Floor Plan

Sl No Descrription Area
1 Reception 1512
2
3
Cabin
Cabin
132
132
A B C D E F W G
N
4 Meeting Room 10 seater 200
5 Board Room 1145
6 Training Room 38 seater 1250
7 Lab 1158
8 Break out area 514
9 Workstation 15800
10 Data Center 1
1650 SHAFT

11 Cabins 808
12 Meeting Room 8 seater 177 PL PL
13 Cabin 128 AHU STORE RECEPTION
ROOM ROOM LIFT LOBBY
14 UPS Room 263 WAITING AREA
Total Area 24869 PL PL

SLIDING DOOR
CABIN

SLIDING DOOR

MEETING ROOM
8 SEATEDR CABIN
PAC ROOM 6'-6"

CABIN
3
CABIN

DATA CENTER
MEETING ROOM
10 SEATEDR
CABIN
4
CABIN BOARD ROOM
31 SEATER

CABIN WORKSTATIONS
5 227 Nos
CABIN

WHITE BOARD

WHITE BOARD

CABIN TRAINING ROOM


38 SEATER
6
LAB
30 Kw
SHAFT

7
Building Description

• A building in Bangalore has Basement , Ground + 3 floors.

• Client ABC corp. has taken the second floor.

• The floor above is built for 50% of the total area. It is used as a
non AC area.

• Floor below is a car showroom. 30% of the floor is used as


service center and spare parts store.

• North and West side has single glazing punch windows.

• South and east sides have double glazing.


Clients Inputs

• Office areas to be designed for 25 deg F and RH not exceeding 60%.

• Power consumption of each work station is 160 watts.

• Fresh air load – 15 cfm person.

• Lighting load to be 1.5 watt/ sft.

• Data center to be maintained at 21 deg C and 50 % RH.

• Equipment load in data center is 124 KVA.

• Equipment load in lab is 30 KW.

• UPS configuration is 90 KVA x 2 nos. Heat loss from the UPS is 10%.
HEAT LOAD ESTIMATION

Archite cts :- Basis Of Design


Clie nt:- Date:- Estimate f or : Summer
Address : Bangalore Heat Load no :1 Location : Bangalore
DB WB RH Gr / Lb
Space Used For : Ambient
Location : Design
Area : Sun gain / Dif f erence
Se ns ible He at Are a Solar diff. U Factor BTU / HR
Glass No rth X X
N.East X X
N.West X X
So uth X X
S.East X X
S.West X X R.S.H.F
East X X ADP
West X X Dehum Rise
Solar Trans m is s ion w alls and roof
Wall No rth X X
N.East X X
N.West X X
So uth X X De.Hum cf m
S.East X X
S.West X X
East X X
West X X
Othe r Trans m is s ion gains
All glass x x
Glass Parti. x
Partition x x
Ceiling x x Che ck Figure s
Exp. Roof x sf t / person
Floor x x sf t / Ton
People x x cf m / sf t
Outside Air x x cf m / TR
Lights x x
Computers x x Fr. Air changes
Equipment x x
R.S.H T. Air changes
Fan + S.Factor
R.T.S.H. Note s :
Room Late nt He at 1
People x
Outdoor air x 2
R.L.H
S.Factor 3
R.T.L.H.
R.T.H. 4
Outs ide air He at
Sensible heat x
Latent heat x
Return air heat gain
Grand Total He at gain
Tonnage
Cf m
HEAT LOAD ESTIMATION FOR BANGALORE CONDITIONS

DB WB RH Gr / Lb
Ambient 96 78 116
Design 75 55 72
Difference 21 44

Page : 1, Table 1

Outside Design Data


Peak Lat Alt Daily Summer °F Mansoon °F Winter °F Summer °C Monsoon °C Winter °C
State & Station month Deg. N Mts. Range DB. WB. RH DB. WB. RH DB. WB. RH DB. WB. DB. WB. DB. WB.
°F % % %
Karnataka
Banagalore April 12.6 921 22 96 78 45 82 78 82 58 54 78 35.6 25.6 27.8 25.6 14.4 12.2
Mysore April 12.2 767 21 100 78 38 85 77 69 66 60 70 37.8 25.6 29.4 25.0 18.9 15.6
Mangalore May 12.5 22 11 92 82 55 85 82 88 70 64 72 33.3 27.8 29.4 27.8 21.1 17.8
Bellary May 15.1 449 23 105 77 28 94 78 50 65 59 70 40.6 25.0 34.4 25.6 18.3 15.0
Belgaum April 15.5 753 29 100 77 35 82 77 80 58 53 71 37.8 25.0 27.8 25.0 14.4 11.7
Raichur 16.1 - - 107 79 29 93 82 62 60 54 69 41.7 26.1 33.9 27.8 15.6 12.2
SOLAR HEAT GAIN THROUGH GLASS
Page 7, Table 7

S olar Heat G ain T hroug h O rdinary G las s


B T U / (hr) (s q ft s as h area)

10° North L atitude AM S UN T IME PM 10° S outh L atitude


T ime O f T ime O f
E xpos ure 6 7 8 9 10 11 Noon 1 2 3 4 5 6 E xpos ure
Y ear Y ear
North 1 15 16 15 15 14 14 14 15 15 16 15 1 S outh
Northeas t 17 113 130 111 80 34 14 14 14 13 11 7 1 S outheas t
E as t 25 138 163 149 104 46 14 14 14 13 11 7 1 E as t
S outheas t 18 79 94 85 60 27 14 14 14 13 11 7 1 Northeas t
Aug 24 & F eb 20 &
S outh 1 7 11 13 14 14 14 14 14 13 11 7 1 North
Apr 20 O ct 23
S outhwes t 1 7 11 13 14 14 14 27 60 85 94 79 18 Northwes t
W es t 1 7 11 13 14 14 14 46 80 149 163 138 25 W es t
Northwes t 1 7 11 13 14 14 14 34 15 111 130 113 17 S outhwes t
Horizontal 2 38 105 167 213 242 250 242 213 167 105 38 2 Horizontal
Dew P oint
S olar G ain Dew P oint Inc reas e S outh L at. Dec ember
S teel S as h, or No S as h Haz e Altitude Dec reas e from
C orrec tion from 67 F or J anuary
67 F
x 1/0.85 or 1.17 -15% (Max) 0.7% per 1000 F t 7% per 10F -7% P er 10 F + 7%
S ample c alc ulation U fac tor for expos ed wall
Solar Transm ission w alls and roof R efer table 21 to 34 c arrier Air C onditioning Hand book
Sun gain / C ons truc tion R es is tanc e
Sensible Heat Area Solar diff. U Factor BTU / HR
O utdoor Air s urfae film (7.5 Mph W ind) 0.25
Wall No rth X 10 X 0.36 B rick facing, 9 Inch 1.60
N.East X 12 X 0.36 0.5" C ement mortar 0.10
N.West X 12 X 0.36 S and cement plas ter 1" (0.5" on B oth s ides ) 0.20
26 Ins ide Air s urface (S till air) 0.68
So uth X X 0.36
T otal R es is tanc e 2.83
S.East X 18 X 0.36
S.West X 32 X 0.36 U = 1 = 1 = 0.35 B T U / (hr) (s q.ft.) (deg F )
East X 12 X 0.36 R 2.83
West X 26 X 0.36

