Lutz Graumann
Version 21.10.2015_1200 Eaton Safety Management GB
November 2016
• Lutz Graumann
• Eaton Industries Germany
• Business Development Manager EMEA
• Safety Specialist – personal and assembly protection @LV switchgear
assemblies
• Consulting IEC 61439, TR61641
• 25 years engineer with „passion“ and expertise in LV switchgear
assemblies upto 6300A, busways, electronic arc flash protection, long term
stays in US, Poland, Lower Gulf
2
© 2015 Eaton Corporation. All rights reserved. 2
Safety Above Standard
Content
3
© 2015 Eaton Corporation. All rights reserved. 3
Safety Above Standard
Why do we meet today?
4
© 2015 Eaton Corporation. All rights reserved. 4
Safety Above Standard
Safety Management
7
© 2015 Eaton Corporation. All rights reserved. 7
Safety Above Standard
Incident from the media
10
© 2015 Eaton Corporation. All rights reserved. 10
Safety Above Standard
Faults in a LV switchgear assembly are not 100% predictable or can be
completely eliminated
11
© 2015 Eaton Corporation. All rights reserved. 11
Safety Above Standard
Influences on the safety and operation of switchboard
• …
Safety for
personnal,
systems and
process
• Selection …
• Selection …
Section: feeder/motor starter
• Motor starter / feeder in fully withdrawable technology
• Form 2-4
• Typical for motor starters up to 250kW and feeder up
to 630A
• Ideal for rapid exchange
Design verification :
• all documents as package
per field or project
• Latest documents
• Un up to 690V 50Hz
• InA up to 6300A - rear/top busbar design
• Fixed installation, plug-in, fully withdrawable
technology
• IP 30/31/42/55
• Form 1 - 4
• Design verification according to IEC 61439
"tested“
• Network licensed and trained Panel Builder
Everything from one source - Eaton enclosure system and Eaton devices as a LV
switchgear assembly according to IEC / EN 61439 - deposited by several thousand
tests in laboratories only (documented in approximately 5000 design verifications)
23
© 2015 Eaton Corporation. All rights reserved. 23
Safety Above Standard
Standards / solutions above standard...
• "Damage prevention" measures
• IEC / EN 61439
• Internal separation
• Fully withdrawable technology instead of fixed installation
• Passive arc fault protection according to TR 61641
• Continuous temperature monitoring
• Seismic-tested assembly
• Measures to "Limit the damage"
• Passive arc fault protection according to TR 61641
• "Maintenance settings" for circuit breakers
• Active electronic arc fault protection system
31
© 2015 Eaton Corporation. All rights reserved. 31
Safety Above Standard
Withdrawable unit instead of fixed installation
32
© 2015 Eaton Corporation. All rights reserved. 32
Safety Above Standard
Withdrawable unit instead of fixed installation
33
© 2015 Eaton Corporation. All rights reserved. 33
Safety Above Standard
Withdrawable unit instead of fixed installation
Characterisics
• Motorstarter conventionell MPCB,
eMPCB, MCCB
• Soft starters and frequency
converters
• Energy feeder MCCB
• iMCC = communication-capable slot
by protection devices with electronic
shutter (SmartWire)
34
© 2015 Eaton Corporation. All rights reserved. 34
Safety Above Standard
Withdrawable unit instead of fixed installation
Lockable
• Prevents access by unauthorized persons
• Safety for operating personnel
Positions
• 3 Positions
• connected, test, disconnected
IP2X or Shutter
• Finger safety cover or
• Completely covered by automatic shutter
35
© 2015 Eaton Corporation. All rights reserved. 35
Safety Above Standard
Withdrawable unit instead of fixed installation
Characterisics
• Motorstarter eMPCB, MCCB
• Internal communication via SmartWire
(green cable)
• Status messages of the electronic protection
devices
39
© 2015 Eaton Corporation. All rights reserved. 39
Safety Above Standard
Basics of an arc fault within a switchboard
40
© 2015 Eaton Corporation. All rights reserved. 40
Safety Above Standard
Basics about passice arc fault protection acc. TR 61641
• Dedicated more for personal protection and limited for system protection
• Arc fault classes A*, B*, C* (personal resp. personal and system protection), class
I (arc ignition protected = „insulation“)
• NEW: Access limited, access unlimited … Test with 150g/m² cretone or 40 g/m² in
300mm distance
*) consist of arc tested and when available arc ingnition zones
41
© 2015 Eaton Corporation. All rights reserved. 41
Safety Above Standard
Test lab procedures
• Pre-defined ignition wires are assembled into the panel to get the arc started at
the defined locations
• Pre-defined cotton indicators, simulate operators and are not allowed to ignite
or burn, during or after the test.
44
© 2015 Eaton Corporation. All rights reserved. 44
Safety Above Standard
Passive arc fault protection according to TR 61641
45
© 2015 Eaton Corporation. All rights reserved. 45
Safety Above Standard
Passive arc fault protection according to TR 61641
Depressuring/ flaps
• predetermined breaking cover for depressuring the internal
in a definded range
• De-dangering of the front (area where the personnel stays
in common)
46
© 2015 Eaton Corporation. All rights reserved. 46
Safety Above Standard
Passive arc fault protection according to TR 61641
47
© 2015 Eaton Corporation. All rights reserved. 47
Safety Above Standard
Standards / solutions above standard...
