW PATTERN UNLESS NOTED ON PLANS. FINISH SHALL
10. ALL RTU'S SHALL BE INSTALLED SUCH THAT ROOF CURBS AND EQUIPMENT TIE-DOWNS MEET ALL APPLICABLE WIND RESISTANCE CODE REQUIREMENTS. BE WHITE OR AS SPECIFIED BY ARCHITECT, FINISH TO MATCH CEILING COLOR. EQUAL TO TITUS TMSA.
11. ALL RTU'S SHALL BE PROVIDED WITH 2-STAGE LOW NATURAL GAS HEATING.
12. ALL RTU'S SHALL BE PROVIDED WITH STANDARD-EFFICIENCY DX COOLING WITH CORROSION PROTECTED COIL AND CONDENSATE OVERFLOW SWITCH. CEILING SUPPLY AIR DIFFUSER FOR MOUNTING IN T'BAR BORDER TYPE 3. 12X12 FACE, NECK SIZE AS NOTED ON PLAN. ALL STEEL
13. RTU-1, 2, 3, 4, & 5 SHALL BE PROVIDED WITH HINGED ACCESS DOORS. RTU-6 SHALL BE PROVIDED WITH STANDARD ACCESS PANELS. "C" CONSTRUCTION, ADJUSTABLE HORIZONTAL AND VERTICAL DISCHARGE, 4-WAY FLOW PATTERN UNLESS NOTED ON PLANS. FINISH SHALL
14. ALL RTU'S SHALL BE PROVIDED WITH FILTERS WITH MINIMUM MERV-14 RATING AND CLOGGED FILTER SWITCH. BE WHITE OR AS SPECIFIED BY ARCHITECT, FINISH TO MATCH CEILING COLOR. EQUAL TO TITUS TMSA.
15. ALL RTU'S SHALL BE PROVIDED WITH STAINLESS STEEL DRAIN PAN WITH CONDENSATE OVERFLOW SWITCH.
16. PIPE CONDENSATE FOR ALL ROOFTOP UNITS TO OUTDOORS, ONTO ROOF, OR TO NEAREST AVAILABLE DRAIN. SURFACE MOUNTED SUPPLY AIR DRUM LOUVER. ALL ALUMINUM CONSTRUCTION WITH PIVOTING BLADES, ROTATING DRUM, AND SPLIT
"D"
17. ALL OPTIONS AND ACCESSORIES THAT CAN BE INSTALLED IN FACTORY OR FIELD CAN BE MODIFIED TO THE OPPOSITE OF WHAT IS SPECIFIED IF LEAD TIME IMPROVES OR IS NOT IMPACTED BY THIS CHANGE. VANE. NECK SIZE AS NOTED ON PLANS. FINISH SHALL BE BLACK OR AS SPECIFIED BY ARCHITECT. EQUAL TO TITUS DL-SV.

CEILING MOUNTED RETURN AND EXHAUST AIR GRILLE FOR MOUNTING IN T'BAR BORDER TYPE 3. ALL ALUMINUM CONSTRUCTION WITH
"E" PERFORATED FACE. 24X24 FACE, NECK SIZE AS NOTED ON PLANS. FINISH SHALL BE WHITE OR AS SPECIFIED BY ARCHITECT, FINISH TO
MATCH CEILING COLOR. EQUAL TO TITUS 8F.
SURFACE MOUNTED RETURN, EXHAUST, AND TRANSFER AIR GRILLE. BORDER TYPE 1. ALL ALUMINUM CONSTRUCTION, 3/4" BLADE
VARIABLE AIR VOLUME BOX SCHEDULE "F" SPACING PARALLEL TO LONG DIMENSION WITH 35° FIXED DEFLECTION, OPPOSED BLADE DAMPER (DAMPER NOT REQUIRED ON TRANSFER
CFM DUCT INLET ELECTRIC REHEAT COIL GRILLES). NECK SIZE AS NOTED ON PLANS. FINISH SHALL BE WHITE OR AS SPECIFIED BY ARCHITECT. EQUAL TO TITUS 350FL. TENANT
SCHEDULE SERVES REMARKS
MIN MAX SIZE MBH KW TEMP RISE VOLTAGE "G" SAME AS TYPE "A" EXCEPT FINISH SHALL BE WHITE. IMPROVEMENT
VAV-3-1 GAME ROOM 4275 2235 24"x16" - - - - EQUAL TO TRANE MODEL #VCCF-24 VAV BOX. "H" SAME AS TYPE "B" EXCEPT SURFACE MOUNTING BOARDER TYPE 1.
VAV-3-2 GUEST CNTR, SNACK BAR, BAR 2250 1125 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX.
VAV-3-3 KITCHEN 2250 1350 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX. "I" SAME AS TYPE "F" EXCEPT FINISH SHALL BE BLACK.
VAV-3-4 PARTY RM 1 700 585 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. NOTES: 3030 PLAZA BONITA RD, SUITE
VAV-3-5 PARTY RM 2 700 540 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. 1. CONTRACTOR SHALL VERIFY DIFFUSER OR GRILLE FRAME WITH MOUNTING SURFACE. 1025
VAV-3-6 PARTY RM 3 700 525 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. 2. ALL VISIBLE SURFACE BEHIND DIFFUSER/GRILLE (INCLUDING DAMPERS) TO BE PAINTED FLAT BACK. NATIONAL CITY, CA 91950
VAV-3-7 PARTY RM 4 700 570 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. 3. BRANCH DUCTS SERVING DIFFUSER/GRILLE TO BE SAME SIZE AS THE DIFFUSER/GRILLE NECK SIZE, UNLESS OTHERWISE NOTED.
VAV-3-8 REDEMPTION STORE & STORAGE 1600 800 12 - - - - EQUAL TO TRANE MODEL #VCCF-12 VAV BOX. 4. PROVIDE EXTRA T'BAR FOR INSTALLATION OF 24X24 LAY-IN DIFFUSER AND GRILLES INTO 28X24 CEILING GRID AS REQUIRED.
VAV-3-9 RESTROOMS 925 462 10 37.6 11.0 35.0 460 V / 3 PH EQUAL TO TRANE MODEL #VCEF-10 VAV BOX WITH 2-STAGE ELECTRIC REHEAT.
VAV-3-10 PLUSH STORAGE 625 270 5 - - - - EQUAL TO TRANE MODEL #VCCF-05 VAV BOX. ROUND1
VAV-4-1 MAIN ENTRY VESTIBULE 1200 600 10 - - - - EQUAL TO TRANE MODEL #VCCF-10 VAV BOX. ENTERTAINMENT
VAV-4-2 STORAGE 100 50 4 - - - - EQUAL TO TRANE MODEL #VCCF-04 VAV BOX.
VAV-4-3 STORAGE & BREAKROOM 800 400 8 15.4 4.5 35.0 460 V / 3 PH EQUAL TO TRANE MODEL #VCEF-08 VAV BOX WITH 2-STAGE ELECTRIC REHEAT.
VAV-4-4 OFFICE & HIGH VALUE STORAGE 900 450 8 17.1 5.0 35.0 460 V / 3 PH EQUAL TO TRANE MODEL #VCEF-08 VAV BOX WITH 2-STAGE ELECTRIC REHEAT. SPLIT SYSTEM UNIT SCHEDULE
VAV-4-5 BILLIARDS 1300 800 10 - - - - EQUAL TO TRANE MODEL #VCCF-10 VAV BOX. NOMINAL INDOOR AIR CONDITIONER UNIT (A/C) OUTDOOR CONDENSING UNIT (ACCU)
VAV-4-6 SEATING 2550 1275 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX. SYMBOL COOLING CAPACITY REMARKS
VAV-4-7 GAME ROOM 2450 1225 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX. MODEL CLG MBH MCA MOCP VOLTAGE MODEL MCA MOCP SEER VOLTAGE WEIGHT
(TONS)
VAV-4-8 VESTIBULE 1200 600 10 - - - - EQUAL TO TRANE MODEL #VCCF-10 VAV BOX.
VAV-6-1 STORAGE & FIRE RISER 900 450 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. A/C-1 (INDOOR UNIT) 208 V / 1
2.0 PKA-A24KA7 24.0 1.0 15A DC24V PUY-A24NHA7 19 26A 21.4 151 EQUAL TO MITSUBISHI.
VAV-6-2 ELECTRICAL & AV 675 340 8 - - - - EQUAL TO TRANE MODEL #VCCF-08 VAV BOX. ACCU-1 (OUTDOOR UNIT) PH
VAV-6-3 MECHANIC'S ROOM 300 150 5 - - - - EQUAL TO TRANE MODEL #VCCF-05 VAV BOX. NOTES:
VAV-6-4 BOWLERS SEATING 3000 1500 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX. 1. TERMINAL UNIT'S POWER TO BE FED FROM ACCU-1 OUTDOOR UNIT.
VAV-6-5 BOWLING LANES 4625 2315 24"x16" - - - - EQUAL TO TRANE MODEL #VCCF-24 VAV BOX. 2. PROVIDE LOCKING BASE FOR WALL MOUNTED THERMOSTAT. LOCATE THERMOSTAT AT A HEIGHT OF ±4'-0" A.F.F., FIELD VERIFY THERMOSTAT LOCATION WITH OWNER.
VAV-6-6 STAIRS 200 100 4 - - - - EQUAL TO TRANE MODEL #VCCF-04 VAV BOX. 3070 SATURN ST. STE. 200
3. ROOF MOUNTED CONDENSING UNITS SHALL BE SECURED TO EQUIPMENT SUPPORTS SET ON UNCURED RUBBER ROOF MEMBRANE AS PER MANUFACTURER'S RECOMMENDATION.
VAV-6-7 PINSETTER SERVICE 2300 1150 14 - - - - EQUAL TO TRANE MODEL #VCCF-14 VAV BOX. BREA, CA 92821
4. REFRIGERANT PIPING FIELD SUPPLIED AND INSTALLED PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS FOR PROPER OIL RETURN. REFRIGERANT PIPING SHALL NOT EXCEED RECOMMENDED
NOTES: MAXIMUM LENGTH.
1. BOX LINER SHALL BE DOUBLE WALLED 1" THERMALLY AND ACOUSTICALLY LINED MATTE-FACED. NO EXPOSED INSULATION. 5. PIPE CONDENSATE DRAIN TO OUTDOORS, ONTO ROOF, OR TO NEAREST AVAILABLE DRAIN. PROVIDE CONDENSATE PUMP EQUAL TO LITTLE GIANT #VCMX-20UL.
2. VAV BOXES SHALL BE PROVIDED WITH FACTORY MOUNTED CONTROLS EQUAL TO TRANE UC210 CONTROLS. 6. ROOF MOUNTED CONDENSING UNITS SHALL MEET ALL APPLICABLE WIND RESISTANCE CODE REQUIREMENTS.
3. VAV BOXES SHALL BE PROVIDED WITH 24V TRANSFORMER AND FACTORY MOUNTED NON-FUSED DISCONNECT SWITCH. 7. PROVIDE OUTDOOR UNIT WITH WIND BAFFLES FOR LOW AMBIENT OPERATION.
4. VAV BOXES SHALL BE PROVIDED WITH FACTORY-WIRED DISCHARGE AIR TEMPERATURE SENSOR.
5. BRANCH DUCT SIZE SERVING VAV BOXES SHALL BE SAME SIZE AS INLET SIZE UNLESS NOTES OTHERWISE.
6. PROVIDE ADJUSTABLE SETPOINT ZONE SENSOR FOR EACH INDIVIDUAL VAV BOX LOCATED IN ASSOCIATED ZONE. BOX CONTROLLERS SHALL COMMUNICATE WITH RTU-3, 4 & 6 VIA THE CONTROL PANEL, SEE ROOFTOP UNIT
SCHEDULE.

