You are on page 1of 2

About contact us Disclaimer Copyright Subscribe Submit Articles Forum Helping Hand Part Time Job Search …   

ALL ANIMATION BASICS  MEASUREMENT  CONTROL SYSTEMS  Q&A  ELECTRONICS  ELECTRICAL  TOOLS MORE 

ALL ANIMATION BASICS  MEASUREMENT  CONTROL SYSTEMS  Q&A  ELECTRONICS  ELECTRICAL  TOOLS MORE 

Ads by Google

Calibration Instrument Procedure Instrument Ratio Calculator

Calibrate How Instrument Flow Transmitter Limit Switch

Pitot Static Air Data Test Set - High precision test systems

Ad Pitot Static Air Data Test Sets for testing military & commercial aircraft

testvonics.com

Learn more

 Home / Calibration / Instrument Turndown Ratio

CALIBRATION

Instrument Turndown Ratio


 S Bharadwaj Reddy  Leave a comment

Calibration: What is it - Download our free white paper


What is balance calibration and why is it important? mt.com/White+Paper/Service

Ads by Google
Like 2 Tweet Share
Share 0 Share 32
Calibration Instrument Procedure
Instrument Turndown Ratio
Calibrate How Instrument
An important performance parameter for transmitter instruments is something often referred to as turndown or rangedown.
Limit Switch
“Turndown” is de ned as the ratio of maximum allowabe span to the minimum allowable span for a particular instrument.
PLC Control
Suppose a pressure transmitter has a maximum calibration range of 0 to 300 pounds per square inch (PSI), and a turndown of
20:1. This means that a technician may adjust the span anywhere between 300 PSI (e.g. range = 0 to 300 PSI) and 15 PSI (e.g. range
= 0 to 15 PSI). This is important to know in order to select the proper transmitter for any given measurement application. The odds Categories
of you nding a transmitter with just the perfect factory-calibrated range for your measurement application may be quite small,
meaning you will have to adjust its range to t your needs. The turndown ratio tells you how far you will be able to practically Select Category
adjust your instrument’s range.

Ads by Google

BALTECH
Calibration Instrument Procedure
New explosion-proof vibration analyzer

Calibrate How Instrument


Ad vibropoint.com Visit Site

Flow Meter Instrument

Level Transmitters

For example, suppose you were working at a facility where the operations personnel requested a pressure transmitter installed on
RISE OF A NEW EMPIRE
a process vessel with a measurement range of 50 PSI to 90 PSI. You go to the warehouse where all the new instruments are
stocked, and nd a pressure transmitter with a (maximum) range of zero to 1000 PSI, and a turndown ratio of 20:1. Dividing the
maximum span of 1000 PSI by 20, we arrive at a minimum span of 50 PSI. The span requested by operations for this pressure A NETFLIX ORIGINAL SERIES

transmitter is 40 PSI (90 PSI − 50 PSI), which means the transmitter you found in the warehouse will not be able to “turn down”
that far. At best, we could range it for 50 PSI to 100 PSI, or perhaps for 40 PSI to 90 PSI, but not the 50 PSI to 90 PSI requested by
All episodes now available.
operations. At this point, you could return to the operations personnel to ask if a 50 PSI span would be acceptable – if not, you will
WATCH NOW
have to order a di erent pressure transmitter with a smaller span (or with a greater turndown ratio).

Another important consideration with turndown is the accuracy of the instrument at the stated turndown. The further an
instrument is “turned down” from its maximum span, generally the worse its accuracy becomes at that reduced span. For
example, the Micro Motion “ELITE” series of Coriolis mass owmeters are advertised to perform within an accuracy envelope of Like our FB Page – Get Updates
±0.05% at turndown ratios up to 20:1, but that measurement uncertainty increases to ±0.25% at a turndown of 100:1, and to
±1.25% at a turndown of 500:1. It should be noted that the degradation of measurement accuracy at large turndown ratios is not InstrumentationTools
some defect of Micro Motion owmeters (far from it!), but rather an inescapable consequence of pushing an instrument’s 66,950 likes

turndown to its limit.

