Substation earthing is required for safety of operating staff and
protection equipments. Earthing of power system and earthing of
equipments are two form of earthing. Connection of the non-current carrying metallic enclosures and parts of electrical equipment to ground is equipment earthing. In Equipment earthing, non-current carrying metallic parts of Transformer tank, Switch gear box, support structure, operating rods of isolators, etc. are connected to the general mass of the earth. Equipment Earthing is for human safety. System grounding implies connection of current carrying transformer neutral in a star-connection or one end of LA or isolator to general mass of the earth. System Grounding is for equipment safety. System Earthing limit rise in magnitude of line to line transient voltage and lightning over voltages. Effective earthing reduces operation & maintenance cost and improves service reliability. The interconnection of system earthing and safety earthing is a common practice in a substation. Earth resistance of 33 KV substation with earth pits must be below to 2 ohm else necessary arrangements are made to improve the same. Earthing in PS provide a low resistance path to flow of electric fault current to the ground. Earth wires and electrodes are designed to withstand and dissipate repeated faults and surge currents and ensure safety of persons and equipments.
Earthing grids are adopted at Generating
Stations and Substations for effective safe functioning. Earthing grid is a system of a number of interconnected, horizontal bare conductors buried in the earth, providing a common ground for electrical devices and metallic structures. OBJECTIVE OF EARTHING Earthing system provides nearly zero potential surface in and around the substation area where the electrical equipment is installed or erected. The Earthing System is designed to limits rise of potential on metallic supports during occurrence of abnormal conditions or insulation failure. Earthing avoid danger of shock to persons in both normal and abnormal conditions. In case of a fault directly to earth, Earth Fault Current will flow back to its source (i.e. the Primary substation). Earthing provides a low impedance path to fault currents to ensure prompt and consistent operation of protective devices during ground faults. When electricity is generated remotely and earth becomes a return path for faults current. During the passage of Earth Fault Current, buried Earth Electrode will be subjected to a rise in voltage. This is called Earth Potential Rise (EPR) and is dependent on the magnitude of Earth Fault Current and Earth Electrode Resistance. Potential gradients develop in the surrounding ground area and these are highest adjacent to the Earth Electrode. High EPR can produce dangerous touch and step ground potential . Touch Voltage (E touch) is the potential difference between a ground metallic structure and a point on the earth‘s surface separated by a distance equal to the normal maximum horizontal reach of a person, approximately one meter. Step Voltage (E step) is the potential difference between two points on the earth's surface separated by distance of one pace that will be assumed to be one meter in the direction of maximum potential gradient. If an earthed metallic structure is accessible, a person standing on the ground and touching the structure will be subject to a Touch Potential. The maximum permissible value of touch potential is 233V, based on fibrillation limits, immobilization or falls/muscular contractions could occur at lower voltages. The maximum Step Potential will be experienced by a person who has one foot on the ground of maximum EPR and other foot one step towards true earth. Due to additional insulation of shoes in feet safe permissible limits for Step Potential 17.5 kV, are usually much higher than limits for Touch Potential. Installation of multiple earth electrodes buried at a relatively shallow depth around the perimeter of substation significantly reduces touch & step potential. In substations costly but efficient strips mesh grid is used for earthing. When several earth electrodes embedded inside the soil are interlinked by earth mat running nearby, the increased contact area results very low earth resistance of combined earth grid. Earth electrodes are connected for dissipation of earth fault currents (1s short time current rating is 31.5 KA) and to reduce the overall substation earthing resistance less than 1ohm. For earth mat, trenches are excavated of size 75cm depth and 30 cm width. The sub-station site including the fence is segregated at intervals, of say five meters width along with length and breadth wise. Trenches extend over the entire switchyard in longitudinal and transverse sections with 5 m spacing. It is preferable to extend the mat beyond the fence for about one meter that fence can also be suitably earthed and made safe for touching. The earthing electrodes of sufficient number and size pipes or rods (as per fault current and substation layout) are placed at the bottom of these trenches in earth pits. Earth pits are excavated of size 75cmx75cmx3m. Earth electrodes of 2.75m length either CI pipe of diameter 125mm and 9.5mm thickness or Copper clad solid MS rod of 32mm is buried vertically in the pits at all peripheral corners and other selected positions. Lightening arrestors, transformer neutrals etc. are provided with separate individual earth electrodes in pits near them for earthing. Distance between two adjacent pipe electrodes preferably is more than twice of the length of the electrode. Top of grounding electrode is welded to clamp and clamp is welded to the ground mat. Earth pit is back filled with Bentonite compound and Black cotton soil a ratio of 1:6, around electrode in 300 mm diameter and entire depth. Earth mat of MS flat of size either 75x8 mm or 50 x 6 is buried horizontally in tranches as per layout. As location of equipment is fixed in plan, the intervals in earth mat are also arranged to pass it nearby equipment location to facilitate easy interlinking. Normally the earth mat is buried at a depth of about 0.5 meter below the ground surface with ground electrodes at suitable points. All the crossing and joints are solid braced by bolting or welding or brazing. Trenches are then back filled by Bentonite compound with uniform fine Black cotton soil a mixture of 1:6 ratio up to 100 mm over the earth mat.
