Professional Documents
Culture Documents
Materials of Construction
AGENCY STANDARD
UL & c-UL (ULC) NFPA & UL Requirements
FM FM Requirements
(NFPA = minimum)
LPC LPC Standard
VDS VDS Standard
NYC & LA Specific City approvals
Types of Sprinkler Heads
Red
(68°C) Yellow
(79°C) Green
(93or100°C) Blue
(141°C)
Ordinary Intermediate High
Upright Sprinklers
Sprinkler Head Identification
Pendent sprinkler
fed through a ceiling
Pendent sprinkler
on exposed piping
K Factors
K factors are known as the coefficient of discharge.
The larger the K factor in number, the more water it
can discharge at a given pressure. There are (3)
current thread sizes used for sprinkler heads, ½”, ¾”,
and 1” threads.
Thermal Response
Requirements
Thermal Sensitivity
• STANDARD RESPONSE
– 3 Min. 51 Sec. Room Fire Test
– 100 Sec. Plunge Test
• QUICK RESPONSE
– 75 Sec. Room Fire Test
– 14 Sec. Plunge Test
• RESIDENTIAL
– Special Fire Test
– 14 Sec. Plunge
Thermal Sensitivity
Plunge Oven
Response
ResponseTime
TimeIndex
Index-- RTI
Classification of Occupancies
Upright and pendent spray sprinklers shall be permitted in all
occupancy hazard classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to
sprinkler design, installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general
classification of occupancy hazards.
5.2* Light Hazard Occupancies.
Light hazard occupancies shall be defined as occupancies or portions
of other occupancies where the quantity and/or combustibility of
contents is low and fires with relatively low rates of heat release are
expected.
EXAMPLES: Churches, Clubs, Hospitals, Museums,
Offices, Restaurant Seating Areas
Occupancy Hazard
Classification of Occupancies
Upright and pendent spray sprinklers shall be permitted in all occupancy hazard
classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,
installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general classification of
occupancy hazards.
5.3.1* Ordinary Hazard (Group 1).
Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of
other occupancies where combustibility is low, quantity of combustibles is moderate,
stockpiles of combustibles do not exceed 8’-0”, and fires with moderate rates of heat
release are expected.
Examples:Restaurant Service Areas, Bakeries, Automobile Parking and
Showrooms, Laundries
5.3.2* Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall be defined
as occupancies or portions of other occupancies where the quantity and combustibility of
contents are moderate to high, stockpiles do not exceed 12’, and fires with moderate to
high rates of heat release are expected.
Examples: Dry Cleaners, Horse Stables, Machine Shops, Library
Classification of Occupancies
Upright and pendent spray sprinklers shall be permitted in all occupancy hazard
classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,
installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general classification of
occupancy hazards.
5.4.1* Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall be defined as
occupancies or portions of other occupancies where the quantity and combustibility of
contents are very high and dust, lint, or other materials are present, introducing the
probability of rapidly developing fires with high rates of heat release but with little or no
combustible or flammable liquids.
Examples: Combustible Hydraulic Fluid Use Areas, Metal
Extruding,
Saw Mills, Upholstering with Plastic Foams, Rubber Reclaiming
5.4.2* Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be defined as
occupancies or portions of other occupancies with moderate to substantial amounts of
flammable or combustible liquids or occupancies where shielding of combustibles is
extensive.
Examples: Flammable Liquids Spraying, Open Oil Quenching,
Standard Spray Sprinklers
Q = Area x Density
Q = Water Flow
K = Coefficient of Q=Kx P
Discharge
P = Pressure
P = (Q/K)2
K = Q/ P
Standard Spray Sprinklers
Sidewall
Standard Spray Sprinklers
Spray Pattern
Standard Coverage Sidewall
Sprinklers
• EXTENDED COVERAGE
– FLOOR AREA PLUS WET THE WALL 30” (762 mm)
ABOVE THE FINISHED FLOOR
ECLH-ELO Pendent
*Based on a 225 sq. ft. coverage area for standard coverage upright and pendent
Extended Coverage Spacing
*Based on a 130 sq. ft. coverage area for standard coverage upright and pendent
Extended Coverage Spacing
*Based on a 130 sq. ft. coverage area for standard coverage upright and pendent
Aesthetic Sprinklers
and Finishes
Aesthetic Sprinklers
Concealed Sprinklers
are installed to “Hide” the
sprinkler’s operating mechanism
and deflector.
Concealed sprinkler cover
plates may only be painted
by the manufacturer.
Viking applies a label with
the same color custom color
paint on the interior of the
cover plate to identify to the
AHJ and owner that the sprinkler
was painted by the manufacturer.
Special metal finishes are also available.
Aesthetic Sprinklers
Adjustable concealed drop and sprinkler assemblies are desired where labor
rates are high.
Aesthetic Sprinklers
Protective Cap
Removal Tool
Small or Large
Cover plate
Installation tool.
Aesthetic Sprinklers
3 ¼” Minimum ½”
Ceiling Flashing
Model G Escutcheon
QREC-Pendent
Institutional Sprinkler
Note: Corrosion resistance does not mean corrosion proof. A sprinkler’s data
page indicates its materials of construction. Appropriate finish choice for an
environment is the responsibility of the customer. Refer inquiries about
corrosion resistance of a sprinkler to Viking Technical Services.
Sprinklers Used in
Storage Occupancies
Typical Types of Storage
Rack Storage
Palletized Storage
Idle Pallet Storage
Miscellaneous Storage Shelf Storage
Rubber Tire Storage
Due to the nature of the fire and the subsequent heat release,
NFPA 13 places limitations on the orifice size that can be
used based on density requirements. (GPM per sq. ft.)
Densities greater than .34 gpm per sq. ft. require K factors of
11.2 or larger.
