Sinamics V50 Catalog V2.11 - 28 - 04 - 2010
Sinamics V50 Catalog V2.11 - 28 - 04 - 2010
55 KW ~ 500 KW
Catalog D11.5I - 2010
SINAMICS V50
Communication
Overview
Single Drive Converter Control method
Cabinet Units
More circumspect
Application
consideration
1
Benefits
Design
Catalog Software and protection
Functions
Technical data
Options overview
D11.5I - 2010
Technical data
V2.11
Dimension drawings
55 KW ~ 90 KW
3
110 KW ~ 250 KW
315 KW ~ 500 KW
Engineering information
Customer terminal block 4
Conductor cross-section
The products and and connection
system described
in this catalog are Grounding
produced /
distributed in Line-side components
accordance with
the requirements
of a quality
Load-side components
management
system which has Max. connectable cable length
been certified to
DIN EN ISO Dimensioning drives
9001.
The certificate is
Motors
recognized in all
EQ Net countries.
Appendix
Environment, resources 5
and recycling
ISO 9001, ISO 14001
SINAMICS V50
Overview
1/2 Application
1/2 Benefits
1/2 Design
1/5 Functions
Application
Input voltage 3AC Output power SINAMICS V50 converter drive cabinet
380 V ~ 415 V 55KW ~ 500KW
Benefits
• Particularly quiet and compact converters due to the use of state-of-the-art IGBT power
semiconductors and an innovative cooling concept.
• All unit modules are easily accessible, making them extremely service-friendly.
• Can be easily integrated into automation solutions due to PROFIBUS interface (optional) and various
analog and digital interfaces.
• Increase in plant availability since individual modules and power components can be replaced quickly
and easily.
Design
SINAMICS V50 single drive converter cabinet units are characterized by their compact, modular and
service-friendly design.
A wide range of options is available which permits optimum adaptation of the drive system to the
respective requirements.
Design
Standard configuration
• 8MF cabinet
3 AC 380 ~415 V
Line connection
Main switch
Fuses
* Main contactor (option)
Rectifier
Voltage DC link
Inverter
Motor connection
Design
Cabinet units
Components
Terminal block
Input reactor
Function
Automatic Parameter
Communication
Ethernet
SINAMICS V50 provides several Monitor
communication methods:
• Peer to peer, for the communication
between control board and BOP-2 (Basic Profibus (option)
Operator Panel)
• RS485 interface, for the communication
between SINAMICS V50 and PC RS485
(standard)
Function (continued)
Control methods
Square torque linear torque Constant power
Various control modes:
• V/F Control
• Multiple-point V/F
• Flux Current Control
Function (continued)
Set point input The set point can be defined internally and externally, internally as fixed or motorized potentiometer or jog
setpoints, externally via the communications interface or an analog input on the customer’s terminal block.
The internal fixed set point and the motorized potentiometer set point can be switched over or adjusted using
control commands via all interfaces.
Motor identification Automatic motor identification permits fast and simple commissioning and optimization of the drive control.
Ramp-function generator A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together
with adjustable rounding times in the lower and upper speed ranges, improves the control response and
therefore prevents mechanical overloading of the drive train. The ramp-down ramps can be parameterized
separately for emergency stop.
Vdc max controller The Vdc max controller automatically prevents overvoltage in the DC link if the set ramp-down ramp is too
short, for example. This may also extend the set ramp-down time.
Flying restart The flying restart permits bump less connection of the converter to a rotating motor.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps
up to the current speed set point.
Technology controller The technology controller is designed as a PID controller. The P, I, and D components can be set separately.
I2t detection for motor The motor temperature is calculated in a motor model stored in the converter software. The Motor protection is
protection possible by means of connecting KTY84 or PT100 sensors in the motor winding to converter.
Motor blocking protection A blocked motor is recognized and protected against thermal overloading by shutting down.
Ground fault monitoring A ground fault on the output side is recognized by aggregate current monitoring, and results in
shutdown in grounded networks
Electronic short-circuit A short-circuit (e.g. on the converter output terminals, in the motor cable or in the motor’s terminal
box) is detected on the output side and the converter switches off with a fault
Thermal overload A warning message is issued first when the over temperature threshold responds. If the
protection temperature rises further, either a shutdown is carried out or an automatic influencing of the pulse
frequency or output current takes place so that a reduction in the thermal load is achieved. After
elimination of the cause of the fault (e.g., improvement in the ventilation), the original operating
values are automatically resumed.
