REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 500
TECHNICAL
HELVAR Electronic Ballasts
TECHNICAL DATA
Lamp Total Circuit Mains Power Power
Wattage Power Current in lamp Frequency Losses
Type (W) (W) (A) (W) (kHz) (W) Dimensions Wiring
EL 1x18 HF 1x18 19 0.10 16 ca. 26 ca. 3 1 1
230-240 V 50-60 Hz
EL 1x36 HF 1x36 36 0 16 32 ca. 26 ca. 4 1 1
230-240 V 50-60 Hz
EL 1x58 HF 1x58 56 0.24 50 ca. 27 ca. 6 1 1
230-240 V 50-60 Hz
EL 1x70 HF 1x70 66 0.29 60 ca. 27 ca. 6 1 1
230-240 V 50-60 Hz
EL 2x18 HF 2x18 36 0.16 16 ca. 27 ca. 4 2 2
230-240 V 50-60 Hz
EL 2x36 HF 2x36 70 0.31 32 ca. 27 ca. 6 2 2
230-240 V 50-60 Hz
EL 2x58 HF 2x58 110 0.51 50 ca. 27 ca. 10 2 2
230-240 V 50-60 Hz
EL 2x70 HF 2x70 133 0.54 60 ca. 27 ca. 13 2 2
230-240 V 50-60 Hz
EL 3x18 HF 3x18 55 0.25 16 ca. 30 ca. 7 3 3
220-240 V 50-60 Hz
EL 4x18 HF 4x18 74 0.32 16 ca. 30 ca. 10 3 4
220-240 V 50-60 Hz
BALLAST DIMENSIONS
8 Dimensions 1 2 3
A (mm) 270 350 415
B (mm) 280 360 430
C (mm) 30 30 30
D (mm) 28 28 28
Weight (g) 270 340 400
501 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Electronic Ballasts
Note: All wiring to the connectors marked with a black dot; (hot wires) should be as short as possible
CHARACTERISTICS
Maximum allowed Temperature at Test Point 80 °C Life time 90 000 h, 60 °C at test point
Ambient Temperature Range 0 . . .+50 °C Mains voltage tolerance Un ±10 %
Maximum Relative Humidity No Condensation Mains quality; all data is based on a pure sinusoidal mains
supply, see Helvar document AL 702006
Storage Temperature Range –40 . . .+80 °C
Can be used on DC, acc. to VDE 0108
Vibration Test EN 60068-2-64 Test Fh
DC range; 180 - 300 VDC
Bump test EN 60068-2-29 Test Eb
Fulfils generic immunity standard EN 50082-1
Warm Start, Cathode Pre-Heat acc. to EN 60929*)
Emission according to
Standard (EN 60081) Fluorescent Lamps Used
Mains current harmonics EN 61000-3-2
Lamp Life according to EN 60081, 3 h cycle
Radio frequency interference EN 55015
Lamp Lumen Output is the same as with
Over Voltage Duration 320 VAC, 1 h
conventional Ballasts
Power Factor 0.98
Fulfils the Standards:
Earth Leakage Current < 0.5 mA
General & Safety Requirements EN 60928
Performance requirements EN 60929*)
*EL3x18HF and EL4x18HF. Warm start acc. to Helvar standard
High number of starts per lamp ca. 20 000 (not acc. to EN 60929).
“STAND-BY” STATE
"Stand-by" is an internal safety circuit in the ballast. The ballast goes into the "Stand-by"-state and the ballast switches the lamps
off when a lamp becomes deactivated.
8
If the supply is on during relamping, disconnect both lamps simultaneously for 1 second, then the ballast will start automatically.
If there are no lamps connected, the ballast will not start at all and will not go to "Stand-by"- state either.
LAYOUT RECOMMENDATION
In order to minimise radio interference problems we recommend that the mains wiring and the lamp wiring are kept as far as
possible from each other. In no case must they be bunched together for long distances. They can however cross each other. The
ballast shall be installed in the same fixture with the lamps. The wires from the ballast to a lamp may not be longer than 2 m. Solid
Core Conductor -type 0.5 - 1.5 mm2 is to be used as connecting wire.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 502
TECHNICAL
HELVAR Slim Electronic Ballasts
TECHNICAL DATA
Lamp Total Circuit Mains Power Operating Power
Wattage Power Current in lamp Frequency Losses Connection
Type (W) (W) (A) (W) (kHz) (W) Dimensions Diagram EEI
EL 1x14-35 s 1x14 16 0.08 14 46 2 1 1 A2
1x21 23 0.11 21 46 2 1 1 A2
1x28 30.5 0.14 28 46 2.5 1 1 A2
1x35 38 0.18 35 46 3 1 1 A2
EL 1x24 s 1x24 25 0.11 22.5 59 2.5 1 1 A2
EL 1x39 s 1x39 42 0.19 39 53 3 1 1 A2
EL 1x49 s 1x49 53 0.24 49 27 4 1 1 A2
EL 1x54 s 1x54 58 0.26 54 42 4 1 1 A2
EL 1x80 s 1x80 85 0.37 80 45 5 1 1 A2
EL 2x14-35 s 2x14 31 0.14 14 46 3 2 2 A2
2x21 45 0.20 21 46 3 2 2 A2
2x28 60 0.27 28 46 4 2 2 A2
2x35 76 0.34 35 46 6 2 2 A2
EL 2x24 s 2x24 49 0.22 22.5 59 4 2 2 A2
EL 2x39 s 2x39 84 0.37 39 53 6 2 2 A2
EL 2x49 s 2x49 105 0.46 49 27 7 2 2 A2
EL 2x54 s 2x54 116 0.51 54 42 8 2 2 A2
EL 3/4x14 s 3x14 47 0.22 14 46 5 2 3 A2
4x14 62 0.29 14 46 6 2 4 A2
BALLAST DIMENSIONS
Dimensions 1 2
A (mm) 270 350
8 B (mm) 280 360
C (mm) 30 30
D (mm) 21 21
Weight (g) 215 285
503 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Slim Electronic Ballasts
Note: All wiring to the connectors marked with a black dot; (hot wires) should be as short as possible
Wire Preparation: 7.5mm +_ 1mm
CHARACTERISTICS
Maximum allowed temperature at test point 80 °C Life time 90 000 h, 60 °C at test point
Ambient temperature range Suitable for Class II fittings
EL 1x14-35 s, EL2x14-35 s & Over voltage duration 320 VAC, 1 h
EL3/4x14 s -20...+50 °C Mains voltage tolerance Un ±10 %
Others 0...+50 °C Can be used on DC, EN 60598-2-22
Thermal protection class EN 60928 B.5e
DC range; 200 - 300 VDC
Maximum relative humidity no condensation
Maximum working voltage U-OUT = 400 V
Storage temperature range -40...+80 °C
Fulfils immunity standard EN 61547
Vibration test EN 60068-2-64 test Fh
Emission according to
Bump test EN 60068-2-29 test Eb
Warm start, acc. to EN 60929 Mains current harmonics EN 61000-3-2
Starting time <1.5 sec. Radio frequency interference EN 55015
General and safety requirements EN 60928 Typical earth leakage current 0.2-0.4 mA
Performance requirements EN 60929 Typical lamp current crest factor 1.45
High number of starts per lamp > 50 000 Typical power factor 0.98
“STAND-BY” STATE
"Stand-by" is an internal safety circuit in the ballast. The ballast goes into the "Stand-by"-state and the ballast switches the lamps
off when the lamps become defective.
If the supply is on during relamping, the ballast will start automatically. If there are no lamps connected, the ballast will not start
at all and not go to "Stand-by"-state either.
8
LAYOUT RECOMMENDATION
In order to minimise radio interference problems we recommend that the mains wiring and the lamp wiring are kept as far as
possible from each other. In no case must they be bunched together for long distances. They can however cross each other.
If a metal plate is positioned closer than 10mm to the lamp the metal plate must be electrically connected to the ballast case. Even
with longer distances this electrical connection is recommended.
The wires from the ballast to a lamp may not be longer than 2 m. The ballast is designed as a "built-in" product and should be
installed in the same fixture as the lamps it operates.
Master-Slave operation is not advised.
Solid Core Conductor -type 0.5 - 1.5 mm2 is to be used as connecting wire.
Safety: Lampholders must be rated up to 500 V.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 504
TECHNICAL
HELVAR Electronic Ballasts
TECHNICAL DATA
Lamp Total Circuit Mains Power Power
Wattage Power Current in lamp Frequency Losses
Type (W) (W) (A) (W) (kHz) (W) Dimensions Wiring
EL 1x18 HFC 1x18 20 0 0.11 16 32-70 4 1 1
230-240 V 50-60 Hz
EL 1x36 HFC 1x36 38 0.17 32 40-70 6 1 1
230-240 V 50-60 Hz
EL 1x58 HFC 1x58 58 0.26 50 40-70 8 1 1
230-240 V 50-60 Hz
EL 2x18 HFC 2x18 38 0.18 16 34-62 6 2 2
230-240 V 50-60 Hz
EL 2x36 HFC 2x36 72 0.32 32 30-60 8 2 2
230-240 V 50-60 Hz
EL 2x58 HFC 2x58 116 0.50 50 30-60 16 2 2
230-240 V 50-60 Hz
BALLAST DIMENSIONS
Dimensions 1 2
A (mm) 270 350
B (mm) 280 360
C (mm) 30 30
D (mm) 21 21
8 Weight (g) 215 285
505 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Electronic Ballasts
Note: All wiring to the connectors marked with a black dot; (hot wires) should be as short as possible
CHARACTERISTICS
Maximum allowed temperature at test point 75/80 °C Mains quality;all data is based on a pure sinusoidal mains
Ambient temperature range 0...+50 °C supply, see Helvar document AL 702006
Maximum relative humidity no condensation Can be used on DC, acc. to VDE 0108
Storage temperature range -40...+80 °C DC range; 180 - 300 VDC
Warm start, cathode pre-heat acc. to EN 60929 Fulfils generic immunity standard EN 50082-1
Standard (IEC 81) fluorescent lamps used Emission according to
Lamp life according to EN 60081, 3 h cycle Mains current harmonics EN 61000-3-2
Fulfils the standards: Radio frequency interference EN 55015
General and safety requirements EN 60928 Over voltage endurance 300 VAC
Performance requirements EN 60929 Power factor 0.98
High number of starts per lamp ca. 20 000 Earth leakage current < 0.5 mA
Life time 90 000 h, 50 °C at test point Control bus (1-10V DC) acc. to EN 60929
Mains voltage tolerance Un ±10 % Control current <1.0 mA/Ballast
“STAND-BY” STATE
"Stand-by" is an internal safety circuit in the ballast. When a lamp becomes deactivated, the ballast goes into the "Stand-by"-state
and the ballast switches the lamps off when the lamps become defective.
