FOVF Adjustment Instruction

in
1 in service
service
FOVF ELEVATOR SUMMARY

• The FOVF elevator control system includes 3


parts mainly, LCBII board, AMCBII board and
SIEI drive 。
• The LCBII board is a logical control board
that we know well.
• The AMCBII board’s function likes the OTIS’s
MCSS board, it receives the motion signals
from LCBII and sends motion signals to SIEI
drive. It also receives the motion state from
SIEI and sends it to LCBII.

in
2 in service
service
FOVF control system
V code
ENABLE

DS code Control FWD


REV
signals SPEED
IP signals
LCBII AVY
DZ
AMCBII Encoder signals
DO
A+ 、 A- 、 B+ 、 B- EXP-
E
Exterior signals
DFC 、 INS 、 Contactors control
Communication

DRIVER FAULT
External
Brake control
RS5 signals
RS14 SE 、 INS
board

RS53
、 XRDS
ES 、 DW

DFC 、 DOL 、 DCL
1LS 、 2LS
in
3 in service
service
LCBII LED indicator
Indicator Instructions
BC On: brake energized (i.e. brake lifted) or valve opened
VLC On: 110VAC output driver okay.
GRP/J On: group function okay
Blinking: 3-phases power supply fault (internal J-relay)
NOR/diag On: normal function
Off: TCI, ERO, NAV, DTO, DTC, ATT, CHC, EFO, EFS, ISC, drive-fault

INS On: TCI or ERO operated


Blinking: TCI-Lock function active (Leave Top of Car Procedure)
ES On: Emergency Stop Button active (i.e. low voltage)
DW On: hoistway door contacts closed
DFC On: safety chain closed
DOL On: Door Open Limit (front or rear) reached
DOB On: Door Reversal Device (front or rear) is operated
DZ On: car is in door zone
RSL Blinking: Remote Serial Link and Watchdog okay

in
4 in service
service
LCBII LED indicator

Signal

LED

in
5 in service
service
Terminal Definition of AMCBII

PIN JP1 JP2 JP3 JP5 JP6 JP7 JP8 JP9


1 A- DFC 1LV V1 30V DO ( NO ) DS1 Enable

2 A+ INS 2LV V2 30V DO ( NC ) DS2 Fwd

3 B+ VF-Fault 1LS V3 0V DO ( COM ) DS3 Rev

4 B- SW 2LS V4 0V BY ( NO ) IP

5 0V BY DO 1LV COM ( 24V )

6 BY ( NO ) 2LV Speed

7 SW ( NO )

8 SW ( NO ) 0V

in
6 in service
service
Terminal Definition of AMCBII

JP2:DFC , INS
, VF-
Fault , SW , B
Y

JP9:
JP3: Enable , Fwd ,
1LV , 2LV , 1L Rev , LZ , COM
S , 2LS , Speed , Load
weight , 0V

JP7:
DO ( NO,NC,COM
), BY ( NO,NC,
COM ), SW ( N
O,COM)

in
7 in service
service
Terminal Definition of AMCBII

PIN JP1 Remark


1 A- Encoder signal A-
2 A+ Encoder signal A+
3 B+ Encoder signal B+
4 B- Encoder signal B-
5 0V

in
8 in service
service
Terminal Definition of AMCBII
PIN JP2 Remark
1 DFC Door switch signal
2 INS Inspection signal
3 VF-Fault Drive alarm signal
4 SW SW-OUT
5 BY BY-OUT

in
9 in service
service
Terminal Definition of AMCBII

PIN JP3 Remark


1 1LV Door zone signal
2 2LV Door zone signal
3 1LS
4 2LS

in
10 in service
service
Terminal Definition of AMCBII
PIN JP9 Remark

1 Enable Enable signal


2 Fwd
3 Rev
4 Not use
5 COM ( 24V )
6 Speed
7 Not use
8 0V 0V

in
11 in service
service
Function of AMCBII
C : Esc +: used to
►: increase value;
interchange move to
previous menu.
between P, F
-: used to
and monitor decrease value;
menu; used move to next
to shift bit menu.
when Enter : enter
changing the the interface of
parameters menu F and
alter
F is function menu which is used to set the basic confirmation.
parameters of AMCBII
P is position menu which is used to save the hoistway
signal from each floor, limit switches and photo-electric
switches.
Monitor menu is used to display on which floor the
elevator is and its speed.
in
12 in service
service
AMCB2---- Parameter

