AUTOMATIC AIR
RELIEF VALVE
FHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
OHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
WORKING PRESSURE = 7 Kg / CM 2 FIRE PUMP CAPACITY
SFP = 1900 L / M
OHB = 4.5 Kg / CM2
DFP = 1900 L / M
JP DFP SFD
JP = 200 L / M
FIRE HYDRANT SYSTEM SCHEMATIC DIAGRAM
FIRE PROTECTION PUMP STATION
***OPERATION SEQUENCE***
JOCKEY ELECTRIC PUMP (JP)
PUMP CAPACITY : 200 L / M
MOTOR POWER : 5.5 KW / 380V / 3P
********OPERATION SEQUENCE********
EFP PUMP “ON” : 6 Kg/Cm2
DFP
PUMP “OFF” : 8 Kg/Cm2
JP
ELECTRIC FIRE PUMP (EFP)
PUMP CAPACITY : 1900 L / M
MOTOR POWER : 55 KW / 380V / 3P
******OPERATION SEQUENCE*******
PUMP “ON” : 5 Kg/Cm2 ( AUTOMATIC )
PUMP “OFF” : DONE MANUALLY
DIESEL FIRE PUMP (DFP)
PUMP CAPACITY : 1900 L / M
PUMP ROOM AREA MOTOR POWER : 55 KW / 380V / 3P
*******OPERATION SEQUENCE*******
PUMP “ON” : 4 Kg/Cm2 ( AUTOMATIC )
PUMP “OFF” : DONE MANUALLY
FIRE PTROTECTION PIPE INSTALLATION
Branch Sprinkler Pipe Main Line Pipe
Automatic Air Relief Valve Fire Pump
FIRE PROTECTION ACCESORIES
Gate Valve Alarm Gong
Rotary Lamp Alarm Bell
FIRE PROTECTION ACCESORIES
Engine
Jockey Main pump
pump pump
Pressure Swicth Pressure Gauge
Head Sprinkler Drain Valve
FIRE PROTECTION ACCESORIES
Engine pump fuel tank Panel Fire Control
Pressure Gauge Fire pump engine panel
FIRE PROTECTION ACCESORIES
Buterfly Valve
Floating Valve
Pressure Gauge Alarm Bell
HYDRANT BOX INDOOR & OUTDOOR TYPE
Indoor Fire Hydrant Box FHB hose and valve
Outdoor Fire Hydrant Box Outdoor Fire Hydrant Box
INDOOR FIRE HYDRANT BOX TYPE
Wall type Indoor FHB Wall type Indoor FHB hose & valve
Indoor Fire hydrant box Indoor FHB hose & valve
DKI FIRE SIMULATION EXERCISE AT SIAMESE CONNECTION
Outdoor Fire Hydrant Box
Siamesse Connection
DKI Fire simulation team
FIRE PUMP CONTROL PANEL
PP - UTILITY INSIDE PP - UTILITY
FIRE HYDRANT PANEL INSIDE FIRE HYDRANT PANEL
FIRE EXTINGUSHER / APAR
• APAR (Alat Pemadam Api Ringan )
• TYPE : ABC POWDER
• CAPACITY : 2.50 Kg
• APAR (Alat Pemadam Api Ringan )
• TYPE : CO
• CAPACITY : 4 Kg AND 6 Kg
FIRE PROTECTION SYSTEM
( OPERATION PROCEDURE)
Dalam rancangan pembuatan gedung kantor & gudang di kumon indonesia education untuk memproteksi
gedung dari bahaya kebakaran di dalam gedung telah tersedia installasi System pemadam api yaitu :