This document discusses arc faults in electrical installations, outlining safety measures and detection technologies to mitigate risks to operators and equipment. It emphasizes the importance of remote operation, proper maintenance, and design considerations to prevent injuries and damage from arc faults. The document also highlights the need for effective operational procedures and the use of personal protective equipment (PPE) in potentially hazardous environments.

Uploaded by

andrew.cormick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views8 pages

TNL67 Arc Faults

This document discusses arc faults in electrical installations, outlining safety measures and detection technologies to mitigate risks to operators and equipment. It emphasizes the importance of remote operation, proper maintenance, and design considerations to prevent injuries and damage from arc faults. The document also highlights the need for effective operational procedures and the use of personal protective equipment (PPE) in potentially hazardous environments.

Uploaded by

andrew.cormick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Issue #67 - September 2013

Technical News
Industrial Electrical and Automation Products, Systems and Solutions

Arc Faults
- Safety Measures and Detection

Written by Nick Thompson


Product Manager - Air Circuit Breakers

nhp.com.au nhp-nz.com
NHP - technical news

ABSTRACT INTRODUCTION
This edition of Technical News will cover the phenomena An arc fault is usually initiated by either a breakdown of
of Arc Faults in electrical installations and the measures insulation or a foreign object (such as a hand tool) causing
that can be taken to reduce the likelihood of injury from a conduction path through an air gap in a switchboard.
these events. When this occurs, an arc is formed between phases or
phase to ground.
The main concepts include isolating the operator from
the switchroom, operational procedures, the design of the The potential danger of arc faults in electrical installations
installation and arc detection technology. is well documented, with a growing number of case
studies and anecdotal evidence to show that precautions
This Technical News illustrates that there are many options
and design considerations with arc faults in mind must be
available to mitigate harm to operators and damage
completed for any electrical installation.
to installations. However, these measures need to be
installed, commissioned and maintained correctly for The consequences of an arc fault include significant
effective protection. damage to switchgear, conductors, switchboards and
the installation. However, the biggest consequence is the
injury or death of operators in the area.
The best form of protection for personnel working in
an electrical installation is to reduce the time spent
in the area of potential danger. The area of danger is
not necessarily an extremely hazardous place for the
operator to be but has the potential to cause harm. This
is analogous to a worksite that requires hard hats to be
worn by workers. The most likely time for an incident to
occur in a switchroom is during electrical and mechanical
operations, such as switching, isolation and racking of
larger circuit breakers.
Time spent in a potentially dangerous area can be
minimised by utilising common accessories for switchgear
which facilitate remote operating such as motor operators
and open/close coils. There are also methods available to
complete the racking of circuit breakers remotely. These
can be used to remove the operator from the switchroom
when switching and racking operations are occurring.
Other forms of protection can also be utilised to reduce
injury from such events. The use of technology to detect
arc flashes and reduce let through energy are also
available. These can be used to limit an arc flash within
a switchboard to prevent injury to operators. The costs
associated with installing this technology are insignificant
compared to compensation, downtime and repairs for any
installation where an arc fault event occurs.