Equivalent Temperature Difference (Deg F)


For Dark Colored †, Sunlight and shaded Walls*

Page 13, Table 9 Based on Dark Colored Walls; 95 F db Outdoor Temp; Constant 80 F db Room Temp;
20 deg F Daily Range; 24 hour Operation; July and 40° N. Lat †
Weight of SUN TIME
Exposure Wall AM PM AM
(lb/sq.ft) 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5
20 5 15 22 23 24 19 14 13 12 13 14 14 14 12 10 8 6 4 2 0 -2 -3 -4 -2
60 -1 -2 -2 5 24 22 20 15 10 11 12 13 14 13 12 11 10 8 6 4 2 1 0 -1
Northeast
100 4 3 4 4 4 10 16 15 14 12 10 11 12 12 12 11 10 9 8 7 6 6 5 5
140 5 5 6 6 6 6 6 10 14 16 14 12 10 10 10 10 10 10 10 9 9 8 7 7

introduce a slide East


20
60
100
1
-1
5
17
-1
5
30
0
6
33
21
8
36
30
14
36
30
14
32
31
24
20
19
25
12
14
24
13
13
20
14
12
18
14
13
16
14
14
14
12
13
14
10
12
14
8
11
13
6
10
12
4
8
11
2
5
10
0
4
9
-1
3
8
-2
1
7
-3
1
7
-3
0
6

for selecting Southeas


140
20
60
11
10
1
10
6
1
10
13
0
19
13
9 8
26
20
26
20
8 10
28
28
15
26
26
18
24
25
19
19
21
18
16
18
17
15
15
16
14
14
14
12
13
12
10
12
13
8
11
14
6
10
14
4
8
14
2
6
13
0
5
13
-1
4
12
-1
3
12
-2
3
12
-2
2

factor for roof t 100


140
20
7
9
-1
7
8
-2
6
8
-4
6
8
1
6
8
4
6
8
4
16
6
22
17
11
27
18
14
30
19
15
28
18
16
26
16
18
20
14
16
16
13
15
12
12
14
10
1
13
7
10
12
6
10
12
3
10
12
2
9
11
1
9
11
1
10
8

0
8
10
0
7
9
-1
60 -1 -3 -4 -3 -2 -2 12 20 24 25 26 23 20 15 12 10 8 6 4 2 1 1 0 -1
South
100 4 4 2 2 2 2 4 8 12 15 16 18 18 15 14 11 10 9 8 8 7 6 6 5
140 7 6 6 5 4 4 4 4 4 7 10 13 14 15 16 16 14 12 10 10 9 9 8 7
20 -2 -4 -4 -2 0 0 6 19 26 34 40 41 42 30 24 12 6 4 2 1 1 0 -1 -1
Southwes 60 2 1 0 0 0 0 2 8 12 24 32 35 36 35 34 20 10 7 6 5 4 4 3 3
t 100 7 5 6 5 4 4 6 7 8 12 14 19 22 23 24 23 22 15 10 10 9 9 8 7
140 8 8 8 8 8 8 6 6 6 7 8 9 10 15 18 19 20 13 8 8 8 8 8 8
20 -2 -3 -4 -2 0 3 6 14 20 32 40 45 48 34 22 14 8 5 2 1 0 0 -1 -1
60 2 1 0 0 0 2 4 7 10 19 26 34 40 41 36 28 16 10 6 5 4 3 3 2
West
100 7 7 6 6 6 6 6 7 8 10 12 17 20 25 28 27 26 19 14 12 11 10 9 8
140 12 11 10 9 8 8 8 9 10 10 10 11 12 14 16 21 22 23 22 20 18 16 15 13
20 -3 -4 -4 -2 0 3 6 10 12 19 24 33 40 37 34 18 6 4 2 0 -1 -1 -2 -2
Northwes 60 -2 -3 -4 -3 -2 0 2 6 8 10 12 21 30 31 32 21 12 8 6 4 3 1 0 -1
t 100 5 4 4 4 4 4 4 4 4 5 6 9 12 17 20 21 22 14 8 7 7 6 6 5
140 8 7 6 6 6 6 6 6 6 6 6 7 8 9 10 14 18 19 20 16 13 11 10 9
20 -3 -3 -4 -2 -2 1 4 8 10 12 14 13 12 10 8 6 4 2 0 0 -1 -1 -2 -2
North 60 -3 -3 -4 -2 -2 -1 0 3 6 8 10 11 12 12 12 10 8 6 4 2 1 0 -1 -2
(Shade) 100 1 1 0 0 0 0 0 1 2 3 4 5 5 5 8 7 6 5 4 3 3 2 2 1
140 1 1 0 0 0 0 0 0 0 1 2 3 4 5 6 7 8 7 6 4 3 2 2 1
6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5
AM PM AM
SUN TIME
Page 14, Table 10

C orrec tions to E quiv alent T emperatures (D eg F )

Outdoor De sig n for


Month At 3 P M
D AIL Y R ANG E
Minus R oom T e m p 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
-30 -39 -40 -41 -42 -43 -44 -45 -46 -47 -48 -49 -50 -51 -52 -53 -54 -55
-20 -29 -30 -31 -32 -33 -34 -35 -36 -37 -38 -39 -40 -41 -42 -43 -44 -45
-10 -19 -20 -21 -22 -23 -24 -25 -26 -27 -28 -29 -30 -31 -32 -33 -34 -35
0 -9 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23 -24 -25
5 -4 -5 -6 -7 -8 -9 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20
10 1 0 -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11 -12 -13 -14 -15
15 6 5 4 3 2 1 0 -1 -2 -3 -4 -5 -6 -7 -8 -9 -10
20 11 10 9 8 7 6 5 4 3 2 1 0 -1 -2 -3 -4 -5
25 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
30 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5
35 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
40 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15

