CHECK FOR PUNCHING SHEAR

Project
Concrete Grade : M30
Steel Grade : 550D IS:456 CLause for Punching Shear

Column Dim. Col. Pedestral offset Net Dimension Depth Cover Depth

Permissi
Area of ble
Critical Sterss

Pu (KN)
Column a' (mm) b' (mm) a'' (mm) b'' (mm) a (mm) b (mm) D (mm) (mm) Effective Sxn. (N/mm2 Acctual
(mm) Fck Ks ) Stress
C-1 900 1500 200 200 1300 1900 1500 50 1450 18575 12200 30 1 1.37 1.05
C-2 500 1300 200 200 900 1700 1500 50 1450 8250 11000 30 1 1.37 0.52
C-3 500 1700 200 200 900 2100 1700 50 1650 17415 12600 30 0.929 1.27 0.84
C-3 400 850 200 200 800 1250 500 50 450 3000 5900 30 1 1.37 1.13
C-4 1000 1000 200 200 1400 1400 1700 50 1650 25690 12200 30 1 1.37 1.28
Check
OK
OK
OK
OK
OK
CHECK FOR PUNCHING SHEAR

Project
Concrete Grade : M 30
Steel Grade : 500D

Footing Dim. Column Dim. Col. Pedestral offset Net Dimension Depth

Column a' (mm) b' (mm) a' (mm) b' (mm) a'' (mm) b'' (mm) a (mm) b (mm) D (mm)

ft5 C-1 4700 4700 900 1500 200 200 1300 1900 1500
cft1 C-2 4700 4700 500 1300 200 200 900 1700 1500
cft3 C-3 4700 4700 500 1700 200 200 900 2100 1700
ft24 C-3 4700 4700 400 850 200 200 800 1250 500
C-4 4700 4700 1000 1000 200 200 1400 1400 750

31.6.3 Permissible Shear Stress


31.6.3.1 When shear reinforcement is not provided, the calculated shear stress at the critical section shall not exceed k
where,
ks = (0.5+βc) but not greater than 1, βc being the ratio of short side to long side of the column/capital; and
τc = 0.25(fck)1/2 in limit state method of design
Shear Stress Calculation:
Shear stress = V/b0 deff.
b0 = 2x(a+b)+4 deff.
deeff. = Effective depth of Raft
IS:456 CLause for Punching Shear

Cover Depth

Permissi
Area of ble
Critical Sterss
Pu (KN)

(mm) Effective Sxn. (N/mm2 Acctual


(mm) Fck Ks ) Stress Check
50 1450 18548 12200 30 1 1.37 0.61 OK
50 1450 7587 11000 30 1 1.37 0.32 OK
50 1650 17415 12600 30 0.929 1.27 0.48 OK
50 450 3000 5900 30 1 1.37 1.02 OK
50 700 5000 8400 25 1 1.25 0.68 OK

section shall not exceed k sτc,

n/capital; and
Pu= Factored load in column from analysis in kN
qnet = Soil bearing pressure at base of footing in kN/m 2
Permissible Stress - Permissible Punching Stress as per IS: 456
Actual Stress - Factored Punching Stress Values as per actual load at critical sectiona
Check-
If Actual Stress < Permissible Stress then "O.K."
If Actual Stress> Permissible Stress then "Increase Thickness"