2
NHP - technical news

SAFETY MEASURES – OPERATIONAL PROCEDURES


Effective procedures for operators in large electrical installations Maintenance Mode settings
can avoid arc fault and other electrical hazards, however, these The reduction of let through energy is also an important method
procedures need to match the site requirements and need to be of reducing potential injury from arc fault incidents. With a
implemented as prescribed. reduction in let through energy, the size and duration of the arc
will be reduced.
Lockout Procedures A simple means for the reduction of let through energy is a
Switchgear lockout facilities, as shown in Figure 1, have temporary ‘maintenance mode’ for the settings of circuit breakers
been available for many years. However, these facilities are upstream of the area of danger. This maintenance mode would
only as strong as the system put in place to manage them. involve changing the instantaneous (or magnetic) setting of
Complacency in practice and misunderstanding of the exact the circuit breaker to a low level, for example, double the rated
nature of the lock out in the electrical system are the main areas current of the circuit breaker.
for concern. This maintenance mode would have a temporary effect on the
Correct lockout and tagging of equipment and switchgear by all selectivity of the electrical installation, but this would only be
personnel in the potential area of danger can ensure that power engaged when operators are downstream of the switchgear.
is safely returned to the area when all operations are complete. When effectively implemented, this is a simple way of reducing
severity of any arc fault when operators are in the area.
Lockout is not only restricted to isolation or control of energy;
safety guards and interlocks can also be utilised in these Personnel Protection Equipment (PPE)
environments. For example, many circuit breaker manufacturers There are many suppliers for PPE in potential arc fault situations.
offer padlock attachments for main circuit safety shutters inside These usually consist of gloves, suits, masks and other protective
carriages of withdrawable circuit breakers (see Figure 2). This apparel. The ideal situation is that the operator is never in an area
facility ensures that the operator cannot accidentally access live of potential danger.
terminals in the breaker. This safety equipment can be very cumbersome, difficult to get
Larger circuit breakers also have the provision for position in and out of, uncomfortable, hot, difficult to work in and usually
padlocking (see Figure 3). This is also an effective locking out very expensive. These difficulties lead to sites avoiding any work
procedure as the main circuit is disconnected as soon as the in areas that require this PPE as it is too difficult to organise and
circuit breaker is moved out of the connected position. This to carry out.
locking then ensures that the breaker cannot close a circuit as However, despite these concerns, Arc Flash PPE is still in some
the main power circuit is disengaged from the breaker closing situations, such as HV line work. In these situations the PPE must
mechanism. This avoids any ‘accidental’ closing of the main be utilised and maintained as necessary (see Figure 4).
circuit, via any local or remote means.
The best method for ensuring that lockout procedures are
followed as prescribed is regular training and policing by site
supervisors. For larger electrical installations, formal meetings
with all operators should also be carried out beforehand to
address any questions or concerns over the lockout and other
safety procedures.

Figure 2: Carriage safety shutter padlock device being installed in


Button cover an ACB.
locking loop

OFF button cover Position padlock loop

Padlock Position
padlock lever

Figure 1: Using a padlock to lock off an air circuit breaker (ACB) Figure 3: Using a padlock to lock an ACB in the ISOLATED position

3
NHP - technical news

SAFETY MEASURES – REMOTE OPERATION


Remote operation of switchgear is also an effective safety Remote Racking
measure against arc fault injuries. The safest place for an operator The manual in and out racking of circuit breakers also represents
during switching or racking of circuit breakers is outside the a point in time where there is some dynamic disturbance
switching room. through a switchboard (see Figure 6). The simplest example
of this danger would be a tool left inside the switchboard that
Remote closing, opening and monitoring drops on to conductors from this mechanical movement and
causes an arc.
Circuit breaker manufacturers have been able to offer remote
opening, closing and spring charging options for their products There are now options for larger circuit breakers to be remotely
for many years. This can range from directly energised coils racked in and out of position. Again, this allows the operator to
and motors, to remote control over communication protocols. be out of the area of danger or even in a different room.
This means that an operator can be in another room, or even The control of remote racking devices is usually via a pendant,
building, to the switchgear, eliminating any risk to their safety. but wireless control options can be used to completely isolate
The remote monitoring of circuits also provides important the operator from the area during racking. Quality remote
feedback to the operators as to where potential danger can lie. racking devices are also battery powered, so that the device
This feedback is usually in the form of electrical circuits, such as is electrically isolated from the installation, and there are no
auxiliary switches, communications protocols from switchgear/ hazardous power leads passing through the switchroom.
loads and metering systems. This remote monitoring of electrical Remote racking devices can also feature an integrated air circuit
installations can be used for operators to accurately identify the breaker (ACB) body lifting trolley. The lifting of ACB bodies can
potential dangers at any given time and allow them to make also be a difficult OH&S issue, as common sizes can weigh
informed decisions about entering potential areas of danger. between 40-70 kilograms. The breaker bodies also need to be
The use of automation equipment in opening and closing carefully moved as these are a protection device, and as such, an
switchgear has also become popular and cost effective in recent adjustable level platform is ideal to place an ACB body on (refer
times. An appropriate Human Machine Interface (HMI) can be to Figure 7 on the next page).
used as an observation and control point for operators, allowing
central control of a facility from a central control room (see
Figure 5).
This type of control is well suited to any sparsely laid out
installation as one operator with very basic training can control
the entire installation from one location. This avoids the need
for teams of operators to visit numerous switchrooms for simple
switching procedures.
A HMI is also well suited to include a single line diagram of the
installation, so that loads on each circuit are easily seen and
decisions can be easily made regarding switching of loads in the
system.

