You are on page 1of 18

Wind Load calculation - AS PER ASCE 7-10

Date: 21.02.17
PROJECT SONG-HAU_FGD Rev: 0

Wind load shall be calculated in accordance with the following formulas:

For Cladded Buildings


F = qz G Cp – qi G Cpi --------- (Refer Eqn No : 27.4.1of ASCE 7-10)
For Wind Load on Other Structures
F = qz G Cf A -- ( Refer Eqn.No : 29.4.1 of ASCE 7- 10)

‘ qz’ shall be calculated by following formula,

qz = 0.613 KzKztKd V2 ( Refer Equ.No : 27.3-1 of ASCE 7- 10)

Where,

Kz : Refer Table 27.3-1 of ASCE 7-10 & below.

Kzt : 1 Refer Cl.26.8.2 (Exposure category – C) of ASCE 7-10

Kd : 0.85 Refer Table 26.6-1 of ASCE 7-10

V : 38.2 m/s 138 km/hr

CONSOLIDATED
At height Kz qz Height Kz qz
(m) (N/m²) (m) (kN/m²)
Up to 4.6 0.85 646.3 Up to 10 1.00 0.76
6.1 0.90 684.3 15 1.09 0.83
7.6 0.94 714.7 20 1.15 0.87
9.1 0.98 745.1 25 1.22 0.93
12.2 1.04 790.8 30 1.26 0.96
15.2 1.09 828.8 35 1.30 0.99
18.0 1.13 859.2 40 1.34 1.02
21.3 1.17 889.6 45 1.37 1.04
24.4 1.21 920.0
27.4 1.24 942.8
30.5 1.26 958.0
36.6 1.31 996.0
42.7 1.36 1034.1
48.8 1.39 1056.9
54.9 1.43 1087.3
Wind Load calculation - AS PER ASCE 7-10
Date: 10.07.17
PROJECT SONG-HAU_FGD Rev: 0

Wind load shall be calculated in accordance with the following formulas:


For Cladded Buildings
F = qz G Cp – qi G Cpi --------- (Refer Eqn No : 27.4.1of ASCE 7-10)
For Wind Load on Other Structures
F = qz G Cf A -- ( Refer Eqn.No : 29.4.1 of ASCE 7- 10)

‘ qz’ shall be calculated by following formula,

qz = 0.613 KzKztKd V2 ( Refer Equ.No : 27.3-1 of ASCE 7- 10)

Where,

Kz : Refer Table 27.3-1 of ASCE 7-10 & below.

Kzt : 1 Refer Cl.26.8.2 (Exposure category – D) of ASCE 7-10

Kd : 0.85 Refer Table 26.6-1 of ASCE 7-10

V : 41.2 m/s 148 km/hr

CONSOLIDATED
At height Kz qz Height Kz qz
(m) (N/m²) (m) (kN/m²)
Up to 4.6 1.03 911.0 Up to 10 1.18 1.04
6.1 1.08 955.2 15 1.27 1.12
7.6 1.12 990.6 20 1.33 1.17
9.1 1.16 1026.0 25 1.39 1.23
12.2 1.22 1079.0 30 1.43 1.26
15.2 1.27 1123.3 35 1.47 1.30
18.0 1.31 1158.6 40 1.50 1.33
21.3 1.34 1185.2 45 1.53 1.35
24.4 1.38 1220.5
27.4 1.4 1238.2
30.5 1.43 1264.8
36.6 1.48 1309.0
42.7 1.52 1344.4
48.8 1.55 1370.9
54.9 1.58 1397.4
Wind Load calculation - AS PER ASCE 7-10
Date: 05.10.18
PROJECT SULSEL BARRU 2 - DSI Rev: 0

Wind load shall be calculated in accordance with the following formulas:


For Vessel ,Chimney & Rooftop equipment
F = qz G Cp – qi G Cpi --------- (Refer Eqn No : 27.4.1of ASCE 7-10)
For Wind Load on Other Structures
F = qz G Cf A -- ( Refer Eqn.No : 29.4.1 of ASCE 7- 10)

‘ qz’ shall be calculated by following formula,

qz = 0.613 KzKztKd V2 ( Refer Equ.No : 27.3-1 of ASCE 7- 10)

Where,

Kz : Refer Table 27.3-1 of ASCE 7-10 & below.