HVAC DUCTWORK ABBREVIATIONS RELEASE DATE

DATE DESCRIPTION
SLOT DIFFUSER MANUAL SPLITTER
S AFF ABOVE FINISHED FLOOR EF EXHAUST FAN OA OUTSIDE AIR 05-18-23 Permits
07-21-23 Bids
SUPPLY AIR DIFFUSER A.H.J. AUTHORITY HAVING JURISDICTION EWC ELECTRIC WATER COOLER RA / RAD RETURN AIR / DUCT
14X20 DUCT SIZE, FIRST FIGURE
IS SIDE SHOWN
RETURN AIR DIFFUSER AL ACOUSTICALLY LINED EWT ENTERING WATER TEMPERATURE SA / SAD SUPPLY AIR / DUCT

AMERICAN SOCIETY OF EXIST. EXISTING SAN SANITARY SEWER


AL ACOUSTICAL LINING (AL) ASME
"A"-475-SA TYPE A SUPPLY AIR DIFFUSER MECHANICAL ENGINEERS
12" NK. WITH 475 CFM, 12" ROUND NECK SC SITE CONTRACTOR
BOD BOTTOM OF DUCT FCO FLOOR CLEAN OUT
R CHANGE IN ELEVATION,
20X14 SUPPLY AIR DUCT SECTION, RISE (R) DROP (D) FD FIRE DAMPER SP STATIC PRESSURE
FIRST FIGURE IS TOP BRITISH THERMAL
BTUH
UNITS PER HOUR
F.S.E.C. FOOD SERVICE EQUIPMENT CONTRACTOR SS SERVICE SINK
20X14 RETURN AIR DUCT SECTION,
FIRST FIGURE IS TOP STANDARD BRANCH, NO SPLITTER
CA COMBUSTION AIR
GD GREASE DUCT S/S STAINLESS STEEL
EXHAUST FAN CFM CUBIC FEET PER MINUTE
HP HORSE POWER ST STORM SEWER
ACOUSTICAL LINED RETURN AIR
DUCT WITH OPEN BELL MOUTH FITTING COND CONDENSATE HWR HOT WATER RETURN UH UNIT HEATER
VERTICAL FIRE DAMPER

CIRCUIT SETTER HWS HOT WATER SUPPLY UR URINAL


CSBV
FLEX CONNECTION BALANCING VALVE
MANUAL VOLUME DAMPER
V.D. I.E. INVERT ELEVATION V VENT
CU CONDENSING UNIT
TV T THERMOSTAT VTR VENT THRU ROOF
ELBOW WITH AERO DYNE HIGH LAT LEAVING AIR TEMPERATURE
EFFICIENT TURNING VANES CUH CABINET UNIT HEATER
T THERMOSTAT WITH GUARD WC WATER CLOSET PROJECT
LWT LEAVING WATER DAMPER
RECTANGULAR RADIUS ELBOW WITH C.W. COLD WATER WCO WALL CLEAN OUT
W S TEMPERATURE SENSOR
R=1.5 W OR GREATER.
R EA EXHAUST AIR
M.C. MECHANICAL CONTRACTOR
WWM 3/8x3/8 WELDED WIRE MESH 2112128GR
H HUMIDISTAT
EAT ENTERING AIR TEMPERATURE MD MOTORIZED DAMPER
GAS SHUT-OFF VALVE WS WORK SINK
SHEET
7/21/2023 3:51:53 PM

PIPE OR DUCT DROP CO CARBON DIOXIDE SENSOR


EC ELECTRICAL CONTRACTOR MP MEDIUM PRESSURE DUCT YCO YARD CLEAN OUT
MECHANICAL
SCHEDULES

M-601
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

PROJECT

2112128GR
SHEET
7/21/2023 3:51:55 PM

MECHANICAL TITLE 24
FORMS

M-602
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

PROJECT

2112128GR
SHEET
7/21/2023 3:51:57 PM

MECHANICAL TITLE 24
FORMS CONT.

M-603
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

PROJECT

2112128GR
SHEET
7/21/2023 3:51:59 PM

MECHANICAL TITLE 24
FORMS CONT.

M-604
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

TENANT
IMPROVEMENT

3030 PLAZA BONITA RD, SUITE


1025
NATIONAL CITY, CA 91950

ROUND1
ENTERTAINMENT

3070 SATURN ST. STE. 200


BREA, CA 92821

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

PROJECT

2112128GR
SHEET
7/21/2023 3:52:00 PM

MECHANICAL TITLE 24
FORMS CONT.

M-605
PARADIGM DESIGN
ARCHITECTS | ENGINEERS

Grand Rapids | Phoenix | Traverse City


www.paradigmae.com

PROJECT

ROUND1 -
PLAZA BONITA

MANDATORY MEASURES
110.1 HEATING AND COOLING EQUIPMENT EFFICIENCY PER 110.1 TENANT
EQUIPMENT SHALL MEET APPLICABLE EFFICIENCY REQUIREMENTS IN TABLE 110.2-A THROUGH 110.2K. IMPROVEMENT
120.4 DUCT INSULATION
PORTIONS OF SUPPLY- AND RETURN-AIR DUCTS CONVEYING HEATED OR COOLED AIR LOCATED IN ONE OR MORE OF THE FOLLOWING SPACES SHALL BE INSULATE...
•OUTDOORS
•IN A SPACE BETWEEN THE ROOF AND AN INSULATED CEILING
3030 PLAZA BONITA RD, SUITE
•IN A SPACE DIRECTLY UNDER A ROOF WITH FIXED VENTS OR OPENINGS TO THE OUTSIDE OR UNCONDITIONED SPACES
1025
•UNCONDITIONED SPACES, SUCH AS UNCONDITIONED CRAWLSPACE NATIONAL CITY, CA 91950
•PORTIONS OF SUPPLY-AIR DUCT THAT ARE NOT IN ONE OF THESE SPACES, INCLUDING DUCTS BURIED IN CONCRETE SLAB, SHALL BE INSULATED TO A...
120.4... AIR DUCT AND PLENUM SYSTEM DESIGN
120.4(b)1 FACTORY FABRICATED DUCT SYSTEMS MUST: ROUND1
•COMPLY WITH UL181 FOR DUCTS AND CLOSURE SYSTEMS AND LABELED AS COMPLYING WITH UL 181.
•ALL PRESSURE SENSITIVE TAPES, HEAT ACTIVATED TAPES, AND MASTICS USED IN MANUFACTURE OF RIGID FIBERGLASS DUCTS SHALL COMPLY WITH ...
ENTERTAINMENT
•ALL PRESSURE SENSITIVE TAPES, HEAT ACTIVATED TAPES, AND MASTICS USED IN MANUFACTURE OF FLEXIBLE DUCTS SHALL COMPLY WITH UL 181 AN...
•JOINTS AND SEAMS SHALL NOT BE SEALED WITH CLOTH BACK RUBBER ADHESIVE DUCT TAPES UNLESS COMBINED WITH MASTICS AND DRAWBANDS.
120.4(b)2 FIELD-FABRICATED DUCT SYSTEMS

