Professional Documents
Culture Documents
Sharaf Hosseini
Product Manager
December 2010
MiCOM ALSTOM P642, P643, P645
APPLICATIONS
Auxiliary
transformers Autotransformers
Two/Three
Generators Winding
Transformers
Short
Reactors
Interconnectors
HV+LV
P642
HV+LV+TV
HV+LV
P643
P643
HV+LV+TV
HV+LV
P645
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 6
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Differential Protection
Directional(1)/Non-directional
Voltage controlled(1) 1-2stages 1-2stages 1-2stages
Stub bus(3)
Breaker Failure
Earth Fault: 2-4stages 3-4 stages 3-4 stages
Directional(1)/Non-directional
Directional(1)/Non-directional
Notes:
(1) 3Φ VT option fitted in P643/P645 and additional 1Φ VT option fitted in P642
(2) IDMT characteristics available for stages 1 and 2 of NPS elements
(3) PSL configuration required
Notes:
(1) Requires 3Φ VT option
(2) Frequency protection may use voltage or current signals
NA = not available
VT Supervision(1)
2 neutral CT inputs
3 neutral CT inputs
8 times/cycle 4 times/cycle
Frequency
Voltage No track channel
signal
order: IA1, IB1,
available
IC1,...IC5
Yes No
Frequency
track Voltage
Yes signal
channel
order: VA, available
VB, VC, Vx
Yes
Voltage
signal No
available
I diff 2H
2nd harmonic Block
mag inrush
detection
I d biased I d biased Trip
delay
Differential
Biased AND
Change Is1 to Characteristic
Is_CTS in I diff HS1
Id biased
CT restraint mode Trip Idiff Trip
K2 Start OR
Supervision
Is1 K1
Is2
AND
Yes
Counter += 1
Counter
>= 2
Yes
Drop off
Block single
phase low-set diff
No
Cross Yes Block three
block phase low-set
setting diff
No
Ratio
P640 correction
Scheme
Vectorial
correction
Zero Seq.
87T trap
Software Compensation
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 24
Software Compensation
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Transformer Differential (87T)
Fifth harmonic restraint
Any phase No
Idiff (5 fn)/Idiff (fn) Counter = 0
> Settings
Yes
Counter +=1
Counter
>=2
Yes
Drop off
Block single
phase low-set diff
No
B B
b b b b b
B B
c c c c c
B B
3:1
D D D
Grounding transformer
AN external I1 inside the protected
fault
zone I3
I2
a a a a a
I7 B B
I4
b b b b
B B
I5 b
c c c c c
B B
I6
D D D
3:1
NOTE:
I1 = INOM Ð180° I4 = I5 + I6
I2 = INOM × KWYE/3KDELTA Ð0° I5 = I6 = |I2|/3
I3 = INOM × KWYE/3KDELTA Ð180° I7 = |I1|/3
No
Idiff peak < Is-HS1
Transient bias = 0
Yes
Yes
Yes
Yes
25.0
20.0
15.0
Idiff (pu)
10.0 charact_maxbias
charct_transientbias_A
charact_transientbias_B
5.0 charact_transientbias_C
0.0
0.0 5.0 10.0 15.0 20.0 25.0 30.0
Ibias (pu)
- m
Im
2 m
Switch on at voltage
V zero - No residual flux
175/145/30 MVA
230/115/13.8 kV
230kV YNynd1
+5%/-15%
19 taps 2000:5
1200:5 A 800:5 a
A
B b
B
C c
C
Grounding
transformer
inside the
protection zone
a a a a a
B B
b b b b b
B B
c c c c c
B B
Yd11 software
Ydy0 software
interposing CT
interposing CT
a a a
b b b
c c c
B
D D D
Ydy0 software
interposing CT P645
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 35
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Application Example
Autotransformer Differential Protection
175 ´ 106
IFLC,TV 7321 .47 A
3 ´ 13.8 ´ 10 3
Inom,LV 2000
K amp,TV 0.273
IFLC,LV 7321 .47
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 38
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Application Example
Autotransformer Differential Protection
►No mal-operation due to tap changer errors:
2.5
Bias characteristic
0.5
0
0 0.5 1 1.5 2 2.5 3 3.5 4
Ibias/Inom
LV UndCurrent
DDB #984 & Dw ell
Output R3
DDB #002
DDB #1694
& S
Q LV StubBus Act
DDB #648
0
R
LV isolatior aux. contact
Input L2 LV StubBus Enabl
DDB #065 DDB #645
The output of the AND gate is HIGH only if CTS I2/I1>2 of CT1 is high and I2/I1 ratio in all
the other current inputs is below the standing unbalance of the system.
