Design of Transformer - RK
Design of Transformer - RK
Details of Transformer
Types of Transformers
Design of Transformers
Details of Transformer
Classification of Transformer
Single phase core type Transformer
Single phase shell type Transformer
Core Type 1 phase Transformer Cruciform section
Types of Core
Schematic diagram of Transformer
Principle of Transformer
Transformer on No load
Transformer on load
Specification of transformer
Transformers of small, medium and large sizes are normally built as per
the standard ratings.
Yoke
• Core
• Yoke
• Window
Core
1. e.m.f. equation.
3. output equation
𝑇1 (2𝜋𝑓)𝜙𝑚
or, rms. value of induced emf , 𝐸1 =
2
𝐸1 = 4.44𝑓𝑇1 𝜙𝑚 volts
𝐸1 = 4.44𝑓𝑇1 𝐵𝑚 𝐴𝑖 volts
Similarly, induced emf. in secondary winding, 𝐸2 = 4.44𝑓𝑇2 𝐵𝑚 𝐴𝑖 Volts
Hence, emf per turn,
𝐸𝑡 = 4.44𝑓𝐵𝑚 𝐴𝑖
the cross-sectional area of the core can be determined, provide the e.m.f. per turn is known.
E.M.F. PER TURN
𝜙𝑚 𝛿
𝐴𝑖 /𝐴𝑐 = × = constant
𝐼𝑇 𝐵𝑚
The ratio of cross-sectional area of the core and the copper area of the windings will be constant for a
particular transformer i.e.
𝐴𝑖 /𝐴𝑐 = constant
As current density, 𝛿 and flux density, 𝐵𝑚 is nearly constant
𝜙𝑚
= 𝑟 = Constant
𝐼𝑇
Contd..
substituting for IT
𝜙𝑚
KVA/phase = 𝐸𝑡 × × 10−3
𝑟
( KVA/phase ) × 𝑟
𝜙𝑚 = × 103
𝐸𝑡
𝐸𝑡 = 𝐾 (KVA/ phase )
K = 4.44𝑓𝑟 × 103
Factor K
cross sectional area of core
Factor, 𝐾 = = 𝐴𝑖 /𝐴𝑐
copper section of the windings
• The factor, K will be higher for single phase core type transformers compared to
3-phase core type transformers.
window space available in the magnetic frame is occupied by both the windings on the core
and insulation
Thus, total copper area in the window
𝐴𝑐𝑢 = 𝑎1 𝑇1 + 𝑎2 𝑇2
= 𝐾𝑤 𝐴𝑤
Here, each window space is occupied by both the windings of two phases i.e.
𝐴𝑤 𝐾𝑤 = 2 𝑎1 𝑇1 + 𝑎2 𝑇2 = 4𝐼1 𝑇1 Τ𝛿
substituting for I1 T1
It is the ratio of total area occupied by copper material of the windings in the
window to the window area i.e.
Total copper area in the window 𝐴𝑐𝑢
𝒌𝒘 =
window area
=
𝐴𝑤
The approximate values of the window space factor can also be calculated by empirical
formula based upon the voltage of HV winding in KV,
Range of Window space factor
Specific magnetic loading, Bm
Choice of flux density in the core basically depends upon the steel grades used for
• Core
• Yoke
As a guide line, the values of flux density considering the economics and
performance are given below:
As guide line, following values may be used for the average current density.
(average of LV and HV winding current density)
ℎ𝑤 =
𝑏𝑤 =
ℎ𝑦 =
𝑏𝑦 =Width of the yoke,
MAIN DIMENSIONS OF MAGNETIC CIRCUIT
ii) Length of the core, L, which is equal to the height of the window.
Value of factor, K
B. Net cross-sectional area of the core 𝑨𝒊
𝐸𝑡 = 4.44𝑓𝐵𝑚 𝐴𝑖
can be calculated by
𝐴𝑖 = 𝑘 × 𝑑 2
Value of factor, k
• A narrow, long core gives better cooling for the iron portion.
D = 𝑏𝑤 +𝑑
3. Main Dimensions of Yoke
3. The diameter of the circumscribed circle, d over the stepped core is calculated i.e.
𝐴𝑖 = 𝑘 × 𝑑 2
𝐿
6. = 2.5 to 4.0 (assume suitable ratio)
𝐷 −𝑑
The LV winding is placed nearer the core, whereas HV winding over the LV winding
Arrangements of windings
Windings are normally arranged, in two ways:
• Concentric winding:
Concentrically in relation to one another (used for core type)
• Interleaved or sandwich winding
In groups of LV & HV coils stacked alternately one over the other,
along the height of the limb (used for shell type)
Types of windings
The number of turns per phase is calculated based on its per phase voltage
rating and the e.m.f. per turn.
𝑉2
Turns per phase, 𝑇2 =
𝐸𝑡
As a guide line,
• The dimension of the rectangular conductor in a direction perpendicular to the leakage flux
lines should not exceed 3.5 mm.
• For proper insulation and cooling, there must be a clearance of 1 to 1.5 cm in the
window between the HV windings on the two adjacent limbs.