•FACTORY-MADE RIGID FIBERGLASS AND FLEXIBLE DUCTS FOR FIELD-FABRICATED DUCT SYSTEMS SHALL COMPLY WITH UL 181. ALL CLOSURE SYSTEM...
•MASTIC SEALANTS SHALL
o COMPLY WITH APPLICABLE REQUIREMENTS OF UL 181, UL 181A, AND UL 181B AND BE NONTOXIC AND WATER RESISTANT.
o PASS ASTM C731 AND D2202, IF USED IN BUILDING INTERIOR.
o PASS ASTMC731, C732, AND D2202, IF USED ON EXTERIOR.
o SEALANTS AND MESHES SHALL BE RATED FOR EXTERIOR USE.
• PRESSURE SENSITIVE TAPES SHALL COMPLY WITH APPLICABLE REQUIREMENTS OF UL 181, UL 181A, AND UL 181B.
• JOINTS AND SEAMS SHALL NOT BE SEALED WITH CLOTH BACK RUBBER ADHESIVE DUCT TAPES UNLESS COMBINED WITH MASTICS AND DRAWBANDS. 3070 SATURN ST. STE. 200
• DRAWBANDS USED WITH FLEXIBLE DUCTS SHALL: BREA, CA 92821
oBE EITHER STAINLESS-STEEL WORM-DRIVE HOSE CLAMPS OR UV-RESISTANT NYLON DUCT TIES.
oHAVE A MINIMUM TENSILE STRENGTH RATING OF 150 LBS
oBE TIGHTENED AS RECOMMENDED BY THE MANUFACTURER.
•AEROSOL-SEALANT CLOSURES SHALL:
oMEET REQUIREMENTS OF UL 723 AND BE APPLIED ACCORDING TO MANUFACTURER SPECIFICATIONS.
oTAPES OR MASTICS USED IN COMBINATION WITH AEROSOL SEALING SHALL COMPLY WITH APPLICABLE REQUIREMENTS OF UL 181, UL 181A AND...
120.4(c) ALL DUCT INSULATION PRODUCT R-VALUES SHALL BE BASED ON INSULATION ONLY AND TESTED IN ACCORDANCE WITH ASTM C518 OR ASTM C177 AND...
120.4(d) INSTALLED THICKNESS OF DUCT INSULATION USED TO DETERMINE ITS R-VALUE SHALL BE DETERMINED AS FOLLOWS:
•DUCT BOARD, LINER, AND FACTORY MADE RIGIDS: USE NOMINAL INSULATION THICKNESS.
• DUCT WRAP: USE 75 PERCENT (25 PERCENT COMPRESSION) OF NOMINAL THICKNESS.
• FACTORY-MADE FLEXIBLE AIR DUCTS: DIVIDE THE DIFFERENCE BETWEEN THE ACTUAL OUTSIDE DIAMETER AND NOMINAL INSIDE DIAMETER BY TWO.

120.4(e) INSULATED FLEXIBLE DUCT PRODUCTS INSTALLED TO MEET THIS REQUIREMENT MUST INCLUDE LABELS (MAX INTERVALS OF 3 FT) SHOWING THERMAL...

120.4(f) INSULATION SHALL BE PROTECTED FROM DAMAGE BY SUNLIGHT, MOISTURE, EQUIPMENT MAINTENANCE AND WIND. CELLULAR FOAM INSULATION SHALL...

RELEASE DATE

DATE DESCRIPTION
05-18-23 Permits
07-21-23 Bids

PROJECT

2112128GR
SHEET
7/21/2023 3:52:01 PM

MECHANICAL TITLE 24
FORMS CONT.

M-606
ELECTRICAL DEVICE ELECTRICAL SYMBOL LEGEND
COLOR SCHEDULE SYMBOL DESCRIPTION MFG. DATA NOTES

OS WALL MOUNTED OCCUPANCY SWITCH LITHONIA #LIRW 120/277 WH MT. 46" A.F.F. TO CENTERLINE OF BOX
AREA DEVICE PLATE
3 THREE-WAY TOGGLE SWITCH SEE SPECS MT. 46" A.F.F. TO CENTERLINE OF BOX
ARCADE/GAME AREA GREY GREY

REDEMPTION SLAT WALLS WHITE WHITE SINGLE POLE TOGGLE SWITCH SEE SPECS MT. 46" A.F.F. TO CENTERLINE OF BOX
PARADIGM DESIGN
REDEMPTION GENERAL WHITE WHITE D DIMMER SWITCH SEE 6/E601, COORDINATE TYPE WITH LIGHTING FOR 0-10V MT. 46" A.F.F. TO CENTERLINE OF BOX
ARCHITECTS | ENGINEERS
REDEMPTION CEILING WHITE WHITE
L LOW VOLTAGE SWITCH SEE 7/E601 MT. 46" A.F.F. TO CENTERLINE OF BOX
KITCHEN WHITE WHITE
PP POWER PACK SEE SPECS (FOR SENSORS BELOW)
BAR GREY GREY
OS OCCUPANCY SENSOR SEE SPECS PROVIDE COMPLETE WITH POWER PACK RELAYS AS NEEDED
SNACK BAR GREY GREY
Grand Rapids | Phoenix | Traverse City
GUEST COUNTER WHITE WHITE www.paradigmae.com
OS OCCUPANCY SENSOR (WALL MOUNT) SEE SPECS PROVIDE COMPLETE WITH POWER PACK RELAYS AS NEEDED
ALCOVE GREY GREY

FAMILY TOILET BLACK BLACK C CONTACTOR SEE PLANS

JANITOR IVORY IVORY DUPLEX RECEPTACLE SEE SPECS MT. 18" A.F.F. TO BOTTOM OF BOX
WOMEN'S RESTROOM IVORY IVORY
DOUBLE DUPLEX RECEPTACLE SEE SPECS, NOTE WHERE CONTROLLED THE DEVICE MT. 18" A.F.F. TO BOTTOM OF BOX
SHALL HAVE PERMANENT MARKINGS PER NEC 406.3(E)
MEN'S RESTROOM BLACK BLACK
DUPLEX RECEPTACLE SPLIT WIRED SEE PLANS
OFFICE GREY GREY

EMPLOYEE LOUNGE GREY GREY GFI PROTECTED DUPLEX RECEPTACLE SEE SPECS GFI BY BREAKER WHERE NOT ACCESSIBLE

SAFE ROOM IVORY IVORY EWC ELECTRIC WATER COOLER RECEPTACLE SEE SPECS MT. 24" ABOVE FINISH FLOOR

KAROKE/PARTY ROOMS GREY GREY


WP WEATHER PROOF GFI RECEPTACLE SEE SPECS
BILLIARDS AREA GREY GREY DUPLEX CONVENIENCE OUTLET MTD. MT. 8" ABOVE COUNTER TO BOTTOM OF BOX, UNLESS
AC "ABOVE COUNTER" SEE SPECS NOTED OTHERWISE. SEE CABINET DRAWINGS.
VESTIBULE GREY GREY
DUPLEX RECEPTACLE ISOLATED GROUND SEE SPECS MT. 18" A.F.F. TO BOTTOM OF BOX
STORAGE ROOMS IVORY IVORY

MECHANICS ROOM GREY GREY SPECIAL RECEPTACLE SEE PLANS


PROJECT
WITHIN STRUCTURAL CEILING BLACK BLACK SPECIAL CONNECTION (HARDWIRE) SEE PLANS
BUS CORD DROP

OUTLETS IN TOE KICK


BLACK

BLACK
BLACK

BLACK
CS X NETWORK LIGHITNG CONTROL STATION REFER TO E601 AND CONTROL STATION SCHEDULE ROUND1 -
4 SQUARE BOX WITH SINGLE GANG PLASTER RING AND 3/4" C. MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
TELEPHONE OUTLET TO ACCESSIBLE CEILING. OTHERWISE. COORDINATE WITH AV CONTRACTOR
PLAZA BONITA
DATA OUTLET 4 SQUARE BOX WITH SINGLE GANG PLASTER RING AND MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
3/4" C. TO ACCESSIBLE CEILING. OTHERWISE. COORDINATE WITH AV CONTRACTOR

COMBINATION 4 SQUARE BOX WITH SINGLE GANG PLASTER RING MT. 18" A.F.F. TO BOTTOM OF BOX, UNLESS NOTED
DATA/TELEPHONE OUTLET AND 3/4" C. TO ACCESSIBLE CEILING. OTHERWISE. COORDINATE WITH AV CONTRACTOR

F FIRE ALARM PULL STATION SEE SPECS

TS TAMPER SWITCH (FIRE ALARM) SEE SPECS

WFS WATER FLOW SWITCH SEE SPECS

S FIRE ALARM SPEAKER/VISUAL DEVICE SEE SPECS

FIRE ALARM SPEAKER/VISUAL DEVICE SEE SPECS MT. 88" A.F.F. TO CENTERLINE OF BOX
S

SD SMOKE DETECTOR SEE SPECS

SD
DUCT SMOKE DETECTOR SEE PLANS
D

H FIRE ALARM HEAT DETECTOR SEE SPECS


TENANT
S FIRE ALARM VISUAL DEVICE SEE SPECS MT. 88" A.F.F. TO CENTERLINE OF BOX

FACP
IMPROVEMENT
FIRE ALARM CONTROL PANEL SEE SPECS

FAAP
FIRE ALARM ANNUNCIATOR PANEL SEE SPECS

PANEL BOARD SURFACE MOUNTED SEE SPECS


3030 PLAZA BONITA RD, SUITE
PANEL BOARD FLUSH MOUNTED SEE SPECS 1025
NATIONAL CITY, CA 91950
J JUNCTION BOX SEE SPECS

T TRANSFORMER SEE SPECS CLIENT

SINGLE PHASE MOTOR SEE PLANS ROUND1


THREE PHASE MOTOR SEE PLANS ENTERTAINMENT
FUSIBLE DISCONNECT SWITCH SEE PLANS

NONFUSIBLE DISCONNECT SWITCH SEE PLANS

HOME RUN SEE PLANS

SEE PLANS, BY AV CONTRACTOR, E.C. SHALL PROVIDE


S WALL MOUNTED SPEAKER SINGLE GANG BOX AND CONDUIT TO ACCESSIBLE CEILING COORDINATE HEIGHTS WITH AV CONTRACTOR
OR JOIST SPACE
SEE PLANS, BY AV CONTRACTOR, E.C. SHALL PROVIDE COORDINATE HEIGHTS WITH AV CONTRACTOR
S WALL MOUNTED SPEAKER SINGLE GANG BOX AND CONDUIT TO ACCESSIBLE CEILING
OR JOIST SPACE
C CEILING MOUNTED F FLOOR MOUNTED