Daily range temperature for Bangalore = 22 Deg F


Difference in Out door and Indoor Temperatures = 21 Deg F
for 20 Deg F correction factor is 4
for 25 Deg F correction factor is 9
so for 21 Deg F correction factor is 5
Solar Transm ission w alls and roof
Sun gain /
Sensible Heat Area Solar diff. U Factor BTU / HR
Wall No rth X (10+5) X 0.36
N.East X (12+5) X 0.36
N.West X (12+5) X 0.36
So uth X (26+5) X 0.36
S.East X (18+5) X 0.36
S.West X (32+5) X 0.36
East X (12+5) X 0.36
West X (26+5) X 0.36

Solar Transm ission w alls and roof


Sun gain /
Sensible Heat Area Solar diff. U Factor BTU / HR
Wall No rth X 15 X 0.36
N.East X 17 X 0.36
N.West X 17 X 0.36
So uth X 31 X 0.36
S.East X 23 X 0.36
S.West X 37 X 0.36
East X 17 X 0.36
West X 31 X 0.36
Table 6 - trans m is s ion coefficient U - Windows , S kylig hts , D oors & G las s B lock walls
B tu/ (hr) (s q.ft) (deg F tem p diff)
G las s
Vertical H orizontal g las s
S ing le D ouble Triple S ing le D ouble (1/4")
Air s pace Thicknes s (in.) 1/4 1/2 .3/4-4 1/4 1/2 .3/4-4 S um m er winter S um m er winter
Without S torm windows 1.13 0.61 0.55 0.53 0.41 0.36 0.34 0.86 1.4 0.5 0.7
With S torm windows 0.54 0.43 0.64

Out side Temp – Room temp. Page 6, Table 5


Other Transm ission gains
All glass x 21 x 0.61
Glass Parti. x 16 x 1.13
((Out side Temp Partition x 16 x 0.4
– Room temp)-5 deg F)
Ceiling x 16 x 0.4 Bypass Factor
Exp. Roof x 37 0.12
Floor x 16 x 0.4
People x 245 x
Outside Air x 21 x 0.12 * 1.08
Lights x 1 x 1.25 x 3.4
Out side Temp – Room temp.
Computers x 160 x 3.4
Equipment x 3400 x

Watts per computer


Ballast Factor
Construction Resistance Sample calculation U factor for un exposed wall
Outdoor Air surface film (7.5 Mph Wind) 0.3 Construction Resistance
Plaster 0.5" 0.1 Indoor Air surface film (Still Air) 0.61
Insulation 2 in 7.0 Plaster 0.5" 0.10
Concrete 4" 0.8 0.80
Brick facing, 4 Inch
Inside air surface (Still Air) 0.9 0.10
Plaster 0.5"
Total Resistance 9.07 0.61
Inside air surface (Still Air)
Total Resistance 2.22

U = 1 = 1 = 0.11 BTU / (hr)(sq.ft.)(deg F)


R 9.07 U = 1 = 1 = 0.4 BTU / (hr)(sq.ft.)(deg F)
R 2.22

Other Transm ission gains


All glass x 21 x 0.61
Glass Parti. x 16 x 1.13
Partition x 16 x 0.4
Ceiling x 16 x 0.4
Exp. Roof x 37 0.12
Floor x 16 x 0.4
People x 245 x
Outside Air x 21 x 0.12 * 1.08
Lights x 1 x 1.25 x 3.4 Sample calculation U factor for floor
Computers x 160 x 3.4 Construction Resistance
Equipment x 3400 x
Indoor Air surfae film (Still Air) 0.61
Concrete 6" 1.20
Insied air surface (Still Air) 0.61
Total Resistance 2.42

U = 1 = 1 = 0.4 BTU / (hr)(sq.ft.)(deg F)


R 2.42
HEAT GAIN FROM PEOPLE
Average Room Dry Bulb Temperature
Metabolic
adjusted
Degree of Activity Typical Application Rate (Adult 75 F 70 F
Metabolic rate
Male) Btu/hr
Btu/hr Sensible latent Sensible latent
Seated at rest Theater, Grade school 390 350 230 120 260 90
Seated, very light work High school 450 400 240 160 275 125
Offices, Hostels, Apts.,
Office worker 475
College
450 245 205 285 165
Standing, walking slowly Dept, Retail, or Variety Store 550
Walking, seated Drug store 550
500 255 245 290 210
Standing, walking slowly Bank 550
Sedentary work Restaurant 500 550 280 270 320 230
Light Bench work Factory, light work 800 750 295 455 365 385
Moderate dancing Dance hall 900 850 325 525 400 450
Walking, 3mph Factory, Fairly heavy work 1000 1000 380 620 460 540
Heavy work Bowling Alley ‡ Factory 1500 1450 525 925 605 845

Other Transm ission gains


All glass x 21 x 0.61
Page 15, Glass Parti. x 16 1.13
Table 12 Partition x 16 x 0.4
Ceiling x 16 x 0.4
Exp. Roof x 37 0.12
Floor x 16 x 0.4
People x 245 x
Outside Air x 21 x 0.12 * 1.08
Lights x 1 x 1.25 x 3.4
Computers x 160 x 3.4
Equipment x 3400 x
HEAT GAIN FROM PEOPLE
Average Room Dry Bulb Temperature
Metabolic
adjusted
Degree of Activity Typical Application Rate (Adult 75 F 70 F
Metabolic rate
Male) Btu/hr
Btu/hr Sensible latent Sensible latent
Seated at rest Theater, Grade school 390 350 230 120 260 90
Seated, very light work High school 450 400 240 160 275 125
Offices, Hostels, Apts.,
Office worker 475
College
450 245 205 285 165
Standing, walking slowly Dept, Retail, or Variety Store 550
Walking, seated Drug store 550
500 255 245 290 210
Standing, walking slowly Bank 550
Sedentary work Restaurant 500 550 280 270 320 230
Light Bench work Factory, light work 800 750 295 455 365 385
Moderate dancing Dance hall 900 850 325 525 400 450
Walking, 3mph Factory, Fairly heavy work 1000 1000 380 620 460 540
Heavy work Bowling Alley ‡ Factory 1500 1450 525 925 605 845

Room Latent Heat


People x 205
Outdoor air x 44 0.12 x 0.68

DB WB RH Gr / Lb
Ambient 96 78 116
Design 75 55 72
Difference 21 44
TRAINING ROOM

• Area of the training room = 1250 Sft.