Figure 5: A site engineer uses a HMI to view the status of the Figure 6: A maintenance worker manually racks the ACB from
ACBs in the adjoining switch room. the connected to the isolated position.

4
NHP - technical news

SAFETY MEASURES – CARE OF SWITCHGEAR


The safety of an installation is directly affected by the level of Spare Circuit Breaker Bodies
maintenance that the breaker experiences over its life cycle. Larger circuit breakers with a withdrawable assembly are well
There are a number of different ways that the switchgear suited for regular servicing. The breaker body or withdrawable
and installation can be kept in a safe and effective operating component in quality air circuit breakers contains the critical
condition. The likeliness of an arc fault event is reduced with components of the circuit breaker:
appropriately maintained protection devices.
• Spring loaded clusters for main circuit connection
• Fixed and moving contact assembly
Regular Servicing
• Accessories such as charging motors, over current protection
Main incoming circuit breakers are commonly in operation for 20 and open/close coils
to 30 years. Over this time, as with any electromechanical device,
When a spare body is kept on-site, this can be cycled with circuit
lubrication will dry out, accessories will begin to fail, corrosion
breakers in service, so that these critical breaker components can
of some parts may occur and internal contact resistance will
be fully serviced away from the switch room.
increase.
With this system in place, circuit breakers can be kept in
Most manufacturers suggest at the very least to open and close
serviced condition with minimal shut down and disturbance to
a large breaker a few times at six month intervals. This will keep
installation. This system also covers the situation where a breaker
the lubrication moving and work the mechanical parts such as
may have cleared a large fault and needs to be inspected. The
springs. This will also be an opportunity to see if anything has
body can easily be swapped for the spare within minutes.
changed in the operation of the breaker, such as noises or visual
indications of damage.
An accredited service technician can thoroughly check
the breaker for any potential problems, inspect and clean
contacts, and test the switchgear before an event occurs.
Regular inspection of electrical installations is also essential to
the maintenance of a switchroom. Inspection for large dust
deposits, corrosion, signs of wear and tear, condensation and
heat damage should also be carried out as these can affect the
performance and operation of the switchgear.

Figure 7: NHP’s remote racking device

SAFETY MEASURES – DESIGN CONSIDERATIONS


The design of a switchroom and switchboard also has a large AS/NZS3439.1:2002 also defines test procedures (Annex ZD),
impact on the potential harm being caused to personnel in close which allows for complete switchboard systems to be built to
proximity due to the initiation of an Arc Fault. withstand arc fault within the enclosure itself (see Figure 8 on
Forms of separation as defined in AS/NZS3439.1:2002 allow for the next page). The benefit of a type tested switchboard which
switchboards to be built which provides varying levels of safety contains certification to Annex ZD, stipulates that personnel
and protection against an internal arcing fault. This built-in are guaranteed that under an arc fault condition within the
separation of components and live terminals means that the switchboard, a propagating arc fault cannot escape from the
likelihood of propagation of an arc fault is significantly reduced switchboard enclosure which may cause injury or even death.
as access to exposed busbar is significantly reduced. The The switchboard segregation is only effective if maintained
Australian & New Zealand wiring rules, AS/NZS3000:2007 further and regularly inspected, ensuring that no breakdown of
defines that switchboards >800A are required to have a form of the insulation and segregation barriers are still effective.
separation of at least Form 3b or higher. Switchboards can also be compromised by unexpected
influences which could occur in a plant such as chemical fumes
or water ingress.