AV AUDIO/VIDEO CONTRACTOR TR TAMPER RESISTANT

PC PLUMBING CONTRACTOR
3070 SATURN ST. STE. 200
GC GENERAL CONTRACTOR
BREA, CA 92821
MC MECHANICAL CONTRACTOR

EC ELECTRICAL CONTRACTOR

GENERAL ELECTRICAL NOTES


A. ELECTRICAL ORDINANCES: ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST
EDITION OF THE NATIONAL ELECTRICAL CODE AND FEDERAL LAWS OR ORDINANCES GOVERNING THE PROJECT. IF, IN ANY INSTANCE, THE
PLANS AND SPECIFICATIONS ARE IN DIRECT CONFLICT WITH SUCH CODES, LAWS OR ORDINANCES, THE CODE, LAWS AND ORDINANCES 4801 Henry St. 1751 Barlow St.
SHALL HAVE JURISDICTION AND THE WORK IN QUESTION SHALL BE INSTALLED ACCORDING TO THE CODES, LAWS AND ORDINANCES. ALL Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
WORK SHALL BE INSTALLED UNDER THE SUPERVISION OF A LICENSED MASTER ELECTRICIAN.
F 231-798-2981 F 231-947-1710
REC #5002
B. BRING ALL DISCREPANCIES SHOWN ON DIFFERENT DRAWINGS AND BETWEEN DRAWINGS AND SPECIFICATIONS OR BETWEEN
DOCUMENTS AND FIELD CONDITIONS TO THE IMMEDIATE ATTENTION OF THE ARCHITECT.

C. COORDINATE ELECTRICAL INSTALLATION WITH ALL OTHER CONTRACTORS AND OWNER FOR THE LOCATION AND SIZES OF ALL
EQUIPMENT PRIOR TO ROUGH-IN. SHOULD ELECTRICAL WORK BE INSTALLED WHICH INTERFERES WITH THE WORK OF OTHER
CONTRACTORS OR OWNER, SUCH WORK SHALL BE CHANGED WITH NO ADDITIONAL COST TO OWNER.

D. MOUNT EQUIPMENT AT NOMINAL MOUNTING HEIGHT INDICATED IN ELECTRICAL SYMBOL SCHEDULE UNLESS NOTED OTHERWISE ON THE
FLOOR PLANS OR DETAILED IN ARCHITECTURAL ELEVATIONS. DIMENSION SHOWN IS TO CENTER LINE OF BOX. SEE ARCHITECTURAL
INTERIOR AND EXTERIOR ELEVATIONS FOR EXACT LOCATION OF WALL MOUNTED DEVICES AND LIGHT FIXTURES.

E. ALL CONDUCTORS SHALL BE COPPER, UNLESS SPECIFIED OTHERWISE. BUILDING POWER WIRING SHALL HAVE THHN/THWN INSULATION.
CONDUCTOR AMPACITY SHALL BE BASED ON TABLE 310-16 OF THE NEC. USE 60-DEGREE C RATING FOR CIRCUITS TERMINATING ON
DEVICES RATED 100A AND BELOW. USE 75-DEGREE RATING FOR CIRCUITS TERMINATING ON DEVICES AND IN ENCLOSURES RATED OVER
100a.

F. INSTALL INSULATED GREEN EQUIPMENT GROUNDING CONDUCTOR WITH ALL BRANCH CIRCUIT AND FEEDER CONDUCTORS, SIZED IN
ACCORDANCE WITH NEC ARTICLE 250.

G. DRAWINGS INDICATE DESIGN LOADS, VOLTAGES, CORRESPONDING CONTROL EQUIPMENT, FEEDERS AND OVER CURRENT DEVICES. IF
EQUIPMENT ACTUALLY FURNISHED HAVE LOADS OTHER THAN THOSE INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN, CONTROL RELEASE DATE
EQUIPMENT, FEEDERS AND OVER CURRENT DEVICES SHALL BE ADJUSTED IN SIZE ACCORDINGLY AT NO ADDITIONAL COST TO THE OWNER.
SUCH ADJUSTMENT SHALL BE SUBJECT TO THE REVIEW OF THE ARCHITECT PRIOR TO ACCEPTANCE OR PURCHASE. DATE DESCRIPTION
H. IN GENERAL, BRANCH CIRCUIT CONDUIT AND WIRE IS NOT SHOWN. PROVIDE CONDUIT AND WIRE TO CONNECT DEVICES TO CIRCUITS
SHOWN. WIRE FILL AND CONDUCTOR SIZE SHALL BE AS SPECIFIED. PROVIDE A MAXIMUM OF THREE PHASE CONDUCTORS IN A SINGLE
05-18-23 FOR PERMITS
HOME RUN. PROVIDE A DEDICATED NEUTRAL FOR EACH PHASE CONDUCTOR UNLESS OTHERWISE NOTED. INSTALL PULL BOXES AND 07-21-23 FOR BIDS
JUNCTION BOXES AS REQUIRED TO AID IN THE INSTALLATION OF CABLES AND CONDUCTORS. LABEL LOCATION OF POWER CIRCUITS ON
COVER OF ALL RECEPTACLES AND ON COVER OF JUNCTION BOXES AND BOXES ASSOCIATED WITH EQUIPMENT. INCLUDE PANEL AND
CIRCUIT IDENTIFICATION. LABEL LOCATION OF POWER CIRCUITS ON COVER OF ALL LIGHT SWITCHES. INCLUDE PANEL AND CIRCUIT
IDENTIFICATION.

I. PROVIDE MINIMUM #12 AWG CONDUCTORS FOR HOMERUNS, #10 AWG CONDUCTORS FOR HOMERUNS THAT EXCEED 100 FEET FOR 120
VOLT CIRCUITS AND 250 FEET FOR 277 VOLT CIRCUITS. HOMERUNS SHALL BE CONSIDERED TO ORIGINATE FROM THE POWER SOURCE TO
THE FIRST PIECE OF EQUIPMENT OR DEVICE.

J. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR FINAL LOCATION OF CEILING MOUNTED EQUIPMENT. MOUNT RECESSED CEILING
FIXTURES WITH FLEXIBLE METAL CONDUIT OF LENGTH REQUIRED TO MEET MOUNTING LOCATION AND NEC REQUIREMENTS. MAXIMUM
FLEXIBLE CONDUIT LENGTH SHALL BE (6') SIX FEET.

K. NOT USED

L. THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL ITEMS NECESSARY TO COMPLETE THE INSTALLATION. THIS CONTRACTOR SHALL
TOUCH-UP OR REFINISH THE FACTORY FINISH OF EQUIPMENT MARRED DURING SHIPMENT, DEMOLITION OR INSTALLATION.

M. ELECTRICAL WORK SHALL NOT INTERFERE WITH CLEARANCES REQUIRED FOR GENERAL AND MECHANICAL CONSTRUCTION.

N. ELECTRICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF ALL NEW EQUIPMENT, DEVICES, FIXTURES AND CABLES/CONDUCTORS
TO BE INSTALLED IN SYSTEM FOR WRITTEN APPROVAL FROM ENGINEER PRIOR TO INSTALLATION. REFER TO SPECIFICATIONS FOR
ADDITIONAL SUBMITTAL REQUIREMENTS.

O. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE.

P. UNLESS NOTED OTHERWISE WITHIN THE DOCUMENTS MOUNTING HEIGHTS FOR ITEMS IN THE ARCADE/OPEN STRUCTURE AREA SHALL
BE AS FOLLOWS TO BOTTOM.
CABLE TRAY: 12'-6" A.F.F.
POWER BUS: 13'-0" A.F.F.
GENERAL LIGHTING: 12'-0" A.F.F. PROJECT

2112128GR
SHEET
7/21/2023 4:13:59 PM

ELECTRICAL GENERAL
INFORMATION

E-001
LIGHTING PLAN NOTES
LEGEND SYMBOL INDICATOR
1 PROVIDE 0-10V DIMMER SWITCH, SET FOR DIMMING RANGE OF 20% TO
100%. SWITCH SHALL NOT ALLOW LIGHTING TO BE TURNED OFF. REFER
TO 6/E601.
SIGN
2 RECEPTACLE MOUNTED ABOVE FOR RGB+UV LIGHTING FIXTURE. E.C.
(INTERNALLY LIT) SHALL PROVIDE RECEPTACLE MOUNTED ABOVE AS DIRECTED BY A.V.
SECTIONS ALONE INSET CONTRACTOR. FIXTURE FURNISHED AND MOUNTED BY A.V.
ANGLE 3'-6" LENGHT CONTRACTOR. FIXTURE TO FIXTURE POWER WIRING BY A.V.
15'-10" 12'-8" 5'-0" 8'-0" 8'-0" 5'-0" 25'-4" CONTRACTOR. E.C. SHALL PROVIDE HOME RUN WIRING BACK TO
"NW" "NW" "NW" "NW" "NW" "NW"
"NW" CONTACTOR, CONTACTOR SHALL BE CONTROLLED VIA MLCP AS PARADIGM DESIGN

4"
"NW" "NW" "NW" INDICATED ON THE ONE LINE DIAGRAM.

