Compatibility
The new Zio TR71 and Zio Plus TR75 have functionality that is only
available when using the new Spyder tool, and the new Spyder tool can
only be used with the latest firmware versions of Spyder. See the chart
below, and view the training presentation on the Spyder Re-Flash Tool
for more info.
HONEYWELL - CONFIDENTIAL
Zio Address Dial & Wire Terminals
Four Terminals
1 and 2 for network jack (optional)
HONEYWELL - CONFIDENTIAL
Zio Wiring
• Polarity insensitive
• 22 AWG, unshielded, twisted pair,
solid wire recommended (smaller
wire makes it easier to land two
wires into one terminal).
• 18-24 AWG allowed depending on
application
• 200 ft max on Sylk bus
• Twisted pair recommended for wire
runs longer than 100 ft
• Can use home run or daisy chain
wiring for multiple Zios. If wire size
is too thick for two wires in the
terminal, use pigtails as shown.
HONEYWELL - CONFIDENTIAL
Configuring Zio
HONEYWELL - CONFIDENTIAL
Add a Network and a Spyder
HONEYWELL - CONFIDENTIAL
Add a Wall Module to Spyder
HONEYWELL - CONFIDENTIAL
SBusWallModule To Spyder Control Program
0 HONEYWELL - CONFIDENTIAL
SBus WM Block imbedded in VAV App
1 HONEYWELL - CONFIDENTIAL
General Settings
2 HONEYWELL - CONFIDENTIAL
Zio Parameter Screens
• Network parameters can be configured in the Configuration
Wizard
3 HONEYWELL - CONFIDENTIAL
Categories and Parameters
4 HONEYWELL - CONFIDENTIAL
Categories and Parameters
Click to add a
parameter or
category, and click
EDIT to customize.
Any screen
showing this
parameter can be
customized by
highlighted the pre-
defined fields in the
green screen at the
lower right.
5 HONEYWELL - CONFIDENTIAL
Categories and Parameters
6 HONEYWELL - CONFIDENTIAL
Zio Customizable Home Screens
• Multiple home screens can be saved to Zio with one set as the default
• From the Home screen, the Tenant can
- Change the setpoint, fan speed and/or initiate override, if configured
- View or view/change other parameters using the View More key if desired, if
configured
8 HONEYWELL - CONFIDENTIAL
Home Screen Options
9 HONEYWELL - CONFIDENTIAL
Occupancy and Override
Customize the
occupancy and
override in this tab.
The valid states
chosen will show
up when the user
presses the
override button on
Zio.
0 HONEYWELL - CONFIDENTIAL
Occupancy and Override
Clicking settings
will allow you to
choose the network
bypass time, or
customize the time
period yourself.
When a user
presses override,
they will see the
minimum time first,
and they can
increment up to the
maximum override
time if desired.
1 HONEYWELL - CONFIDENTIAL
Fan Command
2 HONEYWELL - CONFIDENTIAL
System Status and Command
The system
command can also
now be set up as a
network setpoint,
like the fan
command. Clicking
Show System
Status brings up
the system modes
on the top of the
screen, as shown
below.
3 HONEYWELL - CONFIDENTIAL
System Status and Command
4 HONEYWELL - CONFIDENTIAL
Memory Usage Window
6 HONEYWELL - CONFIDENTIAL
Password
7 HONEYWELL - CONFIDENTIAL
Preview – Tenant View
8 HONEYWELL - CONFIDENTIAL
Finish Zio Configuration
3. Click Finish
9 HONEYWELL - CONFIDENTIAL
Access Zio Contractor Mode
• Accessing Contractor Mode at the Zio
- Enter and exit the contractor mode by pressing Up, Down, and Middle
softkey, then enter the password if password protected
- In the contractor mode, you can choose the home screen, select parameter
access to tenant (Yes or No as desired), and view/change parameters.
0 HONEYWELL - CONFIDENTIAL
Scheduling at the Zio Wall Module
The Spyder schedule is easily accessible on the Zio Plus
TR75 Wall Module
• You can access either in the tenant mode (if
unrestricted) and/or contractor mode.
• Set each daily time period or event (labeled E1-E4) to
occupied, unoccupied, or standby, each with it’s own
start time.
• The Zio Plus gives you access to the Schedule that
resides in the Spyder. Access to the network schedule
from the Zio is not currently supported.
1 HONEYWELL - CONFIDENTIAL
Additional Resources
customer.honeywell.com