You are on page 1of 10

STEPTEST

La Forteza Epson
02-CAN02I
September 19, 2019
DMA PROFILE
02-CAN02I La Forteza Epson

DMA ID 02-CAN02I
INFLOW La Forteza Epson
INFLUENCED
La Forteza Epson
AREA
NO. OF
756
ACCOUNTS
SUPPLY 1.676 MLD
BILLED VOLUME 0.527 MLD
NRW VOLUME 1.149 MLD
NRW % 45%
MINIMUM FLOW 1.236 MLD
MINIMUM
12:00 AM – 3:00 AM
PERIOD
METER TYPE EMM
METER SIZE 150 mm
TOTAL LENGTH
2.80 km
OF MAINS
WATER BALANCE – TOP DOWN
02-CAN02I La Forteza Epson
FLOW & PRESSURE PROFILE
02-CAN02I La Forteza Epson
100.00

90.00

80.00

70.00

60.00

50.00 PRESSURE
FLOW

40.00

30.00

20.00

10.00

0.00
2:10 AM 4:22 AM 6:34 AM 8:46 AM 10:58 AM 1:10 PM 3:22 PM 5:34 PM 7:46 PM 9:58 PM
VALVE OPERATION
02-CAN02I La Forteza Epson

Step Valves

TIME TIME NO. OF


VALVE LOCATION
CLOSED OPENED TURNS
Along La Forteza Rd. corner Rd. going
SV1 1:30 AM 2:38 AM 10 1/2
to Celina Homes 1 (valve box)
Along Zabarte Rd. corner La Forteza
SV2 1:45 AM 2:35 AM 16
Rd. (manhole)
Along La Forteza Rd. near corner
SV3 2:00 AM 2:30 AM FO
Zabarte Rd. (surface box after PRV)
DAILY LEAKAGE
02-CAN02I La Forteza Epson

LOSSES LOSSES
STEP VALVE LOCATION CONNECTIONS
(liter/minute) (liter/connection/day)
Along La Forteza Rd.
corner Rd. going to
SV1 413 13.53 47.19
Celina Homes 1 (valve
box)
Along Zabarte Rd.
SV2 corner La Forteza Rd. 127 720.96 8174.61
(manhole)
Along La Forteza Rd.
near corner Zabarte
SV3 216 120.71 804.70
Rd. (surface box after
PRV)
FLOW DIAGRAM
02-CAN02I La Forteza Epson

LEGENDS:
Step 1 1 32
Step 2

Step 3

Step valve

Supply point
LOSSES
02-CAN02I La Forteza Epson

STEP PER STEP LESS CONSUMPTION NET LOSS NET LOSS


VALVE (liter/second) FOR RESIDENTIAL (liter/minute) (MLD)

SV1 0.23 0.23 -0.23 0.00

SV2 12.02 0.07 716.72 1.03

SV3 2.01 0.12 113.51 0.16

HOUR-DAY FACTOR = 21 psi/24psi x24


HDF = 21
MAP
02-CAN02I La Forteza Epson

LOSSES PER STEP

12.02 l/s

2.01 l/s

0.23 l/s

You might also like