"

R"
2' -
"NW"

10

R"
R"
"NW" "NW" "NW" ARCHITECTS | ENGINEERS

8" "

"N
"NW"

8'- "NR
3' -

"N
"N
"NW" "NW" "NW" "NW" "NW" "NW" "NW"
3 RECEPTACLE MOUNTED ABOVE FOR BRUNSWICK "SPARK" PROJECTOR
(NODE). ALSO PROVIDE UNISTRUT TO ALLOW FOR MOUNTING OF

"
'-3
PROJECTOR AT PRECISE LOCATION NOTED AND PER THE BRUNSWICK

10

W"
SIGN (NOT LIT)

2"
GUIDE. COORDINATE WITH BRUNSWICK FIELD MANAGER.

4' -

"N
4 PROVIDE TOGGLE STYLE DISCONNECT SIWTCH ADJACENT TO

W"
STOREFRONT SIGN.

0"

"N
Grand Rapids | Phoenix | Traverse City

5' -

7"

R"
5 CONNECTION TO LIT SIGN, REFER TO ARCHITECTURAL ELEVATION.

3' -

"N
www.paradigmae.com
6 PENDANT MOUNT DOWN TO 10'-0" A.F.F., UNLESS ALTERNATE HEIGHT IS

"D12"

"D12"
"D8"

"D6"

"D6"

"D8"
NOTED ON PLAN.

7 FOR SHELF LIGHTING, SEE BACK BAR ELEVATION.


8 CONNECTION TO AV ELEMENT. COORDINATE EXACT LOCATION AND
CONNECTION WITH AV CONTRACTOR PRIOR TO ROUGH IN.
9 NOT USED
10 FIXTURE TO BE WIRED TO OPERATE AS EMERGENCY LIGHTING
FIXTURE THROUGH INVERTER. REFER TO INVERTER MANUFACTURERS
3 MALL ENTRY GUIDE FOR POWER AND SWITCHING CONNECTIONS. LETTER
DESIGNATION SHOWN ON PLAN INDICATES WHICH INVERTER IS TO BE
EL101 SCALE: 1/8" = 1'-0"
2 3 CONNECTED. FIXTURE IS TO BE NORMALLY ON BASED ON RELAY
STATE.

11 PROVIDE A LOCKING COVER WITH VIEWING WINDOW FOR LOW


VOLTAGE LIGHTING CONTROL STATION TO PROTECT FROM
UNAUTHORIZED USE IN PUBLIC AREA.
12 MOUNT LED CHANNEL UNDER COUNTER ON CUSTOMER SIDE
APPROXIMATLY 4" FROM MILLWORK VERTICAL WALL THE ENTIRE
LENGTH OF BAR CUSTOMER "KNEE SPACE". MOUNT POWER SUPPLY ON
STAFF SIDE OF COUNTER HIDDEN FROM VIEW OF CUSTOMER AND
STAFF UNDER COUNTER AND NEATLY SECURING ALL CABLES.

13 (LED UNDERCOUNTER) MOUNT UNDER HIGH COUNTER FOR LIGHTING


OF STAFF SIDE WORK SURFACE.
14 LINEAR LED ACCENT LIGHTING MOUNTED IN COVE OF BULKHEAD, PROJECT
REFER TO ARCHITECTURAL DETIALS.
15 REFER TO ARCHITECTURAL DETAILS AND ELEVATIONS FOR BACK BAR
SHELF UP LIGHTING AND/OR LIT SIGN ARRANGEMENT. COORDINATE
WITH GENERAL TRADES. ROUND1 -
I I.5 J K L L.1 M.1 M 1 16
17
HIDE FIXTURE BEHIND BULKHEAD / WALL AT CEILING.
MOUNT TOP OF FIXTURE AT SAME ELEVATION AS TOP OF BULKHEAD
PLAZA BONITA
OR AS NOTED ON PLAN TO REDUCE VIEW OBSTRUCTION OF BULKHEAD
MOUNTED SIGNS.
18 MOUNT TRACK TO CEILING T BAR. E.C. SHALL ADJUST EXACT
PLACEMENT AND AIMING FOR TRACK LIGHTING HEADS PER OWNER
4.1 4.1 DIRECTION PRIOR TO OPENING.
19 NOT USED
A A
20 TRIM CEILING GRID AS REQUIRED TO CENTER RECESSED LIGHITNG
"C3E" "C3" "C3E" "C3" "C3E" "C3" "C3E" "C3" "C3E" "C3" FIXTURE IN SPACE AS REQUIRED. COORDINATE WITH ARCHITECTURAL
TRADES.
S
OS OS
S 20
MENS "C3" "C3" "C3"
"C3" "L1" "L1" "L1" RGB LED LIGHTING TYP "ZB" CONNECTION POINT FOR LED SHELF
108

S
"C3" MOUNTED IN GLASS SHELF LIGHTING, POWER SUPPLY, RGB
"V" "V" "VE" "V" "V"
"L1" "L1" "L1" "L1" "L1" "L1" "L1" "L1" FACING UP, COORDINATE WITH CONTROLLER AND AMPLIFIERS
FOOD SERVICE EQUIPMENT (HIDE BEHIND SIGN)
JANITOR SUPPLIER FOR INSTALLATION
107 6 (TYP. EACH SHELF RUN AS CONNECTION FOR LIT SIGN
"C3E" "C3" "C3" (HIDE BEHIND SIGN)
PLUSH "C3E" "LE" "L" PARTY SHOWN)

107
CS
"C3E" "C3"
STORAGE ROOM 1 OS
OS OS "L1" "L1" "L1" "L1" "L1" "L1" "L1" S
S 105 S MLCP-4 110
0-10V OS 5 MONITOR
OS S
MONITOR
S S S
"C3" "C3" "C3E" PARTY ROOM
OS OS
"C3" 12'-1"
"VE" "V" "V" "V" "VE" "L1" "L1" "L1" "C3" "C3" "C3E" "C3" "C3E" "C3" "C3E" TENANT
LCPA-66 LCPA-65
NEW PANEL NEW PANEL OS FAMILY OS
S WOMENS 20
20
0-10V 0-10V
MONITOR 3'-5" MONITOR 3'-5" MONITOR IMPROVEMENT
"DPB" "2A" MLCP-30 E "XE" MLCP-29 S TOILET 109
0-10V "C3" "C3" "C3"
"C3E" 1A-20 0-10V 106 "C3E"

105
CS
"L1" "L1" "L1" "L1" "L1" "L1"
S

110
"C3"

CSS
5.1 5.1 106 "V4"
BFEC CS B
MLCP-8 MLCP-8
0-10V 16 0-10V
E
S 4'-2" 4'-2"
3030 PLAZA BONITA RD, SUITE
5 RESTROOMS
10 B "XE"

126
1025

CS
"H" 1A-20
"H" "H"
"H" MLCP-12
MLCP-12
MLCP-14
MLCP-14 OS NATIONAL CITY, CA 91950
"H" "H" "H" "H" "H" 10 B "C3" "C3" "C3" S "C3" "C3" "C3"
"V" "V"
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13
"H" CLIENT
MLCP-14
"C3" "C3" "C3E"

"C3E" "C3" "C3"


PARTY ROUND1
"H" ROOM 2 5
MLCP-13
PARTY ROOM

5
PARTY 121
OS
S PARTY ROOM ENTERTAINMENT
OS ROOM 4 REDEMPTION
S
124 STORAGE "C3E" "C3" "C3"
LCPA-67
123 0-10V LCPA-68
"H"
MLCP-11
"H"
MLCP-13
"H"
MLCP-11
"H"
MLCP-13
"H"
MLCP-11
"C3" "C3" "C3E" 0-10V
6 BACKBAR ELEVATION
"H" "H" "C3" "C3" "C3" EL101 SCALE: 1/4" = 1'-0"
10 B 10 B B 10 LCPA-71 LCPA-72
MLCP-14 MLCP-14 0-10V 0-10V
MLCP-14

122
CS
"V" "V" "H"
12'-2"

8'-5"

8'-8"

S
"C3" "C3" "C3"
"H"

4'-10"
1A-20 1A-20
MLCP-13
S
6 6
"X" "X" C C
6.1 6.1 "H" "H"
S MLCP-12 MLCP-12 "C3" "C3" "C3" 5
"H" "H" "H" "H" "H"
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13 10 B 10 B PARTY ROOM
8'-8"

MLCP-53
NOTE: ALL TYPE "H" FIXTURES 1A-20
PARTY "C3" "C3" "C3E"123 3070 SATURN ST. STE. 200

14'-5"
SHALL HAVE 0-10V DIMMING "C3E" "C3E" 4" 6"
12'-2"

