planning and safety of building LESSON OBJECTIVES UPON COMPLETION OF THE LESSON YOU WILL BE ABLE TO UNDERSTAND AND DESCRIBE THE FOLLOWING DEFINITION OF BUILDING CLASSIFICATION OF BUILDING FIRE PROTECTION IN BUILDING WHAT IS BUILDING ANY STRUCTURE FOR WHATSOEVER PURPOSE AND OF WHATSOEVER MATERIALS CONSTRUCTED AND EVERYPART THEREOF WHETHER USED AS HUMAN HAVITATION OR NOT AND INCLUDES FOUNDATION, PLINTH,WALLS,FLOORS,ROOFS,VERA NDAH,BALCONY ETC. IS CALLED BUILDING. CLASSIFICATION OF BUILDING
CLASSIFIED INTO NINE GROUPS
RESIDENTIAL (GR—A) EDUCATIONAL (GR—B) INSTITUTIONAL (GR—C) ASSEMBLY (GR—D) BUSINESS (GR—E) MERCANTILE (GR—F) INDUSTRIAL (GR—G) STORAGE (GR—H) HAZARDOUS (GR—J) FIRE ZONES THE CITY OR AREA UNDER THE JURISDICTION OF THE AUTHORITY SHALL FOR THE PURPOSE OF THE CODE BE DEMARCATED INTO DISTINCT ZONES BASED ON FIRE HAZARD INHERENT IN THE BUILDINGS OR STRUCTURES ACCORDING TO OCCUPANCY WHICH SHALL BE CALLED AS FIRE ZONES. FIRE PROTECTION SYSTEM FIRE EXTINGUISHER/FIXED FIRE FIGHTING INSTALLATIONS PROVIDED
ALL INDUSTRIAL BUILDINGS SHALL BE
PROTECTED BY
FIRE EXTINGUISHER,WET RISER,DOWN
COMER,AUTOMATIC SPRINKLER SYSTEM,
HIGH/MEDIUM VELOCITY WATER SPRAY
PROJECTOR SYSTEM,FOAM
DRY POWDER SYSTEM.
IN CASE ONE BUILDING IS PROVIDED WITH ALL FIRE PROTECTED ARRANGEMENTS AND IT IS SITUATED BESIDE SOME UNPROTECTED BUILDINGS FIRE RESISTANT WALL OR WATER CURTAIN/DRENCHER SYSTEM SHOULD BE ARRANGED ON THE WALL FACING THE UNPROTECTED BUILDINGS INSTALLATION OF HOSE REEL HOSE
FIRST AID HOSE REEL HOSE SHALL BE
INSTALLED ON ALL THE FLOORS
BUILDINGS OF 15 MTRS IN HEIGHT OR
MORE
DIAMETER OF THE HOSE REEL HOSE
SHALL NOT BE LESS THAN 19 mm. STATIC WATER STORAGE TANK A SATISFACTORY SUPPLY OF WATER FOR FIRE FIGHTING
SHALL ALWAYS BE AVAILABLE IN THE FORM
OF TANKS OR
ALTERNATIVE SOURCE OF SUPPLY OF 1000
Ltrs/Min.
FOR UNDERGROUND TANKS AND EASILY
ACCESSIBLE TO THE FIRE ENGINE CONTD… THE STATIC TANK SHALL BE PROVIDED WITH A FIRE BRIGADE CONNECTING HEAD WITH 04 NOS OF 63 mm DIA INSTANTANEOUS ,MALE INLETS AND PIPE FIXED TO THE TANK SHALL NOT BE LESS 150 mm DIA TO THE DISCHARGE WATER @ 2250 Ltrs/Min. AUTOMATIC SPRINKLER THIS SYSTEM SHALL BE INSTALLED IN CAR PARK,STORAGE AREA EXCEEDS 200 Sq. Mtrs AREA. SUB-STATIONAC PLANT AND DG SET ANY ROOM OR COMPARTMENT OF BUILDING EXCEEDS 1125 Sq.Mtrs AREA. SHOPS /DEPT.STORE AREA EXCEEDS 500 Sq.Mtrs. GODOWNS/WAREHOUSES IF CONSIDERED NECESSARY. MULSIFIRE SYSTEM
AUTOMATIC HIGH VELOCITY WATER SPRAY PROJECTION OR MULSIFIRE SYSREM SHALL BE PROVIDED FOR INDOOR OIL COOLED TRANSFORMERS. FIXED FOAM INSTALLATION
IT SHALL BE PROVIDED FOR THE
PROTECTION OF OIL STORAGE AREA.
HIGH EXPANSION FOAM ARE USED
FOR CABLE TUNNELS AND OHER CONFINED AREAS. CARBON DI-OXIDE
CARBON DI OXIDE FIRE
EXTINIGUISHING SYSTEM SHALL ALSO BE PROVIDED. (CONTD….) NOT LESS THAN 02 EXITS SHALL BE PROVIDED FOR EVERY FLOOR. IN ANY ROOM IN WHICH VOLATILE, FLAMMABLE SUBSTANCES ARE USED OR STORED, NO DEVICE GENERATING A GLOW OR FLAME SALL BE INSTALLED. EVERY BOILER ROOM SHALL BE ADEQUATELY SEPARATED FROM THE REST OF THE BUILDING. TRAVEL DISTANCE SHALL NOT BE MORE THAN 22.5 MTRS. ALL HIGH HAZARD INDUSTRIAL BUILDINGS SHALL HAVE AUTOMATIC SPRINKLER SYSTEM. VENTING THERE ARE TWO CATEGORIES OF VENTING 1) SMOKE AND FIRE VENTING 2) EXPLOSION RELIEF VENTING SPEEDY REMOVAL OF SMOKE AND HOT GASES. OPERATE AUTOMATICALLY AT EARLY STAGE AND AS LOW AS 150 DEGREE CENTIGRADE. AUTOMATIC VENTING SHALL BE PROVIDED FOR MEDIUM HAZARD BUILDING HAVING FLOOR AREA EXCEEDING 750 SQUARE METER. SPACING BETWEEN VENTS---- LOW HEAT RELEASE ---- 45 MTRS. MODERATE HEAT RELEASE---- 36 TO 37 MTRS. HIGH HEAT RELEASE ----- 22.5 TO 30 MTRS CLARIFICATION