Protection Fundamentals
By
John Levine
2
GE Consumer & Industrial
Multilin
Outline
• Introductions
• Tools
– Enervista Launchpad
– On – Line Store
– Demo Relays at Levine
• ANSI number
• Training CD’s
• Protection Fundamentals
3
GE Consumer & Industrial
Multilin
Objective
• We are here to help make your job easier.
This is very informal and designed around
Applications. Please ask question. We
are not here to “preach” to you.
• The knowledge base in the room varies
greatly. If you have a question, there is a
good chance there are 3 or 4 other people
that have the same question. Please ask
it.
4
GE Consumer & Industrial
Multilin
Tools
5
GE Consumer & Industrial
Multilin
6
GE Consumer & Industrial
Multilin
Demo Relays at L-3
7
GE Consumer & Industrial
Multilin
Relays at L-3
8
GE Consumer & Industrial
Multilin
9
GE Consumer & Industrial
Multilin
GE Multilin Training CD’s
10
GE Consumer & Industrial
Multilin
ANSI Symbols
11
GE Consumer & Industrial
Multilin
Conversion of Electro-Mechanical
to Electronic sheet
12
GE Consumer & Industrial
Multilin
PowerPoint presentations at:
http://l-3.com/private/ieee/
13
GE Consumer & Industrial
Multilin
Protection Fundamentals
14
GE Consumer & Industrial
Multilin
Desirable Protection Attributes
• Reliability: System operate properly
– Security: Don’t trip when you shouldn’t
– Dependability: Trip when you should
• Selectivity: Trip the minimal amount to clear the fault or
abnormal operating condition
• Speed: Usually the faster the better in terms of
minimizing equipment damage and maintaining system
integrity
• Simplicity: KISS
• Economics: Don’t break the bank
15
GE Consumer & Industrial
Multilin
Art & Science of Protection
Selection of protective relays requires compromises:
• Maximum and Reliable protection at minimum equipment
cost
• High Sensitivity to faults and insensitivity to maximum load
currents
• High-speed fault clearance with correct selectivity
• Selectivity in isolating small faulty area
• Ability to operate correctly under all predictable power
system conditions
16
GE Consumer & Industrial
Multilin
Art & Science of Protection
• Cost of protective relays should be balanced against
risks involved if protection is not sufficient and not
enough redundancy.
• Primary objectives is to have faulted zone’s primary
protection operate first, but if there are protective
relays failures, some form of backup protection is
provided.
• Backup protection is local (if local primary
protection fails to clear fault) and remote (if remote
protection fails to operate to clear fault)
17
GE Consumer & Industrial
Multilin
Primary
Primary Equipment
Equipment &
& Components
Components
• Transformers - to step up or step down voltage level
20
GE Consumer & Industrial
Multilin
Instantaneous Overcurrent Protection (IOC) &
Definite Time Overcurrent
CTI
• Relay closest to fault operates
first
• Relays closer to source
t operate slower
• Time between operating for
same current is called CTI
(Clearing Time Interval)
CTI
50 50
+2 +2
Distribution
Substation
21
GE Consumer & Industrial
Multilin
(TOC) Coordination
• Relay closest to fault operates
first
• Relays closer to source
t operate slower
• Time between operating for
same current is called CTI
CTI
Distribution
Substation
22
GE Consumer & Industrial
Multilin
Time Overcurrent Protection (TOC)
• Selection of the curves uses
what is termed as a “ time
multiplier” or “time dial”
to effectively shift the curve
up or down on the time axis
• Operate region lies above
selected curve, while no-
operate region lies below it
• Inverse curves can
approximate fuse curve
shapes
23
GE Consumer & Industrial
Multilin
Time Overcurrent Protection
(51, 51N, 51G)
Multiples of pick-up
24
GE Consumer & Industrial
Multilin
Types of Protection
Differential
– current in = current out
– Simple
– Very fast
– Very defined clearing area
– Expensive
– Practical distance limitations
• Line differential systems overcome this using
digital communications
26
GE Consumer & Industrial
Multilin
1 pu
IP
CT-X CT-Y IP
Differential
IS IS
• Note CT polarity
Relay dots
IR-X IR-Y
• This is a
through-current
+1
1 + (-1) = 0 representation
• Perfect
Current, pu
waveforms, no
-1 saturation
DIFF CURRENT
27
GE Consumer & Industrial
Multilin
Differential
2 pu 2 pu
IP
Fault
CT-X CT-Y IP
X
IS IS
• Note CT
IR-X
Relay
IR-Y polarity dots
• This is an
+2
internal fault
2 + (+2) = 4
representation
Current, pu
0
• Perfect
-2 waveforms, no
DIFF CURRENT
saturation
28