If the supply is on during relamping, the ballast will start automatically. If there are no lamps connected, the ballast will go into
the "Stand-by"-state.
LAYOUT RECOMMENDATION
In order to minimise radio interference problems we recommend that the mains, control and the lamp wiring are kept as far as
possible from each other. In no case must they be bunched together for long distances. They can however cross each other. The 8
ballast shall be installed in the same fixture with the lamps.
The wires from the ballast to a lamp may not be longer than 2 m. Solid Core Conductor - type 0.5 - 1.5 mm2 is to be used as
connecting wire. Do not use multistranded wires. Control wires must have an insulation rating greater or equal to mains supply
wires. The minimum recommended distance between these wires is 1 cm inside the fitting.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 506
TECHNICAL
HELVAR Slim Controllable Electronic Ballasts
For T5 Lamps Range EL-SHFC, 220-240v, 50-60Hz
TECHNICAL DATA
Lamp Total Circuit Mains Power Operating Power
Wattage Power Current in lamp Frequency Losses Connection
Type (W) (W) (A) (W) (kHz) (W) Dimensions Diagram EEI
EL 1x14 sc 1x14 16 0.07-0.06 14 43-100 2 1 1 A1
EL 1x21 sc 1x21 24 0.11-0.10 21 43-100 3 1 1 A1
EL 1x24 sc 1x24 27 0.13-0.12 24 43-100 3 1 1 A1
EL 1x28 sc 1x28 31 0.15-0.14 28 43-100 3 1 1 A1
EL 1x35 sc 1x35 39 0.18-0.17 35 43-100 4 1 1 A1
EL 1x39 sc 1x39 43 0.20-0.18 39 43-100 4 1 1 A1
EL 1x49 sc 1x49 54 0.25-0.23 49 43-100 5 1 1 A1
EL 1x54 sc 1x54 60 0.28-0.26 54 43-100 6 1 1 A1
EL 1x80 sc 1x80 88 0.41-0.38 80 43-100 8 1 1 A1
EL 2x14 sc 2x14 31 0.15-0.14 14 43-100 3 2 2 A1
EL 2x21 sc 2x21 47 0.22-0.20 21 43-100 5 2 2 A1
EL 2x24 sc 2x24 53 0.24-0.20 24 43-100 5 2 2 A1
EL 2x28 sc 2x28 62 0.30-0.28 28 43-100 6 2 2 A1
EL 2x35 sc 2x35 78 0.36-0.34 35 43-100 8 2 2 A1
EL 2x39 sc 2x39 86 0.40-0.36 39 43-100 8 2 2 A1
EL 2x49 sc 2x49 107 0.50-0.46 49 43-100 9 2 2 A1
EL 2x54 sc 2x54 118 0.56-0.52 54 43-100 10 2 2 A1
BALLAST DIMENSIONS
Dimensions 1 2
A (mm) 350 420
B (mm) 360 430
8
C (mm) 30 30
D (mm) 21 21
Weight (g) 285 365
507 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Slim Controllable Electronic Ballasts
For T5 Lamps Range EL-SHFC, 220-240v, 50-60Hz
CONNECTION DIAGRAMS
Note: All wiring to the connectors marked with a black dot; (hot wires) should be as short as possible
SWITCH-CONTROL CONNECTION
The switch used should be of the automatic return variety. The connection of the switch should be between the 'switch-control'
input and the Neutral (or Live) connection. Switch-Control should only be connected to ballasts on the same mains phase.
Notes: Mains voltage is still present at the mains input terminals if the lamps are switched off via the switch-control. The switch
should be mains rated. Max. length of switch-control wiring = 50 meters.
CHARACTERISTICS
Maximum allowed temperature at test point 80 °C Mains voltage tolerance Un ±10 %
Ambient temperature range +10...+50 °C Can be used on DC, DC range; 200 - 300 VDC
Thermal protection class EN 60928 B.5e Maximum working voltage: U-OUT = 400 V
Maximum relative humidity no condensation Fulfils immunity standard EN 61547
Storage temperature range -40...+80 °C
Emission according to
Vibration test EN 60068-2-64 test Fh
Mains current harmonics EN 61000-3-2
Bump test EN 60068-2-29 test Eb
Radio frequency interference EN 55015
Warm start, acc. to EN 60929
Typical earth leakage current 0.2-0.4 mA
Starting time <1.5 sec.
Typical lamp current crest factor 1.45
General and safety requirements EN 61347-2-3
Performance requirements EN 60929 Typical power factor 0.98
High number of starts per lamp > 50 000 Control bus,
Life time 90 000 h, 60 °C at test point C1/C0 (1-10V DC) acc. to EN 60929
Over voltage duration 320 VAC, 1 h Control current <1.0 mA/Ballast
“STAND-BY” STATE
"Stand-by" is an internal safety circuit in the ballast. The ballast switches the lamps off and goes into the "Stand-by" state when a
lamp becomes defective.
If the supply is on during relamping, the ballast will start automatically.
Stand-by can be activated from the switch-control. The ballast will go to stand-by if the mains voltage drops to a low level.
8
LAYOUT RECOMMENDATION
To minimise RFI problems the mains wiring and lamp wiring must be kept as far as possible from each other. They should not be
bunched together for long distances. They can however cross each other. If a metal plate is positioned closer than 10mm to the
lamp the plate must be electrically connected to the ballast case. Even with longer distances we recommend this connection.
In order to ensure reliable dimming at low levels, and minimise electro-magnetic interference, pairs of lamp wires (one pair is
connected to one lamp cathode) should be run seperately from each other.
The wires from the ballast to a lamp may not be longer than 2 m. The ballast is designed as a "built-in" product and should be
installed in the same fixture as the lamps it operates. Master-Slave operation is not advised. Solid Core Conductor -type 0.5 - 1.5
mm2 is to be used as connecting wire.
Safety: Lampholders must be rated up to 500 V.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 508
TECHNICAL
HELVAR DALI Electronic Ballasts
For Flourescent T5 Lamps Range EL-SHFIT5
TECHNICAL DATA
Type Lamp Total Circuit Mains Power Power
Wattage Power Current In Lamp Frequency Losses
(w) (w) (A) (w) (kHz) (w) Dimensions Wiring
EL 1x14SHFIT5 1 x 14 17 0.07-0.06 14 40-100 2 1 1
EL 1x21SHFITS 1 x 21 24 0.1 1-0.10 21 40-100 3 1 1
EL 1x24SHFITS 1 x 24 28 0.13-0.12 22.5 50-80 3 1 1
EL 1x28SHFIT5 1 x 28 31 0.15-0.14 28 50-80 3 1 1
EL 1x35SHFITS 1 x 35 39 0.1 B-0.17 35 40-100 4 1 1
EL 1x39SHFITS 1 x 39 44 0.20-0.1B 38 60-100 4 1 4
EL 1x49SHFIT5 1 x 49 54 0.25-0.23 49 50-90 5 1 1
EL 1x54SHFITS 1 x 54 61 0.28-0.26 54 40-100 6 1 1
EL 1x80SHFIT5 1 x 80 88 0.41-0.38 80 30-100 8 1 1
EL 2x145HFlT5 2 x 14 31 0.14-0.13 14 40-100 3 2 2
EL 2x21SHFlT5 2 x 21 47 0.22-0.20 21 40-100 5 2 2
EL 2x24SHFIT5 2 x 24 53 0.24-0.20 22.5 40-100 5 2 2
EL 2x28SHFlT5 2 x 28 62 0.28-0.26 28 40-100 0 2 2
EL 2x35SHFlT5 2 x 35 78 0.36-0.34 35 40-100 8 2 2
EL 2x39SHFlT5 2 x 39 86 0.40-0.36 38 40-100 8 2 2
EL 2x49SHFlT5 2 x 49 105 0.50-0.46 49 50-90 9 2 2
EL 2x54SHFlT5 2 x 54 117 0.53-0.49 54 40-100 10 2 2
BALLAST DIMENSIONS
1.
8
Dimensions 1 2
A (mm) 350 420
B (mm) 360 430
2.
C (mm) 30 30
D (mm) 21 21
Weight (g) 285 365
509 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR DALI Electronic Ballasts
For Flourescent T5 Lamps Range EL-SHFIT5
CONNECTION DIAGRAMS
Note: All wiring to the connectors marked with a black dot; (hot wires) should be as short as possible
CHARACTERISTICS
Maximum allowed temperature at tc point 80 °C Mains voltage tolerance Un ±10 %
Ambient temperature range +10...+50 °C Mains quality; all data is based on a pure sinusoidal
mains supply, see Helvar document AL 702006
Maximum relative humidity no condensation
Can be used on DC, acc. to VDE 0108
Storage temperature range -40...+80 °C
DC range; 200 - 300 VDC
Vibration test EN 60068-2-64 test Fh
Fulfils immunity standard EN 61547
Bump test EN 60068-2-29 test Eb
Emission according to
Warm start, cathode pre-heat acc. to EN 60929
Mains current harmonics EN 61000-3-2
For fluorescent T5 lamps, with G5 base
Radio frequency interference EN 55015
Fulfils the standards:
Typical power factor 0.98
General and safety requirements EN 60928
Typical earth leakage current 0.3-0.4 mA
Performance requirements EN 60929
Typical lamp current crest factor 1.45
High number of starts per lamp > 20 000
Maximum working voltage Uout=500V
Life time 90 000 h, 60 °C at test point
Over voltage duration 320 VAC for 1 hour
“STAND-BY” STATE
"Stand-by" is an internal safety circuit in the ballast. The ballast switches the lamps off and goes into the "Stand-by" state when a
lamp becomes defective.
If the supply is on during relamping, the ballast will re-start automatically.
8
LAYOUT RECOMMENDATION
In order to minimise radio interference problems we recommend that the mains wiring and the lamp wiring are kept as far as
possible from each other. In no case must they be bunched together for long distances. They can however cross each other. The
wires from the ballast to a lamp may not be longer than 2 m. The ballast is designed as a "built-in" product and should be installed
in the same fixture as the lamps it operates.