E "XE" ROOM 3
CONTROL WIRING RUN TO CS
RESPECTIVE CONTROL RELAY. "H" MLCP-31 122
BREA, CA 92821
"H" "H" 0-10V OS
MLCP-13 "V" S
MLCP-14 MLCP-14
MLCP-42

"2H" 125
"C3E" "C3" "C3"

CS
S
OS TYPE "Z4" RIGID TYPE "Z1" RIGID ALUMINUM
S LCPA-69 LCPA-70
0-10V 0-10V "H" ALUMINUM CHANNEL CHANNEL AND LENS
"H" "H" "H" "H" "H" (WATERPROOF)
"TR" "V4" "V4" MLCP-14 AND LENS
MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11 MTD. APPROX. 1A-22 "C3" "C3" "C3"
10 B 10 B 10 B
14-7" BTM. OF REDEMPTION
JOIST LEVEL STORE NEW LIGHTING CONTROL
FEATURE LIGHTING (TYP.)
12'-2"

3'-0" 6'-0" 4'-0" 125 PANEL LCPA


SEE ELEVATION "X"
"H" 24X24 24X48 CUSTOMER SIDE STAFF SIDE
VICTORY ZONE SEE DETAIL (THIS SHEET)
MLCP-13 "C3E" "C3E" "L" "LE" "Z4"
5 MLCP-7
6.8 6.8 0-10V 12

CWI
4801 Henry St. 1751 Barlow St.
"H" "H" Muskegon, MI 49441 Traverse City, MI 49686
MLCP-12 MLCP-14 "L" "L" "LE" T 231-798-4328 T 231-947-1707

CWO
D
"H" "H" "H" "H" "H" F 231-798-2981 F 231-947-1710

FE-K
6.9 D 6.9 10 B 18 D REC #5002
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13

24X48
24X48
9'-2"

7.1 7.1

24X48
6 NEW PANELS
3 "X" "2F" & "2G" MLCP-43
5
1A-20

24X48
EL101 24X48
MLCP-34 B 10 15
TYP. OF 8

24X48

24X48

1 8"X1 8"X1 2"


KITCHEN "LE" "L"

24X48
10 B "C3E" 24X48 "L"
"H" "H" "C3E" 128
"H" "H" "H" "H" "H" "H" MLCP-14 MLCP-12
1N MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11 MLCP-13
1N "TRW" S 7

34DR
FLOOR

24X48
10 B 10 B "H" "H" MLCP-5
"W4" 0-10V MLCP-36

24X48
12'-0" A.F.F. 1A-20 "W8" 13'-0" A.F.F. MLCP-14 MLCP-14
"W4" 12'-0" A.F.F. 12'-0" A.F.F. "C3" "C3" NEW PANEL "1A" "L"
5 "W4" 6 "X" TYPE "Z2" MLCP-14 "L" NEW LIGHTING
"W12" 14'-0" A.F.F. 12'-0" A.F.F. "W4" "L" 3

24X48
"W8" 13'-0" A.F.F. 0-10V CONTROL PANEL 6
ROUND 1
"W8" 12'-0" A.F.F. "W8" 14'-0" A.F.F. 1A-20 "C3" "C3E"
MLCP (TUB 1) EL101 EL102 4 UNDERBAR LIGHTING
CWI

GUEST 1A-22 NOT TO SCALE


EL101

C
"X"

D
"W8" 14'-0" A.F.F. "H" "C3" MECHANICAL "L" "L"

TS14BLW
"W12" 14'-0" A.F.F. "W12" 14'-0" A.F.F. "H" COUNTER

CH
H
CWO
D

MLCP-12 MLCP-14 127 "L"


MLCP-40 "W12" 14'-0" A.F.F. 126 RELEASE DATE

D
"W8" 12'-0" A.F.F. MLCP-10 "C3" "C3" "C3" BAR

G
10 "LE"
0-10V B

D
"W12" 130

CRC-63C
G
12'-0" A.F.F. INV "LE"

CH
"X" DATE DESCRIPTION

D
6 "W4" 13'-0" A.F.F. "W12" 13'-0" A.F.F.
A&B

G
MLCP-12

D
1A-20 "W4" "W4"
12'-0" A.F.F. 13'-0" A.F.F. "C3" "C3" "C3" UPPER GRID CEILING 05-18-23 FOR PERMITS
10
07-21-23 FOR BIDS

TYPE "Z2" 45 DEGREE ALUMINUM


CHANNEL AND LENS MOUNTED ON
TOP OF CEILING TRIM RUNNING THE
PERIMETER AS SHOWN ON PLAN.
I I.5 K L L.1 M.1 M 1 2 3

LOWER GRID CEILING

N
ELECTRICAL LIGHTING FIRST FLOOR PLAN 'A'
SCALE: 1/8" = 1'-0"

PLAN
5 BOWLER'S BULKHEAD COVE
EL101 NOT TO SCALE

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:14:22 PM

ELECTRICAL LIGHTING
FIRST FLOOR PLAN 'A'

EL101
KEY PLAN
LIGHTING PLAN NOTES
LEGEND SYMBOL INDICATOR
1 PROVIDE 0-10V DIMMER SWITCH, SET FOR DIMMING RANGE OF 20% TO
100%. SWITCH SHALL NOT ALLOW LIGHTING TO BE TURNED OFF. REFER
TO 6/E601.
2 RECEPTACLE MOUNTED ABOVE FOR RGB+UV LIGHTING FIXTURE. E.C.
SHALL PROVIDE RECEPTACLE MOUNTED ABOVE AS DIRECTED BY A.V.
CONTRACTOR. FIXTURE FURNISHED AND MOUNTED BY A.V.
CONTRACTOR. FIXTURE TO FIXTURE POWER WIRING BY A.V.
CONTRACTOR. E.C. SHALL PROVIDE HOME RUN WIRING BACK TO
CONTACTOR, CONTACTOR SHALL BE CONTROLLED VIA MLCP AS PARADIGM DESIGN
INDICATED ON THE ONE LINE DIAGRAM.
ARCHITECTS | ENGINEERS
3 RECEPTACLE MOUNTED ABOVE FOR BRUNSWICK "SPARK" PROJECTOR
(NODE). ALSO PROVIDE UNISTRUT TO ALLOW FOR MOUNTING OF
PROJECTOR AT PRECISE LOCATION NOTED AND PER THE BRUNSWICK
GUIDE. COORDINATE WITH BRUNSWICK FIELD MANAGER.

4 PROVIDE TOGGLE STYLE DISCONNECT SIWTCH ADJACENT TO


STOREFRONT SIGN.
5 CONNECTION TO LIT SIGN, REFER TO ARCHITECTURAL ELEVATION. Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
6 PENDANT MOUNT DOWN TO 10'-0" A.F.F., UNLESS ALTERNATE HEIGHT IS
NOTED ON PLAN.

7 FOR SHELF LIGHTING, SEE BACK BAR ELEVATION.


8 CONNECTION TO AV ELEMENT. COORDINATE EXACT LOCATION AND
CONNECTION WITH AV CONTRACTOR PRIOR TO ROUGH IN.
9 NOT USED
10 FIXTURE TO BE WIRED TO OPERATE AS EMERGENCY LIGHTING
FIXTURE THROUGH INVERTER. REFER TO INVERTER MANUFACTURERS
GUIDE FOR POWER AND SWITCHING CONNECTIONS. LETTER
DESIGNATION SHOWN ON PLAN INDICATES WHICH INVERTER IS TO BE
CONNECTED. FIXTURE IS TO BE NORMALLY ON BASED ON RELAY
I I.5 J K L L.1 M.1 M 1 2 3 STATE.

11 PROVIDE A LOCKING COVER WITH VIEWING WINDOW FOR LOW


VOLTAGE LIGHTING CONTROL STATION TO PROTECT FROM
UNAUTHORIZED USE IN PUBLIC AREA.
12 MOUNT LED CHANNEL UNDER COUNTER ON CUSTOMER SIDE
NEW PANEL "1A" APPROXIMATLY 4" FROM MILLWORK VERTICAL WALL THE ENTIRE
5 MLCP-14 NEW LIGHTING LENGTH OF BAR CUSTOMER "KNEE SPACE". MOUNT POWER SUPPLY ON
3

24X48
"W8" 13'-0" A.F.F. CONTROL PANEL STAFF SIDE OF COUNTER HIDDEN FROM VIEW OF CUSTOMER AND
ROUND 1
0-10V
6 STAFF UNDER COUNTER AND NEATLY SECURING ALL CABLES.
MLCP (TUB 1) EL101 EL102
"W8" 12'-0" A.F.F. "W8" 14'-0" A.F.F. 1A-20 "C3" "C3E"

CWI
GUEST 1A-22 (LED UNDERCOUNTER) MOUNT UNDER HIGH COUNTER FOR LIGHTING
13

C
"X"

D
"W8" 14'-0" A.F.F. "H" "C3" MECHANICAL "L" "L" OF STAFF SIDE WORK SURFACE.

TS14BLW
"W12" 14'-0" A.F.F. "W12" 14'-0" A.F.F. "H" COUNTER

CH
H
CWO
D
MLCP-12 MLCP-14 127 "L"
MLCP-40 "W12" 14'-0" A.F.F. 126 14 LINEAR LED ACCENT LIGHTING MOUNTED IN COVE OF BULKHEAD, PROJECT

D
"W8" 12'-0" A.F.F. MLCP-10 "C3" "C3" "C3" BAR REFER TO ARCHITECTURAL DETIALS.

