Professional Documents
Culture Documents
CALCULATION
PART 1
PREPARED BY:
ELE 103: ELECTRICAL SYSTEM JESSMAR U. BONGOLTO
AND ILLUMINATION MAR JOHN L. BAGUHIN
Lesson Objectives:
1. Explain what is mean by ampacity
IMPORTANT
• To ensure that the ampacity of a wire or cable is sufficient for
the electrical load it will be carrying, in order to avoid
overheating, damage, or safety hazards.
This table applies to conductors installed in free air or directly buried in earth. It is commonly used in
commercial and industrial electrical installations to ensure that the conductors will not overheat and cause
a fire or damage equipment.
Table 310.15(B)19
This table provides ampacity
values for conductors based on
their size, temperature rating,
and the type of insulation used.
It is used to ensure that the conductors are able to safely carry the current load
without overheating.
Table 310.15(B)20
Used to determine the ampacity of
conductors for branch circuits and
feeders.
Note#1
The asterisk (*) next to the ambient temperature of 30°C (86°F) included in table
description at the top of the table, Refer to table 310.15(B)(2) for application of
the ampacity correction factors where the ambient temperature is other than 30°C
(86°F).
Note#2
The asterisk (**) next to wire sizes 10, 12, and 14 AWG refers to article 240.4(D)
and is letting you know that conductor sizes #14, #12, and #10 copper and
aluminum are limited to certain size overcurrent protection devices (OCPD) even if
the ampacity of the #14, #12, and #10 conductor is higher. The limitations are:
A- For Copper Conductors:
• #14 copper limited to 15-amp OCPD
• #12 copper limited to 20-amp OCPD
• #10 copper limited to 30-amp OCPD
Note#3
Ampacity tables, particularly Table 310.15(B)(16), do not consider all the many
factors affecting ampacity.
If loads are not calculated in accordance with the requirements of Article 220, the table ampacities, even when corrected in
accordance with ambient correction factors and the notes to the tables, might be too high. Especially where many cables or
raceways are routed close to one another underground.
Note#4
Copper conductors of the same size have three different allowable ampacities. The
same is true for aluminum (and copper-clad aluminum) conductors. This is because
the maximum allowable ampacities depend on the conductor’s temperature rating.
Example
A 3 AWG copper conductor with a temperature rating of 60°C has a
maximum allowable ampacity of 85 amperes (A). The maximum allowable ampacity
of the same 3 AWG copper conductor with a temperature rating of 75°C is 100A. If
the temperature rating of the 3 AWG copper conductor is 90°C, the allowable
ampacity is 115A.
Note#3
Ampacity tables, particularly Table 310.15(B)(16), do not consider all the many
factors affecting ampacity.
If loads are not calculated in accordance with the requirements of Article 220, the table ampacities, even when corrected in
accordance with ambient correction factors and the notes to the tables, might be too high. Especially where many cables or
raceways are routed close to one another underground.
Note#4
Copper conductors of the same size have three different allowable ampacities. The
same is true for aluminum (and copper-clad aluminum) conductors. This is because
the maximum allowable ampacities depend on the conductor’s temperature rating.
Example
A 3 AWG copper conductor with a temperature rating of 60°C has a
maximum allowable ampacity of 85 amperes (A). The maximum allowable ampacity
of the same 3 AWG copper conductor with a temperature rating of 75°C is 100A. If
the temperature rating of the 3 AWG copper conductor is 90°C, the allowable
ampacity is 115A.
Note#5
All The Allowable Ampacities Tables refer to table 310.104(A) (see above image)
which contains information about conductors rated 600V. Conductor information in
this table includes trade name, type letter, maximum operating temperature,
application provisions, insulation, thickness of insulation, and outer covering (if
any).
Note#6: Conductor Lettering
Allowable ampacity tables specify the wiring properties that are applicable for each temperature category listed in
the table.
The letters on wiring, such as THHN or THW, indicate specific properties of the wire or insulation. These letters are used
in allowable ampacity tables and help identify the wire's suitability for specific applications.
NOTE:
The general rule is that a conductor
rated as 75°C can be used with
devices rated up to 75°C. However,
there are exceptions such as THW
which can be used with ballasts in
dry locations at 90°C.
Examples for Conductor Lettering:
• TW - Thermoplastic (T) insulation, (W) suitable for wet and dry locations (When suitable for wet generally means it can be
used for dry also) and is rated 60° C (no H in group).
• RHW - Rubber (R) insulation, (H) rated 75° C and (W) suitable for wet and dry locations.
• TF - Thermoplastic (T) insulation, (F) fixture wire
• RFH – Rubber (R) insulation, (F) fixture wire, (H) rated 75° C
Example, if we have a multi-conductor cable with three 6 AWG Type THWN copper installed in a raceway in
free air based on an ambient air temperature of 30° C (86° F), which table we will use; TABLE B.310.15(B)(2)
(1) or TABLE B.310.15(B)(2)(3)?
Yes, it is table B.310.15(B)(2)(1), because tables TABLE B.310.15(B)(2)(3) don’t be used with the following:
Now, move to the right in the 6AWG row until you reach the column for THWN insulation for a copper
conductor. This will be the 75° C (167° F) column.
Step#4: Now read the amapcity of the conductor, you should read 58.
"MUCH BETTER JUD ANG OVERHEAD " DANGIN
www.reallygreatsite.com
ELE 103: ELECTRICAL SYSTEM AND ILLUMINATION 00