• Heat recovery units RPF have been designed density 45 kg/m3. The expandent of the polyu- Its performance is not inferior to 90% (EN308)
for commercial applications and permits to rethane foam is based on water permitting to in function to the external conditions: Air of
combine an excellent ambient comfort with a reach GWP=0 (Global Warming Potential). intake: -10°C/90% - Air of extract 20°C/50% and
sure energy saving. The casing is in fire reaction class M1 according equal capacities between supply and extract.
Always more in the modern plant design there to the French regulation NF P 92-512:1986. It is included also the function of automatic
is the demand to have a Controlled Mechanical Removable panels are also foreseen to access defrosting made easy by the internal modulat-
Ventilation, which implies the expulsion of con- to internal components, equipped with safety ing rolling shutter and from the possible modu-
ditioned air, determining a higher consumption locks, condensate drain and internal modulat- lation with intake flow.
of energy and consequently an increase of pric- ing rolling shutter of motorized and controlled
es. bypass for free-cooling. • Regulation
The units RPF thanks to the cross-current Costituted by power electric panel and pro-
heat recuperator permit to save more than • Fans of supply and extract of plug-fan-type grammable controller with integrated graphic
90% of energy which otherwise would be lost with synchronous motor with electronic con- display. Everything is internally fitted in the unit
with expelled stuffy air. trol permanent magnetos (EC). The impellers in an accessible position.
are oriented in such a way to grant an optimal The function of regulation are:
RPF could be integrated with traditional sys- air flow which goes through the internal com- 1. Ventilation control (manual control of the
tems realized with fan coils, chillers, and could ponents, with the minimum noise. standard fans speed);
work both in winter and in summer. This series 2. Thermo-regulation completed with all elec-
is indicated for both horizontal and vertical • Air filtration with a filter with G4 efficiency tric/electronic components (modality of regu-
installation. (according to EN779) with low pressure drops lation in standard extract);
on extracted air flow and a compact filter and 3. Integrated logics of energy savings: modulat-
Configurations with efficiency F7 (according to EN779) having ing free-cooling / free-heating, anti-freeze,
• RPF_O Horizontal right supply (not available a large filtrating surface made of glass microfi- night cooling, air quality control, dynamic set
for size 42) bre paper, inserted in the intake flow. point, speed economy of ventilation , ranges
• RPF_P Horizontal left supply (not available The two typologies of filters are positioned of time;
for size 42) upstream of the components to be protected, 4. Complete interfaceability with BMS systems.
• RPF_V Vertical right supply in order to grant low pressure drops, having a
• RPF_Z Vertical left supply large surface available.
Each of the different configurations could be fur- The filtrating cells are fixed on a proper bearing
ther customized thanks to the choice of the frame to avoid any by-pass of non-treated air.
accessories (please refer to the technical docu- Their extractability is guaranteed from a proper
mentation) side opening (standard), superior or inferior
(optional) [with reference to the horizontal ver-
• The structure is formed by aluminium pro- sion].
files with thermic cut, connected by nylon • Static high efficiency cross-current heat recov-
angles charged with glassfibre. ery unit with high efficiency and aluminium
The sealing panels, of 50 mm thickness, are of plate.
the sandwich type in pre-painted plate RAL The heat recovery unit guarantees the non-
9002 (external) and galvanized sheet iron contamination of air flows, because the plates
(internal) insulated with polyurethane with are properly sealed.
Functionality and technological advantages
The elimination from closed rooms of the polluting Basic configuration
elements, produced mainly from people and the
simultaneous external air input, are at the basis of the
concept of controlled mechanical ventilation (VMC)
of the internal rooms. RPF O Horizontal configuration RPF P Horizontal configuration
The purpose of ventilation is to raise the standard of Right supply (seen from above) Left supply (seen from above)
internal air quality with consequent positive effects
for health and productivity of the occupiers. The
change of air has positive effects also on the good
S D
maintenance of the building.. For the building to be E I
requalified, the Controlled Mechanical Ventilation is
almost a mandatory choice in order to reach high
energy standards, which are imposed by the current E I
legislation. S D
• MAXIMUM EFFICIENCIES
In this context RPF is proposed as the high effi-
cient and performing solution for double flow
ventilation systems with heat recovery.
The key-concept on which is based the RPF pro-
posal are:
• Very high efficiency heat recovery attested by
EUROVENT certification and maintenance of the
complete separation of intake and discharge air
flow;
Reduced ventilation energy consumptions,
thanks to a detailed dimensioning of the compo-
nents in order to have low total values of SFP
(Specific Fan Power or rather energy consump-
tion for m3/h of total processed capacity);
Fans of supply and extract of plug-fan-type with synchronous motor with
High efficiency filtration and low pressure drops; electronic control permanent magnetos (EC)
Advanced electronic management for the ener-
gy saving and of controlling of internal pollut-
ants functions VOC (Volatile Organic
Compounds);
• Compactness of dimensions and logic of installa-
tion “plug and play”.