Over current protection A warning message is issued first when the over current threshold responds. If the current rises f
urther, either a shutdown is carried out or an automatic influencing of the pulse frequency or outp
ut frequency takes place so that a reduction in the current is achieved. After elimination of the ca
use of the fault (e.g., mechanical obstruction etc.), the original operating values are automatically
resumed.
Over voltage protection The high / abnormal supply voltage leads to overvoltage of dc link and the unit is tripped to avoid
damages to power devices.
Under voltage Failure of line supply or sustained under voltage leads to low dc link and unit is protected by
protection tripping the unit
Phase loss protection Phase loss leads to under voltage and unit is shut to protect the inverter
Options overview
For 400,500 KW
Motor protection:
Emergency stop
Thermistor or PT100 relay
Technical data
Electrical data
Line Voltage and power ranges 380 V ~ 415 V 3AC , ±10 %( -15 % <1 min ) 55 KW ~ 500 KW
Power factor
-Fundamental mode >0.98
-Total 0.93 - 0.96
Mechanical data
RI suppression In accordance with EMC product standard for variable-speed drives IEC 61800-3
Ambient conditions
Environmental class/harmful Class 1C2 to IEC 60721-3-1 Class 2C2 to IEC 60721-3-2 Class 3C2 to IEC 60721-3-3
chemical substances
Biological influence Class 1B1 to IEC 60721-3-1 Class 2B1 to IEC 60721-3-2 Class 3B1 to IEC 60721-3-3
Installation altitude Up to 1000 m (55 KW~90 KW) / 2000 m (110 KW~500 KW) above sea level without derating
Strain resistance
Vibratory load 1.5 mm, 5Hz~9Hz 3.1 mm, 5Hz~9Hz 0.075 mm, 10Hz~58Hz
-Deflection 5m/s2, > 9Hz~200 Hz 10m/s2, > 9Hz~200 Hz 9.8m/s2, > 58Hz~200 Hz
-Acceleration Class 1M2 to IEC 60721-3-1 Class 2M2 to IEC 60721-3-2
Shock load
<2750
<3000
<3250 98%
Technical data
2/4 Options
Selection and ordering data
SINAMICS V50 Rated input Rated output Rated Power Power loss Cooling air Sound pressure
Converter cabinet current current Requirement level at 50 Hz
A A KW KW m3/s dB (A)
The table below show the recommended or maximum possible cable connection on the line and motor
sides. The recommended cross-sections are based on the listed fuses and single routing of the three-
wire cables at an ambition temperature of 40℃.
In the case of different conditions (cable routing, cable grouding, ambient temperature), the
configuration instructions for routing the cables must be taken into account.
Line connection Motor connection Cabinet grounding
Maximum Maximum
Recommended Recommended Mounting Mounting
Power Conductor Mounting Conductor
cross-section cross-section Screw M12 Screw M12
KW Cross-section Screw M12 Cross-section Comment
IEC mm2 IEC mm2 (No. of holes) (No. of holes)
IEC mm2 (No. of holes) IEC mm2
Options
When ordering a converter with options, add ”-Z” to the order number of the converter, followed by the
Order Code (s) for the desired option (s).
1) Only for ratings up to 355 KW. For 400 KW & 500 KW, circuit
breaker is supplied as standard
2) The auxiliary power supply AC230v and DC 24V are supplied as
a standard for 400 KW & 500 KW ratings.
Possible Connection for all Ratings x Not Supported for all Ratings * Not supported for 250kW and 315kW *** Included in Option
E88-E91 G91
Analog input/output isolation amplifier PROFIBUS optional board
Isolation amplifiers for analog inputs and The function of the PROFIBUS communication
outputs Isolation amplifiers for analog inputs board is to provide a PROFIBUS link between
and outputs isolate the different reference drives of the SINAMICS V50 Drive product range
potentials of the signals between the unit and higher-level automation systems. For a
electronics and the higher level controller and complete PROFIBUS connection with up to ≤ 12
also increase electrical immunity to M baud, remote control of the inverter is possible
interference. with the PROFIBUS module. Remote control and
The code K73 necessary for this option must operation at the inverter can be combined using
always be specified. It is most important to an operator panel plugged onto the PROFIBUS
distinguish the difference of the four amplifiers. module.
E88 The PROFIBUS module for the cabinet power
Input isolating amplifier for analog input 1 range from 55KW to 90 KW must be supplied by
Input: 0 mA to 20 mA or 0 V to 10 V the option K73, 24 V DC power or an external 24
Output: 0(4) mA to 20 mA or 0 V to 10 V V DC power and is thus also active when the
inverter is disconnected from the power supply.