Master-Slave operation is not advised. Earthing of the ballast is required for proper operation. Solid Core Conductor -type 0.5 -
1.5 mm2 is to be used as connecting wire. Control wires must have an insulation rating greater or equal to mains supply wires.
Safety: Lampholders must be rated up to 500 V.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 510
TECHNICAL
HELVAR Electronic Ballasts
TECHNICAL DATA
Lamp Total Circuit Mains Power Lamp Starting Power “Stand-by” Wiring
Wattage Power Current in lamp Current Frequency Level Losses Power Diagram
Type (W) (W) (A) (W) (A) (kHz) (%) (W) (max.) (W) Dimensions
EL 1x18 FD 230V, 50Hz 1x18 21 0.10 18 0.29 ca.45 10 3 1.8 1 1
240V, 50Hz 1x20 21 0.09 18 0.29 ca.48 10 3 1.9 1 1
EL 1x36 / 2x18 FD 1x36 37 0.17 32 0.28 ca.35 10 2) 5 2.6 3a 1
230V, 50Hz 1x40 37 0.17 32 0.28 ca.35 10 2) 5 2.6 3a 1
240V, 50Hz 2x18 37 0.16 32 0.28 ca.35 10 2) 5 2.7 3b 1
2x20 37 0.16 32 0.28 ca.35 10 2) 5 2.7 3b 1
EL 1x58 FD 230V, 50Hz 1x58 58 0.26 51 0.44 ca.29 10 7 2.7 1 1
240V, 50Hz 1x65 58 0.25 51 0.45 ca.30 10 7 2.7 1 1
EL 2x36 FD 230V, 50Hz 2x36 73 0.35 32 0.29 ca.46 10 9 2.3 2 2
240V, 50Hz 2x40 73 0.32 32 0.29 ca.53 10 9 2.3 2 2
EL 2x58 FD 230V, 50Hz 2x58 113 0.55 51 0.44 ca.45 10 11 2.7 2 2
240V, 50Hz 2x65 113 0.50 51 0.43 ca.49 10 11 3.0 2 2
2) With two 18W or 20W tubes minimum starting level is 20%
BALLAST DIMENSIONS
Dimensions 1 2
A (mm) 180 220
B (mm) 190 230
C (mm) 73 140
D (mm) 85 150
Weight (g) Electronic Unit 270 325
Weight (g) Filter Choke Pc. 340 610
511 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Electronic Ballasts
For Flourescent Tubes, Dimming Applications Range EL-FD
CHARACTERISTICS
(These characteristics are only valid when FD-ballast is used without a dimmer)
Maximum allowed operational temperature Mains voltage tolerance 230/240 VAC ±10 %
(measured at specified (tc) spot on the case) 80 °C
Mains quality; all data is based on pure sinusoidal mains
Minimum ambient temperature 15 °C supply, see Helvar document AL 702006
Maximum relative humidity no condensation Power factor 0.95
Storage temperature range –40 ...+85 °C Leakage current <0.5 mA acc. to IEC 928
Vibration test IEC 68-2-6 test Fc Mains current harmonics IEC 1000-3-2
Standard (IEC 81) tubes used Radio frequency interference; EN 55015
Lamp life is same as with conventional ballasts Mains transient suppression; 6 kV/10 µs/40 ms
(test IEC 81, 3h cycle) with 2 Ws energy
Lamp lumen output at full level is same as with Can also be used on DC (additional information available)
conventional ballasts
Not to be used without filter chokes
Lamp switching cycles 10 000 (at 10 % starting level)
“STAND-BY” STATE
The ballast switches the lamps off, when a lamp becomes deactivated. After changing the faulty lamp, the ballast can be restarted by
switching the mains off, for minimum 10 seconds. The ballast might also go into "stand-by"-state if the lamp circuit is disrupted or if the
mains voltage rises too high. If there is no lamp connected or the cathodes are broken, the ballast will not start at all. In this case the
ballast may restart without a 10 seconds reset period. The electronic ballast is equipped with a thermal protector which switches the
ballast into the "stand-by"-state in case of overheating. After cooling down it can be restarted by switching the mains off for 10 seconds.
LAYOUT RECOMMENDATION
In order to minimise radio interference problems we recommend When operated at high frequency the tube will start and dim
that the mains wiring and the lamp wiring are kept as far as smoothly also with a too weak pre-heat current (in conventional
possible from each other. In no case must they be bunched 50 Hz pre-heat operation a strong flicker will be visible in this
together for long distances. They can however cross each other. case). A weak pre-heat current can be caused by bad contacts
in the pre-heat circuit (ballast terminals, lamp holder terminals
To assure good dimming the ballast unit should be installed in
or lamp pin connections) and will result in severe end
the fitting with as short a lamp wiring as possible. If single lamp
blackening and thus pre-mature failures of the lamps. To
fittings are installed in a row, two fittings can be connected to
prevent this from happening, special care should be taken to
one two-lamp ballast, if the distance between the lamps does
ensure good contacts in above mentioned points.
not exceed 0.5 meter.
8
DIMMER CONNECTIONS
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 512
TECHNICAL
HELVAR Electronic Ballasts
Lamp Compatibility Chart
HF/CHF/HFT5 HFC/CHFC FD
NON DIMMING 0-10V CONTROLLABLE 240V DIMMING
EMC Compliant 1 - 10v control Patented 2 wire system
Warm Start 5 to 100% dimming range Suits standard T8 lamps
Energy Saving EMC Compliant Suits some PL lamps
Flickerless Light Warm start 3 to 100% dimming range
Low Noise & Harmonics Energy Saving Low Starting Level
High Power Factor Flickerless Light High Power Factor
Long Lamp Service Life Low Noise & Harmonics EMC Compliant
High Power Factor Incl. Filter Chokes
Lamp Comment ILCOS Watt Capacity
TL LAMP_26 mm diameter FD-E
18 G13 EL 1x18 HF EL 1x18 HFC EL 1x18FD
EL 2x18 HF EL 2x18 HFC EL 1 x36/2x18 FD
EL 3x18 HF
EL 4x18 HF
36 G13 EL 1x36 HF EL 1x36 HFC EL 1 x36/2 x18 FD
EL 2x36 HF EL 2x36 HFC EL 2x36 FD
58 G13 EL 1x58 HF EL 1x58 HFC EL 1x58 FD
EL 2x58 HF EL 2x58 HFC EL 2x58 FD
70 G13 EL 1x70 HF EL 1x70 HFC EL 1x70 FD
EL 2x70 HF EL 2x70 HFC EL 2x70 FD
TL LAMP_38 mm diameter FD-E
20 G13 EL 1x18 FD
EL 1x36/2x18 FD
40 G13 EL 1x36/2x18 FD
EL 2x36 FD
65 G13 EL 1x58 HF EL 1x58 FD
EL 2x58 FD
TL LAMP_26mm diameter FD-E
L=450mm 15 G13 EL 1x18 HF
L=720mm 16 G13
L=970mm 23 G13
L=1047mm 42 G13
L=894mm 30 G13 EL 1x36 HF EL 1x36 HFC EL 1x36/2x18FD
EL 2x36 HF EL 2x36 HFC EL 2x36x FD
L=970mm 36 G13 EL 2x36 HF EL 1x36/2x18FD
EL 2x36 FD
EL 2x58 FD
L=1047mm 38 G13 EL 1x36 HF EL 1x36 HFC EL 1x58 FD
EL 2x36 HF EL 2x36 HFC EL 2x58 FD
T5 LAMP_14mm diameter FD-H
14 G5 EL 1X14-35 SHF T5 EL 1x14 SHFC T5
EL 2X14-35 SHF T5 EL 2x14 SHFC T5
21 G5 EL 1X14-35 SHF T5 EL 1x21 SHFC T5
EL 2X14-35 SHF T5 EL 2x21 SHFC T5
28 G5 EL 1X14-35 SHF T5 EL 1x28 SHFC T5
EL 2X14-35 SHF T5 EL 2x28 SHFC T5
35 G5 EL 1X14-35 SHF T5 EL 1x35 SHFC T5
EL 2X14-35 SHF T5 EL 2x35 SHFC T5
CIRCLINE FD-E
22 G10q EL 1x24 FD 2 F
32 G10q EL 1x36/2x18 FD
EL 2x36 FD
40 G10q EL 1x36/2 x18 FD
8 EL 2x36 FD
MOD-U-LINE FU-E
40 G13 EL 1x36 HF EL 1x36/2x18 FD
EL 2x36 FD
TC-L 2 Finger 17.5mm diameter FSD-E
18 2G11 EL 1x18/24 CHF- L/F EL 1x18 CHFC - L/F EL 1x18 FD 2 F
EL 2x18/24 CHF- L/F EL 2x18 CHFC - L/F EL 1x36/2 x18FD 2F
24 2G11 EL 1x18/24 CHF- L/F EL 1x24 CHFC- L/F EL 1x24 FD 2 F
EL 2x18/24 CHF- L/F EL 2x24 CHFC - L/F EL 2x24 FD 2 F
34 2G11 EL 1x36 HF
EL 2x36 HF 2F
36 2G11 EL1x36 HF EL 1x36 HFC 2F EL 1x36/2x18FD 2F
EL 2x36 HF 2F EL 2x36 HFC 2F EL 2x36 FD 2F
40 2G11 EL 1x36 HF
EL 2x36 HF 2F
513 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
HELVAR Electronic Ballasts
Lamp Compatibility Chart
HF/CHF/HFT5 HFC/CHFC FD
NON DIMMING 0-10V CONTROLLABLE 240V DIMMING
EMC Compliant 1 - 10v control Patented 2 wire system
Warm Start 5 to 100% dimming range Suits standard T8 lamps
Energy Saving EMC Compliant Suits some PL lamps
Flickerless Light Warm start 3 to 100% dimming range
Low Noise & Harmonics Energy Saving Low Starting Level
High Power Factor Flickerless Light High Power Factor
Long Lamp Service Life Low Noise & Harmonics EMC Compliant
High Power Factor Incl. Filter Chokes
Lamp Comment ILCOS Watt Capacity
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 514
TECHNICAL
BURN-BRITE NB3 Hand-e-Lite 240/110 Volt AC Handlamps
FEATURES
Strong, clear, impact resistant outer case Available with 10W, 15W, 18W & 36W lamps
Impact absorbing and anti-roll ‘finned’ endcaps 6.4m cable fitted with moulded plug
Integral low-loss ballast Double-insulated construction
Oil and petrol resistant EMC compliant
Uses standard T8 fluorescent lamps 18 - 240V - Blister packed
240 VAC and 110 VAC models available in 50Hz (standard) and 60Hz
SPECIFICATIONS
240 Volt AC
Wattage 240 Volt AC
Description Voltage Current
NB3 10 Watt 10W 240 VAC 0.24A
NB3 15 Watt 15W 240 VAC 0.345A
NB3 18 Watt 18W 240 VAC 0.36A
NB3 36 Watt 36W 240 VAC 0.41A
NB3 58 Watt 58W 240 VAC 0.67A
110 Volt AC
8 Wattage 110 Volt AC
Description Voltage Current
NB3 10 Watt 10W 110 VAC 0.24A
