Air flow rate of whole system


= volume of room x ACH
3600
= (20 x 15 x 3) x 8/3600 m3/s
= 2m3/s

i.e. each air grille has flow rate


of 2/2 or 1m3/s

Air velocity = 5m/s


Air Duct Design
Air Duct Design
Air Duct Design

Plot a line at velocity = 5m/s


Air Duct Design
Air Duct Design

Draw a horizontal line at


volume flow rate = 1m3/s
Air Duct Design
Air Duct Design

The corresponding air duct


diameter is about 0.5m or
500mm,
i.e. Duct B diameter = 500mm
Air Duct Design

Draw a horizontal line at


volume flow rate = 2m3/s
Air Duct Design

The corresponding air duct


diameter is about 0.7m or
700mm,
i.e. Duct A diameter = 700mm
Air Duct Design

Frictional loss at Duct B = 0.55 Pa/m


Air Duct Design

Frictional loss at Duct B = 0.55 Pa/m


Equivalent length of Duct B = 20m
Therefore, static loss at Duct B
= 20 x 0.55 Pa
= 11Pa
Air Duct Design
Air Duct Design

Frictional loss at Duct A = 0.35 Pa/m


Air Duct Design

Frictional loss at Duct A = 0.35 Pa/m


Equivalent length of Duct A = 10m
Therefore, static loss at Duct A
= 10 x 0.35 Pa
= 3.5Pa
Air Duct Design

Air flow rate of whole system


= volume of room x ACH
3600
= (20 x 15 x 3) x 8/3600 m3/s
= 2m3/s

Statistic pressure requirement


= (11 + 3.5)Pa
= 14.5Pa