E89 The board is connected to the PROFIBUS
Isolating amplifier for analog input 2 system via bus connector complying with the
Input: 0 mA to 20 mA or 0 V to 10 V PROFIBUS standard. All connections to this
Output: 0(4) mA to 20 mA or 0 V to 10 V RS485 interface are short-circuit-proof and
isolated.
E90
NOTE: PROFIBUS module is connected by
Motor Current Reference only, if K23 is used.
means of a 9-pin D-Sub connector which is
Isolating amplifier for analog output 1
supplied by user
Input: 0 mA to 20 mA
Output: 0 V to 10 V or 0(4) mA to 20 mA
E91
Motor Speed Reference only, if K23 is used.
Isolating amplifier for analog output 2
Input: 0 mA to 20 mA
Output: 0 V to 10 V or 0(4) mA to 20 mA
SINAMICS V50 Catalog 2/5
Selection and ordering data
K10 K25
With this option, a selector switch allows Start / Stop push button
operation of cabinet from panel in Local mode With option K25, a start button (green) and a
and from Remote location using PB. K73 option stop button (red) are installed on the cabinet
is must. door drive from a distance to operator
K11
Selector switch allows operation in Local mode K26
– Start/Stop PB on door for speed Raise/Lower Potentiometer
with PB on door and Remote mode with Potentiometer can change EMF of the
Start/Stop PB , 4-20mA speed ref. K73 & E88 converter using analog input. And then, the
options are must. output frequency or motor speed can be
controlled by this option. With this option
K12 integrated, E88 is not possible as analog
Selector switch allows Local mode operation input #1 is used to give 0-10VDC speed
with– Start/Stop PB on door, Speed Ref reference for speed
Potentiometer on door & Remote mode -
Start/Stop PB , Raise/Lower remote PB. K73 &
K26 options are must. K73
DC 24V auxiliary power supply
K13 The auxiliary power supply provides 24 V DC
Selector switch allows Local mode operation power for the electronic options. And it is fed
with– Start/Stop PB on door, Speed ref Pot on via the 230 V AC control voltage, which is
door & Remote mode - Start/Stop remote PB, provided from external power supply or using
4-20mA speed ref.K73,K26 & E89 options are the option code K74.In additional, the option
must. K73 includes a relay -K11 which controls
operation of contactor L13, heater
K19 L55 and other options. Note: This option will be
Start/ Stop indicated light replaced by a DC 24V auxiliary power supply
With this option, Indication lamp turns Red as a standard configuration for the cabinet
while drive is in Run operation and another power range 400KW to 500KW.
Amber lamp turns ON when drive trips on
internal Fault. This is useful feature to indicate K74
status of drive from a distance to operator AC 230V auxiliary power supply
The auxiliary power supply is via the mains
K23 supply by means of a control transformer. The
Analog display instrument (speed, current) input side of transformer can obtain the power
Analog meters for speed and current are from line side. K74 has to be provided if options
mounted in the cabinet front door required for this auxiliary voltage are necessary
(e.g. with L13, L55, K73 and so on).
Note: This option will be as a standard
K24 configuration for the cabinet power range
A separate PB on door allows drive to be reset 400KW to 500KW.
after fault. A parallel connection of NC contact
allows fault resetting from remote location. One
digital input must be parameterized for this
function to be actualized.
L13
Main contactor (for converter with o/p currents <700A)
The SINAMICS V50 Drive cabinet unit is designed without a line contactor. Option L13 is needed if a
switching element is required for disconnecting the cabinet from supply (necessary with EMERGENCY
OFF). The contactor (rated current <700A) includes one inner DC 24V auxiliary power supply. So it
must be used with option K73 and K74 or have the condition about AC 230 V power supply. Generally
the contactor work conjunction with L56 and L57.G91 is required for 55 – 90 KW.
L50
Cabinet lighting and service socket outlet in control section If option L50 is chosen, a universal lamp
and a service socket outlet are installed in the cabinet panels. The voltage supply for the cabinet
lighting and service socket outlet is provided externally. The cabinet lighting is switched on manually.
L55
Anti-condensation heating for cabinet
The anti-condensation heating is recommended at low ambient temperatures and high levels of humidity t
o prevent condensation forming. A 100W heater is installed for the width upto 600mm cabinet panel. Fro
m the width of 900 mm & above, 150W heater will be provided in the panel. The voltage supply for the he
ater is provided externally.
