You are on page 1of 4

ABB

Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT
LTB145D1/B
FSA1

Page 1 of 4

Order No:
Serial No:

KD3000706/30
1HSB01408076

Customer
LTL PROJECTS (PTY) LTD
Customer reference
NEPTDP LOTA/O/13-15 REV1

Country
SRI LANKA

Standard
IEC 62271-100

Test completed
2014-04-04
Serial number

ABB reference

Project

Circuit breaker
LTB145D1/B

1HSB01408076

KD3000706/30

K10007490

Mechanism
FSA1

1HSB01408076-A1

KD3000706/30

K10007490

This report concerns testing of a separate breaker pole(s). The purpose of the testing is to control
function, tightness etc. After assembly of this pole(s) with the operating mechanism a function test shall
be performed. At this test operating times etc. according to document "functional values" for the actual
breaker must be checked.
We hereby certify that the above objects have passed all routine tests in accordance with the standard
referred to in above and with the terms of the contract.

ABB AB
High Voltage Products/Circuit Breakers
Quality

Date: 2014-04-04
Per Lindholm

Test witnessed by

...........................................................

.............................................................

...........................................................

.............................................................

...........................................................

ABB AB
Postal address:
ABB AB
High Voltage Products
SE-771 80 Ludvika, Sweden

Visiting address:
Lyviksvgen 4

Telephone:
0240-78 20 00
+46 240 78 20 00

Telefax:
0240-78 32 20
+46 240 78 32 20

Bank details:
223-1686

VAT No.:
SE556029702901
Registered office: Ludvika

ABB

ROUTINE
TEST REPORT

Circuit Breaker
Mechanism:

Page 2 of 4

LTB145D1/B
FSA1

Order No:
Serial No:

KD3000706/30
1HSB01408076

Rated data
Rated filling pressure for operation:

0,70

MPa(abs)

Check of rating plates

Approved: -

POLE RESULTS
Resistance in main circuit
Phase
A
B
C

Unit
Ohm
Ohm
Ohm

Part 1
38
0
0

Part 2

Part 3

Part 4

Approved: Q7

Power frequency test performed at 0,60 MPa(abs)


60 seconds 50 Hz breaking unit
60 seconds 50 Hz to earth:

275 kV
275 / kV

Approved: Q7
Approved: Q7

1,15 MPa(abs)

Approved: Q7

Overpressure test on each pole


10 minutes duration

Tightness test on each pole

Approved: Q7

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT
LTB145D1/B
FSA1

Test Samples
Technical provision: 1HSB425452-41 REV.F
Fill pressure:
0,70 MPa(abs)

Page 3 of 4

Order No:
Serial No:

KD3000706/30
1HSB01408076

ABB
Circuit Breaker
Mechanism:

ROUTINE
TEST REPORT
LTB145D1/B
FSA1

Page 4 of 4

Order No:
Serial No:

KD3000706/30
1HSB01408076