Control Mode Sprinklers for Storage
Larger K factors also can discharge the same water flow rate
at much lower pressures, so they are more efficient at
controlling the fire.
Starting Pressure
P = (Q/K)²
P = Starting Pressure
In-Rack Sprinklers
In-Rack Sprinklers
Generally, when storage exceeds 25’-0” in racks and
control mode sprinklers are utilized, levels of in-rack
sprinklers are within the rack structure.
In-Rack Sprinkler
With Water Shield
Control Mode
Sprinklers
Control Mode Sprinklers for Storage
In-Rack Sprinklers
In-rack sprinklers are typically have k factors of 5.6 and
8.0, but in some cases are as large as 11.2.
CMSA Sprinklers
(Control Mode Special Application)
K 11.2 CMSA Upright Sprinkler
The K 11.2 CMSA upright sprinkler was the first storage sprinkler developed
with full scale fire tests series.
Note: FM approval utilizes hose stream of 250 gpm and a 12 head design at 30’ storage
K 19.6 CMSA Pendent Sprinkler
VK 592 (K 19.6) Pendent Control Mode Special Application (CMSA) Sprinkler
Configuration Commodity Class Maximum Storage Maximum Number of Design Minimum Operating
Height Ceiling/Roof Height Sprinklers Pressure
20 ft. (6.1m) 25 ft. (7.6m) 15 16 PSI (1.1bar)
20 ft. (6.1m) 30 ft. (9.1m) 15 16 PSI (1.1bar)
20 ft. (6.1m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
Single-Row, Double- 20 ft. (6.1m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
Row, and Multiple- Class l, ll, lll, and lV 25 ft. (7.6m) 30 ft. (9.1m) 15 16 PSI (1.1bar)
Row Rack (no open- commodities 25 ft. (7.6m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
top containers) 25 ft. (7.6m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
30 ft. (9.1m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
30 ft. (9.1m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
35 ft. (10.7m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
20 ft. (6.1m) 25 ft. (7.6m) 15 16 PSI (1.1bar)
20 ft. (6.1m) 30 ft. (9.1m) 15 16 PSI (1.1bar)
20 ft. (6.1m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
Single-Row, Double- 20 ft. (6.1m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
Row, and Multiple- Cartoned Un- 25 ft. (7.6m) 30 ft. (9.1m) 15 16 PSI (1.1bar)
Row Rack (no open- expanded Plastics 25 ft. (7.6m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
top containers) 25 ft. (7.6m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
30 ft. (9.1m) 35 ft. (10.7m) 15 25 PSI (1.7bar)
30 ft. (9.1m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
35 ft. (10.7m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
20 ft. (6.1m) 25 ft. (7.6m) 15 16 PSI (1.1bar)
20 ft. (6.1m) 30 ft. (9.1m) 15 16 PSI (1.1bar)
On Floor Idle Wood Pallets
20 ft. (6.1m) 35 ft. (10.7m) 15 30 PSI (2.06bar)
20 ft. (6.1m) 40 ft. (12.2m) 15 30 PSI (2.06bar)
Note: Hose stream allowance is 500 gpm (1900 lpm)
Note: FM approval utilizes hose stream of 250 gpm and a 12 head design at 30’ storage
K19 Pendent CMSA Sprinkler
K19 Pendent CMSA Sprinkler
Avoid Obstructions
Do not have any obstruction directly
Below the pendent ESFR sprinkler head.
Avoid Obstructions
Normally (12) ESFR sprinklers are designed
to operate in a fire. If an ESFR sprinkler is
obstructed, the re-directed water discharge
will cool ESFR sprinklers near it and prevent
them from operating. Heat from the fire will
travel to ESFR sprinklers away from the fire
and cause them to operate, which will have
tragic consequences. More ESFR sprinklers
will operate than designed for and the fire
will not be suppressed or controlled.
K 14 and K 16.8 Pendent ESFR’s
ESFR
Obstruction Criteria
Of Particular Concern:
...anything within 12” (305 mm) laterally of the
deflector within the 24” (610 mm) space under the
sprinkler.
…obstructions as small as 3/4” (19 mm) diameter
bridging can interfere with proper ESFR pendent
Sprinkler performance,….”
Skipping
K 14 and K 16.8 Pendent ESFR’s
Upright ESFR
Factory Mutual Test Facility
When can Upright and Pendent
ESFR’s be installed on the same
system?
Allowable Installation
When the ceiling height does not exceed 35’-0”, and the
commodities being stored are within the allowable
protection schemes of upright ESFR sprinklers.
ROOF SLOPE CANNOT EXCEED 2/12 FOR BUILDINGS OVER 30 FEET (9,1M) HIGH,
HEAD SPACING CAN RUN BETWEEN 8’ TO 10’
MINIMUM OF 36” (914MM) CLEARANCE (2,4 TO 3,1M), AS LONG AS THE AREA PER
FROM DEFLECTOR TO TOP OF STORAGE SPRINKLER DOES NOT EXCEED 100 SQ.FT.
INSTALL ON WET SYSTEMS ONLY (9,3 SQ. M.)
Deflector
Frangible bulb
Frame
Split Seat
Adjustable
Plain Barrel
Recessed
PN 14909AC
Installation on Wet Systems Only
K 14 Dry ESFR
Design Criteria
The VK 501 Dry Barrel ESFR can protect the same
commodity storage in the same storage arrangements
as a standard pendent K14 ESFR
Additional Requirements:
Air Supply
Detection
Low Point Drains
Inspection Points to Search for Frost
Typical Method of Protecting a Freezer Plugs
Located in a Warehouse
Crawl Space Sprinkler Piping
(Heated Space)
Window Sprinklers
Spray Nozzles
Window Sprinklers
Spray Nozzles