DPC DESICCANT - CHEAT SHEET

1 On POWERUP shows program version (DD01v01) for 10 sec then shows PRESS ON .
2 Enter TECH MODE (TM) anytime. Press 2+3. To turn enabled optional features ON or OFF.
3 Enter FACTORY MODE (FM) only when OFF. Press 2 + 5. To enable option features.
4 Press OFF to execute 30 sec SHUTDOWN SEQUENCE, opens inlet valves, closes purge valves.
5 Press "i" 5 sec to set time, see inputs and outputs. Press "i" several times to exit.
6 Press SELECT DISPLAY to move to next screen.
7 Press ENT (if displayed) to move to alternate screen, such as ALARMS or % TIME.
8 Press BLANK KEY to go back one screen in Customer Mode.
9 Press BLANK KEY at BEGIN TECH MODE to go back to Customer Mode.
10 Press BLANK KEY at BEGIN FACTORY MODE to go back to Customer Mode.
11 Main Displays are RT DRY LT REGEN and STEP 4 TIME 10300 (sec)
12 ALARM LIST; ENT to see last 20 ALARMS, DATE (dd;mm) and TIMES (hh:mm)
13 OPERATING TIMES; ENT to see Operating Hours; No purge hours; Heater Hours
14 If OFF, hit OFF to get back to PRESS ON
15 Different DPC than Refrig - has 2 line display, is model M91-2-ZK - ZEKS PN 684149
FACTORY SETPOINTS
FACTORY SETPOINTS Technician Setpoints
FEATURE NAME HL EH HB CUST TM FM ADD HDWRE DESCRIPTION FEATURE NAME HL EH HB CUST TM FM ADD HDWRE DESCRIPTION
1 FTS Enable std std std no yes no none alarm indication for Set OP Mode: std std std no yes no none Changes the operating mode for the
failure to switch style of dryer
2 Select DewTrans -100 -100 -100 no yes no none dewpoint transmitter Cool Sweep Mode: off std std no yes no none On power fail, restart at beginning
rating for new probes (zero) or where failed.
3 Select EMS DEV opt opt opt no Select % no none Only on if Dryer has PDP Adjustment -40 -40 -40 no Select % no none Depressurizes system less times per
Dewpoint Transmitter hour based on number
4 Select HDP DEV opt no opt no no no Dewpoint Transmitter EMS opt opt opt optional no yes none Is optional based on controller setup
Option
5 Enable HOT off opt opt no On/Off; no none High Outlet Temp EMS Setpoint opt opt opt On/Off; set Select Dew trans: -40; Display dewpoint and hi humidity
set (Heated Units Only) (Only with EMS) DEW -100 and alarm
TRANS cell.
6 Power Saver (PSV) opt opt opt opt On/Off; Enable; none Used with EMS option RESTART Last/Zero last last last Never Restart Zero Last/Zero none Set based on how the operation of the
(Only with EMS) set Set only unless system pressure dryer is and what it is being used for
will be at zero on failure
or start up

7 Enable Dry Cool no opt opt opt On/Off; none (Heated Units Only) Purge Flow Adjustment % 100 opt opt 0 - 100% none Reduces duration of purge cycle to
set adjustable match inlet conditions of dryer (Ex.
Not enough airflow)
8 Dual Mode std std std opt On/Off opt none Option used for Comp. Interlock std no no On/off On/Off Enable requires relay Used in sync with compressor cycle
running in Htd or Htls (On or Load)(Not For Heated Dryers)

9 Enable PurgeSync opt no no no Relay Required for Will allow dryer to run High Dewpoint Alarm opt opt opt ON/Off yes Enable none Alarm indicating whether or not the
set up when compressor dewpoint is within the setpoint
runs
10 Enable EXT Heat no opt opt no On/Off; Select Used only for Heated High PDP Setpoint opt opt opt minus 10 to minus 40 opt Select none Set based on what the reading is for
set Dryers customers dewpoint demand
11 PID Gain (P) 200 200 200 no 200 Select none Should not be Jog std std std yes Select none Steps through the cycle that timer on
adjusted DPC is currently in
12 PID Gain Reset (I) 50 50 50 no yes Select none Should not be
adjusted

