Professional Documents
Culture Documents
1
Transformer Design
Design the
Core
Windings
Insulation
Cooling Systems
Tank
Accessories
Mechanical components
2
Output Equation of Transformer
It relates the rated kVA output to the area of core & window
The output kVA of a transformer depends on,
Flux Density (B) – related to Core area
Ampere Turns (AT) – related to Window area
Window – Space inside the core – to accommodate primary &
secondary winding
Let,
T- No. of turns in transformer winding
f – Frequency of supply
Induced EMF/Turn , Et = E / T=4.44 f φm
3
1- Phase core type Transformer
4
Output Equation of Transformer
5
Core and Shell Transformers
• Shell type
• Core type
Half coils
AT=IpTp=IsTs (4)
Total Cu. Area in window, Ac = Cu.area of pry wdg + Cu.area of sec wdg
No. of pry turns X area No. of sec turns X area
of X - section of pry conductor of X - section of sec conductor
Tp a p Ts a s
Tp a p Ts a s
Ip Is
Tp Ts
δ δ
1
δ
Tp I p Ts I s
1 2AT
AT AT (5)
δ δ 8
Output Equation of Transformer
Therefore, equating (2) & (5),
2 AT
KwAw
1
AT K w A w ( 6)
2
4AT
Ac (7)
δ
4AT
Compare (2) & (7), KwAw
δ
K A δ
AT w w 10
4
Output Equation of Transformer
kVA rating of 3φ transformer,
Q 3 E p I p 10 3
Ep
3 Tp I p 10-3
Tp
E t AT 10 3
1
3 4.44 fφ m . K w A w δ 10 3
4
3.33 f Bm A i A w K w δ 10 3 kVA
11
1. EMF per Turn
Design of Transformer starts with EMF/turn.
Let,
Et K Q
13
EMF per Turn
14
Optimum Design
Transformer may be designed to make one of the
following quantities as minimum.
Total Volume
Total Weight
Total Cost
Total Losses
In general, these requirements are contradictory & it is
normally possible to satisfy only one of them.
All these quantities vary with φm
r
AT
15
Optimum Design
Design for Minimum Cost
Let us consider a single phase transformer.
Q 2.22 f Bm A i A w K w 10 3 kVA
Q 2.22 f Bm A i A c 10 3 kVA A c K w A w
Assuming that φ & B are constant, Ac.Ai – Constant
Let, Ac Ai M 2 (1)
In optimum design, it aims to determining the minimum value of
total cost.
r m
AT
m B m A i
1 Ac
AT K w A w
2 2 16
Optimum Design
Design for Minimum Cost
Bm A i 2 Bm A i
r
Ac Ac
2
A i 2 Bm
r
Ac
Ai
r ( 2)
Ac 2 Bm
β is the function of r alone [δ & Bm – Constant]
From (1) & (2),
M
A A M
c i
2
Ai M & Ac
17
Optimum Design
Design for Minimum Cost
Let, Ct - Total cost of transformer active materials
Ci – Cost of iron
Cc – Cost of conductor
pi – Loss in iron/kg (W)
pc – Loss in Copper/kg (W)
li – Mean length of flux path in iron(m)
Lmt – Mean length of turn of transformer winding (m)
Gi – Weight of active iron (kg)
Gc – Weight of Copper (kg)
gi – Weight/m3 of iron
gc – Weight/m
C t Ci 3of
C cCopper
ci G i c c G c
18
Optimum Design
Design for Minimum Cost
C t c i g i li A i c c g c L mt A c
where, ci & c c specific costs of iron and copper respective ly.
M
Ct ci g i li M cc g c Lmt
Differeniating Ct with respect to β,
d 1 1 / 2 1
C t c i g i li M () c c g c Lmt M 3 / 2
d 2 2
d
For minimum cost, Ct 0
d
1 1
c i giliM() 1/ 2 c c gc Lmt M 3 / 2
2 2
c i gili c c gc Lmt 1
Ac
c i gili c c gc Lmt
Ai 19
Optimum Design
Design for Minimum Cost
c i gili A i c c gc Lmt A c
ci G i cc G c
Ci C c
Hence for minimum cost,
the cost of iron must be equal to the cost of copper.
