NEW PHOTOVOLTAIC ROOF MOUNTED SYSTEM - 5.18 KW DC/4.611 KW CEC AC SYSTEM SIZE: DC SIZE: 14 X 370W = 5.18 KW DC (STC)
DC SIZE: 14 x 337.8W = 4.73 KW DC (PTC)
32264 ORTEGA HWY, LAKE ELSINORE, CA 92530 AC SIZE: 4.611 KW CEC
MODULE: (14) DNA-120MF 26-370W
INVERTER: (14) ENPHASE IQ8PLUS-72-2-US (240V)
SCOPE OF WORK
SATELLITE VIEW 1.2.1 CONTRACTOR IS RESPONSIBLE FOR THE SIGN./STAMP
DESIGN AND SPECIFICATIONS OF THE GRID-TIED
PHOTOVOLTAIC SYSTEM. THE CONTRACTOR WILL
BE RESPONSIBLE FOR COLLECTION OF EXISTING
ONSITE CONDITIONS TO DESIGN, SPECIFY, AND
INSTALL THE ROOF-MOUNTED PHOTOVOLTAIC
SYSTEM DETAILED IN THIS DOCUMENT
76'-7"
DESIGN CRITERIA
ROOF SURFACE TYPE: ROLLED ROOFING
ROOF FRAMING: 2"X4" RAFTER @ 48" OC
ORTEGA HWY
BUILDING STORY: ONE STORY
GROUND SNOW LOAD: 0 PSF
WIND SPEED: 91 MPH PROJECT NAME & ADDRESS
WIND EXPOSURE: B
RISK CATEGORY: II BARBARA SHEA-HAN
PROJECT NOTES
22'-8" 32264 ORTEGA HWY,
1.1.1 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL
COMPLY WITH THE RELEVANT YEAR OF
LAKE ELSINORE, CA 92530
LEGEND
173'-5"
171'-11"
MANUFACTURER’S LISTING AND INSTALLATION
- FENCE LINE INSTRUCTIONS, AND THE RELEVANT CODES AS AHJ: LAKE ELSINORE
- DRIVEWAY SPECIFIED BY AUTHORITY HAVING UTILITY: SCE
- ROOF LINES JURISDICTION’S (AHJ) APPLICABLE CODES.
(14) DNA-120MF 26-370W MODULES 1.1.2 THE UTILITY INTERCONNECTION
SHEET INDEX WITH ENPHASE IQ8PLUS-72-2-US APPLICATION MUST BE APPROVED AND THE PV SYSTEM DETAILS
PV-1 COVER PAGE 41'-7"
SYSTEM MUST BE INSPECTED PRIOR TO
(240V) UNDER EACH MODULE
PV-2 SITE PLAN OPERATION
PV-3 ATTACHMENT PLAN & DETAILS 1.1.3 ALL PV SYSTEM COMPONENTS; MODULES, DC SIZE: 5.180 KW DC (STC)
PV-4 ELECTRICAL DIAGRAM UTILITY-INTERACTIVE INVERTERS, AND AC SIZE: 4.611 KW AC (CEC)
PV-5 NOTES SOURCE CIRCUIT COMBINER BOXES ARE (14) DNA-120MF 26-370W
IDENTIFIED & LISTED FOR USE IN PV SYSTEMS (14) ENPHASE IQ8PLUS-72-2-US (240V)
PV-6 WARNING LABELS
AS REQUIRED BY CEC AND OTHER GOVERNING
PV-7 MICROINVERTER CHART
R-1 : R-7 RESOURCE DOCUMENT
(E) UTILITY METER
UM
MSP MAIN CODES
(OVERHEAD SERVICE) 1.1.4 ALL SIGNAGE BE PLACED IN
INSIDE GARAGE
HOUSE ACCORDANCE WITH LOCAL BUILDING CODE. REVISION
NOTES:
IF EXPOSED TO SUNLIGHT, IT SHALL BE UV # REV. INFO DATE
1. ROOF ACCESS POINT SHALL NOT BE LOCATED
(N) MAIN SERVICE RESISTANT. ALL PLAQUES & SIGNAGE WILL BE
IN AREAS THAT REQUIRE THE PLACEMENT OF
GROUND LADDERS OVER OPENINGS SUCH AS
PANEL INSTALLED AS REQUIRED BY THE CEC & AHJ.