5
NHP - technical news

ARC FLASH CALCULATION AND PPE RECOMMENDATIONS


AS/NZS  3000  fPhase
The detection of arc faults via current sensing is a complex ormula  
1 – The tool lands on the conductors, the new path for the
issue. Arc faults by their nature are unpredictable and erratic. electricity has low resistance and a current spike begins.
The current observed during an arc fault is not comparable to a
AS/NZS3000:2007 Phase clause 2.5.5.3spike
2 – The current defines
causesthe magnetic repulsion of the
phase to phase or phase to ground fault. formula for calculating the trip
tool, this causes thecurve
tool tosettings
be thrown for from the poles of the
Phase to phase and phase to ground faults are relatively breakers to clear an arc
circuit fault An
breaker. when it occurs.
air gap opens between the tool and the
This formula isconductors,
straightforward: a foreign conductor completes the circuit, based on the premise
forming an arc.that
Thean airarc
gap introduces a resistance in
fault
bypassing the load and the resulting resistance of the circuit is approximately
the fault, which causes current flowthe
a third of the value of to drop.
immediately drops to a low value. This low resistanceprospective
causes a fault level at the point of initiation.
Phase
large increase in current. This large jump in current is The formula
the basis for itself has its origins from one of thefault and the arc continues
3 – The tool is thrown from the

regular overcurrent tripping by circuit breakers. supply authorities, andconductors.