Like Page Learn More


Typical turndown ratio of various meter types


The examples are here for gas ow, but the same meter types can be used on liquids as well, with similar turndown ratios. Note Latest Comments
ALL ANIMATION BASICS  MEASUREMENT  CONTROL SYSTEMS  Q & A  ELECTRONICS  ELECTRICAL  TOOLS MORE
that meter manufacturers state their products’ turndown ratios—a speci c product may have a turndown ratio that varies from
the list below. kalidhrashanee
fantastic explanation. simple and great.
even non instrument...
1. A Thermal Mass Flow Meter has a turndown ratio of 1000:1.
2. An ori ce plate meter has a practical turndown ratio of 3:1. Feeroz
Information...
3. A Turbine Meter has a turndown ratio of 10:1.
4. Rotary positive displacement meters have a turndown ratio of between 10:1 and 80:1, depending on the manufacturer and the Asif Attari
application. For control valve seat leakage, now as per
new standard ANSI...
5. Diaphragm meters are considered to have a turndown ratio of 80:1.
6. Multipath ultrasonic meters often have a stated turndown ratio of 50:1. amore
thank you this was very informative and
helpful...
Credits : by Tony R. Kuphaldt – Creative Commons Attribution 4.0 License
ubaidillah
actually sir, i have class networking and
Print Facebook Twitter Email More 34 lecture asking bao...

Md Rizwanullah
Nice information sir...

S Bharadwaj Reddy
Step by Step Procedure sent to your email.
Please check....

Process Controllers - Smart Transmitters LRV & Top Quality Flowmeters - What is calibration
Canopus Instruments URV Instrumentation Liquids and Gasses
Tools
Ad canopusinstruments.com instrumentationtools.com Ad flo-gage.com instrumentationtools.com

Try Netflix
WATCH NOW
One Month Free

Vehicle GPS Locating Coriolis Mass Flow Meter Closed Tank DP Type Importance of Hysteresis
Device - Trace & Locate Working Animation Level Measurement with Loop Instrumentation
Your Vehicles Instrumentation Tools wet leg and transmitter... Tools Inst Tools Android App
Ad shop.yepzon.in instrumentationtools.com instrumentationtools.com instrumentationtools.com

Previous Post: Next Post:

 Logic Gates in PLC Ladder Logic What is IEC 61508 ? 


Inst Tools IOS App

Related Articles

CALIBRATION • GUEST ARTICLES • LEVEL MEASUREMENT ANALYZERS • CALIBRATION

Displacer Level Transmitter Dry Calibration with Turbidity Sensor Calibration Procedure
Weights  May 14, 2015

 November 20, 2017


Language Translate :
CALIBRATION • LEVEL MEASUREMENT CALIBRATION

Closed tank DP Level Transmitter with wet leg How to Test a Pressure Gauge
Select Language
elevation zero direct mount Calibration  October 16, 2016

 May 21, 2015

CALIBRATION CALIBRATION

Important Terms in Calibration Trim Pressure Gauge Functional Testing


 August 29, 2016  October 27, 2017

CALIBRATION • GUEST ARTICLES • VIBRATION MEASUREMENT CALIBRATION

Bently Nevada Vibration Probes Functional Testing Field Instrument Calibration Errors
 October 20, 2017  August 16, 2016

CALIBRATION • VIBRATION MEASUREMENT ANALYZERS • CALIBRATION • GUEST ARTICLES

How to do calibration checks of vibration Probe, Conductivity Transmitter Calibration Procedure


extension cable and vibration monitor  January 7, 2018

 May 29, 2015

CALIBRATION • LEVEL MEASUREMENT CALIBRATION

DP Diaphragm Capillary Seal Level instrument Difference between Calibration and Ranging
Calibration Procedure  March 5, 2017

 October 9, 2015

You might also like