12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

IEC 60870­5­104 : Telegram structure
The LIAN 98 manual can and may not contain the complete IEC documentation, caused by legal position. Only all knowledge that is
essential necessary for the LIAN 98 software operation is specified in parts in this manual.

Detailed information to the protocol you will find in the IEC­Standard­Documentation
<IEC 60870­5­104 : Telecontrol equipment and systems>
( English version EN 60870­5­104:2006 ).
 
Telegram format with fixed length

 
Telegram format with variable length

 
APCI Application Protocol Control Information
APDU Application Protocol Data Unit 
ASDU Application Service Data Unit

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 1/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
 
Types of control field formats

Three types of control field formats are used to perform numbered information transfer ( I­format ), numbered supervisory functions ( S­
format ) and unnumbered control functions ( U­format ).
 
I­Format ( Frame with variable length ) :

Bit 0 = 0 of the 1. octets of the control field defines the I­Format. I­Format APDUs contains always an  ASDU.

 
S­Format ( Frame with fixed lengt ) :

Bit 0 = 1 and bit 1 = 0 of the 1. octets of the control field define the S­Format. S­Format APDUs always consist of one APCI only.

 
U­Format ( Frame with fixed length ) :

Bit 0 = 1 and bit 1 = 1 of the 1. octets of the control field define the U­Format. U­Format APDUs always consist of one APCI only. Only
one function TESTFR, STOPDT or STARTDT can be active at the same time.

 
Structure of the  ASDU
 

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 2/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

 
Type identifikation ( TypeID ) :

The  TypeID  <0>  is  not  used.  The  range  of  numbers  1  to  127  is  used  for  standard  definitions  from  IEC  60870­5­101standard.  The
range 128 to 135 is reserved for routing of messages. The numbers 136 up to 255 are for special use.

The  range  of  numbers  128  up  to  255  is  private  and  not  defined  in  the  standard,  but  it  is  recommended  that  the  data  unit  identifier
fields of private ASDUs have the same format as standard ASDUs.

The  following  table  shows  the  definition  of  type  identification  numbers  for  process  and  system  information  in  monitor  and  control
direction.
 
Process information in monitoring direction :
 
1 Single point information M_SP_NA_1

2 Single point information with time tag M_SP_TA_1

3 Double point information M_DP_NA_1

4 Double point information with time tag M_DP_TA_1

5 Step position information M_ST_NA_1

6 Step position information with time tag M_ST_TA_1

7 Bit string of 32 bit M_BO_NA_1

8 Bit string of 32 bit with time tag M_BO_TA_1

9 Measured value, normalized value M_ME_NA_1

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 3/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
10 Measured value, normalized value with time tag M_ME_TA_1

11 Measured value, scaled value M_ME_NB_1

12 Measured value, scaled value with time tag M_ME_TB_1

13 Measured value, short floating point value M_ME_NC_1

14 Measured value, short floating point value with time tag M_ME_TC_1

15 Integrated totals M_IT_NA_1

16 Integrated totals with time tag M_IT_TA_1

17 Event of protection equipment with time tag M_EP_TA_1

18 Packed start events of protection equipment with time tag M_EP_TB_1

19 Packed output circuit information of protection equipment with time tag M_EP_TC_1

20 Packed single­point information with status change detection M_PS_NA_1

21 Measured value, normalized value without quality descriptor M_ME_ND_1
 
Process telegrams with long time tag ( 7 octets ) :
 
30 Single point information with time tag CP56Time2a M_SP_TB_1

31 Double point information with time tag CP56Time2a M_DP_TB_1

32 Step position information with time tag CP56Time2a M_ST_TB_1

33 Bit string of 32 bit with time tag CP56Time2a M_BO_TB_1

34 Measured value, normalized value with time tag CP56Time2a M_ME_TD_1

35 Measured value, scaled value with time tag CP56Time2a M_ME_TE_1

36 Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1

37 Integrated totals with time tag CP56Time2a M_IT_TB_1

38 Event of protection equipment with time tag CP56Time2a M_EP_TD_1

39 Packed start events of protection equipment with time tag CP56time2a M_EP_TE_1

40 Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1
 
Process information in control direction :
 