L56
EMERGENCY OFF button OFF-2 operation, Motor Coasts to Stop. The function includes voltage
disconnection from the supply via the line contactor L13
L57
EMERGENCY STOP category 0 for uncontrolled stop in accordance with EN60204.
The function includes voltage disconnection of the converter via the line contactor with bypassing of
the microprocessor controller by means of a safety combination in accordance with EN 60204-1.The
motor coasts in the process. When delivered, the button circuit is preset to 230V AC. Jumpers must
be set when using 24V DC.
Attention: Option L57 always assumes that the converter can be electrically isolated from the supply.
L86
The PT100 evaluation unit can monitor up to 6 sensors. The sensors can be connected using a two wire
or three-wire system. With the two-wire system, inputs Tx1 and Tx3 must be assigned. With the three-
wire system, input Tx2 must be connected (x=1, 2, 3 … 6).
Note: As per the factory setting, six PT-100 sensors in the PT-100 measurement channels are replaced
by six resistors and will not work. So user must use PT-100 sensors instead of resistors at the working
location.
M
M06
Base 100 mm high, the color of base is the same with the cabinet color. The additional cabinet base
allows greater bending radii for cables (inlet from below) and the routing of them within the cabinet
base. The cabinet base is always coloured RAL 7035. A special colour is not possible. It is delivered
completely fitted with the cabinet. The height of the operator panel changes accordingly.
P Y
PE busbar (cable connection from below) Y09
The PE Aluminum 40x10 mm busbar is used to Special paint finish according to RAL
run the PE conductor for the supply and motor Converters are supplied as standard in RAL 7035
infeed cables and will be provided in all (light grey). A special colour must be specified in
cabinets as standard. plain text when ordering. In case of the
SINAMICS V50 Drive air-cool version, the fans
are still finished in RAL 7035 even if the cabinet is
in a special colour. The molded plastic parts (e.g.
ventilation grilles) are coloured RAL 7035 and
cannot be painted.
3/2 55KW~90KW
3/6 110KW~250KW
3/10 315KW~500KW
Dimension drawing
4/6 Grounding
4/9 Motors
Engineering information
The factory default setting and the description for the terminal block can be found in the circuit diagram.
3 AC 380 ~ 415 V
Note: the analog inputs can be used as digital input (DIN7 and DIN8).
The analog inputs can be used as digital input (DIN7 and DIN8).
When an analog input is configured as a digital input, the threshold value are
as follows:
1.75V DC = off
3.7V DC = on
-X10:3 ADC1+ Analog input 1“+” / input signal range 0~10V, 0~20mA, -10V~+10V
• In this manner, the high IP54 degree of • Under fault conditions, no voltage exceeding
protection can be achieved for the motor 25 V AC or 60 V DC (IEC 61800-5-1 Edition 2
terminal box without any problems because the Subsection 4.3.5.3.3) may occur between
cables are introduced into the terminal box via accessible conductive parts and the means of
screwed glands and the number of possible connection for the protective earthing conductor
glands is limited by the geometry of the terminal until an upstream protective device removes
box. Single cables are less suitable. power from the part.
• With three-phase cables, the summed ampere- • The ground fault current flowing in the PE
turns over the cable outer diameter is equal to conductor in the event of a ground fault must not
zero and they can be routed in ( conductive, place an impermissible load on the PE
metal) cable ducts or racks without any conductor.
noticeable currents (ground current or leakage • If it is possible for continuous currents to flow
current) being induced in these conductive, through the PE conductor when a fault occurs,
metal connections. The danger of induced the PE conductor cross-section must be
leakage currents and thus of increased cable dimensioned for this continuous current.
sheath losses is greater for single cables.
•The PE conductor cross-section should be
The cable cross-section required depends on selected in accordance with IEC 60204-1.
Cross-section of Minimum cross-section of external PE
the current transmitted in the cable. The outer conductor conductor
permissible current loading of cables is defined
<16mm2 Minimum cross-section of outer conductor
e.g. in IEC 60364-5-52 . It depends partly on
the ambient conditions such as temperature and 16mm2~35mm2 16mm2
partly on the type of routing. When laid singly, >35mm2 At least half the cross-section of outer
the cables are cooled relatively well. Where conductor
there are several cables routed together, they
can heat each other up, and thus receive much
poorer ventilation. Reference should be made to • Switchgear and motors are usually grounded
the corresponding reduction factors for such separately with a local ground electrode. With
condition as specified in IEC 60364-5-52 . With this constellation, the ground fault current flows
an ambient temperature of 40℃, the cross- via the parallel ground connections and is
sections of copper cables can be based on the divided. With this grounding, no impermissible
following table. contact voltages can occur, despite the PE
Current loading in accordance with IEC 60364-5- conductor cross-sections used in the above
52 at 40℃ table.