I2/I1 CT1
I2/I1 CT2
CTS I2/I1>2
CTS I2/I1>1
& &
CTS CT1
►CTS I2/I1>1 = 20%
I2/I1 CT3 CTS I2/I1>1
I2/I1 CT4 CTS I2/I1>1
I2/I1 CT5 CTS I2/I1>1
&
►CTS I1 = 10%
CTS CT2
CTS I2/I1>1
&
CTS I2/I1>2
CTS I2/I1>1 ►CTS time delay = 1sec
CTS I2/I1>1
CTS I2/I1>1
&
CTS I2/I1>1
& CTS CT3
CTS I2/I1>1
CTS I2/I1>2
CTS I2/I1>1
CTS I2/I1>1
CTS I2/I1>1
& &
CTS I2/I1>1
CTS CT4
CTS I2/I1>1
CTS I2/I1>2
CTS I2/I1>1
CTS I2/I1>1
& &
CTS I2/I1>1
CTS CT5
CTS I2/I1>1
CTS I2/I1>1
CTS I2/I1>2
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 45
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Patented CT Supervision (3)
Operating region K2
Is-CTS
Is1 K1
Restraint
region
Is1/K1 Is2 Ibias/In
CTS impact on 87T depends on setting:
Alarm Mode: Indication only
Restrain Mode: Is-CTS de-sensitise to avoid a trip on max. load
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 46
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
VT Supervision (1)
A
B
C
1 and 2
logic
3 on load
logic
Alarms
VTS Event record
3 on Blocking
energisation
logic Adaptive setting
MCB digital
input
P64x
I VTS alarm
VTS block
& LCD
Voltage Event records
collapse
P64x
VTS I>
Inhibit VTS alarm
VTS block
& LCD
No Event records
Voltage
C C
B B
A A
0 ... x ... 1
87T
C c
V1
x The earthing resistor is rated to pass full load current IFLC
3R
Assuming that V1 = V2 then:
V 1 T 1
V 2 T 2
T2:T1 V1 3 V 1 3 T 1
3:1
V2 V 2 T2
3 T 1
1 T 2 3 T 1
T2
x.V1
For a fault at x pu distance from the neutral If is If
3R
The secondary fault current referred to the primary is
x V1 x T1
I primary
3R T2
1
x 2 IFLC
3
• Applicable in 1.5 CB
arrangements
• CTm and CTn are the current Operating
inputs associated to a Region
particular winding K2
• High sensitivity (5%)
Differential trip
OR Yes
Ibiasn < 0.5 ´ Is1
No Transient bias = 0
Yes
New transient bias New transient bias
Itbiasn = DIbias ´ D Itbiasn DIbias ´ E
Yes
Yes
Transient bias = New transient bias = Itbiasn Transient bias = 0 Transient bias = transient bias ´ e-t/t
Return
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 56
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. Note:
No representation or warranty isD,
The constants given
E orandto betimplied
whereasdetermined
to the completeness of
by test. In is the nominal current.
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Stability in the Presence of CT Saturation
Transient Bias Logic - 1.5 breaker arrangement Calculate latest bias current = Ibiasn
Differential trip
OR Yes
Ibiasn < 0.5 ´ Is1
No Transient bias = 0
Yes Yes
New transient bias New transient bias New transient bias
Itbiasn = DIbias ´ F Itbiasn DIbias ´ G Itbiasn DIbias ´ H
Yes
Yes
Transient bias = New transient bias = Itbiasn Transient bias = 0 Transient bias = transient bias ´ e-t/t
Return
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 57
© ALSTOM 2010. All rights reserved. Information contained in Note:
this document is provided without
The constants F, G,liability
H and for information purposes
t where determined by test. In is the nominal current.