Kzt : 1 Refer Cl.26.8.2 (Exposure category – D) of ASCE 7-10

Kd : 0.9 Refer Table 26.6-1 of ASCE 7-10

V : 33.3 m/s 120 km/hr

CONSOLIDATED
At height Kz qz Height Kz qz
(m) (N/m²) (m) (kN/m²)
Up to 4.6 1.03 630.1 Up to 10 1.18 0.72
6.1 1.08 660.7 15 1.27 0.77
7.6 1.12 685.2 20 1.33 0.81
9.1 1.16 709.7 25 1.39 0.85
12.2 1.22 746.4 30 1.43 0.87
15.2 1.27 777.0 35 1.47 0.90
18.0 1.31 801.4 40 1.50 0.92
21.3 1.34 819.8 45 1.53 0.94
24.4 1.38 844.2
27.4 1.4 856.5
30.5 1.43 874.8
36.6 1.48 905.4
42.7 1.52 929.9
48.8 1.55 948.3
54.9 1.58 966.6
Wind Load calculation - AS PER UBC-1997

P = Ce x Cq x qs x Iw

Where,

Ce = Gust Factor Co-efficient From Table 16-G

Cq = Pressure Co-efficient

V = 120 Km/h

qs = 0.75 Kn/m2 From Table 16-F

I = 1.15 Occupancy Category - 2


For Exposure - D
At height Ce qz
(m) (kN/m²)
Up to 4.6 1.39 1.20
Up to 6.1 1.45 1.25
Up to 7.6 1.5 1.29
Up to 9.1 1.54 1.33

Up to 12.2 1.62 1.40

Up to 18 1.73 1.49

Up to 24.4 1.81 1.56

Up to 30.5 1.88 1.62

Up to 36.6 1.93 1.66

Up to 48.8 2.02 1.74

Up to
2.1 1.81
60.96
ASCE 7-05

DESCRIPTION LOAD 1 LOAD 2 LOAD 3 LOAD 4 LOAD 5 LOAD 6 LOAD 7


LOAD LOAD COMB. D D D D Dov L Lr
Empty Condition - Seismic Weight Includes only empty Weight
D 101 1 1 1 -
D 102 1 1 1 1
D+L+F 103 1 1 1 1 1
D+Lr 104 1 1 1 1 1
D+S 105 1 1 1 1
D+0.75(L+F) 106 1 1 1 1 0.75 0.75
+0.75(Lr or S) 107 1 1 1 1 0.75
108 1 1 1 1
D+W
109 1 1 1 1
110 1 1 1 1
D+W
111 1 1 1 1
112 1 1 1 1
D+0.7E
113 1 1 1 1
114 1 1 1 1
D+0.7E
115 1 1 1 1
D+0.75L+0.75Lr+0. 116 1 1 1 1 0.75 0.75
117 1 1 1 1 0.75 0.75
118 1 1 1 1 0.75 0.75
75W 119 1 1 1 1 0.75 0.75
D+0.75L+0.75Lr+0. 120 1 1 1 1 0.75 0.75
121 1 1 1 1 0.75 0.75
122 1 1 1 1 0.75 0.75
525E 123 1 1 1 1 0.75 0.75
D+0.75L+0.75S+0.7 124 1 1 1 1 0.75
125 1 1 1 1 0.75
126 1 1 1 1 0.75
5W 127 1 1 1 1 0.75
D+0.75L+0.75S+0.7 128 1 1 1 1 0.75
129 1 1 1 1 0.75
130 1 1 1 1 0.75
5(0.7E) 131 1 1 1 1 0.75
132 0.6 0.6 0.6 0.6
0.6D+0.7E
133 0.6 0.6 0.6 0.6
134 0.6 0.6 0.6 0.6
0.6D+0.7E
135 0.6 0.6 0.6 0.6

