Desiccant_DPC_CHEAT_SHEET_Rev2
Desiccant_DPC_CHEAT_SHEET_Rev2
1 On POWERUP shows program version (DD01v01) for 10 sec then shows PRESS ON .
2 Enter TECH MODE (TM) anytime. Press 2+3. To turn enabled optional features ON or OFF.
3 Enter FACTORY MODE (FM) only when OFF. Press 2 + 5. To enable option features.
4 Press OFF to execute 30 sec SHUTDOWN SEQUENCE, opens inlet valves, closes purge valves.
5 Press "i" 5 sec to set time, see inputs and outputs. Press "i" several times to exit.
6 Press SELECT DISPLAY to move to next screen.
7 Press ENT (if displayed) to move to alternate screen, such as ALARMS or % TIME.
8 Press BLANK KEY to go back one screen in Customer Mode.
9 Press BLANK KEY at BEGIN TECH MODE to go back to Customer Mode.
10 Press BLANK KEY at BEGIN FACTORY MODE to go back to Customer Mode.
11 Main Displays are RT DRY LT REGEN and STEP 4 TIME 10300 (sec)
12 ALARM LIST; ENT to see last 20 ALARMS, DATE (dd;mm) and TIMES (hh:mm)
13 OPERATING TIMES; ENT to see Operating Hours; No purge hours; Heater Hours
14 If OFF, hit OFF to get back to PRESS ON
15 Different DPC than Refrig - has 2 line display, is model M91-2-ZK - ZEKS PN 684149
FACTORY SETPOINTS
FACTORY SETPOINTS Technician Setpoints
FEATURE NAME HL EH HB CUST TM FM ADD HDWRE DESCRIPTION FEATURE NAME HL EH HB CUST TM FM ADD HDWRE DESCRIPTION
1 FTS Enable std std std no yes no none alarm indication for Set OP Mode: std std std no yes no none Changes the operating mode for the
failure to switch style of dryer
2 Select DewTrans -100 -100 -100 no yes no none dewpoint transmitter Cool Sweep Mode: off std std no yes no none On power fail, restart at beginning
rating for new probes (zero) or where failed.
3 Select EMS DEV opt opt opt no Select % no none Only on if Dryer has PDP Adjustment -40 -40 -40 no Select % no none Depressurizes system less times per
Dewpoint Transmitter hour based on number
4 Select HDP DEV opt no opt no no no Dewpoint Transmitter EMS opt opt opt optional no yes none Is optional based on controller setup
Option
5 Enable HOT off opt opt no On/Off; no none High Outlet Temp EMS Setpoint opt opt opt On/Off; set Select Dew trans: -40; Display dewpoint and hi humidity
set (Heated Units Only) (Only with EMS) DEW -100 and alarm
TRANS cell.
6 Power Saver (PSV) opt opt opt opt On/Off; Enable; none Used with EMS option RESTART Last/Zero last last last Never Restart Zero Last/Zero none Set based on how the operation of the
(Only with EMS) set Set only unless system pressure dryer is and what it is being used for
will be at zero on failure
or start up
7 Enable Dry Cool no opt opt opt On/Off; none (Heated Units Only) Purge Flow Adjustment % 100 opt opt 0 - 100% none Reduces duration of purge cycle to
set adjustable match inlet conditions of dryer (Ex.
Not enough airflow)
8 Dual Mode std std std opt On/Off opt none Option used for Comp. Interlock std no no On/off On/Off Enable requires relay Used in sync with compressor cycle
running in Htd or Htls (On or Load)(Not For Heated Dryers)
9 Enable PurgeSync opt no no no Relay Required for Will allow dryer to run High Dewpoint Alarm opt opt opt ON/Off yes Enable none Alarm indicating whether or not the
set up when compressor dewpoint is within the setpoint
runs
10 Enable EXT Heat no opt opt no On/Off; Select Used only for Heated High PDP Setpoint opt opt opt minus 10 to minus 40 opt Select none Set based on what the reading is for
set Dryers customers dewpoint demand
11 PID Gain (P) 200 200 200 no 200 Select none Should not be Jog std std std yes Select none Steps through the cycle that timer on
adjusted DPC is currently in
12 PID Gain Reset (I) 50 50 50 no yes Select none Should not be
adjusted
ENABLE PURGESYNC
Press OFF to turn dryer off; OFF ON
SHUTDOWN SEQUENCE ENB EXT HEAT: OFF ON