DESIGN ENGINEERING OF

ONCE THRU A/C SYSTEM OF


QC LAB (IOCL PANIPAT)

SCOPE OF WORK
1. Survey of the existing HVAC

System.

2. Basic Design Engineering


a. Heat load calculation
b. Chiller and pumps Selection
c. AHU selection
d. SLD of the HVAC System
1. Survey of the existing HVAC
System.
During the site visit it was observed that the existing
system consisting of DX based chiller unit with 63 TR
capacity for old building and package unit for new
building is not delivering the required cooling and was
not designed as per the OISD 211 guideline with
10 – 12 ACPH.
As per the requirement of IOCL it is decided to
replace the existing system with once thru chilled
water system following OISD 211 STD. having a
common chiller for the old and new building.
2. Basic Design Engineering.
a. Heat load calculation

Climatic condition considered

Condition DB WB % RH
Summer 110 75 20
Monsoon 95 83 60
Winter 45 41 70
Inside 75 55
Air changes per hour = 12 ACPH

Lighting Load = 1.5 W / sq. ft

Area of the rooms

False ceiling height of the room


OLD BUILDING NORMAL & ONCE THROUGH

ONCE THROUGH

LOCATION TR CFM
Shift Lab 21.51 4687
General Shift Lab 22.4 5273
Analyzer Room 4.1 1104
Sin dist Room 3.3 920
ICP MS Room 3.35 962
Water Lab 7.7 2199
ATR Testing Lab 7.6 2007
     
TOTAL ONCE THRU 70 17152

NORMAL

LOCATION TR CFM
Officers room 1.43 703
Utility Room 1.44 456
Officers Room 2 1.43 703
Officers Room 3 1.43 703
COCM Room 1.29 653
Engine Room 4.41 1743
     
TOTAL NORMAL 11.43 4961
     
GRAND TOTAL OLD BUILDING 81 22113
NEW BUILDING ALL ONCE THROUGH

ONCE THROUGH

LOCATION TR CFM
Spectroscopy 9.96 2850
Gas Chromotography 13.2 3777
Chemical Store 2.67 748
Glass Ware 2.67 748
G C Spare 2.67 748
Water and Waste Water 6.67 2087
Analyzer Room 5 1284
Process Control 16.91 4752
Sample Retention 7.28 1100
     
TOTAL ONCE THRU 67 18094

ONCE THROUGH

LOCATION TR CFM
Officers Room 5.26 815
Density Room 5.2 815
Officers Room ff 2.7 765
Meeting Room 5.15 1334
AQCM Room 3.2 1100
Lunch and Locker 4.58 1441
     
TOTAL 26.09 6270
     
GRAND TOTAL NEW BUILDING 93 24364
b. Chiller and Pump selection

Chiller
Based on combined heating load requirement of
both building is 182 TR. A Chiller unit is formally
selected of 200 TR capacity.

The type of chiller selected is screw because


of its compact size, low noise level, lower
maintenance cost and high energy efficiency.
Pumps

Chilled water pumps

Based on the operating tonnage capacity of


chillers, water flow quantity in Gallons per
minute is selected.

The selected GPM for the pump is 480 against


the pressure head of 25 meter.
Condenser water Pumps

water flow quantity in Gallons per minute


is selected for the condenser water pump
is 640 GPM

The type of the pump is horizontal centrifugal.


c. AHU selection

The AHU is selected as per the dehumidified


CFM calculated

Air Velocity across the coil is maintained at


500 FPM as per the standard.

Number of rows of the coils is selected as per the


calculation of CFM per TR obtained.
Followings are the range as per standard for
selecting rows of the AHU coils

1. 0 – 225 CFM / TR = 8 Row coil

2. 226 – 400 CFM / TR = 6 Row coil

3. 400 – onward CFM / TR = 4 Row coil