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
NEW
Thermal Overload and Loss of Life
Oil exponent
Top oil
time constant
Ratio of load loss
tTO n
to no load loss
Top oil TO
Temperature
Coolant (oil/air)
H R Temperature a
I2t m
Hot spot w
a
Temperature
Setting Guidelines:
• Set monitor winding to HV, LV, TV or biased current.
• Set the ambient temperature to average or measured
(CLIO or RTD)
• Set top oil temperature as calculated or measured.
• IB is the load in pu. Set it to rated load, i.e. 1.0pu.
• The thermal characteristics are given by the
transformer manufacturer. An example of such
parameters are provided in the next table.
• Three hot spot and three top oil stages are available.
Thermal Characteristic
735 MVA 300 kV +7% to -18% / 23kV ODWF cooled
generator transformer
No load losses (core losses) 340kW
Load losses at nominal tap 1580kW
Load losses at maximum current tap 1963kW
Oil time constant 135 min
Oil exponent 1.0
Top oil rise over ambient temperature at rated 33.4°C
load
Winding time constant at hot spot location 14 mins
Winding hottest spot rise over top oil 30.2°C
temperature at rated load
Winding exponent 2.0
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 63
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
CLIO (Current Loop Input Output)
Connection IO Blocks Connection
Outputs
• Same connectors as
0-1mA channel 1
Screen channel 1
Common return channel 1
Screen channel 2
0-10/ 0-20/ 4-20mA channel 2
0-1mA channel 2
RTD board
Common return channel 2
Screen channel 3
0-10/ 0-20/ 4-20mA channel 3
0-1mA channel 3
• One board per relay
Common return channel 3
Screen channel 4
0-10/ 0-20/ 4-20mA channel 4
0-1mA channel 4
• 0 - 1mA (separate
Common return channel 4
connection)
Inputs
10000
1000
Per Unit Life
100
10
1
0.1
0.01
0.001
0.0001
0 50 100110 150 200 250
Hottest Spot Temperature (°C)
• Temperature principal variable that affects thermal life
• This curve applies for distribution and power
transformers
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 66
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Loss of Life
Ageing Acceleration Factor (relative to 110°C)
Ageing Acceleration Factor
10000
1000
100
10
1
0.1
0.01
0.001
0.0001
110
0 50 100 150 200 250
Hottest Spot Temperature (°C)
• Temperature principal variable that affects thermal life
• This curve applies for distribution and power
transformers
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 67
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Loss of Life
V = kf 2m
Causes
► Low frequency
m
► High voltage
► Geomagnetic disturbances
Effects Ie
► Increase in mag. Current Tripping of differential element
(Transient overfluxing)
► Increase in winding temperature
► overheating of laminations and metal parts
► Increase in noise and vibration
Damage to transformers (Prolonged overfluxing)
P645
V/f>>>
10
1
1
0.1 0.1
1 10 100 1 10 100
Current (Multiples of Is) Current (Multiples of Is)
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 85
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Inverse Time Characteristics
RI Curve (electromechanical)
Overcurrent and Earth Fault Elements
Operating Time (s) RI Curve
100
K = 10
IDG Curve
10 7
IDG Is setting range
6
5
4
3
1
2
K = 0.1 IDG Time setting range
1
0
1 10 100
0.1
1 10 100
Current (Multiples of Is)
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 86
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
Current Summation for Ring-Bus and
(1 ½ Breaker) Windings
• Overcurrent protection is per winding
• HV, LV and TV currents may be reconstructed via
current summation from the individual CT sets
which energise each winding
+
HV Software
Summation
DT, IDMT
I>, IN>, I2>
Backtrip
• Two stage
f
fnom t
Start
f
Trip
t
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 91
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
P642 Hardware Options
Hardware options
Standard – no options 1
IRIG-B only (modulated) 2
Fiber optic converter only 3