13 PID Gain (D) 10 10 10 Enable Should not be


adjusted
14 PID (PWM Cycle) 120 120 120 none Should not be
adjusted
15 TSTAT Differential no 0 0 0 0 0 none only used for
troubleshooting
16 PRI OP Mode HTLS HTD BLWR opt Select Enable none Standard with HTD or
mode BLWR
17 (-100) Enable On/Off no no no On/Off Enable DP TRANS plus Depending on type of
PWR SAVER desiccant used for
dryer
18 Purge Temp no std std HTR Temp HTR opt none Used only for Purge
Temp Air Heatd Dryer
Setpoint

Bergh 4/5/06 Desiccant_DPC


CHEAT SHEET.xls
To get into System Settings Press
and hold the I button for 5
seconds. "Inputs / outputs" will be
displayed. Press arrow 3 times to
get to (System) Press enter and
display "time and date".
DPC DESICCANT - DISPLAYS

POWER UP: Alternate:


ZEKS DD01 V01

OPERATOR DISPLAYS: ALARM DISPLAYS: FACTORY MODE DISPLAYS:


move forward by SELECT DISPLAY button; Press 2 then 5 then 3 to get into FACTORY MODE.
move back by BLANK button only with dryer off.
PRESS ON BEGIN ALARMS Press SELECT DISPLAY to move forward.
Press BLANK button to move back. Press BLANK at\
ALARM LIST See ALARM DISPLAYS ALARM OFF ON BEGIN FACTORY MODE to return to OPERATOR
PRESS ENTER display (PRESS ON).
OPERATING TIMES See OPERATING TIMES HI HUMID ALARM BEGIN FACTORY MODE
PRESS ENTER DISPLAYS TM 1423 DAT 1203 mm:hr DD;MM
OPERATING MODE ENABLE FTS: OFF ON
HEATLESS HTD or BLOWER PRG Press SELECT DISPLAY
LT DRY RT REGEN RT DRY LT REGEN to move forward through last SELECT DEWTRANS
20 alarms NONE -40, -100 (+- to change)
STEP 1 TIME 1 STEP XX TIME XXXXX SELECT MLC DEV
Press BLANK to return to NONE DPTRANS, BRD
DEWPOINT TEMP Customer Displays SELECT HH DEV
-45 NONE DPTRANS, BRD
NO PURGE PURGE ENABLE HOT: OFF ON

HEATER OFF ON ENB PWR SVR: OFF ON

BLOWER OFF ON ENB DRY COOL: OFF ON

HTR TEMP: 375 DUAL MODE: OFF ON

ENABLE PURGESYNC
Press OFF to turn dryer off; OFF ON
SHUTDOWN SEQUENCE ENB EXT HEAT: OFF ON

Returns to PRESS ON screen PID GAIN (P)


200 (0.1%) SET, entry, ENTER
PRESS 2 + 3 TOGETHER TO ENTER TECHNICIAN MODE: TIMES and % Displays: PID RESET (I)
move forward only press SELECT DISPLAY button 50 (1s) SET, entry, ENTER
BEGIN BEGIN TIMES % PID DEV (D)
TECHNICIAN MODE 10 (1s) SET, entry, ENTER
SELECTDRY OPERATING HOURS PID PWM CYCLE TM
DEW POINT: -40 -4 OR 40 OR (-100) 00000000XX 120 (10s) SET, entry, ENTER
MOISTURE LOAD NO PURGE HOURS TSTAT DIFF: 0 not used
CONTROL: OFF ON (IF ENABLED) 00000000XX
MLC SET POINT: HEATER HOURS PRI OP MODE: HTLS HTD, BLWR
0 00000000XX
RESTART: ZERO AT FAIL % SAVINGS -100 ENABLE: OFF ON
0%
PURGE MIZER PWR SVR TEMP: 200 +- to enter
% PURGE SELECT: 100 90, 80……40, 30
PURGE SYNC: Press SELECT DISPLAY
OFF ON Press BLANK to return to
HIHUMID ALARM Customer Displays
OFF ON
HI HUMID SETPOINT
0 DEFAULT IS -10
JOG PRESS ENTER
WAIT JOG Steps 6, 9, 20, 23

