Pipe Load Calculation
Concentrated Load
Operating
Pipe Dia Insulation Outer Dia Tributart Empty load Empty load Operating Test Load Friction
[Link]. load Remarks
(inch) (inch) (inch) Length (ft) (kips/ft) (kips) load (kips) (kips) Load (kips)
(kips/ft)
1 24 4 32 20 0.0947 0.2787 2.08 6.13 6.13 0.613
2 18 4 26 20 0.0707 0.1719 1.55 3.78 3.78 0.378
10% margin
3 16 4 24 20 0.0626 0.1418 1.38 3.12 3.12 0.312 considered for
4 12 4 20 20 0.0466 0.0897 1.03 1.97 1.97 0.197 insulation
5 2 2 6 20 0.0030 0.0041 0.07 0.09 0.09 0.009 weight
1 24 4 32 20 0.0947 0.2787 1.89 5.57 5.57 0.557
Cable tray Load Calculation
Cable tray load Considered 20 psf
Length of
Cable tray
Tributary load (ft) Cable tray
[Link]. load
length (Width of (kips)
(kips/ft)
cable tray)
1 20 0.4 0.5 0.2
Total
Wind Load Calculated as per ASCE 7-16
Risk Category = III
Terrain Exposure Category = C
Basic Wind Speed V = 150 mph
Topographic Factor Kzt = 1
Ground Elevation factor Ke = 1
Wind directionality factor Kd = 0.85
Gust factor for rigid structure G = 0.85
Kz Velocity
= Pressure Exposure coefficient
Design Velocity pressure qz = 0.00256x Kz xKzt x kd x ke x V2
Design Pressure Pz = qz x G x Cf
Design wind load = pz x Af
Wind load on Structure
ELEVATION (ft) Kz qz (psf) Cf (STEEL)
0-15 0.85 41.62 1.8
15-20 0.9 44.06 1.8
20-25 0.94 46.02 1.8
25-30 0.98 47.98 1.8
30-40 1.04 50.92 1.8
40-50 1.09 53.37 1.8
50-60 1.13 55.32 1.8
60-70 1.17 57.28 1.8
70-80 1.21 59.24 1.8
80-90 1.24 60.71 1.8
90-100 1.26 61.69 1.8
100-120 1.31 64.14 1.8
120-140 1.36 66.59 1.8
140-160 1.39 68.05 1.8
160-180 1.43 70.01 1.8
Wind load on Pipe in Transverse direction
Cf = 0.7
Tributary
Pipe dia
Elevation Pressure qz.G (psf) length Width of rack (ft)
(inch)
(ft)
15 35.374 20 32 20
15 35.374 20 26 20
15 35.374 20 24 20
15 35.374 20 20 20
15 35.374 20 6 20
19 37.454 20 24 20
Wind load on Cable tray in Transverse direction
Cf = 2
Tributary Cable
Elevation Pressure qz.G length depth Width of rack (ft)
(ft) (inch)
15 35.374 20 6 20
19 37.454 20 6 20
(As per Input)
Section 26.7 ASCE 7-16
Section 26.8.2 ASCE 7-16
Section 26.9 ASCE 7-16
Table 26.6-1 ASCE 7-16
Section 26.11.1 ASCE 7-16
Table 26.10-1ASCE 7-16
Eq. 26.10-1 ASCE 7-16
F (psf)
63.67
67.42
70.41
73.41
77.91
81.65
84.65
87.64
90.64
92.89
94.39
98.13
101.88
104.12
107.12
Load
Load applied
applied
(kips)
(kips)
2.31
2.06
1.98
1.82
1.24
2.10
Load
Load applied
applied
(kips)
(kips)
3.54
3.75
Wind Load Calculated as per ASCE 7-16
Risk Category = III (As per Input)
Exposure Category = C Section 26.7 ASCE 7-16
Basic Wind Speed V = 115 mph
Topographic Factor Kzt = 1 Section 26.8.2 ASCE 7-16
Ground Elevation factor Ke = 1 Section 26.9 ASCE 7-16
Wind directionality factor Kd = 0.85 Table 26.6-1 ASCE 7-16
Gust factor for rigid structure G = 0.85 Section 26.11.1 ASCE 7-1
Kz = Velocity Pressure Exposure coefficient Table 26.10-1ASCE 7-16
Design Velocity pressure qz = 0.00256x Kz xKzt x kd x ke x V2 Eq. 26.10-1 ASCE 7-16
Design Pressure Pz = qz x G x Cf
Design wind load = pz x Af
Wind load on Structure
ELEVATION (ft) Kz qz (psf) Cf (STEEL) F (psf)
0-15 0.85 24.46 1.8 37.43
Full Cable tray- Wind load on Cable tray in Transverse direction
Cf = 2
Cable
Tributary Load
Elevation Pressure qz.G depth Width of cable tray (ft)
length (ft) applied (lbs)
(inch)
12 20.792 7.75 12 2.5 402.84
ad Calculated as per ASCE 7-16
(As per Input)
Section 26.7 ASCE 7-16
Section 26.8.2 ASCE 7-16
Section 26.9 ASCE 7-16
Table 26.6-1 ASCE 7-16
Section 26.11.1 ASCE 7-16
Table 26.10-1ASCE 7-16
Eq. 26.10-1 ASCE 7-16
Seismic Load Calculated as per ASCE 7-16
Seismic Site Class = C
Short Period Accelaration Ss = 0.163
One- Second Accelaration S1 = 0.05
Site Coefficient Fa = 1.3
Importance factor Ie = 1.25 Table 1.5-2 ASCE 7-16
Risk Category = = III (As per Input)
Design spectral short period accelaration SDS = 0.141
Seismic Design category based on SDS = = A Table 11.6-1
Seismic base shear in Transvesre X direction
Frame type OMF
Response modification factor R = = 3.5 Table 12.2-1 ASCE 7-16
Cs cal = SDS / (R/I) Eq 12.8-2 ASCE 7-16
Cs cal = 0.050
Piperack Dead load and operating load = 27.607 kips
Seismic Base shear in X direction = 1.4 kips
Seismic base shear in Longitudinal direction T- Support Inverted
Pendulum Structure
Response modification factor R = = 2 Table 12.2-1 ASCE 7-16
Cs cal = SDS / (R/I) Eq 12.8-2 ASCE 7-16
Cs cal = 0.09
Seismic Base shear in Z direction = 2.4 kips
Cscal should not be less than 0.03 or 0.044x SDS xIe= 0.008 Hence Okay
able 1.5-2 ASCE 7-16
As per Input)
able 11.6-1
rame type OMF
able 12.2-1 ASCE 7-16
q 12.8-2 ASCE 7-16
T- Support Inverted
Pendulum Structure
able 12.2-1 ASCE 7-16
q 12.8-2 ASCE 7-16