Water REVISION Direct and Indirect system of water distribution
• Minimal pipe work
• storage cistern supplying the hot water cylinder need only have 115 liters capacity. • maintenance valves should be fitted to isolate each section of pipework • Back siphonage can occur when there is a high demand on the main. • Negative pressure can then draw water back into the main from a submerged inlet Indirect system of water distribution
The cold water storage cistern has a
minimum capacity of 230 liters. In addition to its normal supply function, it provides an adequate emergency storage in the event of water main failure. The system requires more pipework than the direct system and is therefore more expensive to install, but uniform pressure occurs at all cistern-supplied outlets. there is less chance of back siphonage. Other advantages of lower pressure include less noise and wear on fittings. Water Storage Cisterns
liters, cisterns must be duplicated and interconnected In the interests of load distribution this should be provided at much lower capacities For maintenance and repairs each cistern must be capable of isolation and independent operation. Back Siphonage Back Siphonage Float Action Valve
Stage 1. Water filling the cistern lifts
hemi-spherical float and closes the canister valve. Stage 2. Water overflows into the canister, raises the ball float to close off water supply. Stage 3. As the cistern empties, the ball float remains closed until low water level releases the hemi-spherical float. As this float valve drops, water is released from the canister to open the ball float valve to replenish the cistern from the pneumatic supply Hot Water Distribution HOT WATER SUPPLY SYSTEMS Water Expansion
Water expands with changes in
temperature. At 40C water is at its most dense At temperatures below 4ƒC down to zero or freezing, water expands about 9% (approximately 1/10) by volume. This is why underground supplies require adequate ground cover and externally exposed water pipes require insulation to prevent damage Direct System of Hot water Supply
The hot water from the boiler mixes
directly with the water in the cylinder. If used in a `soft' water area the boiler must be rustproofed. This system is not suited to `hard' waters, typical of those extracted from boreholes into chalk or limestone strata. The storage cylinder and associated pipework should be well insulated to reduce energy losses Indirect system of Hot water systems
his system is used in `hard' water areas to
prevent scaling or `furring' of the boiler and primary pipework. Unlike the direct system, water in the boiler and primary circuit is not drawn off through the taps. The same water circulates continuously throughout the boiler, primary circuit and heat exchange coil inside the storage cylinder. Boiler water temperature may be set by thermostat at about 800C. Expansion valve and Temperature relief valve Strainers
A strainer is used to filter out and trap
fluid suspended debris, pipe scale and carbonate deposits from hard water. This facility is essential to prevent component wear by erosion and abrasion, and interference with the efficient operation of pipe system controls. Hot Water Storage Cylinders Indirect Hot water system for a building with more than 3 stories… For larger buildings a secondary circuit will be required to reduce `dead-legs' and to maintain an effective supply of hot water at all outlets. Convection or thermo-siphonage may provide circulation, but for a more efficient service a circulatory pump will be necessary. a time control or programmer can be used to regulate use of the pump. Boilers TYPES OF BOILERS Types of Boilers
Cast Iron Fire or flame tube Copper or steel shell
made up of a series of hollow hot combusted fuel and gases These reverse the principle of fire sections, joined together with left- discharge through multiple steel tubes tubes. and right-hand threaded nipples to to the extract fuel. provide the heat capacity required. Water circulates in a series of finned Heat energy from the burnt fuel tubes whilst the combusted fuel transfers through the tube walls into effects an external heat transfer. cylindrical waterways. Duplication of Plant Dual installations or duplication of plant and equipment is required in buildings where operating efficiency is of paramount concern. With this provision, the supply of hot water in hotels, commercial buildings, offices, etc. is ensured at all times. It is most unlikely that all items of plant will malfunction simultaneously. Disease in Hot water systems
Bacterial growths which cause Legionnaires' disease develop in warm, moist,
natural conditions such as swamps. They have adapted to living in the built environment in the artificial atmosphere of air conditioning and hot water systems. Measure recommended for use with hot water systems: 1. Stored hot water temperature 60 to 65ƒC throughout the storage vessel. 2. Routine maintenance involving heating the water to 70ƒC as a precaution. 3. Changing the design of cylinders and calorifiers with concave bases. These are suspect, as the lower recesses could provide areas of reduced water temperature with little or no movement. 4. Connections to storage vessels should encourage through movement of water. 5. Pipework `dead-legs' to be minimal. 6. All pipework to be insulated to reduce water temperature losses. 7. Where secondary circulation is required, supplementary trace element heating tape should be applied to maintain a minimum water temperature of 50ƒC. 8. Showers with recessed/concave outlet roses to be avoided. Other designs to have a self-draining facility to avoid inhalation of contaminated moisture droplets. 9. Spray taps † similar provision to 8 10. cold water to be kept below 200C.