NB3 15 Watt 15W 110 VAC 0.34A
NB3 18 Watt 18W 110 VAC 0.36A
NB3 36 Watt 36W 110 VAC 0.41A
515 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
BURN-BRITE NB3 Hand-e-Lite 240 Volt AC Handlamps
20
COMPONENT IDENTIFICATION
Part No. for Part No. for Part No. for Part No. for Part No. for
ITEM DESCRIPTION 10 Watt 15 Watt 18 Watt 36 Watt 58 Watt
1 Outer Case BBL10079 BBL10080 BBL10081 BBL10087 BBL10088
2 Endcap, Open, Red BBL11068 BBL11068 BBL11068 BBL11068 BBL11068
3 Endcap, Closed, Red BBL11067 BBL11067 BBL11067 BBL11067 BBL11067
4 Cord Grip, Red BBL13040 BBL13040 BBL13040 BBL13040 BBL13040
5 Circlip BBL18006 BBL18006 BBL18006 BBL18006 BBL18006
6 Hanging Hook BBL37007 BBL37007 BBL37007 BBL37007 BBL37007
7 Lead, Red with 3 Pin Plug BBL41097 BBL41097 BBL41097 BBL41097 BBL41097
8 Chassis Assy Complete BBL51011 BBL51013 BBL51014 BBL51016 BBL51019
9 Ballast 240VAC BBL1041 BBL1051 BBL1307 BBL1308 BBL1089
10 Starter BBL30001 BBL30001 BBL30001 BBL30002 BBL30002
11 Lamp BBL33004 BBL33005 BBL33020 BBL33025 BBL33030
12 Starter Holder BBL20027 BBL20027 BBL20027 BBL20027 BBL20027
13 Lampholder, Fixed BBL20035 BBL20035 BBL20035 BBL20035 BBL20035
14 Lampholder, Moveable BBL20036 BBL20036 BBL20036 BBL20036 BBL20036
15 Starter Cover BBL22034 BBL22034 BBL22034 BBL22034 BBL22034
16 Terminal Block BBL34051 BBL34051 BBL34051 BBL34051 BBL34051
17 Chassis BBL6183 BBL6184 BBL6185 BBL6187 BBL6189
18 Ballast Cover BBL7499 BBL7499 BBL7499 BBL7499 BBL7866
19 Label BBL21412 BBL21006 BBL21008 BBL21010 BBL21382
20 Length 610mm 720mm 870mm 1495mm 1920mm
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 516
TECHNICAL
BURN-BRITE NB3 Hand-e-Lite 32/24 Volt AC Handlamps
FEATURES
Strong, Clear, Impact Resistant outer Case 6.4m Cable fitted with moulded T-pin plug
Impact Absorbing and Anti-Roll ‘finned’ Endcaps Double-Insulated construction
Integral Low-Loss Ballast EMC compliant
Oil and Petrol Resistant 18W 32V - Blister packed
Uses Standard T8 fluorescent lamps 32 VAC and 24 VAC Models available in 50Hz
(standard) and 60Hz
Available with 10W, 15W, 18W & 36W lamps
SPECIFICATIONS
32 Volt AC
Description Wattage Voltage Voltage Current
Range
NB3 10 watt 10W 32V AC 29-35V 0.24A
NB3 15 watt 15W 32V AC 29-35V 1.2A
NB3 18 watt 18W 32V AC 29-35V 1.3A
NB3 36 watt 36W 32V AC 29-35V 1.5A
24 Volt AC
Description Wattage Voltage Voltage Current
Range
8
NB3 10 watt 10W 24V AC 21-26V 1.3A
NB3 15 watt 15W 24V AC 21-26V 1.3A
NB3 18 watt 18W 24V AC 21-26V 1.5A
NB3 36 watt 36W 24V AC 21-26V 2.4A
517 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
BURN-BRITE NB3 Hand-e-Lite 32 Volt AC Handlamps
20
COMPONENT IDENTIFICATION
ITEM DESCRIPTION Part No. for Part No. for Part No. for Part No. for
10 Watt 15 Watt 18 Watt 36 Watt
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 518
TECHNICAL
BURN-BRITE Versa-Lite Compact Fluorescent Handlamps
FEATURES
Strong, clear, impact resistant outer case Double-insulated construction
Impact absorbing and anti-roll ‘finned’ handle EMC compliant
Integral electronic ballasts and inverters Cigarette plug and in-line switch for 12 Volt model.
(depending upon voltage) Battery adapter available.
Oil and petrol resistant Removable hanging hook
Uses Compact 11 watt fluorescent lamps (2 Pin for 12 Volt, Optional Universal Magnamount, magnet mount for
4 Pin for 24, 32 & 240 Volt) metal surfaces
Colour coded handles 240 & 32 VAC Models available in 50Hz/60Hz
Red: 240 Volt, Yellow: 32 Volt, 24 Volt & Black: 12 Volt 12 & 24 VDC Model for Battery/DC operation
6.4m Cable fitted with moulded plug All models Blister packed
SPECIFICATIONS
Versa-Lite
Voltage
Description Voltage Range Current
Versalite 11 Watt 12 VDC 9-15V 1A
Versalite 11 Watt 32 VAC 24-38V 0.5A
Versalite 11 Watt In-line Transformer 240/32 VAC 220-250V 0.1A
8 Versalite 11 Watt, Electronic Ballast 240 VAC 220-250V 0.085A
519 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
BURN-BRITE Versa-Lite Compact Fluorescent Handlamps
402mm
COMPONENT IDENTIFICATION
ITEM Part No. Description ITEM Part No. Description
1 BBL37086 Mount, PL11 Lamp 8 BBL1368 Ballast, 11 Watt 240V Electronic
2 BBL33070 Lamp, Fluorescent 11 Watt 4 pin 9 BBL13036 Lead Retainer, Black
3 BBL10378 Lens, Versalite 10 BBL13038 Cable Bush, Round
4 BBL211020 Label, Versalite 240 E VAC 11 BBL41932 Lead, 6.4m Red with Plug
5 BBL20053 Lampholder, PL-S 4 pin 12 BBL37077 Versalite End Protector
6 BBL11169 Barrier, Versalite Handle 13 BBL37007 Hanging Hook
7 BBL14015 Handle, Red
355mm
* Superceded by 240 volt AC Electronic
8
COMPONENT IDENTIFICATION
ITEM Part No. Description ITEM Part No. Description
1 BBL37086 Mount, PL11 Lamp 8 BBL13036 Lead Retainer, Black
2 BBL33034 Lamp, Fluorescent 11 watt 2 pin 9 BBL13038 Cable Bush, Round
3 BBL10378 Lens, Versalite 10 BBL41687 Lead, 8.4m Black
4 BBL21212 Label, Versalite 240 VAC 11 BBL1227 Ballast, Plug Pack
5 BBL20062 Lampholder PL-S 2 pin 12 BBL37077 Versalite End Protector
6 BBL14020 Handle, Red 13 BBL37007 Hanging Hook
7 BBL18087 Cable Tie, 4.8m
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 520
TECHNICAL
BURN-BRITE Versa-Lite Compact Fluorescent Handlamps
521 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
BURN-BRITE Versa-Lite Compact Fluorescent Handlamps
12 VOLT DC
402mm
COMPONENT IDENTIFICATION
ITEM Part No. Description ITEM Part No. Description
1 BBL37086 Mount, PL11 Lamp 8 BBL14017 Handle, Black
2 BBL33034 Lamp, Fluorescent 11 Watt 2 Pin 9 BBL13036 Lead Retainer, Black
3 BBL10378 Lens, Versalite 10 BBL13037 Cable Bush, Figure 8
4 BBL21213 Label, Versalite 12 VDC 11 BBL41764 Lead Assy with cig. Plug & Switch
5 BBL37087 Lamp Support Base 12 BBL37077 Versalite End Protector
6 BBL20042 Lampholder 13 BBL37007 Hanging Hook
7 BBL16092 Inverter, PL11-12 VDC
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 522
TECHNICAL
BURN-BRITE TNB7 Transistorised Hand-e-Lite HANDLAMPS
FEATURES
Strong, clear, impact resistant outer case Uses standard T8 fluorescent lamps
Impact absorbing and anti-roll Available with 6W, 10W, 15W, 18W & 36W lamps
‘finned’ endcaps
6.4m Cable fitted with battery clips
Integral high frequency inverter
12 VDC and 24 VDC models available
Oil and petrol resistant
18W 12VDC + 24VDC blister packed
SPECIFICATIONS
12 Volt
Operation
Description Voltage Range Current Frequency
TNB7 6 Watt 9-15 VDC only 0.7A 30kHz
TNB7 10 Watt 9-15 VDC only 0.95A 28kHz
TNB7 15 Watt 9-15 VDC only 1.3A 22kHz
TNB7 18 Watt 9-15 VDC only 1.8A 27kHz
TNB7 36 Watt 9-15 VDC only 2.8A 23kHz
24 Volt
Operation
Description Voltage Range Current Frequency
8 TNB7 6 Watt 19-30 VDC only 0.35A 27kHz
TNB7 10 Watt 19-30 VDC only 0.48A 26kHz
TNB7 15 Watt 19-30 VDC only 0.65A 21kHz
TNB7 18 Watt 19-30 VDC only 0.90A 26kHz
TNB7 36 Watt 19-30 VDC only 1.7A 25kHz
523 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
BURN-BRITE TNB7 Transistorised Hand-e-Lite HANDLAMPS
19
COMPONENT IDENTIFICATION
ITEM DESCRIPTION Part No. for Part No. for Part No. for Part No. for Part No. for Part No. for
6 Watt 10 Watt 15 Watt 18 Watt 36 Watt/24 Volt 36 Watt/12 Volt
1 Outer Case BBL10150 BBL10079 BBL10080 BBL10081 BBL10087 BBL10850
2 Endcap, Open, Black BBL11106 BBL11106 BBL11106 BBL11106 BBL11106 BBL11106
3 Endcap, Closed, Black BBL11107 BBL11107 BBL11107 BBL11107 BBL11107 BBL11107
4 Cord Grip, Black BBL13035 BBL13035 BBL13035 BBL13035 BBL13035 BBL13035
5 Circlip BBL18006 BBL18006 BBL18006 BBL18006 BBL18006 BBL18006
6 Hanging Hook BBL37007 BBL37007 BBL37007 BBL37007 BBL37007 BBL37007
7 Lead, Black with Battery Clips BBL41245 BBL41245 BBL41245 BBL41245 BBL41245 BBL41245
8 Chassis Assy Complete, 12 Volt BBL51280 BBL51268 BBL51372 BBL51270 - BBL51789
8a Chassis Assy Complete, 24 Volt - BBL51269 - BBL51271 BBL51272 -
9 12 Volt Inverter BBL16047 BBL16041 BBL16039 BBL16039 - BBL16006
9a 24 Volt Inverter - BBL16042 BBL16040 BBL16040 BBL16043 -
10 Lamp BBL33002 BBL33004 BBL33005 BBL33020 BBL33025 BBL33025
11 Crocodile Clip, Red BBL9101 BBL9101 BBL9101 BBL9101 BBL9101 BBL9101
12 Crocodile Clip, Black BBL9102 BBL9102 BBL9102 BBL9102 BBL9102 BBL9102
13 Lampholder, Fixed 142/FAU BBL20029 BBL20035 BBL20035 BBL20035 BBL20035 BBL20035
14 Lampholder, Moveable 142/MAU BBL20029 BBL20036 BBL20036 BBL20036 BBL20036 BBL20036
15 Terminal Block BBL34051 BBL34051 BBL34051 BBL34051 BBL34051 BBL34051
16 Chassis BBL6190 BBL6051 BBL6204 BBL6202 BBL6086 BBL6269