OPERATING Condition - Seismic Weight Includes Dead + operating weight


136 1 1 1 1 1
D+Dov+Dop
137 1 1 1 1 1
D+Dov+Dop+L+F 138 1 1 1 1 1 1
139 1 1 1 1 1 1
D+Dov+Dop+Lr 140 1 1 1 1 1 1
141 1 1 1 1 1 1
D+Dov+Dop+S 142 1 1 1 1 1
143 1 1 1 1 1
D+Dov+Dop+0.75(L 144 1 1 1 1 1 0.75 0.75
145 1 1 1 1 1 0.75 0.75
146 1 1 1 1 1 0.75
+F)+0.75(Lr or S) 147 1 1 1 1 1 0.75
148 1 1 1 1 1
149 1 1 1 1 1
150 1 1 1 1 1
151 1 1 1 1 1
D+Dov+Dop+W
152 1 1 1 1 1
153 1 1 1 1 1
154 1 1 1 1 1
155 1 1 1 1 1
D+Dov+ Dop + 0.7E 156 1 1 1 1 1
157 1 1 1 1 1
158 1 1 1 1 1
159 1 1 1 1 1
160 1 1 1 1 1
161 1 1 1 1 1
162 1 1 1 1 1
163 1 1 1 1 1
D+Dov+Dop+0.75(L 164 1 1 1 1 1 0.75 0.75
165 1 1 1 1 1 0.75 0.75
166 1 1 1 1 1 0.75 0.75
167 1 1 1 1 1 0.75 0.75
)+0.75(Lr or S)
168 1 1 1 1 1 0.75 0.75
169 1 1 1 1 1 0.75 0.75
170 1 1 1 1 1 0.75 0.75
+0.75W 171 1 1 1 1 1 0.75 0.75
D+Dov+Dop+0.75(L 172 1 1 1 1 1 0.75 0.75
173 1 1 1 1 1 0.75 0.75
174 1 1 1 1 1 0.75 0.75