Similarly,
For minimum volume of transformer,
Gi Gc
Volume of iron = Volume of Copper or G i gi
gi gc Gc gc
20
Optimum Design Design
for Minimum Loss and Maximum Efficiency
Total losses at full load = Pi+Pc
At any fraction x of full load, total losses = Pi+x2Pc
If output at a fraction of x of full load is xQ.
Efficiency, xQ
x
xQ Pi x 2 Pc
d x
Condition for maximum efficiency is, 0
dx
dx
xQ Pi x 2 Pc Q - Q 2xPc xQ
0
dx
xQ Pi x Pc2
2
xQ P x P Q 2xP x
i
2
c c
xQ Pi x 2 Pc xQ x 2 Pc x 2 Pc
Pi x 2 Pc
21
Optimum Design
Design for Minimum Loss and Maximum Efficiency
22
3
Q 2.22 f Bm A i A w K w 10 kVA
Et K Q
23
DESIGN OF CORE
2. Design of Core
Core type transformer :
Rectangular/Square /Stepped cross section
25
Design of Core
Core design is governed by rating of transformer, its operating
conditions and transport limitations.
For best economic use of core and conductor material, the core cross
section should be circular.
29
Square Core
d a
d : circumscribing Dia
a d cos
b d sin
b
a
d
Cruciform Core
d : circumscribing dia
a d cos
b d sin
b
a
d
Cruciform Core
d : circumscribing dia
a d cos
b d sin
a
d
Multi Stepped Cores
With an increase in the number of steps core space is utilized more
effectively.
Multi stepped cores also reduce the length of mean turn with
consequent reduction in both cost of copper and copper loss.
Stacking Factor- the net cross sectional area is obtained from the
dimensions of various packets and an allowance is made for the space
lost between lamination ; this allowance is known as stacking factor.
Utilization factor – Ratio of net cross sectional area to the gross area of
the core circle.
Design of Core
Square Core
Let, d - diameter of circumscribing circle
d a
a – side of square
2 2 2
Diameter, d a a 2 a 2 a
d
a
2
Let the stacking factor, Sf=0.9.
2
d
2
Gross core area, Agi Area of square a
2
Agi 0.5d 2
Net core area,
35
Design of Core
Square Core
Gross core area includes insulation area
Net core area excludes insulation area
d a
Area of Circumscribing circle is
d2
4
36
Design of Core
Stepped Core or Cruciform Core
Let , a – Length of the rectangle
b – breadth of the rectangle
d – diameter of the circumscribing circle and diagonal of the
rectangle.
θ – Angle b/w the diagonal and length of the rectangle.
rectangles.
(a-b)/2
Referring to the fig shown,
ab ab d b a
Gross core area, Agi ab b b
2 2 θ
2( a b ) (a-b)/2
ab b
2
ab ab b 2 2ab b 2 a
d : circumscribing dia
a d cos
b d sin
To maximize area for a given
diameter:
31‘45
a = 0.85 d
b = 0.53 d
b
a
d
Design of Core
Stepped Core or Cruciform Core
Gross core area, b
A gi 2ab b 2
(a-b)/2
d b a
2
A gi 2(0.85d)(0 .53d) (0.53d) θ
(a-b)/2
A gi 0.618d 2
a
43
Variation of core diameter
b
a
b d
a
d 44
Variation of core diameter
Higher core diameter increase cross sectional area of the core,
thereby increasing voltage per turn.
Higher voltage per turn reduces the number of turns in various
windings.
The increase in core diameter can result in reduction in core height . In
spite of reduction of core height, due to increase of core diameter ,the
core weight increase thereby increasing the no load loss of the
transformer. Number of winding turns is reduced though length of
mean turn increases.
The net effect reduces the weight of copper and obviously reduces
copper loss in winding.