• No. of occupants = 38 nos.+ 1 instructor
• Computers = 39 nos.
• Other equipment load = 1 KW.
for projector etc..
• Design Conditions - 75 deg F and 55 % RH
size 1250
Total Height 13.8
False ceiling height 9.5
Return air plenum height 4.3

Calculation of Glass area


Length Breadth Area
Glass No rth 6 X 5 30
N.East
N.West
So uth
S.East
S.West
East 33 X 9.5 313.5
West

Total glass area = 343.5 sq.ft.


Calculation of Glass area Calculation of Wall area
Length Breadth Area Solar Transm ission w alls and roof
Glass No rth 6 X 5 30 Wall No rth 38 X 9.5 361
N.East N.East
N.West N.West
So uth So uth
S.East S.East
S.West S.West
East 33 X 9.5 313.5 East 33 X 9.5 313.5
West West

Calculation of Net Wall area ( w all area - glass area)


Solar Transm ission w alls and roof
Wall No rth X 331
N.East
N.West
So uth
S.East
S.West
East X o
West
SOLAR HEAT GAIN THROUGH GLASS
Calculation of Glass area
Length Breadth Area
Glass No rth 6 X 5 30
N.East
N.West
So uth
S.East
S.West
East 33 X 9.5 313.5
West
Sun gain /
Sensible Heat Area Solar diff. U Factor BTU / HR
Glass No rth 30 X 16 X 0.54 259
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth X 11 X 0.54
S.East X 11 X 0.54
S.West X 94 X 0.54
East 313.5 X 11 X 0.54 1862
West X 163 X 0.54
SOLAR HEAT GAIN THROUGH WALLS
Calculation of Net Wall area ( w all area - glass area)
Solar Transm ission w alls and roof
Wall No rth X 331
N.East
N.West
So uth
S.East
S.West
East X o
West

Solar Transmission walls and roof


Wall North 331 X 15 X 0.36 1787
N.East X 17 X 0.36
N.West X 17 X 0.36
South X 31 X 0.36
S.East X 23 X 0.36
S.West X 27 X 0.36
East X 17 X 0.36
West X 31 X 0.36
OTHER TRANSMISSION GAIN
Total glass area

Other Transm ission gains


All glass 343.5 x 21 x 0.61 4400
Glass Parti. x 16 1.13
Partition x 16 x 0.4
Ceiling x 16 x 0.4
Exp. Roof 1250 x 37 x 0.12 5550
Floor x 16 x 0.4 add a slide
before this to
People 39 x 245 x 9555 select bypass
Outside Air 585 x 21 x 0.12 * 1.08 1592 factor of a 4
row coil.
Lights 1875 x 1 x 1.25 x 3.4 7969
Computers 39 x 160 x 3.4 21216
Equipment 1 x 3400 x 3400

Room Sensible heat ( R.S.H) = 57591 BTU/hr


Fan + Safety Factor = 5968 BTU/hr
Room Total Sensible Heat (R.T.S.H) = 63559 BTU/hr
Room Sensible heat ( R.S.H) = 57591 BTU/hr

Depends on air quantity and fan static. A assumption may be made initally and verified based
Fan motor heat gain
on actual dehumidified air quantity requirements
Depends on w heather duct is insulated or unisulated, if duct is routed through Non AC space
Duct heat gain or AC space, length of duct run, temperature difference betw een the air w ithin the duct and
the return air plenum temperature.
Duct leak Loss depends on method of duct fabrication - approx 2 to 5%
Safety Factor up to 5% only on fabric load

Fan + Safety Factor = 5968 BTU/hr

Room Total Sensible Heat (R.T.S.H) = 63559 BTU/hr


ROOM LATENT HEAT

Room Latent Heat


People 39 x 205 7995
Outdoor air 585 x 44 x 0.12 x 0.68 2100

Room Latent heat (R.L.H) = 10095 BTU/hr

Safety Factor (5%) = 505 BTU/hr

Room total latent heat (R.T.L.H) = 10600 BTU/hr

Room Total Heat ( R.T.H) = 74159 BTU/hr


OUTSIDE AIR HEAT GAIN
DB WB RH Gr / Lb
Ambient 96 78 116
Design 75 55 72
Difference 21 44

Outside air Heat


Sensible heat 585 x 21 0.88 x 1.08 11676
Latent heat 585 x 44 0.88 x 0.68 15403
Return air heat gain 1751

Grand Total Heat Gain = R.T.H + Out side air Heat


gain.

Grand total Heat = 102988 BTU/hr.


Tons of Refrigeration = G.T.H (BTU/Hr)/12000
= 8.6 TR.
CALCULATION OF AIR QUANTITY
Dehum Rise ( 1 - BF) ( Room temp - ADP )

R.S.H.F 0.86
ADP 55.8
Dehum Rise 16.90
De.Hum cfm 3483
Room C onditions
DB RH WB W EFFEC T IV E S ENS IBL E HEA T FA C T OR A ND A P P A RA T US DEW P OINT
(F) (%) (F) (g r/lb)
ES HF 1.00 0.98 0.94 0.92 0.92 0.90 0.89
20 53.2 25.7
A DP 31.5 30 26 24 24 22 20
ES HF 1.00 0.95 0.90 0.88 0.88 0.86 0.84
25 54.8 32.1
A DP 36.9 34 30 28 28 25 21
ES HF 1.00 0.97 0.90 0.87 0.87 0.85 0.82 0.80 0.79
30 56.5 38.5
A DP 41.4 40 36 34 34 32 28 24 20
ES HF 1.00 0.96 0.87 0.84 0.84 0.80 0.78 0.76 0.75
35 58.1 45.2
A DP 45.5 44 40 38 38 34 31 27 22
ES HF 1.00 0.96 0.84 0.81 0.81 0.79 0.76 0.73 0.71
40 59.6 51.8
A DP 49.1 48 44 42 42 40 37 32 24
ES HF 1.00 0.94 0.81 0.77 0.77 0.75 0.72 0.69 0.67
75 45 61.1 58.2
A DP 52.2 51 47 45 45 43 40 35 21
ES HF 1.00 0.92 0.78 0.74 0.74 0.71 0.69 0.66 0.64
50 62.6 65.0
A DP 55.2 54 50 48 48 46 44 40 34
ES HF 1.00 0.94 0.87 0.78 0.73 0.69 0.65 0.63 0.61
55 64.0 71.5
A DP 57.8 57 56 54 52 50 47 44 39
ES HF 1.00 0.90 0.71 0.66 0.66 0.63 0.61 0.59 0.58
60 65.3 77.9
A DP 60.1 59 55 53 53 51 49 46 43
ES HF 1.00 0.84 0.65 0.61 0.61 0.59 0.57 0.55 0.54
65 66.7 84.8
A DP 62.4 61 57 55 55 53 51 48 44
ES HF 1.00 0.80 0.68 0.61 0.61 0.57 0.54 0.52 0.51
70 68.0 91.2
A DP 64.5 63 61 59 59 57 55 52 49
HEAT LOAD CALCULATION