GE Consumer & Industrial
Multilin
Types of Protection
Voltage
• Uses voltage to infer fault or abnormal condition
• May employ definite time or inverse time curves
• May also be used for undervoltage load shedding
– Simple
– May be slow
– Selectivity at the cost of speed (coordination stacks)
– Inexpensive
29
GE Consumer & Industrial
Multilin
Types of Protection
Frequency
• Uses frequency of voltage to detect power
balance condition
• May employ definite time or inverse time
curves
• Used for load shedding & machinery
under/overspeed protection
– Simple
– May be slow
– Selectivity at the cost of speed can be expensive
30
GE Consumer & Industrial
Multilin
Types of Protection
Power
• Uses voltage and current to determine
power flow magnitude and direction
• Typically definite time
– Complex
– May be slow
– Accuracy important for many applications
– Can be expensive
31
GE Consumer & Industrial
Multilin
Types of Protection
Distance (Impedance)
– Uses voltage and current to determine impedance of fault
– Set on impedance [R-X] plane
– Uses definite time
– Impedance related to distance from relay
– Complicated
– Fast
– Somewhat defined clearing area with reasonable
accuracy
– Expensive
– Communication aided schemes make more selective
32
GE Consumer & Industrial
Multilin
X ZL
Impedance
• Relay in Zone 1 operates first
• Time between Zones is called
CTI
R
T2 ZB
ZA
T1
21 21
A B
Source
33
GE Consumer & Industrial
Multilin
Typical
Generation-typically at 4-20kV
Bulk
Power
Transmission-typically at 230-765kV System
Receives power from transmission system and
transforms into subtransmission level
Subtransmission-typically at 69-161kV
~
Generator XFMR Bus Line Bus XFMR Bus Motor
37
GE Consumer & Industrial
Multilin
Zone
Zone Overlap
Overlap
1. Overlap is accomplished by the locations of CTs, the key source for protective
relays.
2. In some cases a fault might involve a CT or a circuit breaker itself, which means
it can not be cleared until adjacent breakers (local or remote) are opened.
CTs are located at both sides of CB-fault CTs are located at one side of CB-fault
between CTs is cleared from both remote sides between CTs is sensed by both relays, remote
right side operate only.
38
GE Consumer & Industrial
Multilin
What
What Info
Info is
is Required
Required to
to Apply
Apply Protection
Protection
1. One-line diagram of the system or area involved
2. Impedances and connections of power equipment, system frequency,
voltage level and phase sequence
3. Existing schemes
4. Operating procedures and practices affecting protection
5. Importance of protection required and maximum allowed clearance
times
6. System fault studies
7. Maximum load and system swing limits
8. CTs and VTs locations, connections and ratios
9. Future expansion expectance
10. Any special considerations for application.
43
GE Consumer & Industrial
Multilin
C37.2:
Device
Numbers
• Partial listing
44
GE Consumer & Industrial
Multilin
One Line Diagram
• Non-dimensioned diagram showing how
pieces of electrical equipment are
connected
• Simplification of actual system
• Equipment is shown as boxes, circles and
other simple graphic symbols
• Symbols should follow ANSI or IEC
conventions
45
GE Consumer & Industrial
Multilin
1-Line Symbols [1]
46
GE Consumer & Industrial
Multilin
1-Line Symbols [2]
47
GE Consumer & Industrial
Multilin
1-Line Symbols [3]
48
GE Consumer & Industrial
Multilin
1-Line Symbols [4]
49
GE Consumer & Industrial
Multilin
1-Line [1]
50
GE Consumer & Industrial
Multilin
1-Line [2]
3-Line
52
GE Consumer & Industrial
Multilin
CB Trip Circuit (Simplified)
55
GE Consumer & Industrial
Multilin
Lock Out Relay
PR
86b
86
86a
TC
86b
58
GE Consumer & Industrial
Multilin
CB Coil Circuit Monitoring:
T with CB Closed; C with CB Opened
+
Relay
52/a
or
52/b
Breaker
T/C
Coil
52/a for trip circuit
52/b for close circuit
-
59
GE Consumer & Industrial
Multilin
CB Coil Circuit Monitoring:
Both T&C Regardless of CB state
Relay Relay
Breaker Breaker
60
GE Consumer & Industrial
Multilin
Current Transformers
• Current transformers are used to step primary system currents to
values usable by relays, meters, SCADA, transducers, etc.
• CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5,
300:5
• A 2000:5 CT has a “CTR” of 400
61
GE Consumer & Industrial
Multilin
Standard IEEE CT Relay
Accuracy
• IEEE relay class is defined in terms of the voltage a CT
can deliver at 20 times the nominal current rating
without exceeding a 10% composite ratio error.