On the other hand reduction of core diameter results in reduced core
weight along with lower no load loss but increased copper weight and
higher copper loss.
Selection of Core Area and
Type of Core
Stepped core cross section is preferred to obtain the optimum core
area within the circumscribing circle of the core .
The core area is determined by the number of steps, grade of steel ,
insulation or laminations and type of clamping.
Selection of type of core depends upon the rating ,operation duty and
transport limitations .
For large three phase transformers, five limbed core is recommended
to overcome the problem of higher height of the core .
For single phase shell transformers, one centre-wound limb with two
return limbs is a common configuration.
47
3. Choice of Flux Density
Advantages of higher value of flux density :
Smaller core area
Reduction in length of mean turn
Saving of copper in winding
Reduction in net weight of transformer
VLV AT
No. of turns in LV winding, TLV (or)
Et I LV
where, VLV Rated voltage of LV winding
I LV Rated Current of LV winding
Cont…
No. of turns in l.v. winding is determined in preliminary design.
Vl .v.
Tl .v. An integer
Et
H.V. winding turns per phase
Vh.v.
Th.v. Tl .v.
Vl .v.
Tappings on h.v. side:-
If the tappings are located in the middle part of and h.v.
winding, the number of winding turns must be even to
ensure the symmetry of winding.
For minimum loss, the value of current density in each of the two
winding should be equal.
A current density of 2.3 A/mm2 may be used for Cu conductor
BIS
57
Selection of Windings
Winding should be selected such that the desired electrical
characteristics and adequate mechanical strength is obtained.
In case more than one winding is suitable, the winding with simple
constructional features should be selected.
High voltage windings are usually of the following types :
Cylindrical winding with circular conductors.
Cross-over winding with either circular or small rectangular
conductors.
Continuous disc type winding with rectangular conductors.
Cylindrical windings are used for ratings upto 800 kVA and voltages
upto 433 V.
Helical winding can be used for ratings upto tens of MVA and
voltages upto 33 kV.
61
Design Example
Q. Design a 25kVA, 11000 / 433V, 50Hz, 3phase, delta /star core
type distribution transformer. The transformer is provided with
tappings at ± 2.5%,and ± 5% on H.V. winding.
Max. temperature rise not to exceed 450C with mean temperature
rise of oil 350C
62
EMF per Turn
63
Design Steps
1. , k = 0.45, E = 0.45√25
t = 2.25V
64
Design Steps
7. No of Turns of L.V and H.V. Winding T L.V ,T H.V.
Vl.v.= 433/√3 =250V,
Tl.v = Vl.v / Et
Vh.v.
Th.v. x 111/ T250
= 11000 l .v . =4884
Vl .v.
73
Insulation design
74
Insulation design
75
Insulation design
76
Major Insulation Of Transformers
25-630 12 3 30 - 14 2
800 and above 11 17 5 30 to 50 14 2
25-630 15 3.5 40 - 17 2
800 and above 15 17 5 40-50 17 2
10-800 27 5 60 2 30 3
1000 and above 33 27 5 75 2 30 3
Window Space Factor
Defined as ratio of copper area in the window to the total
window area.
Estimate value of Window space factor (Kw) can be found
using the following empirical formulae:
Kw = 8/(30+kV) transformers of rating about 20kVA
Kw = 10/(30+kV) transformers of rating 50 to 200kVA
Kw = 12/(30+kV) transformers of rating about 1000kVA
Here kV is h.v. winding voltage in kilo-volts.
Value of Kw can be increased or decreased during later stages of
design to decrease or increase window area.
Window Space Factor
Hw
Ww
82
Why window space factor decrease
when the voltage rating of transformer
increase?
For a given power, high voltage transformer requires more
insulation in window from phase to phase and phase to core.