F Code Describe Ref. Setting Unit Remark


F0 Function Menu 0 0: Normal;
1: Enter password;
2: Change
password;
3: Analog test;
4: Shaft running;
5: Reset parameter.
F1 Acceleration 600 m/s2
F2 Deceleration 600 m/s2
F3 Acceleration T0 900 ms
F4 Acceleration T1 900 ms
F5 Acceleration T2 900 ms
F6 Acceleration T3 900 ms

in
13 in service
service
AMCB2---- Parameter

F Code Describe Ref. Setting Unit Remark


F7 Floor Number 10
F8 Rated Speed 1000 mm/s
F9 Encoder Pulses 1024 PPR
F10 Motor Rated RPM 1440 rpm
F11 Inspection Speed 250 mm/s
F12 Door Open Speed 0 mm/s
F13 Stop Speed 0 mm/s
F15 Upward Adj. 42 mm
F16 Downward Adj. 42 mm
F22 Brake Open Delay 1000 ms
F23 Brake Close Delay 1000 ms

in
14 in service
service
AMCB2---- Parameter

F Code Describe Ref. Setting Unit Remark


F24 Run Enable 0 1: Normal;
0: INS or Self-study
F25 DZ Delay 3 mm
F30 Disable LZ 0 if no DBP , set 1
P1-p32 Self-study data m
P34 1LS Distance 2.274 m
P35 2LS Distance 2.287 m
P36 Door Zone 0.250 m
P37 Distance between DZ 0.065 m

in
15 in service
service
Troubleshooting

1. When the first run, the pulley can’t move


round or the round speed is very fast. It may
be the main line from U to U,V to V,W to W
is not correct.
2. The drive alarm: Spd fbk loss; it may be the
encoder line is not correct or the line is
broken.
3. The drive alarm: brake fbk fail ;If it takes
place after the elevator run once ,it should
be to check the brake switch.

in
16 in service
service
Preparation before learn-run

1. Check the safety chain and doors chain

• Verify each safety switch of the safety chain is


available, and make sure each of them (OS, 8LS,
7LS, SOS, TES, PES, GS, DS, GSS) can stop the
elevator under the requirements of inspection
operation

in
17 in service
service
Preparation before learn-run

2. Check the hoistway signals

• Inspection run the elevator in the whole hoistway,


check the signals of 1LV, 2LV, 1LS, 2LS, etc.
• These signals can be check by enter into M1-1-2
with SVT , or by observing the status of LED in
AMCB2 board.

in
18 in service
service
Preparation before learn-run

3.Try running elevator


– Run the elevator in inspection and confirm
the car direction is same as the commanded
direction.
– If the command is up (or down) while the car
is down (or up), it shows the elevator
direction is different from the command
direction. Enter into the drive menu:

in
19 in service
service
Preparation before learn-run

TRAVEL /Speed setpoint /Speed ref src


Change “Speedref inv src” from “DOWN
cont mon” to “UP cont mon” 。

in
20 in service
service
Preparation before learn-run

Press at this menu and


scroll to choose the
right parameter. Press

to confirm

NOTE! Save config at


the “STARTUP” menu
Then the elevator should
run in right direction
in
21 in service
service
Preparation before learn-run

4.
Run the elevator in
inspection and
confirm the direction Exchange
of AMCBII is same as the pin 1
the elevator direction. and pin 2 in
If the car is running up JP1 in
(or down), while the AMCB2.
speed displayed on
AMCBII is minus (or
plus), it shows the
direction of AMCB2 is
different from the
elevator direction.

in
22 in service
service
Hoistway learn-run

1. Input password 1234 in F0

in
23 in service
service
Hoistway learn-run

2. Confirm the F24 of AMCB2 should be 0. if


not, change to 0.

in
24 in service
service
Hoistway learn-run

3. Shift the ERO and TCI to normal position. Set


the F0 of AMCBII to 4, the hoistway learn-run
will start. The car will run to bottom floor level
with low speed, and go up with inspection
speed. When the car reaches the top floor
level, the hoistway learn run accomplishes.

in
25 in service
service
Hoistway learn-run

4. Check if the F24 has change to 1


automatically. The floor table has been in
store in the P menu of AMCB2.

in
26 in service
service
Drive Main Menu

in
27 in service
service
Drive Main Menu

NOTE! Level 1 password must be set


every recycle drive supply

in
28 in service
service
SIEI----Keypad Operation

START
STOP
Shift(select the 2nd function)
Increase
Decrease
Down arrow/Help
Up arrow/Alarm
Left arrow/Escape
Enter]/[Home

in
29 in service
service
SIEI---MONITOR

• The Monitor menu


displays a series of
variables useful to check
the Drive status.