G
10 "LE"
B

D
0-10V
"W12" 130

CRC-63C
G
12'-0" A.F.F. INV "LE" 15 REFER TO ARCHITECTURAL DETAILS AND ELEVATIONS FOR BACK BAR

CH
ROUND1 -

D
"X" "W4" 13'-0" A.F.F. "W12" 13'-0" A.F.F.
6 A&B SHELF UP LIGHTING AND/OR LIT SIGN ARRANGEMENT. COORDINATE

G
MLCP-12

D
1A-20 "W4" "W4" "P3" WITH GENERAL TRADES.
12'-0" A.F.F. 13'-0" A.F.F. "C3" "C3" "C3"
2N 2N
PLAZA BONITA
"H" "H" DC

SC-1 5 -TS
S 16 HIDE FIXTURE BEHIND BULKHEAD / WALL AT CEILING.

CH
10 CS

130

D
CS
D
MLCP-14 MLCP-14 B GAME CARDS
A 128 CS H
C
5 SEE DETAIL (THIS SHEET) 17 MOUNT TOP OF FIXTURE AT SAME ELEVATION AS TOP OF BULKHEAD
"C3" "C3E" "C3E" OR AS NOTED ON PLAN TO REDUCE VIEW OBSTRUCTION OF BULKHEAD
"H" "C3" "C3" "C3" "C3" "C3" "C3E" "C3" "C3" "P3"
"H" "H" "H" "H" "H" 13 MOUNTED SIGNS.
MLCP-13

CRI- 12 -3 0- 7
D
MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11
"Z1" MOUNT TRACK TO CEILING T BAR. E.C. SHALL ADJUST EXACT
10 B
8'-4"
10 B B 10 MLCP-42 18
8.1 E 8.1 E PLACEMENT AND AIMING FOR TRACK LIGHTING HEADS PER OWNER
"C3" "C3" "C3" "C3" "C3" "C3" "C3" "C3" "C3" "C3" "P3"
"H" DIRECTION PRIOR TO OPENING.
MLCP-14 MLCP-9 MLCP-35
RC NOT USED
0-10V C
H R
D
C 19
8.2 8.2 MLCP-14
D
0-10V
"H" FEC "H" "H" "H" "H" PARTY INFO
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13 GUEST COUNTER 20 TRIM CEILING GRID AS REQUIRED TO CENTER RECESSED LIGHITNG
8.3 8.3 TYPE "Z2" MLCP-41 SNACK FIXTURE IN SPACE AS REQUIRED. COORDINATE WITH ARCHITECTURAL
"H" 5
S MLCP-12 5 FOOD&DRINKS
BAR TRADES.
5
11'-4"

10 B 10 B 129
"C3" "C3"
"H" MLCP-12
MLCP-13
"H" "H" "H" "H" "H" "H" "P3" "P3" "H"
MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14
"C3" "C3"
10 B 10 B 10 B
"H" "H" "H" "H" "H"
MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11
10 B 10 MLCP-14
B B 10 0-10V
"H" "H" "H" "H" "H" "H" "H" "H"
11'-4"

MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14


"H"
MLCP-13
6
"X" MOUNT LIGHTING WITHIN
4'-3"
TENANT
"H"
IMPROVEMENT

5'-6"
MLCP-14 1A-20 OUTLINE AT 14'-0" A.F.F. TO
BOTTOM.
"H" "H" "H" F
"H" "H" F
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13
FEC
9.1 9.1 "C9E"
"H" "H" "H" "H" "H"
11'-4"

MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-14


"H"
"H"
MLCP-13
10 A 10 A MLCP-12 3030 PLAZA BONITA RD, SUITE
10 A 1025
"H" NATIONAL CITY, CA 91950
MLCP-14
"H" "H" "H" "H" "H"
MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11 CLIENT
10 A 10 A 10 A "H" "H" "H" "H" "H" "H"
MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 ROUND1
11'-4"

1A-20
1A-20
13'-10" 13'-10" 13'-10" 13'-10" 13'-10" ENTERTAINMENT

16'-0"
6
6
1A-20
"H" "H"
"X" MLCP-14
"H" "H" "H" "H" "H" MLCP-13 6 "X"
"X"
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13
"H" "H" "H" "H" "H" "H" "H" "H"
9'-5"

MLCP-13 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14

G 10 A 10 A 10 A G

"H" "H" "H" "H" "H"


10.1 10.1
MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11
10 A 10 A 10 A "C9E"
"H" "H" "H" "H" "H" "H"
9'-5"

MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14


"H"
6
MLCP-13 EL101
3070 SATURN ST. STE. 200
BREA, CA 92821
"H" "H" "H" "H" "H"
MLCP-13 MLCP-13 MLCP-13 MLCP-13 MLCP-13
9'-5"

"H" "H" "H" "H" "H" "H"


"H" MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14
MLCP-13 A 10
A 10 A 10
A 10 A 10 A 10 "X"

"H" "H" "H" "H" "H" 1A-20

16'-0"
FEC

MLCP-11 MLCP-13 MLCP-11 MLCP-13 MLCP-11 "H" "H" "H" "H" "H"
14'-0" 14'-0" 14'-0" 14'-0" 2'-11" MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14
LINEAR SIGN BAND ON
VERTICAL SURFACE OF
BULKHEAD
H H 4801 Henry St. 1751 Barlow St.
Muskegon, MI 49441 Traverse City, MI 49686
T 231-798-4328 T 231-947-1707
F 231-798-2981 F 231-947-1710
REC #5002

11.1 11.1

"C9E"

MLCP-44
0-10V
"Z2" (LED COVE) MOUNT IN
COVE AND AIM TO WASH
CEILING (STAFF SIDE)
MLCP-55

RELEASE DATE
I I.5 K L L.1 M.1 M 1 2 3
LINEAR SIGN BAND ON MLCP-43 DATE DESCRIPTION
VERTICAL SURFACE
OF BULKHEAD 05-18-23 FOR PERMITS
07-21-23 FOR BIDS

ELECTRICAL LIGHTING FIRST FLOOR PLAN 'B' 3 BAR CEILING LIGHTING PLAN
N SCALE: 1/8" = 1'-0"
EL101 SCALE: 1/4" = 1'-0"

PLAN

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:14:38 PM

ELECTRICAL LIGHTING
FIRST FLOOR PLAN 'B'

EL102
KEY PLAN
LIGHTING PLAN NOTES
LEGEND SYMBOL INDICATOR
1 PROVIDE 0-10V DIMMER SWITCH, SET FOR DIMMING RANGE OF 20% TO
100%. SWITCH SHALL NOT ALLOW LIGHTING TO BE TURNED OFF. REFER
TO 6/E601.
2 RECEPTACLE MOUNTED ABOVE FOR RGB+UV LIGHTING FIXTURE. E.C.
SHALL PROVIDE RECEPTACLE MOUNTED ABOVE AS DIRECTED BY A.V.
CONTRACTOR. FIXTURE FURNISHED AND MOUNTED BY A.V.
CONTRACTOR. FIXTURE TO FIXTURE POWER WIRING BY A.V.
CONTRACTOR. E.C. SHALL PROVIDE HOME RUN WIRING BACK TO
CONTACTOR, CONTACTOR SHALL BE CONTROLLED VIA MLCP AS PARADIGM DESIGN
INDICATED ON THE ONE LINE DIAGRAM.
ARCHITECTS | ENGINEERS
3 RECEPTACLE MOUNTED ABOVE FOR BRUNSWICK "SPARK" PROJECTOR
(NODE). ALSO PROVIDE UNISTRUT TO ALLOW FOR MOUNTING OF
PROJECTOR AT PRECISE LOCATION NOTED AND PER THE BRUNSWICK
GUIDE. COORDINATE WITH BRUNSWICK FIELD MANAGER.

4 PROVIDE TOGGLE STYLE DISCONNECT SIWTCH ADJACENT TO


STOREFRONT SIGN.
5 CONNECTION TO LIT SIGN, REFER TO ARCHITECTURAL ELEVATION. Grand Rapids | Phoenix | Traverse City
www.paradigmae.com
6 PENDANT MOUNT DOWN TO 10'-0" A.F.F., UNLESS ALTERNATE HEIGHT IS
NOTED ON PLAN.

7 FOR SHELF LIGHTING, SEE BACK BAR ELEVATION.


8 CONNECTION TO AV ELEMENT. COORDINATE EXACT LOCATION AND
CONNECTION WITH AV CONTRACTOR PRIOR TO ROUGH IN.
4 5 6 7 8 9 NOT USED
10 FIXTURE TO BE WIRED TO OPERATE AS EMERGENCY LIGHTING
FIXTURE THROUGH INVERTER. REFER TO INVERTER MANUFACTURERS
GUIDE FOR POWER AND SWITCHING CONNECTIONS. LETTER
DESIGNATION SHOWN ON PLAN INDICATES WHICH INVERTER IS TO BE
4 5 CONNECTED. FIXTURE IS TO BE NORMALLY ON BASED ON RELAY
MLCP-20 STATE.
MLCP-51
24'-6" 1A-20 16'-0" 6
11 PROVIDE A LOCKING COVER WITH VIEWING WINDOW FOR LOW
"XE" 3
24X48

6 "XE" "XE" "XE" "XE" "XE" VOLTAGE LIGHTING CONTROL STATION TO PROTECT FROM
EL102 "H" 3
EL101 E E E E E E "X" EL104 UNAUTHORIZED USE IN PUBLIC AREA.
C C C C BILLIARDS C C "C3" "C3" "X" "C12" "C12" "C12" 12 MOUNT LED CHANNEL UNDER COUNTER ON CUSTOMER SIDE
1A-20 1A-20
MTD. AT BTM. SEATING 1A-20 132 1A-20 1A-20
D

VESTIBULE 1A-20 APPROXIMATLY 4" FROM MILLWORK VERTICAL WALL THE ENTIRE
TS14BLW

6'-3"
CH

OF JOIST (TYP.) 131 LENGTH OF BAR CUSTOMER "KNEE SPACE". MOUNT POWER SUPPLY ON
133

10'-0"
D

STAFF SIDE OF COUNTER HIDDEN FROM VIEW OF CUSTOMER AND


BAR MLCP-3 STAFF UNDER COUNTER AND NEATLY SECURING ALL CABLES.
D

130
CRC-63C

CH
D

0-10V "W8" "W8" "W8" "BT" "BT" "BT" "C3" "C3" (LED UNDERCOUNTER) MOUNT UNDER HIGH COUNTER FOR LIGHTING
13
D

"P3" OF STAFF SIDE WORK SURFACE.