Architects : Basis Of Design


Client : Date: 20.06.09 Estimate f or : Summer
Address : Bangalore Heat Load no :6 Location: Bangalore
DB WB RH Gr / Lb
Space Used For : Training Room 38 seater Ambient 96 78 116
Location : Second Floor Design 75 55 72
Area : 1250 Dif f erence 21 44
Sun gain /
Sensible Heat Area Solar diff. U Factor BTU / HR
Glass No rth 30 X 16 X 0.54 259
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth X 11 X 0.54
S.East X 11 X 0.54
S.West X 94 X 0.54 R.S.H.F 0.86
East 313.5 X 11 X 0.54 1862 ADP 55.8
West X 163 X 0.56 Dehum Rise 16.90
Solar Transm ission w alls and roof
Wall No rth 331 X 15 X 0.36 1787
N.East X 17 X 0.36
N.West X 17 X 0.36
So uth X 31 X 0.36 De.Hum cf m 3483
S.East X 23 X 0.36
S.West X 27 X 0.36
East X 17 X 0.36
West X 31 X 0.36
Other Transm ission gains
All glass 343.5 x 21 x 0.61 4400

Glass Parti. x 16 1.13


Partition x 16 x 0.4
Ceiling x 16 x 0.4 Check Figures
Exp. Roof 1250 x 37 x 0.12 5550 sf t / person 32.05
Floor x 16 x 0.4 sf t / Ton 146
People 39 x 245 x 9555 cf m / sf t 2.79
Outside Air 585 x 21 x 0.12 * 1.08 1592 cf m / TR 406
Lights 1875 x 1 x 1.25 x 3.4 7969
Computers 39 x 160 x 3.4 21216 Fr.air changes 2.96
Equipment 1 x 3400 x 3400
R.S.H 57591 T. Air changes 17.60
Fan + S.Factor 5968
R.T.S.H. 63559 Notes:
Room Latent Heat 1
People 39 x 205 7995
Outdoor air 585 x 44 x 0.12 x 0.68 2100 2
R.L.H 10095
S.Factor 505 3
R.T.L.H. 10600
R.T.H. 74159 4
Outside air Heat
Sensible heat 585 x 21 0.88 x 1.08 11676
Latent heat 585 x 44 0.88 x 0.68 15403
Return air heat gain 1751
Grand Total Heat gain 102988
Tonnage 8.6
Cfm 3483
OFFICE AREA/ WORK STATIONS

• Area of the work station area = 15800 Sft.


• No. of occupants = 227 people.
• Computers = 227 nos.
• Load per computer = 160 watts.
• Other equipment load = 1.5 KW.
for printer etc..
• Fresh air = 15 cfm/person.
• Lighting Load = 1.5 watt/Sft
• Design Conditions = 75 deg F and 55 % RH
size sft 15800
Total Height ft 13.8
False ceiling height ft 9.5
Return air plenum height ft 4.3

Calculation of Glass area


Length Breadth Area
Glass North X
N.East X
N.West X
South 11.8 X 9.5 112.1
S.East X
S.West X
East 51.4 X 9.5 488.3
West X
Calculation of Glass area Calculation of w all area
Length Breadth Area Wall No rth X 9.5
Glass North X N.East X 9.5
N.East X
N.West X 9.5
N.West X
So uth 15.1 X 9.5 143.45
South 11.8 X 9.5 112.1
S.East X
S.East X 9.5
S.West X S.West X 9.5
East 51.4 X 9.5 488.3 East 57.4 X 9.5 545.3
West X West X 9.5

Calculation of Net Wall area ( wall area - glass area)


Solar Transmission walls and roof
Wall North
N.East
N.West
South X 31.35
S.East
S.West
East X 57.4
West
SOLAR HEAT GAIN THROUGH GLASS
Calculation of Glass area
Length Breadth Area
Glass North X
N.East X
N.West X
South 11.8 X 9.5 112.1
S.East X
S.West X
East 51.4 X 9.5 488.3
West X

Sun gain / Solar


Sensible Heat Area diff. U Factor BTU / HR
Glass North X 16 X 0.54
N.East X 11 X 0.54
N.West X 130 X 0.54
South 112.1 X 11 X 0.54 666
S.East X 11 X 0.54
S.West X 94 X 0.54
East 488.3 X 11 X 0.54 2901
West X 163 X 0.56
SOLAR HEAT GAIN THROUGH WALLS

Solar Transmission walls and roof


Wall North X 15 X 0.36
N.East X 17 X 0.36
N.West X 17 X 0.36
South 31.35 X 31 X 0.36 350
S.East X 23 X 0.36
S.West X 27 X 0.36
East 57 X 17 X 0.36 349
West X 31 X 0.36
OTHER TRANSMISSION GAIN

Other Transm ission gains


All glass 600.4 x 21 x 0.61 7691
Glass Parti. x 16 1.13
Partition 1263.5 x 16 x 0.4 8086
Ceiling 9752 x 16 x 0.4 62413
Exp. Roof 6048 x 37 x 0.12 26853
Floor x 16 x 0.4
People 227 x 245 x 55615
Outside Air 3405 x 21 x 0.12 * 1.08 9267
Lights 23700 x 1 x 1.25 x 3.4 100725
Computers 227 x 160 x 3.4 123488
Equipment 1.5 x 3400 x 5100
Depends on air quantity and fan static. A assumption may be made initally and verified based
Fan motor heat gain
on actual dehumidified air quantity requirements
Depends on w heather duct is insulated or unisulated, if duct is routed through Non AC space
Duct heat gain or AC space, length of duct run, temperature difference betw een the air w ithin the duct and
the return air plenum temperature.
Duct leak Loss depends on method of duct fabrication - approx 2 to 5%
Safety Factor up to 5% only on fabric load