WINDOWS OR DOORS, AND LOCATED AT
31'-10"
ORTEGA HWY
E:\Projects\3. TP\20 June 2023\Christopher Hiura\Image 5-22-23 at 11.20 AM.jpeg
CB - IQ COMBINER BOX
(E) UTILITY METER - SKYLIGHT (ROOF OBSTRUCTION)
(OVERHEAD SERVICE)
METER #: ---- - CHIMNEY (ROOF OBSTRUCTION)
(N) MAIN SERVICE PANEL - VENT, ATTIC FAN (ROOF OBSTRUCTION)
(N) AC COMBINER PANEL
- (14) DNA-120MF 26-370W MODULES WITH
ENPHASE IQ8PLUS-72-2-US (240V)
(N) NON-FUSED AC DISCONNECT MICROINVERTERS UNDER EACH MODULE SIGN./STAMP
(N) JUNCTION BOX
NEMA 3R
ROOF 1
MSP
ACD
UM
CB
JB JB
PROJECT NAME & ADDRESS
BARBARA SHEA-HAN
FRONT OF HOUSE
BACK OF HOUSE
LAKE ELSINORE, CA 92530
36" FIRE SETBACK
APN #: 387240003
SYSTEM DETAILS
REVISION
36" FIRE SETBACK # REV. INFO DATE
SLOPE - 5°
POINT LOAD AT EACH ATTACHMENT 22.63 LBS ARRAY SLOPE - 20°
AREA OF MODULE 19.63 SQFT. ROOF 1 AZIMUTH - 180°
MODULE QTY - 14
TOTAL ARRAY AREA 274.89 SQFT. RAFTER - 2"X4" @ 48" O.C.
DISTRIBUTED LOAD 2.37 PSF SURFACE TYPE - ROLLED ROOFING
5" OR 7"
M-1 STRUCTURAL SEALANT
M-1 STRUCTURAL ALONG STANDOFF REVISION
SEALANT ALONG PIPE # REV. INFO
1- PART POURABLE SEALER OR DATE
PV MODULE PRO PACK POURABLE SEALER
1" (TYP.)
2" CHEM CURB
REVISION
# REV. INFO DATE
ENPHASE MICROINVERTERS MEET NEC
690.12 RAPID SHUTDOWN REQUIREMENTS MAIN SERVICE PANEL
UPGRADED TO 225A
SOLAR BREAKER LOCATED AT THE BUSBAR & 200A MAIN
FURTHEST END OF BUSBAR FROM THE BREAKER
MAIN BREAKER OR FEEDER UNIT
SHEET TITLE
ELECTRICAL
705.12 DIAGRAM
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
PV-4
INSTALLER/CONTRACTOR
GENERAL NOTES
1. EXISTING PLUMBING VENTS, SKYLIGHTS,EXHAUST 13. EACH SOURCE INTERCONNECTION OF ONE OR MORE 23. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES
OUTLETS, VENTILATION INTAKE AIR OPENINGS SHALL NOT POWER SOURCES INSTALLED IN ONE SYSTEM SHALL BE SMALLER THAN 6 AWG SHALL BE PROTECTED FROM
BE COVERED BY THE SOLAR PHOTOVOLTAIC SYSTEM. MADE AT A DEDICATED CIRCUIT BREAKER OR FUSIBLE PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR. E:\Projects\3. TP\20 June 2023\Christopher Hiura\Image 5-22-23 at 11.20 AM.jpeg
2. EQUIPMENT, INVERTERS, MOTOR GENERATORS, DISCONNECTING MEANS IN ACCORDANCE WITH CEC 705.12. [CEC 690.46 & 250.120(C)]
PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC 14. THE SUM OF THE AMPERE RATING OF THE 24. AN EQUIPMENT GROUNDING CONDUCTOR SHALL NOT BE
PHOTOVOLTAIC MODULES, SOURCE-CIRCUIT COMBINERS, OVERCURRENT PROTECTION DEVICES IN CIRCUITS SMALLER THAN 14 AWG [CEC 690.45]
AND CHARGE CONTROLLERS INTENDED FOR USE IN SUPPLYING POWER TO THE BUSBAR OR CONDUCTOR SHALL 25. GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE INSTALLED
PHOTOVOLTAIC POWER SYSTEMS SHALL BE IDENTIFIED NOT EXCEED 120% OF THE RATING OF BUSBAR OR IN ONE CONTINUOUS LENGTH WITHOUT A
AND LISTED FOR THE APPLICATION. [CEC 690.4(B)] CONDUCTOR IN ACCORDANCE WITH CEC 705.12 SPLICE OR JOINT. IF NECESSARY, SPLICES OR CONNECTIONS SHALL
3. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, 15. A CONNECTION AT EITHER END, BUT NOT BOTH ENDS, BE MADE AS PERMITTED
INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND OF A CENTER-FED PANEL BOARD IN DWELLINGS SHALL BE [CEC 250.64 C)] SIGN./STAMP
NON ROOF SWITCHES. ROOF SWITCHES TO BE NEMA 3R PERMITTED WHERE THE SUM OF 125 PERCENT OF THE 26. ALL SMOKE ALARMS, CARBON MONOXIDE ALARMS AND
RATED. POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE AUDIBLE NOTIFICATION DEVICES SHALL BE LISTED AND LABELED
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND RATING OF THE OVERCURRENT DEVICE PROTECTING THE IN ACCORDANCE WITH UL 217 AND UL 2034. THEY WILL BE
BONDED IN ACCORDANCE WITH CEC ARTICLE 250. BUSBAR DOES NOT EXCEED 120 PERCENT OF THE CURRENT INSTALLED IN ACCORDANCE WITH NFPA 72 AND NFPA 720 [IRC
5. PROTECTION DEVICES FOR PV SOURCE CIRCUITS AND PV RATING OF THE BUSBAR IN ACCORDANCE WITH CEC 705.12. 2019 R314 & R315]
OUTPUT CIRCUITS ALSO CONNECTED TO SOURCES HAVING 16. EQUIPMENT CONTAINING OVERCURRENT PROTECTION 27. SMOKE ALARMS AND CARBON MONOXIDE ALARMS WILL BE
SIGNIFICANTLY HIGHER CURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUS BAR OR RETROFITTED INTO THE EXISTING DWELLING. THESE SMOKE
AVAILABILITY (E.G., PARALLEL STRINGS OF CONDUCTOR SHALL BE MARKED TO INDICATE THE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH
MODULES, UTILITY POWER), SHALL BE PROTECTED AT THE PRESENCE OF ALL SOURCES IN ACCORDANCE WITH CEC BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE
SOURCE FROM OVERCURRENT [CEC 690.9(A)] 705.12. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED
6. PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS 17. CIRCUIT BREAKER, IF BACKFED, SHALL BE SUITABLE FOR OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR
PROJECT NAME & ADDRESS
SHALL INCLUDE A RAPID SHUTDOWN FUNCTION [CEC SUCH OPERATION IN ACCORDANCE WITH CEC 705.12. OF THE HOUSE. THESE ALARMS MAY BE SOLELY BATTERY
690.12] 18. TO MINIMIZE OVERHEATING OF THE BUSBAR IN OPERATED IF THE PHOTOVOLTAIC PROJECT DOES NOT INVOLVE
BARBARA SHEA-HAN
7. THE UTILITY INTERACTIVE INVERTERS SHALL ELECTRICAL ENCLOSURE, THE MAIN CIRCUIT BREAKER AND THE REMOVAL OF INTERIOR WALL AND CEILING FINISHES INSIDE
THE PV POWER SOURCE CIRCUIT BREAKER SHALL BE 32264 ORTEGA HWY,
AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE THE HOME, OTHERWISE, THE ALARMS MUST BE HARD WIRED LAKE ELSINORE, CA 92530
CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION PHYSICALLY LOCATED AT THE OPPOSITE END OF THE AND INTERCONNECTED.
BUSBAR. APN #: 387240003
NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND
SHALL REMAIN IN THAT STATE UNTIL 19. ALL THE CEC REQUIRED WARNING SIGNS, MARKINGS, AHJ: LAKE ELSINORE
THE ELECTRICAL PRODUCTION AND DISTRIBUTION AND LABELS SHALL BE POSTED ON EQUIPMENT AND UTILITY: SCE
NETWORK VOLTAGE HAS BEEN RESTORED. DISCONNECTS PRIOR TO ANY INSPECTIONS.