"XE"

E
"H" 14 LINEAR LED ACCENT LIGHTING MOUNTED IN COVE OF BULKHEAD, PROJECT
SC-1 5 -TS

CH
130

D
CS

1" 1A-20

9'-9"
REFER TO ARCHITECTURAL DETIALS.
2'-8" MLCP-33 "C12" "C12" "C12E"
SEE DETAIL (THIS SHEET)
15 REFER TO ARCHITECTURAL DETAILS AND ELEVATIONS FOR BACK BAR

6'-2"
13
"P3"
"TR"
"C3" "C3" SHELF UP LIGHTING AND/OR LIT SIGN ARRANGEMENT. COORDINATE
ROUND1 -

4'-0"
42'-0"

3'-4"
CRI- 12 -3 0- 7

"TR"
D

"P2" "P2" "P2" "P2" "P2" "P2" WITH GENERAL TRADES.


"Z1" 2'-8" 7'-3"
E
"P3"
E 16 HIDE FIXTURE BEHIND BULKHEAD / WALL AT CEILING.
PLAZA BONITA

3'-1"
MLCP-14 3'-3" MLCP-14 2'-7" 17 MOUNT TOP OF FIXTURE AT SAME ELEVATION AS TOP OF BULKHEAD
MLCP-35 0-10V 0-10V
OR AS NOTED ON PLAN TO REDUCE VIEW OBSTRUCTION OF BULKHEAD
"C3" "C3" "C3" "C3" "C3" "C3" "C3" "C3"
"H" "H" "H" 10 B MOUNTED SIGNS.
MLCP-14 6'-3" 6'-3" 6'-3"
0-10V 6'-3" 6'-3" 6'-3" 5'-1" MLCP-14 MLCP-14 MLCP-14 "C12" 18 MOUNT TRACK TO CEILING T BAR. E.C. SHALL ADJUST EXACT
13'-10" 13'-10"
PLACEMENT AND AIMING FOR TRACK LIGHTING HEADS PER OWNER
MTD. AS HIGH AS POSSIBLE 1A-20 MLCP-37
6 1A-20 DIRECTION PRIOR TO OPENING.

FEC
TO STRUCTURE AIM TO "X"
HIGHLIGHT ARCHITECTURAL 19 NOT USED
"TR" "H" "H" "H" "H" "H" "H" "H" "H" "H"
FEATURE. MLCP-33 "X"
MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14
6
10 B 10 B 10 B 10 B 20 TRIM CEILING GRID AS REQUIRED TO CENTER RECESSED LIGHITNG
FIXTURE IN SPACE AS REQUIRED. COORDINATE WITH ARCHITECTURAL

10'-11"
"H" TRADES.
MLCP-14 1A-20 POWER BUSWAY
(SEE EP SERIES SHEETS)
6
"X"
STAIR
S-2
"H" "H" "H" "H"
"H" "H" "H" "H" "H" "H" "H"
MLCP-14 MLCP-14 MLCP-14 MLCP-14
MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14

10'-11"
NOTE: ALL TYPE "H" FIXTURES
MOUNT LIGHTING WITHIN SHALL HAVE 0-10V DIMMING S
OUTLINE AT 14'-0" A.F.F. TO CONTROL WIRING RUN TO
BOTTOM. RESPECTIVE CONTROL RELAY.
F "H" F
S
"H"
MLCP-14
TENANT
"H" "H" "H" "H" "H" "H" "H" "H" "H" "H"
MLCP-14 MLCP-12 MLCP-14 MLCP-12 ? MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-12 IMPROVEMENT
10 A 10 A ? 10 A 10 A 10 A 10 A

10'-11"
3030 PLAZA BONITA RD, SUITE
"H" "H" "H" "H" "H" 1025
"H" "H" "H" "H" "H" "H" "H"
MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14
MLCP-14 MLCP-14 MLCP-14 MLCP-14 MLCP-14 NATIONAL CITY, CA 91950
13'-10" 12'-11" 12'-11" 12'-11" 12'-11" 12'-11" 12'-11" 12'-11" 12'-11"
CLIENT

10'-11"
6 "X"
1A-20
1A-20
"C3" "C3" "C3"
1A-20 ROUND1
6 "X" 6 "X"
MLCP-14
0-10V ENTERTAINMENT
"H" "H" "H"
"H" "H" "H" "H" "H" "H" "H" "H"
"C3" "C3" MLCP-14 MLCP-14 MLCP-14
MLCP-14 MLCP-12 MLCP-14 MLCP-12 MLCP-12 MLCP-12 MLCP-12 MLCP-12

G A 10 A 10 A 10 A 10 A 10 A 10 G

"C3" "C3" "C3"


"H" "H" "H" "H" "H"
"H" "H"
MLCP-14 MLCP-14 MLCP-14 NEW MLCP-14 MLCP-14
MLCP-14 MLCP-14
"X" 1A-20 PANEL "2J"
"H" "H" "H" "H" MLCP-41
MLCP-14 MLCP-14 MLCP-14 MLCP-14
E 1A-20 MLCP-18 MLCP-25 CS MLCP-24 MLCP-23 0-10V

"XE" 0-10V 0-10V 136 0-10V 0-10V


FEC

"V4" "V4" "L"

S
VESTIBULE "RPE" "RP" "RP" "RP" "RP"
S

"C3" "C3" "C3" "C3" "C3" HIGH


101 STORAGE/
"H" "H" "H" VALUE OS
MLCP-12 MLCP-12 S OS LACTATION
MLCP-14 STORAGE 1A-20
S
OS 134
"V4" 3070 SATURN ST. STE. 200

REF.
A 10 A 10 137 E S "LE"
"H" OS
"XE" S BREA, CA 92821
MLCP-14 1A-22 "C12" "C12" "C12"
S
E

"XE" MLCP-18 "RP" "RP" "RPE" "RPE" "RP"


1A-20 "C12" "C12" "C12"
"V4" "V4"

134
137

CS
CS

S
"V4" "L"
"C12" "C12"
EMPLOYEE
MLCP-19 OFFICE LOUNGE
NEW PANEL "2B" "C12E" "C12E" 135
136 135
CS
H H
4 5
MLCP-38
"FL20" "FL20"
FEATURE LIGHTING (TYP.) MLCP-52
SEE ELEVATION
UNDERGROUND WIRING
4801 Henry St. 1751 Barlow St.
(TYP. DASHED) 32'-2" Muskegon, MI 49441 Traverse City, MI 49686
COORD. CUTTING & PATCHING T 231-798-4328 T 231-947-1707
WITH GENERAL TRADES. "NW" F 231-798-2981 F 231-947-1710
REC #5002
"FL10"

4'-5"
3 "FL10"

"NW"

"NW"
EL103
PIN MONUMENT

"FL20"

"NW"
"NW"
"NW"

"NW"
"NW"
"NW"
LIT SIGN

10'-0"
PIN MONUMENT,
LIT FROM
GROUND

22'-0"
4 7 8

RELEASE DATE

DATE DESCRIPTION
5 6 05-18-23 FOR PERMITS
07-21-23 FOR BIDS

N
ELECTRICAL LIGHTING FIRST FLOOR PLAN 'C'
SCALE: 1/8" = 1'-0"

PLAN

3 SOUTH MAIN ENTRY ELEVATION


EL103 SCALE: 1/8" = 1'-0"

A D
PROJECT

2112128GR
SHEET
B C
7/21/2023 4:14:54 PM

ELECTRICAL LIGHTING
FIRST FLOOR PLAN 'C'

EL103
KEY PLAN
LIGHTING PLAN NOTES
LEGEND SYMBOL INDICATOR
1 PROVIDE 0-10V DIMMER SWITCH, SET FOR DIMMING RANGE OF 20% TO
100%. SWITCH SHALL NOT ALLOW LIGHTING TO BE TURNED OFF. REFER
TO 6/E601.
2 RECEPTACLE MOUNTED ABOVE FOR RGB+UV LIGHTING FIXTURE. E.C.
SHALL PROVIDE RECEPTACLE MOUNTED ABOVE AS DIRECTED BY A.V.
CONTRACTOR. FIXTURE FURNISHED AND MOUNTED BY A.V.
CONTRACTOR. FIXTURE TO FIXTURE POWER WIRING BY A.V.
CONTRACTOR. E.C. SHALL PROVIDE HOME RUN WIRING BACK TO
CONTACTOR, CONTACTOR SHALL BE CONTROLLED VIA MLCP AS PARADIGM DESIGN
INDICATED ON THE ONE LINE DIAGRAM.