100 V = 20 * 5 * (1ohm)
200 V = 20 * 5 * (2 ohms)
400 V = 20 * 5 * (4 ohms)
800 V = 20 * 5 * (8 ohms)
62
GE Consumer & Industrial
Multilin
Standard IEEE CT Burdens (5 Amp)
(Per IEEE Std. C57.13-1993)
Application Burden Impedance VA @ Power
Designation (Ohms) 5 amps Factor
Relaying B1 1 25 0.5
B2 2 50 0.5
B4 4 100 0.5
B8 8 200 0.5
64
GE Consumer & Industrial
Multilin
Voltage Transformers
• Voltage (potential) transformers are used to isolate and step down and
accurately reproduce the scaled voltage for the protective device or
relay
• VT ratios are typically expressed as primary to secondary; 14400:120,
7200:120
• A 4160:120 VT has a “VTR” of 34.66
VP
VS
Relay
66
GE Consumer & Industrial
Multilin
Typical CT/VT Circuits
Secondary Circuit
69
GE Consumer & Industrial
Multilin
System Grounding
– Limits overvoltages
– Limits difference in electric potential through local
area conducting objects
– Several methods
• Ungrounded
• Reactance Coil Grounded
• High Z Grounded
• Low Z Grounded
• Solidly Grounded
70
GE Consumer & Industrial
Multilin
System Grounding
1. Ungrounded: There is no intentional
ground applied to the system-however
it’s grounded through natural
capacitance. Found in 2.4-15kV
systems.
72
GE Consumer & Industrial
Multilin
System Grounding
73
GE Consumer & Industrial
Multilin
Basic Current Connections:
How System is Grounded
Determines How Ground Fault is Detected
Medium/High Low/No
Resistance Ground Resistance Ground 79
GE Consumer & Industrial
Multilin
Substation Types
• Single Supply
• Multiple Supply
80
GE Consumer & Industrial
Multilin
Industrial Substation Arrangements
(Typical)
81
GE Consumer & Industrial
Multilin
Industrial Substation Arrangements
(Typical)
82
GE Consumer & Industrial
Multilin
Utility Substation Arrangements
(Typical)
Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual 2-sections Bus with HS Tie-Breaker,
Supply 2 Tx, Dual Supply
83
GE Consumer & Industrial
Multilin
Utility Substation Arrangements
(Typical)
Bus
1
Bus 2
Main bus
Aux. bus
Main
Reserve
Transfer
Bus 1
breaker
Tie
Bus 2
96
GE Consumer & Industrial
Multilin
Contribution to Faults
97
GE Consumer & Industrial
Multilin
Fault Types (Shunt)
98
GE Consumer & Industrial
Multilin
AC & DC Current Components
of Fault Current
102
GE Consumer & Industrial
Multilin
Useful Conversions
105
GE Consumer & Industrial
Multilin
Per Unit System
Establish two base quantities:
106
GE Consumer & Industrial
Multilin
Per Unit Basics
107
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System
Vpu = Vactual
Vbase
Ipu = Iactual
Ibase
Zpu = Zactual
Zbase 108
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System
MVAbase x 1000
I base =
3 x kV L-L base
kV2L-L base
Z base = MVA
base
109
GE Consumer & Industrial
Multilin
Short Circuit Calculations
Per Unit System – Base Conversion
Zpu2 =Zpu1 x kV 2
base1 x MVAbase2
kV 2base2 MVAbase1
110
GE Consumer & Industrial
Multilin
A Study of a Fault…….
123
GE Consumer & Industrial
Multilin
Arc Flash Hazard
125
GE Consumer & Industrial
Multilin
Protective Relaying Methods
of Reducing Arc Flash Hazard
– Bus differential protection (this – FlexCurve for improved
reduces the arc flash energy by coordination opportunities
reducing the clearing time – Employ 51VC/VR on feeders
– Zone interlock schemes where fed from small generation to
bus relay selectively is allowed improve sensitivity and
to trip or block depending on coordination
location of faults as identified – Employ UV light detectors with
from feeder relays current disturbance detectors
– Temporary setting changes to for selective gear tripping
reduce clearing time during
maintenance
• Sacrifices coordination
129
GE Consumer & Industrial
Multilin
Arc Flash Hazards
131
GE Consumer & Industrial
Multilin
Arc Pressure Wave
132
GE Consumer & Industrial
Multilin
Copy of this presentation are at:
www.L-3.com\private\IEEE
136
GE Consumer & Industrial
Multilin
Protection Fundamentals