[CEC 705.41] 20. WHERE PV SYSTEM DC CIRCUIT'S RUN INSIDE A
BUILDING, THEY SHALL BE CONTAINED IN METAL RACEWAYS SYSTEM DETAILS
8. ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE
LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT. [CEC TYPE MC METAL CLAD CABLE OR METAL ENCLOSURES FROM
POINT OF PENETRATION OF THE DC SIZE: 5.180 KW DC (STC)
310.10(D)(1)] AC SIZE: 4.611 KW AC (CEC)
9.THE MODULE CONDUCTORS MUST BE TYPE USE-2 OR SURFACE OF THE BUILDING TO THE FIRST READILY (14) DNA-120MF 26-370W
LISTED FOR PHOTOVOLTAIC (PV) WIRE [CEC 690.31(C)] ACCESSIBLE DISCONNECTING MEANS [CEC 690.31(G)]. (14) ENPHASE IQ8PLUS-72-2-US (240V)
10. ALL CONDUCTORS SHALL BE MARKED ON EACH END 21. FLEXIBLE, FINE-STRANDED CABLES SHALL BE
FOR UNIQUE IDENTIFICATION. TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR
11. AN INSULATED GROUNDED CONDUCTOR OF 6 AWG OR CONNECTORS THAT ARE LISTED IN ACCORDANCE WITH CEC REVISION
SMALLER SHALL BE IDENTIFIED AS A CONTINUOUS WHITE 110.14. # REV. INFO DATE
FINISH [CEC 200.6] 22. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE.
12. THE OUTPUT OF AN INTERCONNECTED ELECTRICAL CONNECTORS THAT ARE READILY
POWER SOURCE SHALL BE PERMITTED TO BE CONNECTED ACCESSIBLE AND OPERATING AT OVER 30V DC OR 15V AC
TO THE LOAD SIDE. INTERCONNECTING SHALL REQUIRE TOOL TO OPEN AND MARKED "DO NOT
PROVISIONS FOR OTHER POWER SOURCES SHALL COMPLY DISCONNECT UNDER LOAD" OR "NOT
FOR CURRENT INTERRUPTING"[CEC 690.33(C) & (E)(2)]. SHEET TITLE
WITH CEC 705.12.
NOTES
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
PV-5
INSTALLER/CONTRACTOR
AND REDUCE
LABEL LOCATION: COMBINER PANEL, AC SHOCK HAZARD
DISCONNECT, POINT OF INTERCONNECTION IN THE ARRAY
PER CODE: CEC 706.15(C)(4), CEC 690.13(B)
SOLAR PV DC CIRCUIT
LABEL LOCATION: DC CONDUIT/RACEWAYS ! CAUTION
PER CODE: CEC 690.31(D)(2) PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED PROJECT NAME & ADDRESS
LABEL LOCATION: MAIN SERVICE DISCONNECT
PHOTOVOLTAIC SYSTEM AC DISCONNECT PER CODE: CEC 705.12(D), CEC 690.59
BARBARA SHEA-HAN
RATED AC OUPUT CURRENT: 16.94 A DO NOT DISCONNECT
CAUTION
32264 ORTEGA HWY,
NOMINAL OPERATING AC VOLTAGE: 240 V UNDER LOAD
LAKE ELSINORE, CA 92530
LABEL LOCATION: AC DISCONNECT/POINT OF INTERCONNECTION LABEL LOCATION: MAIN SERVICE DISCONNECT
PER CODE: CEC 690.54 PER CODE: CEC 690.15(B) & CEC 690.33(D)(2)
APN #: 387240003
ACD
MSP
AC COMBINER
UM
CB
CONNECTION. DO NOT RELOCATE CONNECTION. DO NOT RELOCATE PANEL DRAWN BY DK
THIS OVERCURRENT DEVICE. THIS OVERCURRENT DEVICE.
UTILITY METER SHEET NUMBER
LABEL LOCATION: POINT OF INTERCONNECTION
LABEL LOCATION: POINT OF INTERCONNECTION ORTEGA HWY
PER CODE: CEC 705.12(B)(3)(2)
PER CODE: CEC 705.12(B)(3)(2) MAIN SERVICE PANEL AC DISCONNECT
PV-6
INSTALLER/CONTRACTOR
1-10 11-20 21-30 31-40 41-50 51-60 MICRO-INVERTER CHART
1
E:\Projects\3. TP\20 June 2023\Christopher Hiura\Image 5-22-23 at 11.20 AM.jpeg
SIGN./STAMP
3
BARBARA SHEA-HAN
5
32264 ORTEGA HWY,
LAKE ELSINORE, CA 92530
APN #: 387240003
REVISION
# REV. INFO DATE
SHEET TITLE
9 MICRO-INVERTER
CHART
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
10
PV-7
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
SAFETY PLAN
PV-8
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
JOB HAZARD
ANALYSIS
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
PV-9
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-1
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-2
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-3
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-4
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-5
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-6
INSTALLER/CONTRACTOR
SIGN./STAMP
BARBARA SHEA-HAN
SYSTEM DETAILS
REVISION
# REV. INFO DATE
SHEET TITLE
RESOURCE
DOCUMENT
DRAWN DATE 8/9/2023
DRAWN BY DK
SHEET NUMBER
R-7