45 Single command C_SC_NA_1

46 Double command C_DC_NA_1

47 Regulating step command C_RC_NA_1

48 Setpoint command, normalized value C_SE_NA_1

49 Setpoint command, scaled value C_SE_NB_1

50 Setpoint command, short floating point value C_SE_NC_1

51 Bit string  32 bit C_BO_NA_1
 
Command telegrams with long time tag ( 7 octets ) :
 
58 Single command with time tag CP56Time2a C_SC_TA_1

59 Double command with time tag CP56Time2a C_DC_TA_1

60 Regulating step command with time tag CP56Time2a C_RC_TA_1

61 Setpoint command, normalized value with time tag CP56Time2a C_SE_TA_1
http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 4/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

62 Setpoint command, scaled value with time tag CP56Time2a C_SE_TB_1

63 Setpoint command, short floating point value with time tag CP56Time2a C_SE_TC_1

64 Bit string 32 bit with time tag CP56Time2a C_BO_TA_1
 
System information  in monitoring direction :
 
70 End of initialization M_EI_NA_1
 
System information in control direction :
 
100 (General­) Interrogation command C_IC_NA_1

101 Counter interrogation command C_CI_NA_1

102 Read command C_RD_NA_1

103 Clock synchronization command C_CS_NA_1

104 ( IEC 101 ) Test command C_TS_NB_1

105 Reset process command C_RP_NC_1

106 ( IEC 101 ) Delay acquisition command C_CD_NA_1

107 Test command with time tag CP56Time2a C_TS_TA_1


 
Parameter in control direction :
 
110 Parameter of measured value, normalized value P_ME_NA_1

111 Parameter of measured value, scaled value P_ME_NB_1

112 Parameter of measured value, short floating point value P_ME_NC_1

113 Parameter activation P_AC_NA_1


 
File transfer :
 
120 File ready F_FR_NA_1

121 Section ready F_SR_NA_1

122 Call directory, select file, call file, call section F_SC_NA_1

123 Last section, last segment F_LS_NA_1

124 Ack file, Ack section F_AF_NA_1

125 Segment F_SG_NA_1

126 Directory F_DR_TA_1

127 QueryLog – Request archive file F_SC_NB_1


 
LIAN  98  is  able  to  process  user  defined  messages  of  non  standard  types  from  127  up  to  255,  provided  they  have  the  same
general telegram format as IEC 60870­5­101/104 standard.   
 
Variable structure qualifier :

The SQ bit specifies the method of addressing of the following information objects or elements.

SQ = 0 Each  single  element  or  a  combination  of  elements  is  addressed  by  the  information  object  address.  The  ASDU  may
consist of one or more than one equal information object. The number of objects is binary coded ( number of objects )
and defines the number of the information objects.

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 5/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
SQ = 1 A sequence of equal information objects ( e.g. measured values of identical format ) is addressed by the information
object address. The information object address specifies the associated address of the first information element of the
sequence.  The  following  information  elements  are  identified  by  numbers  continuously  by  +  1  from  this  offset.  The
number  of  objects  is  binary  coded  (  number  of  elements  )  and  defines  the  number  of  the  information  elements.  In
case of a sequence of information elements only one information object per ASDU is allocated.

number objects/ = 0 : ASDU contains no information object
elements > 0 : ASDU contains one or more ( number ) information objects or elements
 
Cause of transmission ( COT ) :

The  cause  of  transmission  directs  the  ASDU  to  a  specific  application  task  (  program  )  for  processing.  ASDUs  in  control  direction  are
confirmed application services and may be mirrored in monitor direction with different causes of transmission. The value ZERO is not
used.
 
