You are on page 1of 10

EET-127

Canadian Electrical Code 2

Canadian Electrical
School of Engineering and Technology and applied Science
(SETAS)
Code

Week # 3
Section – 60
Electrical Communication Systems
60-000: Scope
(1) This Section applies to the installation of communication systems.
(2) The requirements of this Section supplement or amend the general
requirements of this Code.

Exposed plant — the circuit or any portion of it subject to lightning


strikes, to voltage exceeding 300 V rms due to accidental contact with
electric lighting or power conductors, to induction from power line
unbalance operation or faults, and to ground potential rise.
2
60-104: Circuits in communication
cables
Radio and television circuits, remote control circuits, and fire alarm circuits
or parts of this equipment shall be:
(a) permitted to use conductors in a communication building entrance cable
assembly having other conductors used as communication circuits;
(b) deemed to be communication circuits for those portions of circuits that
use conductors within the communication building entrance cable assembly;
and
(c) suitably protected at the point of interface connection with the
communication cable conductors.

3
60-108: Inspection by an
inspector
(1) Communication circuits employed by an electrical or communication
utility in the exercise of its function as a utility shall not be subject to
inspection by an inspector.

(2) Where the communication circuit derives power for operation from a
supply circuit, the transformer or other current-limiting device used at the
junction of the communication and the supply circuit shall be subject to
inspection by an inspector.

4
60-308 Separation from other
conductors

• least 50 mm from insulated conductor of a Class 1 circuit or


an electric light or power system operating at 300 V or less,

• 300v or more, be separated at least 600 mm from any


insulated conductor or an electric light or power system

5
60-310 Penetration of Fire
Separation
• Conductors of communication circuits extending through a
fire separation shall be installed to limit fire spread in
accordance with Rule 2-128.

6
60-402 Equipment in air ducts, plenums,
or suspended ceilings

• Shall not be placed in ducts, plenums, or hollow spaces that


are used to transport environmental air nor in suspended
ceiling areas, except that where a duct, plenum, or hollow
space is created by a suspended ceiling having lay-in
panels or tiles.
• Connecting blocks that are of a non-protective type shall be
permitted to be installed if they are placed in an accessible
enclosure

7
60-502 Overhead conductors
on roofs
(1) Communication conductors passing over buildings shall be kept
at least 2.5 m above any roof that can be readily walked upon.

(2) Communication conductors shall not be attached to the upper


surfaces of roofs or be run within 2 m, measured vertically, of a roof
unless a deviation has been allowed in accordance with Rule 2-030

(3) A deviation in accordance with Rule 2-030 shall not be necessary


where the building is a garage or other auxiliary building of one
storey.

8
60-512 Communication conductors
entering buildings

(a) are in metal-sheathed or shielded cable;


(b) pass through masonry;
(c) are without fuses in the primary protectors as provided for
in Rule 60-202(2); or
(d) are used to extend circuits to a building from a cable
having a grounded metal sheath or shield.

9
60-706 Grounding Electrode

(1) The grounding conductor shall preferably be connected to


a water pipe grounding electrode, as close to the point of
entrance as possible.

10

You might also like