17 Ballast Cover BBL7499 BBL7499 BBL7499 BBL7499 BBL7499 BBL7762
18 Label, 12 Volt BBL21273 BBL21274 BBL21275 BBL21276 - BBL21180 8
18a Label, 24 Volt - BBL21279 BBL21280 BBL21281 BBL21282 -
19 Length 500mm 610mm 720mm 870mm 1495mm 1505mm
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 524
TECHNICAL
Classification of Hazardous Areas
Class I
Explosive gas atmospheres AS2380 Part 1
Class II
Areas which are hazardous because of the presence of combustible dust, fibres or flyings AS2430
Class I Zone 0
Classification Definition Areas in which an explosive gas/air mixture is continuously present for long periods
Type of Protection Ex i Intrinsically Safe
Products in Class No BBL products in this classification
Class I Zone 1
Classification Definition Areas in which an explosive gas/air mixture exists intermittently or periodically under
normal operating conditions and areas in which an explosive gas/air mixture may
exist frequently because of leakage.
Type of Protection Ex d Flameproof
Ex e Increased Safety
Products in Class FLP1, FLP2, Portable FLP, FLP/DIP-WG, Exe OD, Exe WPT,
SLA, FLP PI-NME, FLP2, ME, Exe OD ME, Exe WPT ME
Class I Zone 2
Classification Definition Areas in which an explosive gas/air mixture is not likely to occur and
if it occurs will only exist for a short time.
Type of Protection Ex n Non-Sparking
Products in Class Exn-OD, Exn-WPT, PP, FLP/DIP-WG, Exn-OD ME, Exn-WPT ME
Class II
Classification Definition Areas in which a mixture of combustible dust, fibres or filings with air under atmospheric
conditions are present. For this class, portable equipment must be Ex d.
Type of Protection DIP Dust excluding and ignition protected. Minimum IP65.
Products in Class DIP-OD, PP, DIP-WPT, DIP-OD ME, PP-PINME, FLP/DIP-WG, DIP-WPT ME
Unlike the gas or vapour zones, dust zones cannot be divided into normal and abnormal conditions dependent upon time, as dust
is not self-correcting by ventilation over a stipulated period. In fact the opposite occurs as accelerated ventilation may lead to dust
clouds therefore creating greater, not lesser, hazardous conditions (See also AS/NZS & IEC 61241 Series).
8
NOTE: Always check compatibility of gas, vapour and cleansers with polycarbonate outercases when recommending any of this
equipment. Glass is available as an option in many instances.
525 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Types of Protection & Explosion Techniques
IP Rating
Classification of degrees of ingress protection as defined by AS1939 1990. The degree of protection
provided by an enclosure is indicated by the IP code in the following way.
IP 2 3 C H
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 526
TECHNICAL
Types of Protection & Explosion Techniques
Dust Excluding Ignition Proof - (DIP) AS/NZS & IEC 61241 Series
An enclosure which excludes dust and will not permit arcs, sparks or heat otherwise generated or liberated inside the enclosure
to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure.
This standard recognises the T1 to T6 temperature classification in lieu of two groups 80 and 120 degrees C.
Note: A dust excluding ignition proof enclosure as defined above will not be flameproof unless constructed in accordance with
AS2380 Part 2 1991.
Ignition Temperatures
Maximum surface temperatures of equipment referenced to 40 degrees C ambient operating at fault condition.
T1 - 450 degrees T4 - 135 degrees
T2 - 300 degrees T5 - 100 degrees
T3 - 200 degrees T6 - 85 degrees
Accordingly, hazardous materials are also classified into the minimum temperature ranges required to ignite or cause
self-sustained combustion. See Table 5.1 AS1076 Part 1 1977.
Hazards
Grouped according to explosive characteristics
8
Gas group I Methane, underground mining
Gas group IIA & B Above ground gases and vapours
Gas group IIC Hydrogen and acetylene
527 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
FLP1 Series Single Lamp Luminaire
CERTIFICATE NO.
AUS Ex 424
FLP1 Series
Low profile, single or double compact fluorescent fittings with wide light distribution encased in UV stabilised polycarbonate, or
optional toughened glass outcases sealed by a composite nut and boss assembly, moulded from flame retardant reinforced nylon
6 material. Suitable for hazardous, flameproof and weatherproof locations, for example, spray booths, chemical plants, refineries,
flammable liquid stores, petrol and gas dispensers and fume cupboards.
Available in a variety of AC or DC operating voltages.
Please note that the polycarbonate outercases for the FLP series are not interchangeable with the PP range of outercases. They
are of different construction and will compromise the integrity of the unit if used incorrectly.
Suitable for: Inflammable stores, spray booths, chemical plants, ammunition plants,
refineries, above and below ground mining.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 528
TECHNICAL
FLP1 Series
PHOTOMETRIC DATA
The following curve is based upon a 36 Watt luminaire.
Light Output Ratio is 44%
DIMENSIONS
All length dimensions (A) and (B) given here are
indicative only and may be subject to variation
Model A B Model A B
10 LPF 687mm 636mm 10 HPF 757mm 708mm
15 LPF 794mm 743mm 15 HPF 863mm 815mm
18 LPF 947mm 893mm 18 HPF 1015mm 965mm
8 36 LPF 1556mm 1503mm 36 HPF 1626mm 1575mm
58LPF 1993mm 1943mm 58 HPF 2064mm 2015mm
529 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
FLP2 Series Lamp Luminaire
CERTIFICATE NO.
AUS Ex 229
FLP2 Series
Single or Twin tube fluorescent fitting with an anodised cast aluminium junction box with 3 x M20 cable entries as standard. Low
profile, single or double fluorescent fittings with wide light distribution encased in UV stabilised polycarbonate, or optional toughened
glass outercases sealed by a composite nut, moulded from flame retardent reinforced nylon 6 material.
Zinc junction boxes for mining applications available on request.
Available in a variety of AC or DC operating voltages
Please note that the polycarbonate outercases for the FLP series are not interchangeable with the PP range of outercases. They
are of different construction and will compromise the integrity of the unit if used incorrectly.
Suitable for: Flammable stores, spray booths, chemical plants, ammunition plants, refineries,
above and below ground mining.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 530
TECHNICAL
FLP2 Series Lamp Luminaire
PHOTOMETRIC DATA
The following curve is based upon a 36 watt luminaire.
Light Output Ratio 64.0%
DIMENSIONS
All length dimensions (A) and (B) given here are indicative only and may be subject to variation
Model A B
2x18 Watt 1030mm 775mm
2x36 Watt 1640mm 1385mm
2x58 Watt 1940mm 1685mm
531 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
OD5 Series Twin Lamp Luminaire
OD Product Overview & Exe OD5SP Series (for single pin lamps)
OD5 Series
Corrosion resistant enclosure. Heavy duty moulded reinforced nylon end caps.
Slide out chassis for easy maintenance. Hinged down mounting.
High impact resistant, UV stabilised 2 x M20 cable entries.
polycarbonate outercase
Internal double "O" ring seal.
Ex e OD5SP Series
(for single pin lamps)
Category
Class I Zone 1 Ex e llC T4 lP66
Certificate No
Aus Ex 572
Increased safety twin tube circular unit with internal disconnect plug and socket. This series uses single pin (Fa6) TLX lamps, a
polycarbonate case with two M20 cable entry, hinge down batten or optional pipe mounting. Double cable entry is standard. Has
a 304 Stainless steel internal reflector and chassis.
Note: This unit uses single pin TLX lamps which are being phased out. For Ex e applications use BBL Ex e Bipin models.
Accessories
Description
PIPE MOUNT, 1.25"
PIPE MOUNT, 1.5" 8
PIPE MOUNT, 2"
Model A B
20 Watt 816mm 612mm
40 Watt 1426mm 1222mm
65 Watt 1726mm 1522mm
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 532
TECHNICAL
OD5 Series Twin Lamp Luminaire
Certificate No
Aus Ex 3684
Increased safety twin tube circular unit using conventional bi-pin fluorescent lamps in a Burn-Brite designed and manufactured
lampholder. Polycarbonate outercase with two M20 Cable entries, hinge down batten or optional pipe mounting with internal self-
disconnecting plug and socket. Double cable entry standard. 304 stainless steel internal reflector and chassis. Standard unit uses
iron cored ballasts for long life at elevated temperatures.