P/ N The P / N bit indicates the positive or negative confirmation of an activation requested by a primary application function.
In the case of irrelevance the P / N bit is zero.

T In addition  to  the  cause  the  test  bit  defines  ASDUs  which  were  generated  during  test  conditions.  The  test  bit  is  used
e.g. to test transmission and equipment without controlling the process.
 
...    

1 periodic, cyclic  

2 background interrogation  

3 spontaneous  

4 initialized init

5 interrogation or interrogated req

6 activation act

7 confirmation activation actcon

8 deactivation deact

9 confirmation deactivation deactcon

10 termination activation actterm

11 feedback, caused by distant command  

12 feedback, caused by local command  

13 data transmission  

...    

20 interrogated by general interrogation inrogen

21 interrogated by interrogation group 1  

22 interrogated by interrogation group 2  

23 interrogated by interrogation group 3  

24 interrogated by interrogation group 4  

25 interrogated by interrogation group 5  

26 interrogated by interrogation group 6  

27 interrogated by interrogation group 7  

28 interrogated by interrogation group 8  

29 interrogated by interrogation group 9  

30 interrogated by interrogation group 10  

31 interrogated by interrogation group 11  

32 interrogated by interrogation group 12  

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 6/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

33 interrogated by interrogation group 13  

34 interrogated by interrogation group 14  

35 interrogated by interrogation group 15  

36 interrogated by interrogation group 16  

37 interrogated by counter general interrogation  

38 interrogated by interrogation counter group 1  

39 interrogated by interrogation counter group 2  

40 interrogated by interrogation counter group 3  

41 interrogated by interrogation counter group 4  

...    

44 type­Identification unknown  

45 cause unknown  

46 ASDU address unknown  

47 Information object address unknown  

...    
 
Originator address :

The  originator  address  directs  mirrored  ASDUs  and  interrogated  ASDUs  in  monitor  direction  (  e.g.  interrogated  by  a  general
interrogation ) to the source that activated the procedure. ( in case of redundant systems ).

If  the  originator  address  is  not  used  and  there  is  more  than  one  single  source  in  a  system  defined,  the  ASDUs  in  monitor  direction
have to be directed to all relevant sources of the system. In this case the specific affected source has to select its specific ASDUs..
 
Common address of ASDU :

The common address is associated with all objects in an ASDU. The global address is a broadcast address directed to all stations of a
specific system ( broadcast address ). ASDUs with a broadcast address in control direction have to be answered in monitor direction by
the  address  that  is  the  specific  defined  common  address  (  station  address  ).  According  to  the  standard  this  parameter  consists  of  2
octets.
 
information object address :

The information object address is used as destination address in control direction and as source address in monitor direction.

The  third  octet  is  only  used  in  case  of  structuring  the  information  object  address  in  order  to  define  unambiguous  addresses  within  a
specific  system.  In  all  cases  the  maximum  number  of  different  object  addresses  is  limited  to  65  535  (  as  for  two  octets  ).  If  the
information object address is not relevant ( not used ) in some ASDUs, it is set to zero.
 

IEC 60870­5­104 : Ethernet­frame
 
Link layer ( Layer 2 )

Ethernet v.2.0 MAC Header
 

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 7/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

I/ G = 0 Individual address
I/ G = 1 Group address
U/ L = 0 Global administered address
U/ L = 1 Local administered address
 
Preamble 7 Bytes
The  preamble  is  needed,  that  the  recipient  or  recipients  (  network  card  )  synchronize  with  the
transmitter  (  network  card  )  and  therefore  the  start  frame  delimiter  and  the  following  Ethernet  data
frame can be interpreted correctly.

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 8/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
These fields are not forwarded to the software by the network card !

Start Frame Delimiter Start Frame Delimiter is 1 octet long and is the sequence 10101011 binary.
It immediately follows the preamble pattern and indicates the start of a frame.

This field is not forwarded to the software by the network card !

Destination address Receiver address for which the frame is intended.