at BEGIN TECHNICIAN MODE, press BLANK button


to return to Customer Screens
Generic, All Purpose Timing chart and IO TABLE 4/12/2006 CJB Desiccant_DPC Cheatsheet

relay: O0 O2 O1 O3 EO3 E02 E01 O4 EO0 TE = 0 TE = 30 TE = 60 TE = 90 TE = 120 TE = 150 TE = 180 TE = 210


valve config: NO NC NO NC NC NC NC <---------------ZPA---------------------------------->
Step function: Rtin RTprg Ltin LTprg Rprs Ltdep Rtdep -100 -40 -4 40 ZHA ZBA ZBAcac ZH/ZBhtls
No Action Pltwr Prtwr V1 V2 V3 V4 V5 V6 V7 HTR BLWR Time Time Time Time Time Time Time Time
1 Open LT Inlet val hi hi O C O C C C C off off 3 3 3 3 3 3 3 3
2 Close RT Inlet val hi hi C C O C C C C off off 3 3 3 3 7 7 7 3
3 Open RT Depress val hi lo C C O C C C O off off na na na na 10 130 130 20
4 Open RT Purge val/Close RT depress val hi lo C O O C C C C off off 104 249 429 669 10 10 10 244 3
5 Turn on blower hi lo C O O C C C C off on na na na na na 10 10 na 7
6 Enable heater (PID function) hi lo C O O C C C C on on na na na na 10770 13440 10640 na 130
7 Enabled: JOG, MLC, PwrSvr, ExtHtg,Prgloc,%prg hi lo C O O C C C C on on na ok ok ok ok ok ok ok 10
8 Disable heater hi lo C O O C C C C off on na na na na 3420 600 600 na 10
9 Turn off blower hi lo C O O C C C C off off na na na na na 20 0 na 13440
10 Open RT purge val (Dry Purge - enable JOG) hi lo C O O C C C C off off na na na na na na 2870 na 600
11 Close RT purge val (%prg calc) hi hi C C O C C C C off off 2 44 44 44 10 10 2 2 20
12 Open Repress val hi hi C C O C O C C off off 7 na na na 169 169 127 27 10
13 Close Repress val hi hi C C O C C C C off off 0 na na na 1 1 1 1 169
14 MLC Standby hi hi C C O C C C C off off 1 1 1 1 ok ok ok ok 1
15 Open RT inlet val hi hi O C O C C C C off off 3 3 3 3 3 3 3 3 14400 Second
16 Close LT Inlet val hi hi O C C C C C C off off 3 3 3 3 7 7 7 3 3600 second
17 Open LT Depress val lo hi O C C C C O C off off na na na na 10 130 130 20 4 Hours
18 Open LT Purge val/Close LT depress val lo hi O C C O C C C off off 104 249 429 669 10 10 10 244
19 Turn on blower lo hi O C C O C C C off on na na na na na 10 10 na
20 Enable heater (PID function) lo hi O C C O C C C on on na na na na 10770 13440 10640 na
21 Enabled: JOG, MLC, PwrSvr, ExtHtg,Prgloc,%prg lo hi O C C O C C C on on na na na na ok ok ok ok
22 Disable heater lo hi O C C O C C C off on na na na na 3420 600 600 na
23 Turn off blower lo hi O C C O C C C off off na na na na na 20 0 na
24 Open LT purge val (Dry Purge - enable JOG) lo hi O C C O C C C off off na na na na na na 2870 na
25 Close LT Purge val (%prg cal) hi hi O C C C C C C off off 2 44 44 44 10 10 2 2
26 Open Repress val hi hi O C C C O C C off off 7 na na na 169 169 127 27
27 Close repress val hi hi O C O C C C C off off 0 na na an 1 1 1 1
28 MLC Standby hi hi O C O C C C C off off 1 1 1 1 ok ok ok ok
29 Repeat step 1 hi hi O C O C C C C off off 0 0 0 0 0 0 0 0