AVAILABLE OPTIONS
Double Entry (DE) Pipe mounting
Glands and cable Pre-painted mild steel components
Single channel electronic ballast Other AC & DC voltages
Earth continuity strap
Standard
Description Wattage Voltage Length mm
Ex e OD5BPE2X18-240V 2x18 240 AC 887
Ex e OD5BPE2X36-240V 2x36 240 AC 1497
Ex e OD5BPE2X58-240V 2x58 240 AC 1797
Stainless Steel
Description Wattage Voltage Length mm
Ex e OD5BPE2X18-240V 2x18 240 AC 887
Ex e OD5BPE2X36-240V 2x36 240 AC 1497
Ex e OD5BPE2X58-240V 2x58 240 AC 1797
DIMENSIONS
All length dimensions (A) and (B) given here are indicative only and may be subject to variation
Model A B
18w 887mm 627mm
36w 1497mm 1237mm
8 58w 1798mm 1538mm
533 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
OD5 Series Twin Lamp Luminaire
Ex n OD5EC Series
Ex n OD5EC Series
Category
Class I Zone 2 Class II Ex n llC T5 lP66
Certificate No
Aus Ex 3079
A universal weatherproof, low maintenance, twin tube hazardous location luminaire. This series is designed for easy installation
with 2 x M20 cable entries, prepainted mild steel internal metalware, hinge down batten mount (optional pipe mounting) and
internal disconnect plug and socket.
AVAILABLE OPTIONS
Double Entry (DE) Earth continuity strap
Stainless steel components High efficiency compact fluorescent lamps
Glands and cable Pipe mounting
Single channel electronic ballast Other AC & DC voltages
Accessories
Description Wattage Voltage Length mm Description
Exn OD5EC2X18240V 2x18 240 AC 816 PIPE MOUNT, 1.25"
Exn OD5EC2X36240V 2x36 240 AC 1426 PIPE MOUNT, 1.5"
Exn OD5EC2X58240V 2x58 240 AC 1726 PIPE MOUNT, 2"
Note: Lamps are not included with EC models.
DIMENSIONS
All length dimensions (A) and (B) given here are indicative only and may be subject to variation
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 534
TECHNICAL
OD5 Series Twin Lamp Luminaire
Ex n Series
Description Wattage Voltage Length
Exn OD5EC-2x18-240 ME 2x18 240 AC 1126 mm
Exn OD5EC-2x36-240 ME 2x36 240 AC 1426 mm
Note: Lamps are not included with EC models.
Electrical Data
The following data is applicable for twin lamp luminaires with a power factor
correction capacitor fitted to produce a power factor not less than 0.9.
PHOTOMETRIC DATA
The following curve is based upon a 2x36 Watt luminaire.
Light Output Ratio is 44%
535 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
WPT Series Twin Lamp Luminaire
WPT Series
304 stainless steel body Simple end of fitting mounting system
Toughened glass lens Slide out stainless steel chassis for easy
maintenance
Extra heavy duty moulded reinforced
nylon end caps
Ex e WPT Series
Category
Class I Zone 1 Ex e IIC T5 IP66
Certificate No.
AUS Ex 3954
Increased safety twin tube troffer type unit, with toughened glass lens and 304 stainless steel
body with nylon end caps and M20 cable entry.
Ex n Series
Description Wattage Voltage
Exn WPT-2x18-240 2x18 240 AC
Exn WPT-2x36-240 2x36 240 AC
Exn WPT-2x58-240 2x58 240 AC
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 536
TECHNICAL
WPT Series Maintained Emergency Twin Lamp Luminaire
Ex e WPT ME Series
Maintained emergency fittings include an emergency pack consisting of a solid-state inverter, battery charger, high temperature
Nicad battery and change-over circuit. In a twin luminaire, both tubes will be illuminated during normal supply under control of
the switched active supply. When the monitored supply (unswitched) fails, one of the tubes operates at 10 Watt illumination for
2 hours, after 16 hours recharge from fully disharged. This luminaire requires an unswitched active supply for battery charging
and supply monitoring and a switched active for normal operation. The emergency pack requires 10VA for supply monitoring and
battery charging. A red LED provides indication of the operation of the battery charger and the readiness of the emergency pack.
Ex n Series
Description Wattage Voltage Length (mm)
Exn WPT-2x18-240 ME 2x18 240 1126
Exn WPT-2x36-240 ME 2x36 240 1426
Ex e Series Bi Pin
Description Wattage Voltage
Exe WPT-2x18-240ME 2x18 240 AC
Exe WPT-2x36-240ME 2x36 240 AC
Electrical Data
The following data is applicable for twin lamp luminaires with a power factor
correction capacitor fitted to produce a power factor not less than 0.9.
Lamp Watts Voltage Current [Run] Current [Start]
2x18 240 220mA 260mA
2x36 240 380mA 640mA
2x58 240 620mA 1140mA
PHOTOMETRIC DATA
The following curve is based upon a 2x36 Watt luminaire.
Light Output Ratio is 44%
LEGEND: Co - Solid, C45 - Dashed, C90 - Grey
(Cd/klm)
8
537 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
PP Series Luminaire
Category
Class I Zone 2 Ex n llC T5 lP66
Certificate No.
AUS Ex 235
PP Series
Low profile, single or double fluorescent fittings with wide light distribution encased in UV stabilised polycarbonate, or optional
toughened glass outercases. They are sealed by a composite nut and boss assembly and moulded from flame retardant reinforced
nylon 6 material. Suitable for weatherproof locations, for example fume cupboards, wheat silos and grain handling facilities. Also
suited to hazardous areas such as paper manufacturers.
Available in a variety of AC or DC operating voltages.
Please note that the polycarbonate outercases for the PP series are not interchangeable with the FLP range of outercases. They
are of different construction and will compromise the integrity of the unit if used incorrectly.
Suitable for: Weatherproof locations, fume cupboards, wheat silos and grain handling facilities.
Accessories
Description Wattage Voltage Length mm Description
DIPP18240VCCP 18 240 AC 965 Reflector, Stainless Steel
DIPP18240VGA 18 240 AC 965 Reflector, Stainless Steel & Wire Guard
DIPP36240VCCP 36 240 AC 1575 Exit Sign
DIPP36240VGA 36 240 AC 1575
DIPP58240VCCP 58 240 AC 2015
DIPP58240VGA 58 240 AC 2015
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 538
TECHNICAL
SLA Series Portable Single Lamp Luminaire
Category
Class I Zone 1 Ex d IIB T6 IP66
Certificate No.
AUS Ex 406
SLA Series
Compact, slim, light weight Optional Ex d junction boxes with
a range of step-down transformers
Oil and petrol resistant protective outer
sleeve and glass lamp enclosure Double-insulated construction
Moulded rubber handle and end cap
SLA Portable
Single compact fluorescent lamp encased in an impact resistant outer case and further protected by a petrol and oil resistant
plastic outersleeve, held by a rubberised handle. An appropriate low voltage power supply, either 12VDC or 32VAC is available.
Single M20 cable entry as standard. (Cable gland and hazardous location flexible cable is optional).
539 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
WG-100 Series Well-glass Luminaries
CERTIFICATE NO.
AUS Ex 678
WG Series
Corrosion resistant anodised and powder coated Coloured, high impact UV stabilised polycarbonate
marine grade cast aluminium base. Internal 'O' lens, clear polysulphone or toughened glass lens
ring seal
Optional rotating beacon or xenon flash
2 x M20 cable entries
Suitable for use with a wide range of lamps
Screw in lens
FLP/DIP WG Series
Custom designed light fitting with choice of base, light source, voltage and lens. Add components
to create the fitting required for your specific requirements. Double cable entry standard. Also
approved for underground use (zinc base only). T rating is dependant on light source.
BASES
Description
WELL GLASS BASE, Aluminium
WELL GLASS BASE, Zinc
LENSES
Description Max. Watts
WELL GLASS LENS, GLASS 150W
WELL GLASS LENS, POLYSULPHONE CLEAR 100W
WELL GLASS LENS, POLYCARBONATE RED 60W
WELL GLASS LENS, POLYCARBONATE AMBER 60W
WELL GLASS LENS, POLYCARBONATE GREEN 60W
8
WELL GLASS LENS, POLYCARBONATE BLUE 60W
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 540
TECHNICAL
Pedestal & Wall Fans
541 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Pedestal & Wall Fans
REV201MG REV203MG
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 542
8
543
Small Med / Large W/C Small Med / Large Small Med / Large Duct Diam. Recommended Fan Manuf. Preformance Important
APPLICATIONS
Bathroom Bathroom Laundry Laundry Kitchen Kitchen (mm) Max. Duct Length Order Codes Model (no ducting) (see notes)
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
LOW-Voltage Window fans if required. fan efficiency. ventilate (eg. Bathroom), decide whether small, medium or large 0.
Fan only. Purchase duct and grille/s separately. Note "Duct Diam" PULLCORD 3. Follow that line across to identify the suggested fan 'Order Code'.
and select duct size (adaptor may be required) and grille size Integral pullcord switch on fan. Most fan models are available in a The 'Refer to Section' column indicates where you will find further
accordingly from Accessory Components' section. pullcord option. product information relating to the fan eg. 'thru Wall'- 'Small
bathroom' - 'FAN0080' - 'Section 2 XP Models' check 'Important
These products supplied in "Kit" form with ducting/grilles/fan. BATHROOM SIZES Notes' and 'Switching Options' for specific consideration.
Small Bathroom: Up to 4 square metres floor ares
Requires circular hole cut in window. Hole diameters: (eg.2metres x 2 metres).
WF100-120mm, WF230-260mm. Glazier cutting recommended. Medium Bathroom: Up to 8 square metres floor area.
Large Bathroom: Above 8 square metres floor area.
Recommended Usages ( )
TECHNICAL
Air Movement Details
TYPE of FAN
CIRCULATION
8
Poor Medium Best
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 544
TECHNICAL
MANROSE Fan Performance Curves
MANROSE FAN PERFORMANCE CURVES
100mm Fans
PERFORMANCE GRAPH
PERFORMANCE GRAPH
EXTRACT-A-LITE
MULTIVENT SERIES CF234
64M3/hr, 18 litres per second
545 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
MANROSE Fan Performance Curves
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 546
TECHNICAL
MANROSE Fan Performance Curves
547 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
MANROSE Fan Performance Curves
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 548
TECHNICAL
MANROSE Fan Performance Curves
549 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
MANROSE Comfort Zone Series
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 550
TECHNICAL
Heat & Vent
TECHNICAL DATA
250mm
400mm
Voltage : 220-240V
Wattage : 1200W
Switch Plate : 4 sw.