between has been The usedconductors
for this begin to melt and become
purpose for a gaseous,
number the air alsoTo
of years. becomes
minimise ionized.
the These effects cause the
Arc faults, on the other hand, can go through a number damage that an arc can cause to a switchboard, the the current observed.
of resistance to drop once again, increasing
different stages. An example that demonstrates this wouldmain circuit breaker trip steps
These three curvein anmust be set
arc flash to contradict the traditional
directly
be the dropping of a tool across two poles of the loadclearside a calculated arc faultprotection
overcurrent within a featured
specific intime
circuit breakers. The current
connection of a circuit breaker. frame. observed by the circuit breaker may not cross the trip curve until
the third phase of the fault, by which time much damage may
have already be done 250  𝑥𝑥  𝐼𝐼(𝑟𝑟)
(see Figure 9).
𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡  𝑡𝑡(𝑠𝑠) =
𝐼𝐼(𝑓𝑓)!.!
AS/NZS  3000  formula  
𝐼𝐼(𝑟𝑟) = 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐  𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟  𝑜𝑜𝑜𝑜  𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏
AS/NZS 3000
AS/NZS3000:2007 clause FORMULA
2.5.5.3 defines the 𝐼𝐼(𝑓𝑓) = 30%  𝑜𝑜𝑜𝑜  𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝  𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓  𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐
formula for calculating the trip curve settings for
breakersAS/NZS3000:2007
to clear an arc fault clause
when2.5.5.3 defines the formula for
it occurs. Assuming 20kA for a 1250A switchboard
Assuming 20kA for a 1250A switchboard
calculating
This formula the trip
is based curve
on the settingsthat
premise for breakers
an arc to clear an arc fault
when it occurs. a third of the value of the 𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡  𝑡𝑡(𝑠𝑠) = 0.672𝑠𝑠𝑠𝑠𝑠𝑠
fault is approximately
prospective fault level at the point of initiation.
This formula is based on the premise that an arc faultThis is result means that a 6kA fault needs to be
The formula itself has aits origins This result means that a 6kA arc fault needs to be cleared in 672
approximately third of thefrom
valueone of prospective
of the the fault level
cleared in at
672 milliseconds.
supply authorities, and has been used for this milliseconds.
the point of initiation. Although this does give some guidance to
purpose for a number of years. To minimise the Although itthismust
switchboard designers, doesbe givenoted
somethat guidancean to switchboard
The formula itself has its origins from one of the supply
damage that an arc can cause to a switchboard, the designers, it must
arc fault for this length of time would still cause be noted that an arc fault for this length of
authorities, and has been used for this purpose for a number
main circuit breaker trip curve must be set to significant damage. time would still cause significant damage.
of years. To minimise
clear a calculated arc fault the damage
within that antime
a specific arc can cause to a
switchboard, the main circuit breaker trip curve must be set to Figure 10.0: Above arc detect
frame.
clear a calculated arc fault within a specific time frame. Utilisation  of  Light  Sensors   sensor.
250  𝑥𝑥  𝐼𝐼(𝑟𝑟)
𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡  𝑡𝑡(𝑠𝑠) = The time for the circuit break
𝐼𝐼(𝑓𝑓)!.! An effective means for detecting Arc Faults is to
circuit then becomes importan
step away from current detection. An Arc flash
𝐼𝐼(𝑟𝑟) = 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐  𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟  𝑜𝑜𝑜𝑜  𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠ℎ𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏 breaker manufacturers can achiev
releases a large amount of energy in the form of
𝐼𝐼(𝑓𝑓) = 30%  𝑜𝑜𝑜𝑜  𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝  𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓  𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 little as 40mS via a shunt trip c
heat, pressure and brilliant, blinding light. This light
total arc fault time of 41mS is a
is produced as the arc forms and becomes
and reduces the let through energ
Assuming 20kA for a 1250A switchboard increasingly brighter as the fault continues.
A 41mS is comparable to th
𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶𝐶  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡  𝑡𝑡(𝑠𝑠) = 0.672𝑠𝑠𝑠𝑠𝑠𝑠 Light sensors can be utilised with dedicated trip
tripping time for a quality air circu
units to sense light from an arc flash and trip
A sample calculation is as follows:
This result means that a 6kA fault needs to be upstream breakers. These dedicated trip units
cleared in 672 milliseconds. react very quickly to the flash of light, as quick as
Although this does give some guidance to 1mS (see figure 10.0 below). 𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣
𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼  𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸  (𝑐𝑐𝑐𝑐𝑐𝑐  /  𝑐𝑐𝑐𝑐! ) =
switchboard designers, it must be noted that an 5
arc fault for this length of time would still cause
Assuming 440VAC, 6kA, 50cm, Ti
significant damage.
Figure 10.0: Above arc detection relay and Without Arc Detection relay
Utilisation  of  Light  Sensors   sensor. With Arc Detection relay
The time for the circuit breaker to clear the
An effective means for detecting Arc Faults is to
circuit then becomes important. Some circuit
step away from current detection. An Arc flash
breaker manufacturers can achieve clearance in as
releases a large amount of energy in the form of
little as 40mS via a shunt trip coil. A maximum
heat, pressure and brilliant, blinding light. This light
total arc fault time of 41mS is a very good result
is produced as the arc forms and becomes
and reduces the let through energy to a minimum.
increasingly brighter as the fault continues.
A 41mS is comparable to the instantaneous
Light sensors can be utilised with dedicated trip
tripping time for Figurea quality air circuit
9: A typical circuitbreaker.
breaker protection curve in green
units toFigure
sense8:light from
A CUBIC an arc flash
switchboard and triparc fault
undergoing
A sample calculation and the isapproximate
as follows: behaviour of an arcing fault in red.
upstreamcontainment
breakers. testing.
These dedicated trip units
react very quickly to the flash of light, as quick as
1mS (see figure 10.0 below). 𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣  𝑥𝑥  𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐  𝑥𝑥  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼  𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸  (𝑐𝑐𝑐𝑐𝑐𝑐  /  𝑐𝑐𝑐𝑐! ) =
52.5  𝑥𝑥  𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 !

