IEC 60870-5-104 Test Method

- 2021. 10 -
Communication Test Method 1 – using FreyrSCADA application

1. Read and check value with timestamp LDC DCS


(on FreyrSCADA IEC 60870-5-104 Client Simulator) IEC 60870-5-104 Client IEC 60870-5-104 Server

Ethernet TCP/IP
(IEC 60870-5-104 )

IEC 60870-5-104
Ovation Ethernet Link
Client Simulator
Controller Module
(or equivalent module to support IEC 60870-5 Interface)
2. Command to Server
• IP : Ovation ELC IP (xxx.xxx.xxx.xxx)
(Command from FreyrSCADA IEC 60870-5-104 Client Simulator and check on DCS) • Port No : 2404

Example test points for Client Example test points for server :
SIGNAL ID REMARK IEC 60870-5 Group ID

M_SP_NA_1 Monitoring Single Point M_SP_TB_1 (30)


Map
C_SC_TA_1 Command Single Point Command C_SC_TA_1 (58)

M_DP_NA_1 Monitoring Double Point M_DP_TB_1 (31)


Map
C_DC_TA_1 Command Double Command C_DC_TA_1 (59)

M_ST_NA_1 Monitoring Step Position M_ST_TB_1 (32)


Map
C_RC_TA_1 Command Regulating Step Command C_RC_TA_1 (60)

M_ME_NB_1 Monitoring Measured Scaled M_ME_TE_1 (35)


Map
C_SE_TB_1 Command Set Point Command –Scaled Value C_SE_TB_1 (62)

M_ME_NC_1 Monitoring Measured Short Float M_ME_TF_1 (36)


Map
C_SE_TC_1 Command Set Point Command – Float Value C_SE_TC_1 (63)

M_BO_NA_1 Monitoring Bitstring M_BO_TB_1 (33)


Map
C_BO_TA_1 Command Bitstring of 32bit Command C_BO_TA_1 (64)

2
Communication Test Method 2 – using KEPserverEX6 (OPC server)

LDC DCS
IEC 60870-5-104 Client IEC 60870-5-104 Server
1. Configuration on KEPserverEX6 and tag assignment
- Channel name : IEC 60870-5-104 Master
- Destination Host : Ovation ELC IP (xxx.xxx.xxx.xxx)
Ethernet TCP/IP
- Destination Port : 2404
(IEC 60870-5-104 )

KEPserverEX6
Ovation Ethernet Link
Controller Module
(or equivalent module to support IEC 60870-5 Interface)
• IP : Ovation ELC IP (xxx.xxx.xxx.xxx)
• Port No : 2404

OPC Communication
(OPC SERVER - KEPserverEX6)

2. Connect to KEPserverEX6 OPC Server by OPC quick client

(OPC CLIENT - OPC Quick Client)

3. Read/Write test on OPC quick client and DCS


(Example test point is same as previous page)

3
Communication Test Method 1 – using FreyrSCADA application

1. Read and check value with timestamp LDC DCS


(on FreyrSCADA IEC 60870-5-104 Client Simulator) IEC 60870-5-104 Client IEC 60870-5-104 Server

Ethernet TCP/IP
(IEC 60870-5-104 )

IEC 60870-5-104
Ovation Ethernet Link
Client Simulator
Controller Module
(or equivalent module to support IEC 60870-5 Interface)
2. Command to Server
• IP : Ovation ELC IP (xxx.xxx.xxx.xxx)
(Command from FreyrSCADA IEC 60870-5-104 Client Simulator and check on DCS) • Port No : 2404

Example test points for Client Example test points for server :
SIGNAL ID REMARK IEC 60870-5 Group ID

M_SP_NA_1 Monitoring Single Point M_SP_TB_1 (30)


Map
C_SC_TA_1 Command Single Point Command C_SC_TA_1 (58)

M_DP_NA_1 Monitoring Double Point M_DP_TB_1 (31)


Map
C_DC_TA_1 Command Double Command C_DC_TA_1 (59)

M_ST_NA_1 Monitoring Step Position M_ST_TB_1 (32)


Map
C_RC_TA_1 Command Regulating Step Command C_RC_TA_1 (60)

M_ME_NB_1 Monitoring Measured Scaled M_ME_TE_1 (35)


Map
C_SE_TB_1 Command Set Point Command –Scaled Value C_SE_TB_1 (62)

M_ME_NC_1 Monitoring Measured Short Float M_ME_TF_1 (36)


Map
C_SE_TC_1 Command Set Point Command – Float Value C_SE_TC_1 (63)

M_BO_NA_1 Monitoring Bitstring M_BO_TB_1 (33)


Map
C_BO_TA_1 Command Bitstring of 32bit Command C_BO_TA_1 (64)