You are on page 1of 17

GIS

CIRCUIT BREAKER
2 GIS CIRCUIT BREAKER

On completion of this lesson, the trainee will be able to:


 Identify the components of GIS Circuit Breaker and state their functions

 Describe the components and operation of the blast chamber in a GIS circuit

breaker

The three-phase circuit breaker (enclosure) arrangement is shown


in Fig.-15. The circuit breaker inside the enclosure is shown in
Fig.-16.
Fig.-16 Circuit Breaker Components
Gas Density Monitor (13170):
The gas density monitor 13170 monitors the density of the gas in the SF6 space
If the gas density falls below a permissible value, the density monitor signals
Refill Gas‘ and prevents any further operations of the breaker pole by means of
the electrical control system.
‫ة‬2‫ن القيم‬2‫ة الغاز ع‬2‫ت كثاف‬2‫ إذا انخفض‬SF6 ‫احة‬2‫ي مس‬2‫غاز ف‬2‫ة ال‬2‫ كثاف‬13170 ‫ة الغاز‬2‫ة كثاف‬2‫ب جهاز مراقب‬2‫يراق‬
‫ارة عن‬2‫ي عمليات أخرى لعمود الكس‬2‫ى غاز إعادة التعبئة ويمنع أ‬2‫ فإن مراقب الكثافة يشير إل‬، ‫ا‬2‫موح به‬2‫المس‬
.‫طريق نظام التحكم الكهربائي‬
Control system:
The control system correlates all the commands of the monitoring devices
and the operating units and directs the circuit-breaking actions. The control
system is housed in the control cabinet.
‫ يوجد نظام‬.‫يربط نظام التحكم بين جميع أوامر أجهزة المراقبة ووحدات التشغيل ويوجه إجراءات تشغيل الدائرة‬
.‫التحكم في خزانة التحكم‬
Operating Mechanism - Drive (16000):
The hydraulic operating mechanism
16000 operates the blast chambers. It
receives operating commands from the
control system.
‫ل غرف‬2‫ بتشغي‬16000 ‫ة‬2‫ل الهيدروليكي‬2‫ة التشغي‬2‫تقوم آلي‬
.‫ يتلقى أوامر التشغيل من نظام التحكم‬.‫االنفجار‬

Power supply:
The (hydraulic) power supply supplies
one or three operating mechanisms of the
three circuit-breaker poles with high-
pressure oil, depending on the type of
installation.
‫و ثالث آليات‬2‫ة أ‬2‫ي) آلي‬2‫ة (الهيدروليك‬2‫در الطاق‬2‫ر مص‬2‫يوف‬
‫ي‬222‫ت عال‬222‫ة بزي‬222‫ع الدائرة الثالث‬222‫ل ألقطاب قاط‬222‫تشغي‬
.‫ اعتمادا على نوع التركيب‬، ‫الضغط‬
2.1.1 BLAST CHAMBER

Arc-quenching principle
2.1.2 HITACHI CIRCUIT BREAKER

Fig.-18 Single Phase Reclosing Type GCB – Hitachi, 380 kV

Number Name of Part Number Name of Part


100 Interrupter Assembly 400 Control Box Assembly
200 Current Transformer 800 Framework Assembly
Assembly
300 Control Mechanism 850 Air Receiver Assembly
Assembly
Fig.-19 Internal Components of GCB – Hitachi, 380 kV
Fig.-20 Opening Principle of Interrupter
Low-Pressure Locking for Operating Air Pressure:
When the operating air pressure lowers, the pressure switch
(bellows pressure detection type) in the control cubicle operates,
closing the alarm contact and opening the control circuit at the
same time. Thus, electric control is rendered inoperative. The
equipment is provided with pressure switches which include those
for use of closing lock and alarm, opening and closing lock and
reclosing preparatory circuit lock. For alarm and locking pressure
set points of respective pressure switches and pneumatic system,
refer to the operation manual.
‫ق‬2‫ ويغل‬، ‫م‬2‫ي حجرة التحك‬2‫ط ف‬2‫ل مفتاح الضغ‬2‫ يعم‬، ‫ل‬2‫ط هواء التشغي‬2‫ض ضغ‬2‫ا ينخف‬2‫عندم‬
‫م‬22‫ل التحك‬22‫م تعطي‬22‫ يت‬، ‫ي‬22‫ وبالتال‬.‫س الوقت‬22‫ي نف‬22‫م ف‬22‫ح دائرة التحك‬22‫بيه ويفت‬22‫ال التن‬22‫اتص‬
‫ل اإلغالق‬2‫تخدام قف‬2‫ة باس‬2‫ك الخاص‬2‫ل تل‬2‫ط تشم‬2‫ح ضغ‬2‫د المعدات بمفاتي‬2‫م تزوي‬2‫ يت‬.‫الكهربائي‬
‫ى‬22‫ول عل‬22‫ للحص‬.‫ل الدائرة التحضيرية‬22‫ح واإلغالق وإعادة إغالق قف‬22‫ل الفت‬22‫ وقف‬، ‫بيه‬22‫والتن‬
.‫نقاط ضبط ضغط التنبيه والقفل لمفاتيح الضغط والنظام الهوائي المعنيين‬
SF6 gas system:
Fig.-21 shows the SF6 gas system diagram. The SF6 gas is monitored
by the gas pressure gauge (601) and gas density detector (602).

Fig.-21 Gas System Diagram


In case of gas density drop, locking and alarming are automatically
effected by the gas density detector shown in Fig.-21. The rated
pressure is 0.6 MPa.
If the pressure drops to 0.55 MPa, an alarm (for gas feed
instruction) is issued. When the pressure drops to 0.50 MPa, the
control circuit (for closing) is locked.
‫ة الغاز‬2‫ف كثاف‬2‫طة كاش‬2‫ا بواس‬2‫بيه تلقائي‬2‫ل والتن‬2‫م إجراء القف‬2‫ يت‬، ‫ة الغاز‬2‫ة انخفاض كثاف‬2‫ي حال‬2‫ف‬
‫ى‬2‫ط إل‬2‫ض الضغ‬2‫ إذا انخف‬.‫كال‬2‫ا باس‬2‫ ميج‬0.6 ‫و‬2‫ن ه‬2‫ط المقن‬2‫ الضغ‬.21- ‫ل‬2‫ي الشك‬2‫ح ف‬2‫الموض‬
‫ى‬2‫ط إل‬2‫ض الضغ‬2‫ا ينخف‬2‫ عندم‬.)‫ة الغاز‬2‫دار إنذار (لتعليمات تغذي‬2‫م إص‬2‫ يت‬، ‫كال‬2‫ا باس‬2‫ ميج‬0.55
.)‫ يتم قفل دائرة التحكم (لإلغالق‬، ‫ ميجا باسكال‬0.50