Room Sensible heat ( R.S.H) = 403504 BTU/hr


Fan + Safety Factor = 44009 BTU/hr
Room Total Sensible Heat (R.T.S.H) = 447512 BTU/hr
ROOM LATENT HEAT

Room Latent Heat


People 227 x 205 46535
Outdoor air 3405 x 44 0.12 x 0.68 12225

Room Latent heat (R.L.H) = 58760 BTU/hr

Safety Factor (5%) = 2938 BTU/hr

Room total latent heat (R.T.L.H) = 61698 BTU/hr

Room Total Heat ( R.T.H) = 509210 BTU/hr


OUTSIDE AIR HEAT GAIN
DB WB RH Gr / Lb
Ambient 96 78 116
Design 75 55 72
Difference 21 44

Outside air Heat


Sensible heat 3405 x 21 0.88 x 1.08 67958
Latent heat 3405 x 44 0.88 x 0.68 89652
Return air heat gain 5895

Grand Total Heat Gain = R.T.H + Out side air Heat


gain.

Grand total Heat = 672716 BTU/hr.


Tons of Refrigeration = G.T.H (BTU/Hr)/12000
= 56.1 TR.
CALCULATION OF AIR QUANTITY

Dehum Rise ( 1 - BF) ( Room temp - ADP )

R.S.H.F 0.88
ADP 56.2
Dehum Rise 16.54
De.Hum cfm 25046
Room C onditions
DB RH WB W EFFEC T IV E S ENS IBL E HEA T FA C T OR A ND A P P A RA T US DEW P OINT
(F) (%) (F) (g r/lb)
ES HF 1.00 0.98 0.94 0.92 0.92 0.90 0.89
20 53.2 25.7
A DP 31.5 30 26 24 24 22 20
ES HF 1.00 0.95 0.90 0.88 0.88 0.86 0.84
25 54.8 32.1
A DP 36.9 34 30 28 28 25 21
ES HF 1.00 0.97 0.90 0.87 0.87 0.85 0.82 0.80 0.79
30 56.5 38.5
A DP 41.4 40 36 34 34 32 28 24 20
ES HF 1.00 0.96 0.87 0.84 0.84 0.80 0.78 0.76 0.75
35 58.1 45.2
A DP 45.5 44 40 38 38 34 31 27 22
ES HF 1.00 0.96 0.84 0.81 0.81 0.79 0.76 0.73 0.71
40 59.6 51.8
A DP 49.1 48 44 42 42 40 37 32 24
ES HF 1.00 0.94 0.81 0.77 0.77 0.75 0.72 0.69 0.67
75 45 61.1 58.2
A DP 52.2 51 47 45 45 43 40 35 21
ES HF 1.00 0.92 0.78 0.74 0.74 0.71 0.69 0.66 0.64
50 62.6 65.0
A DP 55.2 54 50 48 48 46 44 40 34
ES HF 1.00 0.94 0.87 0.78 0.73 0.69 0.65 0.63 0.61
55 64.0 71.5
A DP 57.8 57 56 54 52 50 47 44 39
ES HF 1.00 0.90 0.71 0.66 0.66 0.63 0.61 0.59 0.58
60 65.3 77.9
A DP 60.1 59 55 53 53 51 49 46 43
ES HF 1.00 0.84 0.65 0.61 0.61 0.59 0.57 0.55 0.54
65 66.7 84.8
A DP 62.4 61 57 55 55 53 51 48 44
ES HF 1.00 0.80 0.68 0.61 0.61 0.57 0.54 0.52 0.51
70 68.0 91.2
A DP 64.5 63 61 59 59 57 55 52 49
HEAT LOAD CALCULATION

Architects : Basis Of Design


Client : Date: 20.06.09 Estimate f or : Summer
Address : Bangalore Heat Load no :9 Location: Bangalore
DB WB RH Gr / Lb
Space Used For : Workstation Ambient 96 78 116
Location : Second Floor Design 75 55 72
Area : Sun 15800
gain / Dif f erence 21 44
Sensible Heat Area Solar diff. U Factor BTU / HR
Glass No rth X 16 X 0.54
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth 112.1 X 11 X 0.54 666
S.East X 11 X 0.54
S.West X 94 X 0.54 R.S.H.F 0.88
East 488.3 X 11 X 0.54 2901 ADP 56.2
West X 163 X 0.56 Dehum Rise 16.54
Solar Transm ission w alls and roof
Wall No rth X 15 X 0.36
N.East X 17 X 0.36
N.West X 17 X 0.36
So uth 31.35 X 31 X 0.36 350 De.Hum cf m 25046
S.East X 23 X 0.36
S.West X 27 X 0.36
East 57 X 17 X 0.36 349
West X 31 X 0.36
Other Transm ission gains
All glass 600.4 x 21 x 0.61 7691

Glass Parti. x 16 1.13


Partition 1263.5 x 16 x 0.4 8086
Ceiling 9752 x 16 x 0.4 62413 Check Figures
Exp. Roof 6048 x 37 x 0.12 26853 sf t / person 69.60
Floor x 16 x 0.4 sf t / Ton 282
People 227 x 245 x 55615 cf m / sf t 1.59
Outside Air 3405 x 21 x 0.12 * 1.08 9267 cf m / TR 447
Lights 23700 x 1 x 1.25 x 3.4 100725
Computers 227 x 160 x 3.4 123488 Fr. Air changes 1.36
Equipment 1.5 x 3400 x 5100
R.S.H 403504 T. Air changes 10.01
Fan + S.Factor 44009
R.T.S.H. 447512 Notes:
Room Latent Heat 1
People 227 x 205 46535
Outdoor air 3405 x 44 0.12 x 0.68 12225 2
R.L.H 58760
S.Factor 2938 3
R.T.L.H. 61698
R.T.H. 509210 4
Outside air Heat
Sensible heat 3405 x 21 0.88 x 1.08 67958
Latent heat 3405 x 44 0.88 x 0.68 89652
Return air heat gain 5895
Grand Total Heat gain 672716
Tonnage 56.1
Cf m 25046
DATA CENTER

• Area of the Data Center = 1650 Sft.

• No. of occupants = 2 people.

• Fresh air = 15 cfm/person.