in
30 in service
service
SIEI\STARTUP\Startup config\Enter setup mode

• According to the
motor nameplate

in
31 in service
service
SIEI\STARTUP\Startup config\Mechanical data

• According to the
machine
nameplate

in
32 in service
service
SIEI\STARTUP\Startup config\BU protection

• According to the BU
resistance nameplate
• The BU resistance
15kw:27.2ohm,2.4kw;
11kw:50ohm,2kw;

in
33 in service
service
SIEI\TRAVEL\Speed profile

• Speed profile Max


linear speed=The
AMCB2 F8 Rated
Speed

in
34 in service
service
SIEI\TRAVEL\Lift sequence

• Lift sequence

in
35 in service
service
SIEI\TRAVEL\Speed reg gains

• Speed reg gains

in
36 in service
service
SIEI \ ALARM CONFIG

• These parameter must


to be affirm.

in
37 in service
service
SIEI----DO Function

DO 2

DO 3

in
38 in service
service
SIEI----DO Function

DRIVE OK

DRIVE OK

DO 0

DO 1

in
39 in service
service
Motor autotune

• Motor autotune has been done in the


factory.
• If the motor runs abnormally or the
parameters in the drive are different from
motor parameters, motor autotune should
be done in the field.
• If the parameters of motor have been
changed in the drive, redoing the autotune
is necessary.

in
40 in service
service
Motor autotune
Press “ENTER” to “ALARM CONFIG”
• Press “DOWN” to “Contact feedback”
• “ENTER” to “CNT activity”: change “disable” to “ignore”

in
41 in service
service
Motor autotune

Switch off and short the


SW-A1 to AC110V.
Short JP7-7 to JP7-8
NOTE! When power on, the
SW will close

Connect terminal 12
(Enable) to terminal 19
(+24VDC) by shorting JP9-1
to JP9-5 or pressing the up
button of ERO during
autotune

in
42 in service
service
Motor autotune

Press to this
menu

Press

in
43 in service
service
Motor autotune

Press

Press

in
44 in service
service
Motor autotune

Scroll to perform Current


Regulator Autotune procedure

Press

in
45 in service
service
Motor autotune

Press

Press

in
46 in service
service
Motor autotune

Blinking to show the


end of procedure

Press 2 times to
exit from the procedure

in
47 in service
service
Motor autotune

Press and
wait few seconds
Then press

Press to exit from


menu and the prompt
displays “Save config?”
Then press to
execute the procedure

in
48 in service
service
Motor autotune
Press “ENTER” to “ALARM CONFIG”
Press “DOWN” to “Contact feedback”
“ENTER” to “CNT activity”: change “ignore” to “disable”

in
49 in service
service
Motor autotune

• NOTE!
• Save config , and switch off power. Then
remove the Jumps.
• Autotune procedure can take different minutes to
be completed.
• Autotune can be aborted at any time by
pressing

in
50 in service
service
Check alarm in drive

When the red “Alarm” LED blinks, it is


indicating one (or more) alarm conditions

red LED alarm blinking

in
51 in service
service
Check alarm in drive
See following steps to view current alarm and reset it,
1. Press + .The “Alarm list” will be displayed.
2. Press Enter one or more times until “Sequencer”
message appears, to acknowledge the alarm

NOTE! If the alarm is still active, red LED will


blink again. If it not active, red LED will stop.

in
52 in service
service
Regulation Alarm Events

• Undervoltage: Voltage on the drive DC link is lower


than the minimum threshold for the given Mains
voltage setting.
• Spd fbk loss: A failure of the speed feedback sensor or
power supply was detected.(Encoder, Encoder line)
• Cont fbk fail: It trips when the contact (SW) feedback
signal is not detected.
• Drv overload: Drive overload accumulator exceeded
trip threshold.
• BU overload: Braking resistor overload accumulator
exceeded trip threshold.
• Overspeed: Maximum speed threshold was exceeded
while drive in RUN status.

in
53 in service
service
Ragulation Alarm Events
• Door fbk fail: It trips when the door feedback signal is
not detected.
• Brake fbk fail: It trips when the brake feedback signal
is not detected.
• Sequencer: Alarm event caused drive disable.
NOTE! Press “ ” and “ ” to check the
current fault. If there is only “Sequence” left, the detail
fault information has been in stored to “Monitor/Alarm
log”

in
54 in service
service
Ragulation Alarm Events
• NOTE!
1. The activity of some alarms have been set to
“Disable drive”, and it will happen with
“Sequence”, then the drive cannot restart.
2. We can change the activity to “Ignore” or
“Warning”. Set to “Ignore”, the alarm will be
ignored and the drive will still work.
3. Set to “Warning”, when the alarm happens, the
alarm indicator will blink while the drive will still
work.
4. Changing the activity of the drive may cause
unpredictable result. It is not recommended
except for test.
in
55 in service
service
XRDS

• Adjust the XRDS door system:


Door open speed, adjust the R2(12);
Door close speed, adjust the R1(11);
Door open jerk , adjust the R4(23,24);
Door close jerk, adjust the R4(13,14).

in
56 in service
service
THANKS !

in
57 in service