IRIG-B (modulated)& fiber optic converter 4
Ethernet with 100Mbit/s fibre-optic port 6
2nd Rear Comms Port (Courier EIA232/EIA485/k-bus) 7
2nd Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus) 8
Ethernet (100Mbit/s) + IRIG-B (modulated) A
Ethernet (100Mbit/s) + IRIG-B (de-modulated) B
IRIG-B (de-modulated) C
Product Specific
Size 8 (40TE) case, 8 optos + 8 relays A
Size 8 (40TE) case, 8 optos + 8 relays + RTD B
Size 8 (40TE) case, 8 optos + 8 relays + CLIO (mA I/O) C
Size 8 (40TE) case, 12 optos + 12 relays D
Size 8 (40TE) case, 8 optos + 12 relays (including 4 High Break) E
Hardware options
Standard – no options 1
IRIG-B only (modulated) 2
Fiber optic converter only 3
IRIG-B (modulated)& fiber optic converter 4
Ethernet with 100Mbit/s fibre-optic port 6
2nd Rear Comms Port (Courier EIA232/EIA485/k-bus) 7
2nd Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus) 8
Ethernet (100Mbit/s) + IRIG-B (modulated) A
Ethernet (100Mbit/s) + IRIG-B (de-modulated) B
IRIG-B (de-modulated) C
Product Specific
Size 12 (60TE) case, 16 optos + 16 relays A
Size 12 (60TE) case, 16 optos + 16 relays + RTD B
Size 12 (60TE) case, 16 optos + 16 relays + CLIO (mA I/O) C
Size 12 (60TE) case, 24 optos + 16 relays D
Size 12 (60TE) case, 16 optos + 24 relays E
Transformer Protection,
Size 12 and (60TE)
Monitoringcase,
IEDs – Nov
16 2010 - P+
optos 9320 relays (including 4 High Break) F
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
P645 Hardware Options
Hardware options
Standard – no options 1
IRIG-B only (modulated) 2
Fiber optic converter only 3
IRIG-B (modulated)& fiber optic converter 4
Ethernet with 100Mbit/s fibre-optic port 6
2nd Rear Comms Port (Courier EIA232/EIA485/k-bus) 7
2nd Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus) 8
Ethernet (100Mbit/s) + IRIG-B (modulated) A
Ethernet (100Mbit/s) + IRIG-B (de-modulated) B
IRIG-B (de-modulated) C
Product Specific
Size 12 (60TE) case, 16 optos + 16 relays A
Size 12 (60TE) case, 16 optos + 16 relays + RTD B
Size 12 (60TE) case, 16 optos + 16 relays + CLIO (mA I/O) C
Size 12 (60TE) case, 24 optos + 16 relays D
Size 12 (60TE) case, 16 optos + 24 relays E
Size 16 (80TE) case, 24 optos + 24 relays F
Size 16 (80TE) case, 24 optos + 24 relays + RTD G
Size 16 (80TE) case, 24 optos + 24 relays + CLIO (mA I/O) H
Size 16 (80TE) case, 24 optos + 24 relays + RTD + CLIO (mA I/O) J
Size 12 (60TE) case, 16 optos + 20 relays (including 4 high break) K
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) L
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD M
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + CLIO (mA I/O) N
Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD + CLIO (mA I/O) P
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) Q
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD R
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + CLIO (mA I/O) S
Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD + CLIO (mA I/O) T
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 94
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
MiCOM P64x Series Transformer Protection:
Summary
• Full protection, monitoring, measurements and recording in a single
IED solution
• Modern numerical platform built on long design pedigree of
transformer protection within AREVA
− DTH, MBCH, KBCH, PQ, P63x
• Equipped for up to three windings: HV, LV, TV
• With up to 5 bias inputs (CT sets)
• All main protection: 87T, REF, thermal
• And backup elements: I>, IN>, I2>….
− Directionalised where applicable
− Breaker fail
• Expandable hardware options
− VTs, CLIO, RTDs, IRIG-B, ethernet, user selectable I/O
• Intuitive software
− Settings minimised to reduce potential for error
− Settings wizards
Transformer Protection, and Monitoring IEDs – Nov 2010 - P 95
© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes
only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of
information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority,
is strictly prohibited.
www.alstom.com