• Lighting Load = 1.5 watt/Sft

• Design Conditions = 70 deg F and 50% RH

• Equipment load ( Server load ) in KVA = 124

Equipment load ( Server load ) in KW = 124 x Power factor

In case of servers, the power factor is almost equal to 1 as this is not an


inductive load.

So the load in the data center will be 124 KW.


HEAT LOAD CALCULATION

Architects : Basis Of Design


Client : Date: 20.06.09 Estimate f or : Summer
Address : Bangalore Heat Load no :10 Location: Bangalore
DB WB RH Gr / Lb
Space Used For : Data Center Ambient 96 78 116
Location : Second Floor Design 70 50 55
Area : 1650 /
Sun gain Dif f erence 26 61
Sensible Heat Area Solar diff. U Factor BTU / HR
Glass No rth X 16 X 0.54
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth X 11 X 0.54
S.East X 11 X 0.54
S.West X 94 X 0.54 R.S.H.F 1.00
East X 11 X 0.54 ADP 57.8
West X 163 X 0.56 Dehum Rise 10.74
Solar Transm ission w alls and roof
Wall No rth X 20 X 0.36
N.East X 22 X 0.36
N.West X 22 X 0.36
So uth X 36 X 0.36 De.Hum cf m 44186
S.East X 28 X 0.36
S.West X 42 X 0.36
East X 22 X 0.36
West X 36 X 0.36
Other Transm ission gains
All glass x 26 x 0.61
Glass Parti. x 21 1.13
Partition 1729 x 21 x 0.4 14524
Ceiling 1650 x 21 x 0.4 13860 Check Figures
Exp. Roof x 37 x 0.12 sf t / person 825.00
Floor 1650 x 21 x 0.4 13860 sf t / Ton 38
People 2 x 245 x 490 cf m / sf t 26.78
Outside Air 30 x 26 x 0.12 * 1.08 101 cf m / TR 1017
Lights 2475 x 1 x 1.25 x 3.4 10519
Computers x 160 x 3.4 Fr.air changes 0.11
Equipment 123.75 x 3400 x 420750
R.S.H 474103 T. Air changes 169.13
Fan + S.Factor 38225
R.T.S.H. 512329 Notes:
Room Latent Heat 1 200 Kva x 2nos.
People 2 x 205 410
Outdoor air 30 x 61 x 0.12 x 0.68 149 2
R.L.H 559
S.Factor 28 3
R.T.L.H. 587
R.T.H. 512916 4
Outside air Heat
Sensible heat 30 x 26 0.88 x 1.08 741
Latent heat 30 x 61 0.88 x 0.68 1095
Return air heat gain 6574
Grand Total Heat gain 521326
Tonnage 43.4
Cf m 44186
UPS ROOM

• Area of the UPS Room = 260 Sft.


• Lighting Load = 1.5 watt/Sft
• Design Conditions = 75 deg F and 55 % RH
• UPS Configuration = 90 Kva X 2 nos.
Total UPS load in KVA = 180 Kva.
Total UPS load in KW = 180 Kva. X Power factor
As the UPS power is an inductive power, the power factor
will be 0.8.
Total UPS load in KW = 144
Heat Dissipation = 14.4 KW
( 10% of the UPS load )
HEAT LOAD CALCULATION

Archite cts : Basis Of Design


Clie nt : Date: 20.06.09 Estimate f or : Summer
Addre s s : Bangalore Heat Load no :14 Location: Bangalore
DB WB RH Gr / Lb
Space Used For : UPS Room Ambient 96 78 116
Location : Se cond Floor Design 75 55 72
Area : 263 /
Sun gain Dif f erence 21 44
Se ns ible He at Are a Solar diff. U Factor BTU / HR
Glass No rth X 16 X 0.54
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth X 11 X 0.54
S.East X 11 X 0.54
S.West X 94 X 0.54 R.S.H.F 1.00
East X 11 X 0.54 ADP 57.8
West 30 X 163 X 0.56 2738 Dehum Rise 15.14
Solar Trans m is s ion w alls and roof
Wall No rth X 15 X 0.36
N.East X 17 X 0.36
N.West X 17 X 0.36
So uth X 31 X 0.36 De.Hum cf m 4213
S.East X 23 X 0.36
S.West X 27 X 0.36
East X 17 X 0.36
West 117.25 X 31 X 0.36 1309
Othe r Trans m is s ion gains
All glass 30 x 21 x 0.61 384
Glass Parti. x 16 1.13
Partition 470.25 x 16 x 0.4 3010
Ceiling 263 x 16 x 0.4 1683 Che ck Figure s
Exp. Roof x 37 x 0.12 sf t / person #DIV/0!
Floor 263 x 16 x 0.4 1683 sf t / Ton 44
People x 245 x cf m / sf t 16.02
Outside Air x 21 x 0.12 * 1.08 cf m / TR 712
Lights 394.5 x 1 x 1.25 x 3.4 1677
Computers x 160 x 3.4 Fr.air changes
Equipment 15 x 3400 x 51000
R.S.H 63484 T. Air changes 101.17
Fan + S.Factor 5385
R.T.S.H. 68869 Note s :
Room Late nt He at 1 200 Kva x 2nos.
People x 205
Outdoor air x 44 x 0.12 x 0.68 2
R.L.H
S.Factor 3
R.T.L.H.
R.T.H. 68869 4
Outs ide air He at
Sensible heat x 21 0.88 x 1.08
Latent heat x 44 0.88 x 0.68
Return air heat gain 2106
Grand Total He at gain 70975
Tonnage 5.9
Cf m 4213
LAB

• Area of the Lab = 1150 Sft.