Source address Identifies the station from which the frame is initiated.

Ethernet Internet Protocol ( IPv4 ) = 0800 HEX
Length­ / Type Field
For  IEC  60870­5­104  this  field  is  used  as  type  field  with  a  fixed  value  of  0800  HEX.  This  field
indicates the nature of the MAC client protocol ( IPv4 ).

MAC Client Data The data consist of :
. IPv4 header
. TCP header
. User data IEC 60870­5­104

. PAD fields ( Trailer ), if available

The  client  data  must  have  a  minimum  length,  so  that  the  Ethernet  data  frames  starting  with  the
destination address and including the trailer, has a minimum frame length of 60 bytes. If the frame
length is less than 60 bytes, the client data have to be filled with PAD fields (  padding  bits  )  up  to
the required minimum length. This will be done automatically by the network card.

Frame Check Sequence 4 Bytes
The  content  of  the  Ethernet  data  frames  starting  with  the  destination  address  and  including  the
client  data  is  secured  with  a  block  checksum.  The  receiver  (  network  card  )  recognizes  therefore
each transmission failure.

These fields are not forwarded to the software by the network card !
 
Netzwork Layer ( Layer 3 )
 
IPv4 Header

For more detailed information about the  I P v4   header, check the document RFC 791 "Internet Protocol" on the IETF Website. <RFC
791 : Internet Protocol>.
 

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 9/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

 
Version Internet Protocol Version = 4 ( IPv4 ), see [ RFC 791 ].
This field indicates the format of the IP header and has a fixed value of 4 for IPv4.

IHL The Internet Header Length is the length of the IP header counted in double words ( 32 bit
units ), and thus points to the beginning of the data area. The minimum value for a correct
header is 5 ( = 20 bytes ).

Type of service The  type  of  service  describes  the  indication  of  the  abstract  parameters  of  the  desired
service.  These  parameters  are  used  in  order  to  indicate  the  selection  of  the  actual  service
bit 0 : reserved parameters  when  transmitting  a  datagram  through  a  particular  network.  Several  networks
bit 1 : reserved offer service precedence, which somehow treats high precedence traffic as more important
bit 2 : R ( Reliability ) than other traffic ( generally by accepting only traffic above a certain precedence at time of
bit 3 : T ( Throughput ) high load ). The major choice is a three way tradeoff between low­delay, high­reliability, and

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 10/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
bit 4 : D ( Delay ) high­throughput.
bit 5 ­ 7 : PRECEDENCE
R : 0 = normal Reliability,  1 = high Reliability
T : 0 = normal Throughput, 1 = high Throughput
D : 0 =normal Delay, 1 = low delay

Total length Total  Length  is  the  length  of  the  datagram,  measured  in  octets,  including  internet  header
and data.

Identification An  identifying  value  assigned  by  the  sender  in  order  to  indicate  to  which  datagram  the
fragments are allocated.

Flags Various control flags

Bit 5 : MF ( more fragments ) MF : 0 = last fragment, 1 = more fragments
Bit 6 : DF ( don't fragment ) DF : 0 = may fragmented, 1 = don't fragment
Bit 7 : reserved, must be 0

Fragment offset This  field  indicates  where  in  the  datagram  this  fragment  is  placed.  The  fragment  offset  is
measured in units of 8 octets ( 64 bits ). The first fragment has offset zero.

Time to live This  field  indicates  the  maximum  time  the  datagram  is  allowed  to  remain  in  the  internet
system. If this field contains the value zero, then the datagram must be destroyed. This field
is  modified  in  internet  header  processing.  The  time  is  measured  in  units  of  seconds,  but
since every module that processes a datagram must decrease the TTL by at least one even
if it processes the datagram in less than a second.

Protocol Transmission Control Protocol = 6 ( TCP ), see [ RFC 793 ].
This field indicates the next level protocol used in the data portion of the internet datagram
and has a fixed value of 6 for TCP ( Transmission Control Protocol ).

