SYSTEM
Basic Regulation
for
Design & Installation
パコ-ン パリヤワテ。
1
Rev.04 , Date : Sep’2009/01
Fire alarm system for each building size
4
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Heat Detector
1) Height < 4 m. 2) Height 4 m.< h < 6 m.
4.00 7.20
4.50 6.80
5.00 6.50
5.50 6.10
6.00 5.80
Note :-
1) Wall Heat Detector < 300 mm.
2) Supply Air Grill Heat Detector < 400
5
パコ-ン パリヤワテ。 mm. Rev.04 , Date : Sep’2009/01
Smoke Detector (1/2)
( Height < 10.5 m. ) *
Note :-
1) Wall Heat Detector < 300 mm.
2) Supply Air Grill Heat Detector < 400 mm.
3) Exit Stair (Fire proof area)
Install every 3 story
* Normal distance
6
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Smoke Detector (2/2)
7
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Smoke Beam Detector
8
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Aspirating Smoke Detector (ASD) or
Very Early Smoke Detection Apparatus (VESDA) (1/2)
9
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Aspirating Smoke Detector (ASD) or
Very Early Smoke Detection Apparatus (VESDA) (2/2)
10
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Alarm Device
12
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Zone of Detection (1/3)
Area Independent Zone
Open Area 1) Detection side distance < 30 m.
- General Room 2) Area < 500 m2 ( can be mixed with 3 storey )
3) Area < 1,000 m2 ( in same floor )
4) Area < 2,000 m2 ( in open area no have wall & room )
Close Area *
- Under Floor Independent Zone
- Above Ceiling * If need automatic detector followed EIT standard.
- Under Roof
Vertical Area
- Exit Fire Stair
Independent Zone
- Elevator Shaft
- M&E Shaft
Important Area
- Exit Fire Way
- E/E Room
Independent Zone
- M/C Room
- Hazardous Area
- Wind Duct
13
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Zone of Detection (2/3)
14
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Zone of Detection (3/3)
15
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Minimum space of Detector
16
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Close Area Protection
* Close area no need for protect all area , but detect for Electrical equipment only.
Note :-
Under Access Floor use same concept 17
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Intermediate Horizontal Surface
and
Open Grid Ceiling
Protection
18
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Area No need Protection
Except :
Cable in Fire wall
protection area (> 1 Hr.)
20
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
BATTERY RATE
1) Stand by 24 Hrs.
2) Alarm Status 15 Mins
3) Capacity more than total load 25%
21
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01
Fire Alarm System
Can be connect to
Fire Protection System
22
パコ-ン パリヤワテ。 Rev.04 , Date : Sep’2009/01