• No. of occupants = 35 people.
• Equipment load = 30 KW
• Fresh air = 15 cfm/person.
• Lighting Load = 1.5 watt/Sft
• Design Conditions = 75 deg F and 55 % RH
HEAT LOAD CALCULATION

Archite cts : Basis Of Design


Clie nt : Date: 20.06.09 Estimate f or : Summer
Addre s s : Bangalore Heat Load no :7 Location: Bangalore
DB WB RH
Space Used For : Lab Ambient 96 78
Location : Se cond Floor Design 75 55
Area : 1158 /
Sun gain Dif f erence 21
Se ns ible He at Are a Solar diff. U Factor BTU / HR
Glass No rth X 16 X 0.54
N.East X 11 X 0.54
N.West X 130 X 0.54
So uth X 11 X 0.54
S.East X 11 X 0.54
S.West X 94 X 0.54 R.S.H.F 0.94
East 418 X 11 X 0.54 2483 ADP 57
West X 163 X 0.56 Dehum Rise 15.84
Solar Trans m is s ion w alls and roof
Wall No rth X 15 X 0.36
N.East X 17 X 0.36
N.West X 17 X 0.36
So uth X 31 X 0.36 De.Hum cf m 8426
S.East X 23 X 0.36
S.West X 27 X 0.36
East 49.4 X 17 X 0.36 302
West X 31 X 0.36
Othe r Trans m is s ion gains
All glass 418 x 21 x 0.61 5355

Glass Parti. x 16 1.13


Partition x 16 x 0.4
Ceiling x 16 x 0.4 Che ck Figure s
Exp. Roof 1158 x 37 0.12 5142 sf t / person 33.09
Floor x 16 x 0.4 sf t / Ton 78
People 35 x 245 x 8575 cf m / sf t 7.28
Outside Air 525 x 21 x 0.12 * 1.08 1429 cf m / TR 564
Lights 1737 x 1 x 1.25 x 3.4 7382
Computers x 160 x 3.4 Fr. Air changes
Equipment 30 x 3400 x 102000
R.S.H 132667 T. Air changes
Fan + S.Factor 11483
R.T.S.H. 144151 Note s :
Room Late nt He at 1
People 35 x 205 7175
Outdoor air 525 x 44 0.12 x 0.68 1885 2
R.L.H 9060
S.Factor 453 3
R.T.L.H. 9513
R.T.H. 153664 4
Outs ide air He at
Sensible heat 525 x 21 0.88 x 1.08 10478
Latent heat 525 x 44 0.88 x 0.68 13823
Return air heat gain 1295
Grand Total He at gain 179260
Tonnage 14.9
Cfm 8426
BASIS OF DESIGN

Floors 1 2 3 4 5 6 7 8 9 10 11 12 13
Meeting Training Meeting
Board Break out Workstatio Data
Basis of Design Reception Cabin Cabin Room 10 Room 38 Lab Cabins Room 8 Cabin
Room area n Center
seater seater seater
Second Second Second Second Second Second Second Second Second Second Second Second Second
Floors Floor Floor Floor Floor Floor Floor Floor Floor Floor Floor Floor Floor Floor
Air conditioned area - 1512 132 132 200 1145 1250 1158 514 15800 1650 808 177 128
Sft
Height - ft 10 10 10 10 10 10 10 10 10 10 10 10 10

Ambient Conditions
Dry Bulb 96 96 96 96 96 96 96 96 96 96 96 96 96
Wet Bulb 78 78 78 78 78 78 78 78 78 78 78 78 78

Inside conditions
Temperature - Deg F 75 75 75 75 75 75 75 75 75 70 75 75 75
Humidity - % RH 55 55 55 55 55 55 55 55 55 50 55 55 55

Internal Loads
No. of occupants 10 3 3 10 31 39 35 28 227 2 18 8 3
fresh air quantity in 150 45 45 150 465 585 525 420 3405 30 270 120 45
CFM
Lights- watts 2268 198 198 300 1718 1875 1737 771 23700 2475 1212 266 192
No. of computers 1 1 1 4 15 2 227 6 3 1
sensible load in KW 2 1 30 1 2 124
TR 4.6 0.7 0.6 1.7 6.2 6.8 14.9 4.3 56.1 43.4 4.2 1.5 0.8
De-humidified Cfm 2451 252 216 505 2289 2184 8426 1155 25046 44186 1847 510 309
SUMMARY
Area
S.No Description TR cfm S.H.F A.D.P cfm/TR cfm/sft sft/TR
(sft)

1 Reception 1512 4.6 2451 0.94 57 530 1.6 327

2 Cabin 132 0.7 252 0.85 55.6 387 1.9 203

3 Cabin 132 0.6 216 0.83 55 357 1.6 218

4 Meeting Room 10 seater 200 1.7 505 0.79 54.2 302 2.5 120

5 Board Room 1145 5.7 1998 0.82 55.2 351 1.7 201

6 Training Room 38 seater 1250 8.6 3483 0.86 55.8 406 2.8 146

7 Lab 1158 14.9 8426 0.94 57 564 7.3 78

8 Break out area 514 4.3 1155 0.76 53.6 269 2.2 120

9 Workstation 15800 56.1 25046 0.88 56.2 447 1.6 282

10 Data Center 1650 43.4 44186 1.00 57.8 1017 26.8 38

11 Cabins 808 4.2 1847 0.87 56 437 2.3 191

12 Meeting Room 8 seater 177 1.5 510 0.82 55 337 2.9 117

13 Cabin 128 0.8 309 0.87 56 411 2.4 170

14 UPS Room 263 5.9 4213 1.00 57.8 712 16.0 44

Total 24869 153 94596


EQUIPMENT CONFIGURATION FOR DX SYSTEM

Nos of
S.No Description Area TR cfm Type of Unit Capacity of unit
unit

1 Reception 1512 4.6 2451

2 Cabin 132 0.7 252


Ductable split units 8.75 TR, 3500 cfm 1 no.
3 Cabin 132 0.6 216

4 Meeting Room 10 seater 200 1.7 505

5 Board Room 1145 5.7 1998 Ductable split units 5.5 TR, 2200 cfm 1 no.

6 Training Room 38 seater 1250 8.6 3483 Ductable split units 8.75 TR, 3500 cfm 1 no.

7 Lab 1158 14.9 8426


Floor mounted
8 Break out area 514 4.3 1155 17 TR, 6800 cfm 5 Nos.
Packaged unit
9 Workstation 15800 56.1 25046

Floor mounted, Bottom


discharge type 5 Nos. (4
10 Data Center 1650 43.4 44186 18 TR, 10800 cfm
precision air W+1 S)
conditioning units.

2 TR (2 TR ODU, 1 TR
Multi split Hiwall units
11 Cabins 808 4.2 1847 x 2 nos IDU) 3 nos.

12 Meeting Room 8 seater 177 1.5 510 Hiwall unit 1.5 TR , 520 cfm 1 no.

13 Cabin 128 0.8 309 Hiwall unit 1 TR, 420 cfm 1 no.

Floor mounted Plenum


discharge Hisensible 2 nos.
14 UPS Room 263 5.9 4213 unit 8.3 TR,4500 cfm (1W+1S)