Hw
Hw
Ww
Ww
88
3-Phase core Type Transformer
D = 1.7d
D = d + Ww
DY = a Hw H
H = Hw + 2HY
Hy
W = D + a a
W
Dy
d Ww d
91
Overall Dimensions
Single phase Shell Type
a
2a Hw
DY = b
HY = a a
H = Hw + 2a Ww
W = 2Ww + 4a
Depth
b Over
winding
92
Overall Dimensions
Thee phase Core Type
Hy Hy
a
Hw H Hw H
H = Hw + 2HY Hy Hy
W = 2D + a
a
W
Dy Dy
d Ww dd Ww d
D = d + Ww
D D
H = Hw + 2HY
DY = a W = 2D + a 93
TRANSFORMER DESIGN
Assignment
1.Design a 200 kVA, 50 Hz, 6.6kV/400V single phase core type, oil immersed
natural cooled power transformer. Temperature rise not to exceed 45℃,
with mean temperature rise of oil 35℃.
2. Design a 75 kVA, 11kV/400V, 50 Hz 3 phase ∆ / Y core type oil immersed
natural cooled distribution transformer. The transformer is provided with
tappings ±2.5 %, ±5 % on the HV winding. Maximum
temperature rise not to exceed 45℃, with mean temperature rise of
oil 35℃.
3. Design a 150 kVA, 6.6kV/440 V, 50 Hz single phase core type, oil immersed,
self-cooled power transformer. Average temperature rise of oil not to
exceed 35℃.
4. Design a 200 kVA, 50 Hz 11kV/400V single phase core type, oil immersed
natural cooled power transformer. The mean temperature rise not to
exceed 35℃. Maximum temperature rise not to exceed 45℃.
TRANSFORMER DESIGN
Assignment
5. Design a 100 kVA, 6.6kV/400V, 50 Hz 3 phase ∆/Y core type oil immersed natural
cooled distribution transformer. The transformer is provided with tapping±
2.5%, ± 5% on HV side. Mean temperature rise of oil should not exceed
35℃. Maximum temperature rise not to exceed 45℃.
6. Design a 150 kVA, 6.6kV/440V, 50 Hz single phase core type oil immersed, self-
cooled distribution transformer. Average temperature rise of oil not to
exceed 35℃. Maximum temperature rise not to exceed 45℃.
7. Design a 125 kVA, 11kV/400 V, 50 Hz 3 phase, ∆/Y core type oil immersed
natural cooled power transformer. Temperature rise not to exceed 35℃.
Maximum temperature rise not to exceed 45℃.
10. Design a 125 kVA, 6.6 kV/400V, 3 phase ∆/Y core type distribution
transformer. The mean Temperature rise not to exceed 35℃.
Maximum temperature rise not to exceed 45℃.
Cooling of transformers
Losses in transformer-Converted in heat energy.
Heat developed is transmitted by,
Conduction
Convection
Radiation
The paths of heat flow are,
From internal hot spot to the outer surface(in
contact with oil)
From outer surface to the oil
From the oil to the tank
From tank to the cooling medium-Air or water.
Increasing Surface area of tanks
98
Cooling of transformers
99
100
Cooling of transformers
Transformer Oil as Cooling Medium
107
Design of tanks with cooling tubes
C4
HT
D D
C3
WT
LT
C2 Doc C1
Design of tanks with cooling tubes
Dimensions of the tank:
Let
C1 – Clearance b/w winding and tank along width
C2 - Clearance b/w winding and tank along length
C3 – Clearance b/w the transformer frame and tank at the bottom
C4 - Clearance b/w the transformer frame and tank at the top
Doc – Outer diameter of the coil.
Width of the tank, WT = 2D + Doc + 2 C1 (For 3 Transformer)
= D + Doc + 2 C1 (For 1 Transformer)
Length of the tank, LT = Doc +2 C2
Height of the tank, HT = H + C3 + C4
Design of tanks with cooling tubes
Clearance on the sides depends on the voltage & power
ratings.
Clearance at the top depends on the oil height above the
assembled transformer & space for mounting the terminals
and tap changer.
Clearance at the bottom depends on the space required for
mounting the frame.
Design of tanks with cooling tubes
Clearance in mm
Voltage kVA Rating
C1 C2 C3 C4