Battery Safety and Handling

EFCOG Electrical Safety Task Group

Module 9

09/06/07 EFCOG Electrical Safety Task 1


Group
Lead Acid Batteries
• Typically Lead-
Antimony.
• Made up of plates, lead,
lead oxide with 35%
sulfuric acid and 65%
water solution.
• The solution is called
electrolyte, which causes
a chemical reaction that
produces electrons.

09/06/07 EFCOG Electrical Safety Task 2


Group
Cell Element
Sepa ra tor

N eg a ti ve
Posit ive
Pl at e Group
Pl at e Group

09/06/07 EFCOG Electrical Safety Task 3


Group
Hazards Associated With
Industrial Batteries
Hydrogen Gas

Sulfuric Acid

Shock

Weight of the Battery

09/06/07 EFCOG Electrical Safety Task 4


Group
Hydrogen Gas

A by-product of the battery’s charging process.


Lighter than air.
Flammable in nature.
 Explosive mixture at 4 – 74% by volume of air.
Can not taste or see the gas vapors. You can smell
the acid in the battery if it heats up.

09/06/07 EFCOG Electrical Safety Task 5


Group
Acid Hazards

Ph <2 (Typically Sulfuric Acid)


Corrosive material
Burns to skin
Burns to eyes
Never open the battery caps with your face
directly over the battery.

09/06/07 EFCOG Electrical Safety Task 6


Group
Electrical Hazard
• Exposed terminals, even on disconnected batteries,
present an electrical shock hazard.
• Some battery systems are capable of discharging at
extremely high rates of current. Accidental shorting
of terminals or cables can result in severe electrical
arcing, causing burns and electric shock to nearby
personnel

09/06/07 EFCOG Electrical Safety Task 7


Group
Electrical Safety Precautions
Never touch both battery terminals with your bare
hands at the same time!
Remove rings, watches and dangling jewelry when
working with or near batteries. The metal in the
jewelry can cause a shock or burn if they contact the
battery terminals.
Only use insulated/non-conducting tools to remove
cell caps. Never lay tools or other metal parts on top
of a battery.

09/06/07 EFCOG Electrical Safety Task 8


Group
Electrical Safety Precautions
Consider covering battery terminals and connectors if
possible with an insulating blanket before overhead
inspections or repairs

Ensure charger is turned off before connecting or


disconnecting a battery to prevent arcing

09/06/07 EFCOG Electrical Safety Task 9


Group
Electrical Hazard
• DOE Event-Worker lost
control of a jumper wire
while working above battery
bank
• Ends of jumper were not
insulated and blanket was
not installed over battery
terminals
• Event resulted in severe
arcing and potential for
injury to worker

09/06/07 EFCOG Electrical Safety Task 10


Group
Fire and Explosion Precautions
 Do not smoke in battery charging areas.
 Prevent open flames, sparks or electric arcs in battery charging
areas.
 Do not strike the sides of the battery with any spark producing
item.
 Keep tools and other metallic objects away from uncovered
batteries.
 Have an ABC dry chemical fire extinguisher in charging areas
or readily available.

09/06/07 EFCOG Electrical Safety Task 11


Group
Fire and Explosion Precautions
 Neutralize static buildup just before working on battery by
contacting nearest grounded surface

 Ensure battery area ventilation is operating prior to working on

09/06/07 EFCOG Electrical Safety Task 12


Group
Battery Explosions
• DOE Event-This
starting battery
exploded during a load
test for a diesel
generator
• Explosion can expel
debris and battery acid
resulting in burns and
injury to nearby
personnel
09/06/07 EFCOG Electrical Safety Task 13
Group
Handling Battery Acid
• Use extreme caution when handling electrolyte and keep an acid
neutralizing solution—such as baking soda readily available

• Always wear proper eye, face and hand protection.

• Use non-metallic containers to handle liquid

• If the electrolyte is splashed into an eye, immediately force the eye open
and flood it with clean, cool water for at least 15 minutes. Get prompt
medical attention.