6 Assuming 440VAC, 6kA, 50cm, Time=0.672S

Without Arc Detection relay 13.5 cal/cm2


NHP - technical news

UTILISATION OF LIGHT SENSORS


An effective means for detecting arc faults is to step away from Hazard / Risk Clothing Description Required Minimum
current waveforms. An arc flash releases a large amount of Category Arc Rating of PPE
energy in the form of heat, pressure and brilliant, blinding light. (cal/cm2)
This light is produced as the arc forms and becomes increasingly 1 Arc rated FR shirt and FR pants OR 4
FR coverall.
brighter as the fault continues. 2 Arc ratedand
FR shirt
Figure 10.0: An arc detection relay and sensor. relatively easy canandbe FR pants OR out during
carried 8 a
Light sensors can be utilised with dedicated trip units to FR coverall, AND arc flash suit so
scheduledthat
shutdown. The only
the system arc rating meets
requirements for a
sense light from an arc flash and trip upstream breakers. These
The time
dedicated triptaken for the
units react verycircuit
quickly breaker toofopen
to the flash the
light, as retrofit are control power
the required minimum. and that the circuit
circuit then
quick as 1mS. becomes important. Some circuit breaker/s
3 that
Arc need
rated toandbepants
FR shirt tripped
OR will require
25 a
breaker manufacturers can achieve clearance in as method ofFRelectrically
coverall, AND tripping,
arc flash suitsuch as a shunt trip
The time taken for the circuit breaker to open the circuit then selected so that the system
little as 40mS via a shunt trip coil. A maximum
becomes important. Some circuit breaker manufacturers can
coil.
arc rating meets the required
total clearance
achieve arc fault intime of as41mS
as little 40mSisviaaa very
shuntgood result
trip coil. A minimum.
and reduces
maximum the
total arc lettime
fault through energy
of 41mS togood
is a very a minimum.
result 4 Arc rated FR shirt and pants OR 40
A reduces
41mS theisletcomparable FR coverall, AND arc flash suit
and through energytoto athe instantaneous
minimum. A 41mS is
tripping time
comparable to thefor a quality airtripping
instantaneous circuittime
breaker.
for a quality air Summary selected so that they system arc
rating meets the minimum.
circuit breaker.
A sample
A sample calculation
calculation is as follows:
is as follows: The incidence of arc Requiredfaults can cause significant
Head Protection Requirement Minimum Arc Rating of PPE
damage to installations,(cal/cm2)
but more importantly, can
𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣  𝑥𝑥  𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐  𝑥𝑥  𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 An cause
arc-ratedsignificant injury or death to1.2operators in
hood or balaclava
𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼  𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸  (𝑐𝑐𝑐𝑐𝑐𝑐  /  𝑐𝑐𝑐𝑐! ) = withthe
an arc-rated
52.5  𝑥𝑥  𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 ! area. faceshield
An arc rated hood only 12
Assuming
Without 440VAC,
Arc Detection 20kA, 50cm, Time = 0.3 S
relay: This edition of Technical News has described
V=440VAC, I=6kA, Time = 0.672 S Figure
some10: of
NFPA
the70E PPE recommendations
techniques that can befor Arc Flash
used to reduce
Without
30cm: 37.5 Arc Detection
cal/cm2 relay 20 cal/cm2 the risk to personnel working in the area. From
With Arc Detection relay 2.8 cal/cm2 simple lockout procedures to arc detection relays,
50cm: 13.5 cal/cm
2
there are numerous ways that electrical
installations can be equipped to deal with arc
With Arc Detection relay: PPE requirement
Energy faults.
cal/cm2I=6kA, Time = 0.041 S
V=440VAC,
1.2
30cm: Protective
2.3 cal/cm2
Shirt/Pants or Overall Implementation of these concepts can reduce
50cm: 0.8 cal/cm Face2 Shield damage to installations, injury to operators and
Safety Glasses/Goggles costly downtime.
Hearing Protection
The calculation results in Figure 10 show that a significant
Gloves
reduction in PPE requirement can be achieved with the addition
1.2 - 12
of an arc detectionArcrelay.
Rated shirt/pants or overall or Arc
flash suit
Note that “Arc Rated” means clothing designed and tested to the
Arc Rated Face Shield/Balaclava or
energy level calculated for that particular installation – a 10 cal/
hoodrequires a 10 cal/cm2 coverall, where a 2
cm rated installation
2