• Through their fast control, the converters limit
Cross-section of With single With several cables on a
the load current (motor and ground fault
3-wire cable routing common cable rack currents) to a rms value corresponding to the
50mm2 138A 95A rated current. Because of this, we recommend
70mm2 176A 121A
95mm2 212A 146A
the use of a PE conductor cross-section that is
120mm2 245A 169A analogous to the outer conductor cross-section
150mm2 282A 194A for grounding the control cabinet.
185mm2 323A 222A
240mm2 380A 261A
300mm2 418A 289A
Line-side components
Line fuses
In SINAMICS V50, the SIEMENS fuses
(3NA3) are installed as standard for
protecting the line side of the converter.
• Superfast
• Low arc voltage
• Improved current limiting
Line reactor
A line reactor is required for high system The SINAMICS V50 cabinet units are
short-circuit power, partly to protect the equipped with a 2% line reactor as standard.
converter against excessive harmonic
currents, and thus against overload, and
partly to limit the harmonic effects on the
system to the permissible values. The
harmonic current are limited by the complete
inductance comprising the line reactor and
main power input inductance.
Load-side components
motor reactor (L08)
IGBT-converter switching frequencies result
in high voltage rises dv/dt at the converter
output. If long motor cables are used, this
leads to an additional current load on the
converter due to capacitive charge/discharge
currents.
In addition to, the high voltage rises, and the
resulting voltage peaks at the motor
terminals, cause the motor’s electrical
winding load to increase in comparison to
direct on-line operation.
The motor reactor (L08) can limit the voltage
rise dv/dt and the voltage peak at the motor
terminal.
Max. connectable motor cable length
Refer to page 2/6
Dimensioning drives
Motors
1LA and 1LG motor
It is generally recommendable to use the
standard Siemens motors 1LA and 1LG. Other motors
With regard to the voltage stress, the standard In addition to the 1LA and 1LG motors, the
insulation of the motors is designed such that 1PH7/1PL6 compact asynchronous motors can
operation on the converter is possible without also be used. These are recommended for:
limitation at voltages V≤500V. Large speed range with high maximum speeds.
For detailed data about motor types, please Limited mounting space.
refer to catalog M11. 1PH7/1PL6 motors are on average 1 to 2 shaft
heights smaller than comparable standard
Self-ventilated, IP55 (1LG4/1LG6 and 1LA8) asynchronous motors with the same rated output.
Motor protection
A motor protection function can be implemented
using the I2t detection present in the converter
software.
If precise motor protection is required, this can be
afforded by direct temperature measurement
using KTY84 sensors or PTC thermistors in the
motor winding.
When using the KTY84 sensors, motor option
A23 must be specified when ordering 1LA8 and
1LG4/1LG6 motors. With 1PH7 and 1PL6
motors, the sensors are fitted as standard.
1LG4/1LG6 motors If PTC thermistors are required, motor option
A11 or A12 must be specified when ordering
1LG4/1LG6 motors. With 1LA8/1PQ8 motors, the
sensors are fitted as standard.
The KTY84 sensor and PTC thermistor can be
evaluated by connecting to the customer's
terminal block –X10 in the converter
1LA8 motors
Motors (continued)
Bearing currents
In order to apply currents to the motor which are sinusoid
al as far as possible (smooth running, oscillation torques s
tray losses), a high clock frequency is required for the con
verter’s output voltage. The rated (very steep) switching e
dges of the converter output voltage (and also, therefore,
of the common-mode voltage) cause correspondingly hig
h capacitive currents and voltages on the machine’s inter
nal capacitances.
This physical effect, which occurs in isolated cases, has
mostly been observed in connection with large motors.
The most important measures for reducing bearing curren
ts:
• Insulated motor bearing at the non-drive end. The insula
ted bearing is standard for all 1LA8 motors designated for
converter operation.
• Use of motor reactors (option L08)
5/2 Environment,
resources
and recycling
Siemens feels a responsibility to play a role in • We inform interested members of the public
protecting our environment and saving our about the consequences of our corporate policies
valuable natural resources. This is true for for the environment as well as our achievements
both our production and our products. Even to the benefit of the environment.
during development, we consider any
possible environmental impact of future • Our complete documentation is printed on
products/systems. Our aim is to prevent chlorine-free bleached paper.
harmful environmental effects or at least to
reduce them to an absolute minimum –
beyond present regulations and legislation.