09/06/07 EFCOG Electrical Safety Task 14


Group
Handling Battery Acid
• If electrolyte is taken internally, drink large quantities of water or milk. DO
NOT induce vomiting. Call a physician immediately.

• Neutralize with baking soda any electrolyte that spills on a vehicle or in the
work area. After neutralizing, rinse contaminated area clean with water.

• To prepare electrolyte of a desired specific gravity, always pour the


concentrated acid slowly into the water; DO NOT pour water into the acid.
Always stir the water while adding small amounts of acid. If noticeable
heat develops, allow the solution to cool before continuing to add acid.

09/06/07 EFCOG Electrical Safety Task 15


Group
Changing Batteries
 Industrial batteries used to power mobile equipment can
weight upwards of 1,500 lbs.

 Ensure the battery is securely locked in place prior to


pulling away from the battery changing area.

 Do not attempt to stop a battery if it slides out of the


equipment.

09/06/07 EFCOG Electrical Safety Task 16


Group
Changing Batteries
 Work on Batteries requires Non-Sparking and Insulated
tools.
 Insulation must be listed for the voltage present
 Taped wrenches are not listed

 Batteries should never be lifted by the post.

09/06/07 EFCOG Electrical Safety Task 17


Group
Safe Handling of Batteries

 Use appropriate equipment to load/unload batteries from


mobile equipment.
 Ensure you are trained in using the loading equipment.
 Keep tools and other metallic objects away from uncovered
batteries.
 Use Baking Soda or cleaning agent specified in AHA to
neutralize spilled acid.

09/06/07 EFCOG Electrical Safety Task 18


Group
Jumping a Discharged Vehicle Battery
• When jump starting a vehicle, always wear proper eye
protection and never lean over battery.

• Inspect both batteries before connecting booster cables. Do not


jump start a damaged battery.

• Be sure vent caps are tight and level.

• Make certain that the vehicles are not touching and both
ignition switches are turned to the OFF position.

• Refer to the vehicle owners' manual for other specific


information.

09/06/07 EFCOG Electrical Safety Task 19


Group
Jumping a Battery

09/06/07 EFCOG Electrical Safety Task 20


Group
Battery Jumping Sequence
• Connect positive (+) booster cable to positive (+) terminal of discharged
battery.

• Connect other end of positive (+) cable to positive (+) terminal of assisting
battery.

• Connect negative (-) cable to negative (-) terminal of assisting battery.

• MAKE FINAL CONNECTION OF NEGATIVE (-) CABLE TO ENGINE


BLOCK OF STALLED VEHICLE, AWAY FROM BATTERY.

• Start vehicle and remove cables in REVERSE order of connections.

09/06/07 EFCOG Electrical Safety Task 21


Group
PROTECTIVE CLOTHING
General Requirements for Handling

For general handling of


batteries with terminal
post taped

PPE Requirements:
• As specified in local
AHA or procedure

09/06/07 EFCOG Electrical Safety Task 22


Group
PROTECTIVE CLOTHING Requirements
for Electrolyte Handling
PPE Requirements:
• Safety Glasses/goggles
• Rubber Gloves
• Face Shield
• Chemical Apron
• Boots

09/06/07 EFCOG Electrical Safety Task 23


Group
Safety Eye Wash & Shower
Requirements
•An eyewash facility should be capable of
flushing both eyes simultaneously for fifteen
minutes and a water hose or safety shower
that, if portable, is capable of drenching the
body.
•Eyewash and drenching facilities are to be
located as close to the point of exposure as
possible of battery handling areas (not to
exceed 25 ft.) (OSHA)

•If Acid comes in contact with eyes, flush for 15


minutes and report to medical immediately.
• If acid comes in contact with skin or clothing,
rinse off for several minutes and try not to spread
the electrolyte. Report to medical after rinsing.

Note: Eyewash and drenching facilities are not required for non-vented batteries.
09/06/07 EFCOG Electrical Safety Task 24
Group
Battery Safety

Know the Hazards


Use the required PPE
No Open Flame

09/06/07 EFCOG Electrical Safety Task 25