)+0.75(Lr or S)
D+Dov+Dop+0.75(L

175 1 1 1 1 1 0.75 0.75


)+0.75(Lr or S)
176 1 1 1 1 1 0.75 0.75
177 1 1 1 1 1 0.75 0.75
178 1 1 1 1 1 0.75 0.75
+0.75(0.7E) 179 1 1 1 1 1 0.75 0.75
D+Dov+Dop+0.75(L 180 1 1 1 1 1 0.75
181 1 1 1 1 1 0.75
182 1 1 1 1 1 0.75
183 1 1 1 1 1 0.75
)+0.75(Lr or S)
184 1 1 1 1 1 0.75
185 1 1 1 1 1 0.75
186 1 1 1 1 1 0.75
+0.75W 187 1 1 1 1 1 0.75
D+Dov+Dop+0.75(L 188 1 1 1 1 1 0.75
189 1 1 1 1 1 0.75
190 1 1 1 1 1 0.75
191 1 1 1 1 1 0.75
)+0.75(Lr or S)
192 1 1 1 1 1 0.75
193 1 1 1 1 1 0.75
194 1 1 1 1 1 0.75
+0.75(0.7E) 195 1 1 1 1 1 0.75
0.6 (D+Dov+Dop) + 196 0.6 0.6 0.6 0.6 0.6
197 0.6 0.6 0.6 0.6 0.6
198 0.6 0.6 0.6 0.6 0.6
199 0.6 0.6 0.6 0.6 0.6
200 0.6 0.6 0.6 0.6 0.6
201 0.6 0.6 0.6 0.6 0.6
202 0.6 0.6 0.6 0.6 0.6
0.7E 203 0.6 0.6 0.6 0.6 0.6
0.6 (D+Dov+Dop) + 204 0.6 0.6 0.6 0.6 0.6
205 0.6 0.6 0.6 0.6 0.6
206 0.6 0.6 0.6 0.6 0.6
207 0.6 0.6 0.6 0.6 0.6
208 0.6 0.6 0.6 0.6 0.6
209 0.6 0.6 0.6 0.6 0.6
210 0.6 0.6 0.6 0.6 0.6
W 211 0.6 0.6 0.6 0.6 0.6
GRAVITY
(D+L) 212 1.0 1.0 1.0 1.0 1.0 1.0 1.0
OVERSTRENGTH FACTOR
301 1 1 1 1
D+0.7E
302 1 1 1 1
303 1 1 1 1
D+0.7E
D+0.7E
304 1 1 1 1
305 1 1 1 1 0.75 0.75
D+0.75(L+Lr) 306 1 1 1 1 0.75 0.75
+0.525E 307 1 1 1 1 0.75 0.75
308 1 1 1 1 0.75 0.75
309 1 1 1 1 0.75 0.75
D+0.75(L+S) 310 1 1 1 1 0.75 0.75
+0.525E 311 1 1 1 1 0.75 0.75
312 1 1 1 1 0.75 0.75
313 0.6 0.6 0.6 0.6
314 0.6 0.6 0.6 0.6
0.6D+0.7E
315 0.6 0.6 0.6 0.6
316 0.6 0.6 0.6 0.6
317 1 1 1 1 1
318 1 1 1 1 1
D+Dov+0.7E
319 1 1 1 1 1
320 1 1 1 1 1
321 1 1 1 1 1
322 1 1 1 1 1
D+Dov+0.7E
323 1 1 1 1 1
324 1 1 1 1 1
325 1 1 1 1 1 0.75 0.75
D+Dov+Dop+0.75(L 326 1 1 1 1 1 0.75 0.75
+Lr)+0.525E 327 1 1 1 1 1 0.75 0.75
328 1 1 1 1 1 0.75 0.75
329 1 1 1 1 1 0.75 0.75
D+Dov+Dop+0.75(L 330 1 1 1 1 1 0.75 0.75
+Lr)+0.525E 331 1 1 1 1 1 0.75 0.75
332 1 1 1 1 1 0.75 0.75
333 1 1 1 1 1 0.75
D+Dov+Dop+0.75(L 334 1 1 1 1 1 0.75
+S)+0.525E 335 1 1 1 1 1 0.75
336 1 1 1 1 1 0.75
337 1 1 1 1 1 0.75
D+Dov+Dop+0.75(L 338 1 1 1 1 1 0.75
+S)+0.525E 339 1 1 1 1 1 0.75
340 1 1 1 1 1 0.75
341 0.6 0.6 0.6 0.6 0.6
0.6(D+Dov+Dop) 342 0.6 0.6 0.6 0.6 0.6
+0.7E 343 0.6 0.6 0.6 0.6 0.6
344 0.6 0.6 0.6 0.6 0.6
345 0.6 0.6 0.6 0.6 0.6
0.6(D+Dov+Dop) 346 0.6 0.6 0.6 0.6 0.6
+0.7E
0.6(D+Dov+Dop)
+0.7E 347 0.6 0.6 0.6 0.6 0.6
348 0.6 0.6 0.6 0.6 0.6
LOAD 8 LOAD 9 LOAD 10 LOAD 11 LOAD 12 LOAD 13 LOAD 14 LOAD 15
S Dop Dop W W Eq Eq F A.     PRIMARY ACTION

- - - Load 1- Self weight + Dead


- - Load 2 - Equipment Dead
- - 1 Load 3 - Connection Dead
- - Load 4 - Self weight of duc
1 - - B.     VARIABLE ACTION
0.75 Load 5 - Liquid bottom + Li
0.75 0.75 Load 6 - Live Load & Contig
1 Load 7 – Roof Live Load
-1
1 Load 8 – Snow Load
-1
0.7 0.21 Load 9 - Pressure (+) ve
-0.7 -0.21
0.21 0.7 Load 10 - Pressure (-) ve
-0.21 -0.7
0.75 Load 11 - Wind (+) x
-0.75
0.75 Load 12 - Wind (+) y
-0.75
0.525 0.16 Load 13 - Seismic (+) x
-0.525 -0.16
0.16 0.525 Load 14 - Seismic (+) y
-0.16 -0.525
0.75 0.75 Load 15 - Friction load
0.75 -0.75
0.75 0.75
0.75 -0.75
0.75 0.525 0.16
0.75 -0.525 -0.16
0.75 0.16 0.525
0.75 -0.16 -0.525
0.7 0.21
-0.7 -0.21
0.21 0.7
-0.21 -0.7