No. Heat Lamps : 4
Lighting Wattage : 60W
Performance : 41 l/s,
255mm 148m3/hr
(tested with 3 metres of duct & one bend -
normal installation)
350mm
square
8
365mm
square
551 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Chimes, Bell Pushes, Wirefree and Transformers
Libra
Part No. Description Colour Signal 1 Signal 2 Batteries Average Sound Sound Sound
Battery Life** Level Frequency Frequency
dB @ 1m** Signal 1 Signal 2
D338 50mChime & Bell Push Grey 2 Note 4 Note Chime:2x"AA" 18 months 82 740/587Hz 740/587
cell 5 years 660/440Hz
D339 50 m Chime & Bell Push White 2 Note 4 Note Chime:2x"AA" 18 months 740/587Hz 740/587
cell 5 years 660/440Hz
D344 100m Chime & Bell Push * Grey 2 Note 4 Note Chime: 2x "AA" 18 months 82 740/587Hz 740/587
cell 5 years 660/440Hz
D346 200m Chime with Light & Bell Push* Grey 2 Note 4 Note plus 3 Chime:2x"C" Cell 1 Year 87 740/587Hz 740/587
additional 2 notes 5 years 660/440Hz
Pushes Transformers
Part No. Description Lighted Spare Lamp Finish Part No. Description Switch Mounting Type Primary Secondary
8
D534 Lightspot Yes D70 D770 Transformer No DIN/Surface 220-240V 50Hz 8V 0.5A
D611 Gem D780 Transformer No DIN/ Surface 220-240V 50Hz 8V 1A
D620 Elite 16mm hole req. Brass D765 Transformer No DIN/Surface 220-240V 50Hz 12V 1A
D624 Halo Yes 1114 Brass
D639 Mesa 16mm hole req. Yes 1114
D642 Button 16mm hole req.
D663 Florian 16mm hole req. Yes 1114 Brass
D667 Benton 16mm hole req. Yes 1114 Brass
D723 Pushlite Yes D70
D814 Sesame
D824 Dimex
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 552
TECHNICAL
553 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
CODE NON TENSION FULL TENSION JUMPER ALUMINIUM LUG ALUMINIUM LUG TERM. ADAPTOR BI-METAL LUG
STRAND
NAME SLEEVE DIE SLEEVE DIE SLEEVE DIE 1 HOLE DIE 2 HOLE DIE TYPE DIE DIE
Gemini 7/1.75 NT36 38-132AL FT36A 38-132AL JS36R 38-132AL SL36 38-132AL AL36 38-132AL BA36 38-132AL H15304 38-90AL
Jupitor 7/2.25 NT36 38-140AL FT36A 38-140AL JS36R 38-140AL SL36 38-140AL AL36 38-140AL BA36 38-140AL H15306 38-90AL
Leo 7/2.50 NT36 38-140AL FT36A 38-140AL JS36R 38-140AL SL36 38-140AL AL36 38-140AL BA36 38-140AL H15308 38-90AL
Leondis 7/2.75 NT44 38-173AL FT44A 38-173AL JS44R 38-173AL SL44 38-173AL AL44 38-173AL H15308 38-90AL
Libra 7/3.00 NT44 38-180AL FT44A 38-180AL JS44R 38-180AL SL44 38-180AL AL44 38-180AL H15311 38-132AL
Mars 7/3.75 NT50 38-180AL FT50A 38-180AL JS50R 38-180AL SL50 38-180AL AL50 38-180AL BA50 38-180AL H15317 38-173AL
Mercury 7/4.50 NT58 38-190AL FT58A 38-190AL JS58R 38-190AL SL58 38-190AL AL58 38-190AL BA58 38-190AL H15320 38-173AL
Mercury 7/4.50 NT61 38-220AL FT61A 38-220AL JS61R 38-220AL SL61 38-220AL AL61 38-220AL BA61 38-220AL H15320 38-173AL
Moon 7/4.75 NT61 38-220AL FT61A 38-220AL JS61R 38-220AL SL61 38-220AL AL61 38-220AL BA61 38-220AL H15320 38-173AL
Neptune 19/3.25 NT68 38-220AL FT68A 38-220AL JS68R 38-220AL SL68 38-220AL AL68 38-220AL BA68 38-220AL H15323 38-220AL
Orion 19/3.50 NT80 38-250AL FT80A 38-250AL JS80R 38-250AL SL80 38-250AL AL80 38-250AL BA80 38-250AL H15326 38-220AL
Pluto 19/3.75 NT80 38-262AL FT80A 38-262AL JS80R 38-262AL SL80 38-262AL AL80 38-262AL BA80 38-262AL H15329 38-284AL
Saturn 37/3.00 NT94 38-284AL FT94A 38-284AL JS94R 38-284AL SL94 38-284AL AL94 38-284AL H15332 38-284AL
Sirius 37/3.25 NT94 38-284AL FT94A 38-284AL JS94R 38-284AL SL94 38-284AL AL94 38-284AL H15332 38-284AL
Taurus 19/4.75 NT94 38-303AL FT94A 38-303AL JS94R 38-303AL SL94 38-303AL AL94 38-303AL H15334 38-390AL
Triton 37/3.75 NT114 40-432AL FT114A 40-432AL
CODE NON TENSION FULL TENSION JUMPER ALUMINIUM LUG ALUMINIUM LUG TERM. ADAPTOR BI-METAL LUG
STRAND
NAME SLEEVE DIE SLEEVE DIE SLEEVE DIE 1 HOLE DIE 2 HOLE DIE TYPE DIE DIE
Quince 3/4/1.75 NT36 38-132AL JS36R 38-132AL SL36 38-132AL AL36 38-132AL BA36 38-132AL H15304 38-90AL
Almond 6/1/2.50 NT36 38-140AL JS36R 38-140AL SL36 38-140AL AL36 38-140AL BA36 38-140AL H15308 38-90AL
Raisin 3/4/2.50 NT36 38-140AL JS36R 38-140AL SL36 38-140AL AL36 38-140AL BA36 38-140AL H15308 38-90AL
Apricot 6/1/2.75 NT44 38-173AL FT44R 38-173AL JS44R 38-173AL SL44 38-173AL AL44 38-173AL BA44 38-173AL H15308 38-90AL
Apple 6/1/3.00 NT44 38-173AL FT44R 38-173AL JS44R 38-173AL SL44 38-173AL AL44 38-173AL BA44 38-173AL H15311 38-132AL
Sultana 4/3/3.00 NT44 38-180AL JS44R 38-180AL SL44 38-180AL AL44 38-180AL BA44 38-180AL H15311 38-132AL
Banana 6/1/3.75 NT50 38-180AL FT50R 38-180AL JS50R 38-180AL SL50 38-180AL AL50 38-180AL BA50 38-180AL H15317 38-173AL
Walnut 4/3/3.75 NT50 38-180AL JS50R 38-180AL SL50 38-180AL AL50 38-180AL BA50 38-180AL H15317 38-173AL
6/4.75
Cherry NT61 38-220AL FT61R 38-220AL JS61R 38-220AL SL61 38-220AL AL61 38-220AL BA61 38-220AL H15320 38-173AL
7/1.60
Grape 30/7/2.50 NT80 38-250AL JS80R 38-250AL SL80 38-250AL AL80 38-250AL H15326 38-220AL
Fig 18/1/3.50 NT80 38-250AL JS80R 38-250AL SL80 38-250AL AL80 38-250AL H15326 38-220AL
Lemon 30/7/3.00 NT94 38-284AL
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 554
TECHNICAL
ACSR/AC – ALUMINIUM CONDUCTOR (ALUMINIUM CLAD) STEEL REINFORCED. AUST. STANDARD – AS1220 PART 3
STRANDS/ OVERALL CALCULATED CALCULATED APPROXIMATE
CODE WIRE DIAMETER EQUIVALENT SECTIONAL MINIMUM MASS
NAME DIAMETER (APPROX) ALUMINIUM AREA BREAKING PER KM
mm mm AREA mm2 mm2 LOAD kN kg
Angling 6/1/2.50 7.50 30.7 34.36 10.7 113
Archery 6/1/3.00 9.00 44.1 49.48 15.0 163
Baseball 6/1/3.75 11.3 68.9 77.31 22.4 255
Bowls 6/4.75+7/1.60 14.3 109 120.4 32.6 385
Cricket 30/7/2.50 17.5 155 181.6 64.6 635
Darts 30/7/3.00 21.0 224 261.5 91.3 913
Diving 30/7/3.50 24.5 305 356.0 121 1240
Golf 54/7/3.00 27.0 390 431.2 119 1380
Gymnastics 54/7/3.25 29.3 457 506.0 138 1620
Hurdles 54/7/3.50 31.5 530 586.9 159 1880
Lacrosse 54/3.75+19/2.25 33.8 608 671.7 181 2150
Rugby 54/4.75+19/2.85 42.8 976 1078 287 3450
EXTRA HIGH STRENGTH
Skating 3/4/1.75 5.25 10.4 16.84 12.3 83.5
Soccer 3/4/2.50 7.50 21.2 34.36 24.9 170
Swimming 4/3/3.00 9.00 35.2 49.48 28.8 217
Tennis 4/3/3.75 11.3 54.9 77.31 42.8 339
555 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 556
TECHNICAL
557 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Fast Cable Fixing
USEFUL REFERENCE TABLES
ACSR/AZ – ALUMINIUM CONDUCTOR (ALUMINISED) STEEL REINFORCED. Aust. Standard – AS1220 PART 2
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 558
TECHNICAL
559 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Fast Cable Fixing
USEFUL REFERENCE TABLES
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 560
TECHNICAL
Fast Cable Fixing
USEFUL REFERENCE TABLES
OVERHEAD CONDUCTORS
AAC AAAC (1120) AAAC (6201A) ACSR
STRAND O.D. AREA STRAND O.D. AREA STRAND O.D. AREA STRAND O.D. AREA
CODE AL mm mm2 CODE AL mm mm2 CODE AL mm mm2 CODE AL mm mm2
Gemini 7/1.75 5.25 16.8 Argon 7/1.75 5.25 16.8 Agate 7/1.75 5.25 16.8 Quince* 3/4/1.75 5.25 16.8
Jupiter 7/2.25 6.75 27.8 Boron 7/2.25 6.75 27.8 Amethyst 7/2.25 6.75 27.8