• "Damage prevention" measures
• IEC / EN 61439
• Internal separation
• Fully withdrawable technology instead of fixed installation
• Passive arc fault protection according to TR 61641
• Continuous temperature monitoring
• Seismic-tested SGK
• Measures to "Limit the damage"
• Passive arc fault protection according to TR 61641
• "Maintenance settings" for circuit breakers
• Active electronic arc fault protection system
49
© 2015 Eaton Corporation. All rights reserved. 49
Safety Above Standard
"Maintenance settings" for circuit breaker with electronic release
Characteristics ARMS
• Reduce the arc energy to approximately ¼ of the
energy at a “non-delayed" ACB
• Protection of persons during maintenance
• Remote activation e.g. door contact of the switchgear
51
© 2015 Eaton Corporation. All rights reserved. 51
Safety Above Standard
"Maintenance settings" for circuit breaker with electronic release
Non-delayed setting
Maximum arc energy (cal/cm2)
Non-delayed testing
ARMS settings
52
© 2015 Eaton Corporation. All rights reserved. 52
Safety Above Standard
Layout of a Main Switchgear Assembly
CAT 1 CAT 1
CAT 0 CAT 0
CAT 1
CAT 4 CAT 1 CAT 0
CAT 1
C CAT 1 CAT 1
CAT 0
A
CAT 1
T CAT 1
CAT 4 CAT 0 CAT 0 CAT 1 0 CAT 1
CAT 1
CAT 1
CAT 1
56
© 2015 Eaton Corporation. All rights reserved. 56
Safety Above Standard
Basics of an arc fault within a switchboard
57
© 2015 Eaton Corporation. All rights reserved. 57
Safety Above Standard
Active electronic arc fault protection system with quenching device
• Quenching device – Fast tripping time by gas pressure generator drive
61
© 2015 Eaton Corporation. All rights reserved. 61
Safety Above Standard
Active electronic arc fault protection system with quenching device
• Consequences with or without usage of ARCON
66
© 2015 Eaton Corporation. All rights reserved. 66
Safety Above Standard
Standards / Solutions
67
© 2015 Eaton Corporation. All rights reserved. 67
Safety Above Standard
xSpider V3.0 Software Tool …
69
© 2015 Eaton Corporation. All rights reserved. 69
Safety Above Standard
xSpider V3.0 Software Tool …
70
© 2015 Eaton Corporation. All rights reserved. 70
Safety Above Standard
xSpider V3.0 Software Tool …
71
© 2015 Eaton Corporation. All rights reserved. 71
Safety Above Standard
xSpider V3.0 Software Tool …
• Network calculation etc.
• Risk assessment / „Arc flash hazzard study“
• Acc. IEEE 1584™-2002 (EN 50110-1,-2)
• Integration of ARMS, ARCON etc.
• xSpider is free of charge
• Download and register: www.xspider.eaton.eu
72
© 2015 Eaton Corporation. All rights reserved. 72
Safety Above Standard
Standards / solutions above standard...
• "Damage prevention" measures
• IEC / EN 61439
• Internal separation
• Fully withdrawable technology instead of fixed installation
• Passive arc fault protection according to TR 61641
• Continuous temperature monitoring
• Seismic-tested assembly
• Measures to "Limit the damage"
• Passive arc fault protection according to TR 61641
• "Maintenance settings" for circuit breakers
• Active electronic arc fault protection system
73
© 2015 Eaton Corporation. All rights reserved. 73
Safety Above Standard
Basics concerning temperature monitoring
• Conjested ventilation
• …
74
© 2015 Eaton Corporation. All rights reserved. 74
Safety Above Standard
Basics concerning temperature monitoring
Procedure:
75
© 2015 Eaton Corporation. All rights reserved. 75
Safety Above Standard
Permanent temperature monitoring
79
© 2015 Eaton Corporation. All rights reserved. 79
Safety Above Standard
Permanent temperature monitoring for predictive maintenance
Controller
Hub
Receiver
Temperature sensors
81
© 2015 Eaton Corporation. All rights reserved. 81
Safety Above Standard
Continuous temperature monitoring for predictive maintenance
• Trend (24h)
82
© 2015 Eaton Corporation. All rights reserved. 82
Safety Above Standard
Continuous temperature monitoring for predictive maintenance
• Trend (28d)
83
© 2015 Eaton Corporation. All rights reserved. 83
Safety Above Standard
Standards / Solutions
89
© 2015 Eaton Corporation. All rights reserved. 89
Safety Above Standard
Standards / solutions above standard...
• New device to protect against electrical ignited fires …
93
© 2015 Eaton Corporation. All rights reserved. 93
AFDD
Arc fault detection device (IEC 60364)
L N
Line
Load
Load Load
© 2015 Eaton Corporation. All rights reserved. 98
The Eaton solution
+ „All-in-one“ device
+ Short-circuit and overload
+ RCD
+ AFDD
+ Safely detects arcs above 1A (2,5A)
+ 10 - 40A max.
+ Simple, easy and robust installation
+ Cost effective
Any questions?