Header checksum The checksum is only valid for the header. Since some header fields change ( e.g. time to
live ) the checksum has to be new calculated after each pass through the rooter.

Source address This parameter identifies the IP address of the transmitting host. ( Sender )

Destinatin address This parameter defines the IP­address of the receiving host ( Receiver )

Options ( variable ) The option field is variable in length
Options  may  appear  or  not  in  datagrams.  They  must  be  implemented  by  all  IP  modules  (
host  and  gateways  ).  Optional  is  their  transmission  in  any  particular  datagram,  not  their
implementation. In some environments the security option may be required in all datagrams.

Padding ( variable ) The padding field is variable in length
The  internet  header  padding  is  used  to  ensure  that  the  internet  header  ends  on  a  32  bit
boundary. The padding is composed of zeros.
 
Transport layer ( layer 4 )
 
TCP Header

For more detailed information about the TCP Header please read on the IETF Website
the document <RFC 793 : Transmission Control Protocol>.
 

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 11/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure

 
Source port Identifies the PORT from which the frame is initiated.

Destination port Destination PORT for which the frame is intended.

Sequence number The  sequence  number  of  the  first  data  octet  in  this  segment,  except  the  SYN  bit  is  set.  If
SYN  is  present  the  sequence  number  is  the  initial  sequence  number  (  ISN  )  and  the  first
data octet is ISN + 1.

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 12/13
12/25/2014 LIAN 98(en) : Protocol IEC 60870­5­104, Telegram structure
Acknowledgement number If  the  ACK  control  bit  is  set  this  field  contains  the  value  of  the  next  sequence  number  the
sender of the segment is expecting to receive. As soon as a connection is established this
is always sent.

Data offset The  number  of  double  words  (  32  bit  units  )  in  the  TCP  Header.  This  indicates  where  the
data begin. The TCP header ( even one including options ) is an integral number of 32 bits
long.

reserved Reserved for later use and must be zero.

Control field URG : Urgent Pointer
ACK : Acknowledgment
PSH : Push function
RST : Reset the connection
SYN : Synchronize sequence numbers
FIN  : No more data from the sender

Window The  number  of  data  octets  beginning  with  the  one  indicated  in  the  acknowledgment  field
which the sender of this segment is willing to accept.

Checksum The  checksum  is  used  for  all  16  bit  units  in  the  header  and  in  the  data.  If  a  segment
contains  un  odd  number  of  header­  and  data  bytes  to  be  checked,  the  last  byte  on  the
right is replenished  with  noughts  in  order  to  built  a  16  bit  word  for  the  check.  The  block  is
not  transmitted  as  part  of  the  segment.  The  check  field  itself  is  replenished  with  nougths
while the checksum is calculated.

Urgent pointer This  field  transmits  the  current  value  of  the  urgent  pointer  as  a  positive  offset  from  the
sequence  number  in  this  segment.  The  urgent  pointer  points  to  the  sequence  number  of
the octet following the urgent data. This field is only interpreted in segments with the URG
control bit set.

Options ( variable ) The option field is of variable length.
Options  may  occupy  space  at  the  end  of  the  TCP  header  and  are  a  multiple  of  octets  in
length.  All  options  are  included  in  the  checksum.  An  option  may  begin  on  any  octet
boundary.

Padding ( variable ) The padding field is of variable length.
The TCP header padding is used to ensure that the TCP header ends and data begins on
a 32 bit boundary. The padding character is always zero.
 
User data IEC 60870­5­101/ 104 Data frames
 
 
MAY R  S oftw a re Wu e rzb u rg e r  Rin g   3 9 ,     D  9 1 0 5 6   E rla n g e n Ma nua l   LI AN  9 8
LIAN 98 Protocol Router, Simulator and Analyzer
© Copyright 2001, 2006, 2011 by Werner Mayr. All Rights reserved.

http://manuals.lian98.biz/doc.en/html/u_iec104_struct.htm 13/13