UPS12-100MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
158
168
172
174
179
10
111
115
117
118
119
15
87
90
91
91
92
20
73
75
75
76
76
30
56
57
57
57
58
40
46
47
47
47
47
45
42
43
43
43
43
50
39
40
40
40
40
60
34
35
35
35
35
90
24
24
24
25
25
.083
51.1
62.8
72.3
80.0
.25
33.0
38.4
42.1
44.3
.50
22.4
25.3
27.1
28.1
.75
18.2
20.5
21.8
22.5
1
14.0
15.6
16.4
16.9
2
6.30
9.10
9.50
9.75
3
6.05
6.60
6.86
7.00
5
3.94
4.29
4.45
4.53
8
2.62
2.85
2.95
3.00
10
2.14
2.33
2.41
2.45
12
1.82
1.98
2.05
2.08
20
1.14
1.24
1.28
1.30
24
0.96
1.05
1.08
1.10
72
0.34
0.37
0.38
0.39
100
0.24
0.26
0.27
0.28
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
UPS12-150MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
270
282
288
292
296
10
182
188
192
196
200
15
141
144
148
150
152
20
115
118
120
122
123
30
86
87
89
90
91
40
69.0
70.0
71.1
71.8
72.5
45
63.0
63.9
64.9
65.3
66.0
50
58.0
58.8
59.5
60.0
60.5
60
49.7
50.4
51.0
51.5
51.8
90
35.0
35.5
36.0
36.3
36.5
20
1.65
1.69
1.73
24
1.39
1.42
1.45
72
0.47
0.48
0.49
50
83.0
84.2
85.0
85.4
86.0
60
71.8
72.8
73.3
73.8
74.2
90
51.0
52.0
52.4
52.6
52.8
20
2.50
2.63
2.67
24
2.10
2.21
2.24
72
0.73
0.76
0.77
1
22.5
23.8
25.2
2
12.5
13.1
13.7
3
8.80
9.20
9.52
5
5.68
5.90
6.05
8
3.76
3.90
4.00
10
3.10
3.21
3.29
12
2.63
2.72
2.78
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
UPS12-210MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
340
366
376
380
392
10
240
252
257
259
261
15
195
201
206
207
209
20
164
168
170
171
172
30
121
123
125
126
127
40
98
99
101
101
102
45
90
91
92
93
93
1
33.0
35.0
36.5
2
18.7
19.5
20.6
3
13.3
13.9
14.5
5
8.60
9.20
9.40
8
5.78
6.10
6.23
10
4.74
5.02
5.09
12
4.02
4.25
4.30
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.