Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

1
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 432 lx 73.2 lx 773 lx 0.17 0.095 WP1


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.194 m

Working plane (Room 2) 177 lx 37.2 lx 312 lx 0.21 0.12 WP2


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.194 m

Working plane (Room 3) 296 lx 152 lx 363 lx 0.51 0.42 WP3


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.418 m

Working plane (Room 4) 623 lx 323 lx 851 lx 0.52 0.38 WP4


Perpendicular illuminance (adaptive) (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.098 m

Working plane (Room 5) 240 lx 174 lx 314 lx 0.73 0.55 WP5


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.262 m

Working plane (R6) 109 lx 106 lx 110 lx 0.97 0.96 WP6


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.000 m, Wall zone: 0.135 m