The remaining earth trench is to be back
filled with the soil. After the completion of earth mat, the earth resistance is measured. If earth resistance is more than one ohm the earth mat shall be extended by installing extra electrodes. Tap connections or Earth risers from earthing grid for the earth bonding of equipment /structure are taken up. Risers taken along the main switchyard structures and equipment structures (up to their top) are clamped to the structures. All the junctions of the earth mat steel flats are properly bolted or welded with suitable overlapped angle pieces. All paint, enamel, grease, rust, dirt and scale is removed from surface of contact on metal surface before making connection. Earth Mat or Grid in a Substation involves inter linking of all earth Electrodes inside the soil. This interlinking of electrodes increases the area in contact with soil and creates number of parallel paths for effective low resistance earthing. All non-current carrying parts and strategic system points at substation are connected to this earth grid. This earthing ensure that under fault conditions, none of these parts of substation are at a higher potential than the grounding grid. Earthing of equipment’s to the earth mat with 50 x 6 MS flat is as follows: 1. Power transformers: The transformer body or tank is directly connected to main earth grid. The transformer track rail should be earthed separately by bonding at each end of the track. Twin neutral earthing is done to Power Transformer. The star winding neutral point of transformer is directly connected to an independent earth electrode by MS flat of size 75 x 8mm. Earth electrode is again connected to the Earth mat. The second neutral is directly connected to the earth mat. When the fault current is expected to be low and not likely to cause damage to plant, equipments, cables and loss of stability of system, the solid earthing may be done directly through metallic conductor from system neutral to the main earthing ring without any impedance Use of platein the circuit. is recommended for electrode higher current carrying capacity i.e. generating stations and major substations. But in 33/11 transformer earthing pipe or rod earthing electrodes are generally used. Electrode of B class G.I rod of minimum internal diameter 38mm and length 2.75 m are embedded vertically in ground. Neutral of 33/11 KV transformer is earthed with 21.1 ohm NER to limit earth fault current to 300Ampst and its damage to transformer. 2. Potential and current transformers: The base supporting structures of Current Transformer and Potential Transformer are to be earthed. All bolted cover plates of the bushing are also connected to the earthing mat by means of two separate distinct connections made with MS flat of size 50 x 6 mm. One connection is made with the nearest longitudinal conductor, while the other is made to the nearest transverse conductor of the mat. 3. Lightning arresters: Base terminals of all LAs are earthed with short and straight conductors to ensure minimum impedance. Each L.A. has individual earth electrode, which are in turn connected to earth grid. Earth conductors of the lightning protection system shall not be connected with the conductors of the other safety earthing system above ground level or run inside G.I. conduits. 4. Circuit breakers: For every breaker there will be five earth connections to the earth mat with MS flat 50x6mm size (i) breaker body (ii) relay panel (iii) CTs of the breaker (iv) Two side of the breaker structure. 5. Other equipment’s: All equipment metallic enclosures and frame work of switches and isolators and other non-current carrying parts in the substation are earthed by two separate connections. Handle of the operating pipe of isolators is connected to earthing mat by means of two separate distinct connections made with MS flat. One connection is made with the nearest longitudinal conductor, while the other is made to the nearest transverse conductor of the mat. 5. Other equipment’s: A separate earthing conductor shall be provided for earthing lighting fixtures, lighting poles, receptacles, switches, junction boxes, lighting conduits, etc. Metallic sheaths and armour of all multi core power cables and cable boxes/glands, lockout switches etc. are connected to the earthing conductor and earthing grid conductor at both equipment and switchgear end. Cable (11 x 33KV) sheaths are earthed with 25 x 3 GI strip to Earth mat. 5. Other equipment’s: The neutral of the station transformer is to be connected to the Earth mat directly with 25 x 3 GI strip. The body of the Station transformer two sides to be connected to the earth mat with 25 x 3 GI strip. Earthing at Control and Relay Panel is also done from a frame earth bar of provided near the base. The frame earth bar shall in turn be connected to the earth grid by an earthing conductor. 75 x 8 MS flat is to be laid around the control room from main earth. Panels of the VC breakers, midpoint of the Battery and Battery stand structures are earthed to the earth flat in control room. 6. Fences: The station fence can be connected to the station ground or grounded separately. Gates and support are also earthed through an earth rod. 7. Ground wires: The ground wires over the station are connected to the station earth. In order that the station earth potentials during fault conditions are not applied to transmission line ground wires and towers, all ground wires coming to the stations shall be broken or insulated on the first tower external to station by means of strain disc insulators. The resistivity of soil for earthing system depends upon the following factors: 1. Type of soil and its moisture content 2. Chemical composition and concentration of dissolved salt 3. Grain size and distribution of grain size 4. Size and spacing of earth electrodes Resistivity is least (500-5000 ohm cm) for Loamy garden soil and clay. Resistivity increases for sand, slate, stone and crystalline rocks. When the earth resistance is high, even the multiple electrodes in large number may also fail to produce low resistance to earth. To reduce the resistivity of soil immediately surrounding the electrode some salt substances are made available as a solution with water. The substances salt sodium chloride (NaCl), Calcium chloride (CaCl2), Sodium carbonate (Na2CO3), copper sulphate (CuSO4) and soft cock and charcoal in suitable proportion are used. Economic practice is to treat the soil around the ground electrode with alternate layers of common salt and charcoal. Bentonite is a clay with excellent electrical properties. It absorbs and retains water over a long period. Bentonite suspension in water when used to surround the earth electrode virtually increases the electrode surface area and maintain low earth resistance, even during the summer months. Fly ash from thermal stations can also be used for the electrical installations in areas of high ground resistivity as a chemical treatment material to reduce soil resistivity. On the ground surface near pole structure a layer of crushed rock is used. Advantages It provides high resistivity surface layer. It serves as impediment to the movement of reptiles and thereby helps in minimizing the hazards which can be caused by them. It discourages the growth of weeds. It helps retention of moisture on the underlying soil and thus helps in maintaining the resistivity of the subsoil at lower value. It discourages running or wider footsteps of persons in the switch yard and saves them from the risk of high step potentials.