1
1
1 1
1 1
1
1
1 1
1 1
1 0.75
1 0.75
0.75 1 0.75
0.75 1 0.75
1 1
1 -1
1 1 Seismic
Weight
1 -1 Includes
1 1 Dead
1 -1 +operatin
1 1
1 -1
1 0.7 0.21
1 -0.7 -0.21
1 0.21 0.7
1 -0.21 -0.7
1 0.7 0.21
1 -0.7 -0.21
1 0.21 0.7
1 -0.21 0.7
1 0.75
1 -0.75
1 0.75
1 -0.75
1 0.75
1 -0.75
1 0.75
1 -0.75
1 0.525 0.16
1 -0.525 -0.16
1 0.16 0.525
1 -0.16 0.525
1 0.525 0.16
1 -0.525 -0.16
1 0.16 0.525
1 -0.16 0.525
0.75 1 0.75
0.75 1 -0.75
0.75 1 0.75
0.75 1 -0.75
0.75 1 0.75
0.75 1 -0.75
0.75 1 0.75
0.75 1 -0.75
0.75 1 0.525 0.16
0.75 1 -0.525 -0.16
0.75 1 0.16 0.525
0.75 1 -0.16 0.525
0.75 1 0.525 0.16
0.75 1 -0.525 -0.16
0.75 1 0.16 0.525
0.75 1 -0.16 0.525
0.6 0.7 0.21
0.6 -0.7 -0.21
0.6 0.7 0.21
0.6 -0.7 -0.21
0.6 0.21 0.7
0.6 -0.21 0.7
0.6 0.21 0.7
0.6 -0.21 0.7
0.6 1
0.6 -1
0.6 1
0.6 -1
0.6 1
0.6 -1
0.6 1
0.6 -1

1.0 0.6 -1

1.4 0.42
-1.4 -0.42
0.42 1.4
-0.42 -1.4
1.05 0.32
-1.05 -0.32
0.32 1.05
-0.32 -1.05
1.05 0.32
-1.05 -0.32
0.32 1.05
-0.32 -1.05
1.4 0.42
-1.4 -0.42
0.42 1.4
-0.42 -1.4
1.4 0.42
-1.4 -0.42
0.42 1.4
-0.42 -1.4
0.42 1.4
-0.42 -1.4
1.4 0.42
-1.4 -0.42
1 1.05 0.32
1 -1.05 -0.32
1 0.32 1.05
1 -0.32 -1.05
1 1.05 0.32
1 -1.05 -0.32
1 0.32 1.05
1 -0.32 -1.05
0.75 1 1.05 0.32
0.75 1 -1.05 -0.32
0.75 1 0.32 1.05
0.75 1 -0.32 -1.05
0.75 1 1.05 0.32
0.75 1 -1.05 -0.32
0.75 1 0.32 1.05
0.75 1 -0.32 -1.05
1.4 0.42
-1.4 -0.42
0.42 1.4
-0.42 -1.4
0.42 1.4
-0.42 -1.4
1.4 0.42
-1.4 -0.42
A.     PRIMARY ACTION The primary loads considered in analysis and design are the followin

Load 1- Self weight + Dead load A.     PRIMARY ACTION


Load 2 - Equipment Dead Load 1- Self weight + Dead load
Load 3 - Connection Dead Load 2 - Equipment Dead
Load 4 - Self weight of duct (inlet & outlet) Load 3 - Connection Dead
B.     VARIABLE ACTION Load 4 - Self weight of duct (inlet & outlet)
Load 5 - Liquid bottom + Liquid @tray & demister
Load 6 - Live Load & Contigency
Load 7 – Roof Live Load

Load 8 – Snow Load

Load 9 - Pressure (+) ve

Load 10 - Pressure (-) ve

Load 11 - Wind (+) x

Load 12 - Wind (+) y

Load 13 - Seismic (+) x

Load 14 - Seismic (+) y

Load 15 - Friction load


B.     VARIABLE ACTION
Load 5 - Liquid bottom + Liquid @tray & demister
Load 6 - Roof live & Contigency
Load 7 - Pressure (+) ve
Load 8 - Pressure (-) ve
Load 9 - Wind (+) x
Load 10 - Wind (+) y
Load 11 - Friction load
and design are the following:

You might also like