Leo 7/2.50 7.50 34.4 Chlorine 7/2.50 7.50 34.4 Diamond 7/2.50 7.50 34.4 Almond 6/1/2.50 7.50 34.4
Raisin* 3/4/2.50 7.50 34.4
Leonids 7/2.75 8.25 41.6 Chronium 7/2.75 8.25 41.6 Dolomite 7/2.75 8.25 41.6
Libra 7/3.00 9.00 49.5 Fluorine 7/3.00 9.00 49.5 Emerald 7/3.00 9.00 49.5 Apple 6/1/3.00 9.00 49.5
Sultana* 4/3/3.00 9.00 49.5
Mars 7/3.75 11.25 77.3 Helium 7/3.75 11.25 77.3 Garnet 7/3.75 11.25 77.3 Banana 6/1/3.75 11.25 77.3
Walnut* 4/3/3.75 11.25 77.3
Mercury 7/4.50 13.50 111.3 Hydrogen 7/4.50 13.50 111.3 Jade 7/4.50 13.50 111.3
Moon 7/4.75 14.25 124.0 Iodine 7/4.75 14.25 124.0 Jasper 7/4.75 14.25 124.0
Cherry 6/4.75 14.30 120.4
7/1.60
Neptune 19/3.25 16.25 157.6 Krypton 19/3.25 16.25 157.6 Opal 19/3.25 16.25 157.6
Orion 19/3.50 17.50 182.8 Lutetium 19/3.50 17.50 182.50 Patronite 19/3.50 17.50 182.50 Grape 30/7/2.50 17.50 181.6
Pluto 19/3.75 18.75 209.8 Neon 19/3.75 18.75 209.8 Pearl 19/3.75 18.75 209.8
Saturn 37/3.00 21.00 261.5 Nitrogen 37/3.00 21.00 261.5 Ruby 37/3.00 21.00 261.5 Lemon 30/7/3.00 21.00 261.5
Sirius 37/3.25 22.75 306.9 Nobelium 37/3.25 22.75 306.9 Ruthenium 37/3.25 22.75 306.9
Taurus 19/4.75 23.75 336.7 Oxygen 19/4.75 23.75 336.7 Rutile 19/4.75 23.75 336.7
Lime 30/7/3.50 24.50 356.0
Triton 37/3.75 26.25 408.6 Phosphorus 37/3.75 26.25 408.6 Sapphire 37/3.75 26.25 408.6
Mango 54/7/3.00 27.00 431.2
Uranus 61/3.25 29.25 506.4 Selenium 61/3.25 29.25 506.4 Spinel 61/3.25 29.5 506.4 Orange 54/7/3.25 29.25 506.4
Ursula 61/3.50 31.50 586.9 Silicon 61/3.50 31.50 586.9 Tantalum 61/3.50 31.50 586.9 Olive 54/7/3.50 31.50 586.9
Venus 61/3.75 33.75 673.7 Sulphur 61/3.75 33.75 673.7 Topaz 61/3.75 33.75 673.7 Paw Paw 54/3.75 33.75 672.0
19/2.25
Peach 54/4.75 42.75 1078.0
19/2.85
Virgo 91/4.50 49.50 1447.0 Xenon 91/4.50 49.50 1447.0 Zircon 91/4.50 49.50 1447.0
561 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
Fast Cable Fixing
USEFUL REFERENCE TABLES
TOOL AND DIE SELECTION
STANDARD COPPER LUGS, LINKS, STALKS ETC.
HYDRAULIC TOOLS – HEXAGONAL DIES
CONDUCTOR DIE 12 TONNE
HAND 5 TONNE 22 TONNE 60 TONNE
SIZE A/F #38A #98
CRIMPERS #111 #66H #40B
mm2 mm #41AH #98H
1.5 –
2.5 –
#00 #102U
4 –
6 4.4 38-44CU
#16/1
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 562
TECHNICAL
1/1.38 1.38
1.5 3.2 4.4 9.4
7/0.50 1.5
2.5 7/0.67 2.01 3.7 5.1 10.8
4 7/0.85 2.55 4.6 6.0 12.2
6 7/1.04 3.12 5.2 6.6 13.4
10 7/1.35 4.05 6.1 8.1 16.6 18.1 20.0
16 7/1.70 5.10 7.2 9.3 18.6 20.4 22.6
25 19/1.35 6.75 8.9 11.4 22.1 23.8 26.5
35 19/1.53 7.65 10.1 12.6 24.4 26.5 29.5
50 19/1.78 8.9 11.9 14.1 28.0 30.6 34.3
70 19/2.14 10.70 13.5 16.0 31.5 34.8 39.0
95 37/1.78 12.46 15.9 18.2 39.6 44.6
120 37/2.03 14.21 17.4 20.0 43.3 48.8
150 37/2.25 15.75 19.5 22.2 48.4 54.6
185 37/2.52 17.64 24.4 53.7 60.7
240 61/2.25 20.25 27.4 61.0 69.1
300 61/2.52 22.68 30.3 67.6 76.6
400 61/2.85 25.65 33.8
500 61/3.20 28.80 35.7
630 127/2.52 32.76 40.2
563 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
TERMINATION RECOMMENDATIONS
The palm contact areas of Utilux lugs are designed to give more than that the surface of lugs are used upon has
corresponding contact area. Excessive drilling out of palm holes must be avoided, to ensure that adequate palm
contact, heavy gauge washers are recommended. in relation to stalk lugs and consistent with the above, care must be
taken to adequately match the stalk diameter of the tunnel or mounting connector, to ensure maximum surface contact
area. Bolting torques are listed in the following table.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 564
TECHNICAL
8 150 427/0.67
4773/0.2 18.6 150.0
185 528/0.67
5881/0.2 184.8
5920/0.21 18.8 205.1
240 672/0.67
7400/0.21 23.7 256.3
73630/0.2 239.7
300 8911/0.2 280.0
9102/0.21 26.6 315.3
400 11970/0.2 376.1
12672/0.21 30.8 438.9
565 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au
TECHNICAL
UTILUX CRIMP LUG FLEXIBLE CONDUCTOR SIZE (mm2) UTILUX HALF HEX UTILUX HALF HEX RECOMMENDED
PART NUMBER SET PART NUMBER DIE SET CONSISTS OF UTILUX TOOLING
NOMINAL RANGE
MIN MAX
H1415A M6
H1415 M8 Half 38-98CU
H1416 M10 16 15 19.3 38-98HHEX17/1 plus
H1416A M11 38-FLAT17
H1416B M12
H1365 M6
Half 38-98CU
H1366 M8
25 23.5 30.5 38-122HHEX17/1 plus
H1368 M10
38-FLAT17
H1369 M12
H1419 M6 Half 38-130CU
H1420 M8 35 27.5 35 38-130HHEX17/1 plus #38A
H1421 M10 38-FLAT17
#38ROBO
H1422B M6
H1422A M8 Half 38-153CU #41A
H1422 M10 50 47.5 58 38-153HHEX17/1 plus
#42A
H1423 M12 38-FLAT17
H1423A M16 #66H
H1424B M6 #98
H1424C M8
H1424 M10 HAlf 38-183CU #98H
70 66.5 82 38-183HHEX14/1 plus
H1425 M12 #98ROBO
38-FLAT14
H1440 M16
H1438 M20
H1381 M10
Half 38-220CU
H1382 M12
95 89.5 112.5 38-220HHEX14/1 plus
H1383 M16
38-FLAT14
H1382B M20
H1384A M10
Half 38-245CU
H1384 M12
120 113.5 141.5 38-245HHEX14/1 plus
H1385 M16
38-FLAT14
H1386 M20
H1387A M10
Half 40-260CU
H1387 M12
150 131 162.5 40-260HHEX25/1 plus
H1388 M16
40-FLAT25
H1389 M20
H1390 MB
H1390D M10 Half 40-310CU
H1390A M12 185 174.5 219.5 40-310HHEX25/1 plus
H1390B M16 40-FLAT25
H1390C M20 #40B
H1391 MB Half 40-340CU
H1391A M16 240 226.5 283.5 40-340HHEX25/1 plus #40BH
H1391B M20 40-FLAT25
H1448 MB Half 40-370CU
H1448A M16 300 266 330.5 40-370HHEX25/1 plus
H1448B M20 40-FLAT25 8
H1449 MB Half 40-410CU
H1449A M16 400 381.5 460 40-410HHEX25/1 plus
H1449B M20 40-FLAT25
Notes:
1. Refer to pages 2 & 3 for copper lug descriptive part numbers
2. To calculate cross sectional area of cable, use following formula;
CSA = Nxd2xπ
4
3. Cable chart is for single core double insulated flexible cables 0.6/1kV V90.
REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au 566
TECHNICAL
METRIC DESCRIPTION
For simplicity in identifying connectors in this catalogue, we have designated certain products with metric coding.
This coding can be used to identify a product if the Utilux catalogue number is unknown.
The following coding applies:
A = Aluminium K = Link
B = Bi-Metal S = Sector
C = Copper M = Palm Hole in mm
G = Lug MB = Blank Palm
AGS = Aluminium Lug Sector
AKS = Aluminium Link Sector
BGS = Bi-Metal Lug Sector
BKS = Bi-Metal Link Sector
AG = Aluminium Lug AK = Aluminium Link
BG= Bi-Metal Lug BK = Bi-Metal Link
BS = Bi-Metal Stalk CG= Copper Lug
CK = Copper Link
The cable area in sqmm and the palm hole is included to complete the description, eg:
(a) BKS70/50 is a Bi-Metal Link Sector, 70mm2 solid aluminium to 50mm2 stranded copper.
(b) AGS300/M16 is an Aluminium Lug Sector Cable 300mm2 solid 16mm palm hole.
(c) AKS240 is an Aluminium Link Sector Cable 240mm2 solid.
Note: This guide covers a wide, but not exhaustive, range of our products. If you have a special requirement it may be available
in our extensive non standard range or, through our Utilux Express service. Please discuss with your Repelec representative.
567 REPELEC Ph: 1300 555 586 Fax: 1300 666 066 www.repelec.com.au