12+
rated installationArconlyRated shirt/pants
requires a 2 cal/cm2or overall or Arc
coverall.
flash suit
These light sensor based relays can also be retrofitted to
Arc toRated
existing installations add extraFace Shield/Balaclava
protection or
to the system. The
hood easy and can be carried out during a
installation is relatively
scheduled shutdown.SafetyTheGlasses/Goggles
only requirements for a retrofit are
control power and Hearing Protection
that the circuit breaker/s that need to be
Glovesof electrically tripping, such as a shunt
tripped have a method Figure 11: An arc detection relay and sensor.
trip coil. Safety Shoes
Table 1.0: NFPA 70E PPE recommendations for
Arc Flash

The calculation results and Table 1 show that a


significant reduction in PPE requirement can be
achieved with the addition of an arc detection
relay.

Note that “Arc Rated” means clothing designed


and tested to the energy level calculated for that
particular installation – a 10 cal/cm2 rated
installation requires a 10 cal/cm2 coverall, where a
2 rated installation only requires a 2 cal/cm2
coverall. 7
NHP - technical news

SUMMARY
The incidence of arc faults can cause
significant damage to installations, but
more importantly, can cause significant
injury or death to operators in the area.
This edition of Technical News has
described some of the techniques
that can be used to reduce the risk to
personnel working in the area. From
simple lockout procedures to arc
detection relays, there are numerous
ways that electrical installations can be
equipped to deal with arc faults.
Implementation of these concepts can
reduce damage to installations, injury to
operators and costly downtime.

REFERENCES
http://literature.rockwellautomation.com/idc/groups/literature/documents/
ar/journj-ar011_-en-p.pdf
http://www.nfpa.org/
NFPA 70E - Standard for Electrical Safety in the Workplace
AS/NZS 3000:2007 – Wiring Rules

If you would like previous copies of Technical News, simply visit www.nhp.com.au/media and navigate
Scan the QR code to to ‘Catalogues & Literature‘ or download the NHP eCatalogues App by scanning the QR code.
download the eCatalogues or
Variable Speed Drives App
Editorial content: Please address all enquiries to marketing@nhp.com.au.

NHP Electrical AUSTRALIA VICTORIA NEW SOUTH QUEENSLAND SOUTH NEW ZEALAND
Engineering Melbourne WALES Brisbane * AUSTRALIA
nhp.com.au +61 3 9429 2999 Sydney * +61 7 3909 4999 Adelaide nhp-nz.com
Products Pty Ltd
Laverton +61 2 9748 3444 Townsville +61 8 8297 9055 SALES 0800 NHP NHP
A.B.N. 84 004 304 812 SALES
+61 3 9368 2901 Newcastle * +61 7 4779 0700 WESTERN Auckland
1300 NHP NHP +61 2 4960 2220
Albury/Wodonga Rockhampton AUSTRALIA +64 9 276 1967
© Copyright NHP 2013 +61 2 6049 0600 Wollongong * +61 7 4927 2277 Perth Hamilton
Dandenong + 61 1300 NHP NHP Toowoomba * +61 8 9277 1777 +64 7 849 0257
NTNL67 08 13
+61 3 8773 6400 ACT +61 7 4634 4799 Napier
NORTHERN
TASMANIA Canberra Cairns TERRITORY +64 6 843 6928
+61 2 6280 9888 +61 7 4035 6888 Darwin New Plymouth
Hobart
+61 3 6228 9575 +61 8 8947 2666 +64 800 NHP NHP
Launceston Wellington
+61 3 6345 2600 +64 4 570 0634
Christchurch
* Rockwell Automation products
not available from these locations +64 3 377 4407
Dunedin
0800 NHP NHP

You might also like