(5) Mean length of turn
𝑉1
𝑇1 = 𝑇2 ×
𝑉2
• These turns will be split up into a number of coils in order to create oil ducts between
them for better cooling of winding
• For small and medium size transformer, maximum number of turns may
be taken upto 100.
(2) Cross-sectional area of conductor
• Insulated diameter with proper insulation can also be found out from the
same table.
(4) Dimensions of conductor
(ii) Rectangular Conductor
• The winding height = space occupied by coils + certain percentage space for the
end insulation + insulating spacers between the coils +metal ring at the top of the
winding+ slackness.
• End insulation can be found as per the voltage rating of HV winding and KVA
rating of the transformer.
Contd..
• Thickness for the space in between the coils may be taken 4 to 8 mm depending
upon the rating of the transformer.
• Thickness of the metal ring provided at the top of the winding for uniform pressure
may be taken from 2.0 to 3 cm.
The winding height may be assumed approximately 70 percent of the window height i.e.
ℎ𝑤
Axial length available for one coil =
𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑐𝑜𝑖𝑙𝑠
Recommended
Sizes of
rectangular
copper
conductor
(5) Arrangement of turns
𝑉1
= 𝑇2 ×
1.025 × 𝑉2
𝑉1
= 𝑇2 ×
0.975 × 𝑉2
𝑉1
= 𝑇2 ×
0.95 × 𝑉2
Performance characteristics of the designed transformer
Magnetization Curve
Total ampere turns for the magnetic circuit,
𝐴𝑇 = 𝐴𝑇𝑐 + 𝐴𝑇𝑦
no load current
2 2
𝐼𝑜 = 𝐼𝑚 + 𝐼𝑤
Performance limitation
• Hysteresis loss
• Eddy current loss
Determination from design data
Core loss
Performance limitation
Performance limitation
𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
𝜂=
𝐼𝑛𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
𝜂=
𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟 + 𝑖𝑟𝑜𝑛 𝑙𝑜𝑠𝑠𝑒𝑠 + 𝑐𝑜𝑝𝑝𝑒𝑟 𝑙𝑜𝑠𝑠𝑒𝑠
𝑀𝑎𝑥𝑖𝑚𝑢𝑚 𝜂
𝑊𝑐 = 𝑊𝑖
Performance limitation
The effect of leakage reactance is to cause a voltage drop in the respective windings.
LV & HV windings
(iv) Half of the leakage flux in duct links with each winding.
(viii) The windings are uniformly distributed and hence the winding mmf. varies
linearly from one end to the other.
The total flux linkages of the HV winding consists of the following two parts:
(a) HV winding flux linking the HV turns.
(b) Duct (between LV and HV) flux linking the HV turns
Total flux linkage of HV winding
𝜇𝑜 𝐴𝑇 𝑇1 𝑙𝑚𝑡1 𝑏1 𝑎
Ψ1 = +
𝐿𝑐 3 2
Ψ1
Leakage inductance of HV winding 𝐿1 =
𝐼1
𝜇0 𝐼1 𝑇1 𝑇1 𝑙𝑚𝑡1 𝑏1 𝑎
= +
𝐿𝑐 × 𝐼1 3 2
2
𝑇1
𝑋1 = 𝑥1 + 𝑥2
𝑇2
2𝜋𝑓𝜇0 lm𝑡 𝑇12 𝑏1 + 𝑏2
= 𝑎+
𝐿𝑐 3
per unit reactance,
𝐼1 𝑋1
𝜀𝑥 =
𝑉1
2𝜋𝑓𝜇𝑜 lm𝑡 𝐼1 𝑇12 𝑏1 + 𝑏2
𝜀𝑥 = 𝑎+
𝐿𝑐 𝑉1 3
2𝜋𝑓𝜇𝑜 l 𝑚 𝑡 𝐴𝑇 𝑏1 + 𝑏2
= 𝑎+
𝐿𝑐 𝐸𝑡 3
𝐴𝑇 = Ampere turns for the HV winding.
𝑙𝑚𝑡1 = Mean circumferential length of the annular duct,
which is approximately taken as mean length of the HV turns.
𝐵𝜎 = flux density in the duct
lm𝑡 = mean length of the turns, i.e. mean of l𝑚𝑡1 and l𝑚𝑡2
𝐷𝑚𝑡 = mean of 𝐷𝑚𝑡1 & 𝐷𝑚𝑡2
Weight of transformer
𝑏𝑡 = 𝑑𝑜1 + ∆𝑏
∆𝑏 = Total clearance width wise on both the sides between the HV windings and the tank.
ℎ𝑡 = 𝐿 + 2ℎ𝑦 + ∆ℎ
∆ℎ includes
• the clearance at the base,
• oil height above the assembled transformer,
• clearance for the leads etc.
Clearance for the tank
2. Calculation of temperature-rise
(i) Calculate the cooling area of the plain tank, neglecting top and bottom surfaces.
𝑆t = 2 𝑏𝑡 × ℎ𝑡 + 2 𝑙t × ℎ𝑡
= 2 𝑏𝑡 + 𝑙t ℎ𝑡 𝑚2
(i) Calculate the total area of the cooling tubes, required for limiting the temperature rise to a
particular value, 𝜃1 i.e.
(ii) Select the size of the cooling tube i.e. diameter and length of the cooling tubes.