Data Hasil Praktikum

Mode Cooling - Capilary Tube


Tekanan (Bar) Temperature (°C)
No Jenis Bukaan Flow Ampere
P1 P2 P3 P4 T1 T2 T3 T4
1 Air Off Bukaan Atas 26 2.75 2.4 11.75 12 2.6 23 62 45 2
2 Air Off Bukaan Bawah 25 2.75 2 11.25 11.4 2.5 23 56 43 0
3 Ceiling Fan 26 2.8 2.5 12 12.1 2.75 24 64 46 3
4 Attic Heater 26 2.8 2.5 12 12.1 3.75 24 64 46 3
5 Attic Fan 27 2.9 2.5 11.9 12 3.75 24 64 45 4

Mode Cooling - Thermostatic Expantion Valve


Tekanan (Bar) Temperature (°C)
No Jenis Bukaan Flow Ampere
P1 P2 P3 P4 T1 T2 T3 T4
Thermostatic Expantion
1 53 3.4 3.7 13.5 13.6 4 17 65 50 12
Valve

Keterangan
P1 = Tekanan keluar evaporator
P2 = Tekanan masuk kondensor
P3 = Tekanan eluar kondensator
P4 = Tekanan keluar evaporator
T1 = Temperatur masuk kompresor
T2 = Temperatur masuk kondensor
T3 = Temperatur keluar kondensor
T4 = Temperatur Kkeluar expantion valve

*) laju aliran sistem pendigin (capillary tbe) pada suhu 45°C aladah 0.003761 kg/s
*) laju aliran sistem pendigin (thermostatic exp. valve) pada suhu 47°C aladah 0.006395 kg/s
Semua variable diukur berdasarka rentang waktu setiap pegambilan data yaitu 20 menit
Hasil Pembacaan Diagram dan Perhitungan

Entalpi berdasarkan P-H diagram R-134A


Entalpy (kj/kg)
NO Aliran Melalui Flow
T1 T2 T3 T4
1 Air Off Bukaan Atas 26 416 445 265 265
2 Air Off Bukaan Bawah 25 416 439 263 263
3 Ceiling Fan 26 417 447 266 266
4 Attic Heater 26 417 447 266 266
5 Attic Fan 27 417 447 265 265

Entalpy (kj/kg)
NO Aliran Melalui Flow
T1 T2 T3 T4
Thermostatic Expantion
1 53
Valve 408 438 270 270

Perhitungan

Air Off Bukaan Atas


1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.109069 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.567911 Kw

3.) Kalor yang Dilepas Kondensor


Qcon = m.reff x (h2-h3)
= 0.67698 Kw
4.) Coeffisient Of Performance
COP = Qev/Wcom
= 5.206897

Air Off Bukaan Bawah


1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.086503 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.575433 Kw

3.) Kalor yang Dilepas Kondensor


Qcon = m.reff x (h2-h3)
= 0.661936 Kw

4.) Coeffisient Of Performance


COP = Qev/Wcom
= 6.652174

Ceiling Fan
1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.11283 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.567911 Kw
3.) Kalor yang Dilepas Kondensor
Qcon = m.reff x (h2-h3)
= 0.680741 Kw

4.) Coeffisient Of Performance


COP = Qev/Wcom
= 5.033333

Attic Heater
1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.11283 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.567911 Kw

3.) Kalor yang Dilepas Kondensor


Qcon = m.reff x (h2-h3)
= 0.680741 Kw

4.) Coeffisient Of Performance


COP = Qev/Wcom
= 5.033333
Attic Fan
1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.11283 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.571672 Kw

3.) Kalor yang Dilepas Kondensor


Qcon = m.reff x (h2-h3)
= 0.684502 Kw

4.) Coeffisient Of Performance


COP = Qev/Wcom
= 5.066667

Thermostatic Expantion Valve


1.) Daya Kompresor
Wcomp = m.reff x (h1-h2)
= 0.11283 kW

2.) Kalor yang Diserap Evaporator


Qev = m.reff x (h1-h4)
= 0.519018 Kw

3.) Kalor yang Dilepas Kondensor


Qcon = m.reff x (h2-h3)
= 0.631848 Kw
4.) Coeffisient Of Performance
COP = Qev/Wcom
= 4.6

Hasil Perhitungan

NO Aliran Melalui Wcomp Qev Qcon COP

1 Air Off Bukaan Atas 0.109069 0.575433 0.67698 5.206897


2 Air Off Bukaan Bawah 0.086503 0.575433 0.661936 6.652174
3 Ceiling Fan 0.11283 0.567911 0.680741 5.033333
4 Attic Heater 0.11283 0.567911 0.680741 5.033333
5 Attic Fan 0.11283 0.571672 0.684502 5.066667

NO Aliran Melalui Wcomp Qev Qcon COP

Thermostatic Expantion
1 0.11283 0.519018 0.631848 4.6
Valve
COP
7

0
1 2 3 4 5 6
201
199
202
202
203