PRESSURE TRANSMITTER
OPERATING & INSTRUCTION SHEET
Zero
Test
2. OVERPRESSURE: For the EN50045, pull down and rotate the bottom –P
–
Pressure spikes in excess of the rated over- out. 3.18
Span
Zero
pressure capability of the transducer may V+ V– Out
Multiple units can be stacked accross the rail.
cause irreversible electrical and/or mechanical
Internal circuitry is vented through the bottom of
damage to the pressure measuring and con-
each unit. Tag holes are fabricated into the lower
taining elements.
rear lever and the housing below the terminal
3. STATIC ELECTRICAL CHARGES: strip for calibration reference tagging and/or ID 3.92 .89
DXLdp dimension with SpoolCal and LED options
Any electrical device may be susceptible to location. Refer to Drawing #1.
damage when exposed to static electrical
Power requirements:
charges. To avoid damage to the transducer
The DXLdp is wired (3 wire) (2 wire) for Voltage
the operator/installer should follow proper
and Current output respectively. Reference
ESD (electrostatic discharge) protection
Drawing #2.
procedures before handling the pressure
transducer. Voltage Output Model: DXLdp
4.96
Description: The DXLdp will operate on any supply voltage
Congratulations on your purchase of the from 12-36Vdc drawing less than 10mA in full 3.18
Span
Zero
Ashcroft® Model DXLdp low differential pressure function LED variations (24Vdc typical). V+ V– Out
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com. All specifications subject to change without
notice. All sales subject to standard terms and conditions of sale I&M011-10074 Rev A 5/11
MODEL DXLdp DIFFERENTIAL
PRESSURE TRANSMITTER
OPERATING & INSTRUCTION SHEET
1250
1091
1000
750
545
500
250
0 10 12 20 24 30 36 40
Drawing #3
+ + + RS
POWER POWER
SUPPLY SUPPLY
– – –
Voltage Output Current Output
Drawing #2
OPTION: SPOOLCAL™ (XPV) • Apply zero pressure. This can be best produced
The rotating process valve actuator in conjunction by shorting the HI and LO ports on the SpoolCal™
with the SpoolCal™ actuator tool provides two actuator tool using the silicon tubing supplied.
types of tests including Calibrate (CAL) and Verify or make zero adjustment.
Monitor (MON) through the appropriate Hi and Lo • An external pressure generator can be used to
Port of the SpoolCal actuator tool. In the (CAL) produce the required span pressure. Verify or
mode the DXLdp is isolated from the process and make span adjustment.
allows externally generated test pressure input for
• Measure record signal via front access test jacks,
calibration. In the (MON) mode the system pres-
option (XDL).
sures can be monitored with an Ashcroft ATE
Calibrator or other handheld instrument without Monitor (MON):
physically unplugging the process tubes. In this Provides on line or uninterrupted measurement
mode an on-line measurement can be captured. In point capability when XPV option is again selected
conjunction with the (XDL) option, a reference sig- in combination with the (XDL) option, including
nal can also be captured without process interrup- the front access test jacks.
tion. • Insert SpoolCal™ actuator tool
The (XPV) option supplies a SpoolCal™ actuator • A 90-degree counterclockwise rotation tee’s the
tool and 7˝ of silicon tubing. The actuator tool process to both the DXLdp sensor and out
identifies the above positions and tests, including through the SpoolCal™ actuator tool, to provide
high (HI) and low (LO) differential pressure reference. external measurement or recording capabilities.
OPTION: 2:1 TURN DOWN (X21)
From the (OFF) position the SpoolCal™ actuator
Provides optional in field scalability via internal
tool can be inserted and removed. The following
jumpers.
tests can be performed:
Example: Given a 1.0˝ DXLdp with 4-20mA output.
Calibration (CAL): The unit can be adjusted to operate full scale at
Both zero and Span adjustment pots are non- 0.5˝. In addition, the 4-20mA reference output
interactive and accessible from the front of the unit. remains in calibration.
Note: Due to the sensing technology used rarely
Steps (Following instructions on label):
are actual zero and span adjustments needed.
1. Lay unit on right side. Remove reusable left side
Zero and span pots are available on the basic unit.
label.
Requires XDL and XPV options.
2. Pry off access door and discard.
• Insert SpoolCal™ actuator tool. 3. Using needle nose pliers or twisters, move
• A 90-degree clockwise rotation isolates the jumper from top to bottom position. ASHCROFT, INC.
DXLdp from the process. 4. Reattach label. 250 EAST MAIN STREET, STRATFORD, CT 06614
TEL: 203-378-8281 • FAX: 203-378-0499
5. Reverse range label on face of unit. EMAIL: INFO@ASHCROFT.COM
www.ashcroft.com
© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com. All specifications subject to change without
notice. All sales subject to standard terms and conditions of sale I&M011-10074 Rev A 5/11