You are on page 1of 2

Worldwide

www.tyco-fire.com
Contacts

Ultra Low Flow AQUAMIST Nozzles


Type ULF AM30
Automatic (Closed)
General depending on the characteristics and
nature of the hazard and the basic
Description purpose of the water mist system.
Because of these variations, the design
TYCO Ultra Low Flow AQUAMIST of water mist systems for fire protec-
Nozzles Type ULF AM30 are closed tion must only be performed by expe-
(automatic) nozzles intended for use rienced designers who thoroughly
with engineered, water-mist systems. understand the limitations as well as
They are low-pressure nozzles that capabilities of such systems.
utilize a single fluid jet impinging on a The owner is responsible for main-
diffuser to produce a spray having a taining their fire protection system
range of water droplet sizes suitable and devices in proper operating con-
for the control of Class A fires and the dition. Contact the installing contrac-
protection of data centers. tor or product manufacturer with any
It is recommended that the end user questions.
be consulted with respect to the suit-
ability of the materials of construction
for any given corrosive environment.
Approvals Temperature Bulb
The TYCO Type ULF AM30 AQUA- Rating Fluid Color
The effects of ambient temperature,
concentration of chemicals, and gas/ MIST Nozzles in a 57°C (135°F) tem- 57°C (135°F) Orange
chemical velocity should be consid- perature rating and in a natural brass
finish is VdS approved when used as 68°C (155°F) Red
ered, at a minimum, along with the cor-
rosive nature to which the nozzles may part of an engineered wet pipe low 79°C (175°F) Yellow
be exposed. pressure system. Testing was per-
formed in accordance with VdS Test 93°C (200°F) Green
Protocol, “Fire tests for false floors and 141°C (286°F) Blue
NOTICE false ceilings as a completion of the fire
The TYCO Ultra Low Flow AQUAMIST 182°C (360°F) Mauve
tests ‘Office, OH1’ and similar,” dated
Nozzles Type ULF AM30 de­scribed December 6, 2007. TABLE A
herein must be installed and main- TEMPERATURE RATING
tained in compliance with this docu- The TYCO Type ULF AM30 AQUA-
MIST Nozzles in a 57°C (135°F) or SELECTION
ment and with the applicable standards
of the NATIONAL FIRE PROTECTION 68°C (155°F) temperature rating and in
a natural brass finish are FM Approved Physical Characteristics
ASSOCIATION (NFPA), in addition to Frame ���������������������������������������������������������Brass
the standards of any authorities having for the protection of data processing
Strainer ���������������������������������������������������� Copper
jurisdiction. Failure to do so may impair equipment rooms/halls in either wet Orifice Insert ���������������������������������������������Bronze
the performance of these devices. pipe or single-interlock preaction con- Button �������������������������������������������������������Bronze
figurations. Testing for the single-inter- Sealing Assembly. . Beryllium Nickel w/TEFLON
The design of individual water mist lock preaction data center application Ejection Spring ���������������������������� Stainless Steel
systems can vary considerably, was conducted in accordance with FM Bulb ������������������������������������������������������������� Glass
Approvals 5560 “Approval Standard for Diffuser �����������������������������������������������������Bronze
Loading Screw �����������������������������������������Bronze
Water Mist Systems.”
IMPORTANT The smallest waterway (orifice) diam-
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
Technical eter of the Orifice Insert is nominally
4,4 mm (0.172 in.). The diameter of the
regulatory and health information. Data Inlet Strainer perforations is nominally
3,2 mm (0.125 in.).
Always refer to Technical Data Discharge Coefficient
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
K=8,5 lpm/bar1/2 (K=0.59 gpm/psi1/2 )
Design
Thread Connection
with respect to handling and instal-
lation of sprinkler systems and com- 1/2 Inch NPT Criteria
ponents. Improper handling and Finish Obtain guidance for the design of a
installation can permanently damage Natural Brass water mist system that utilizes the
a sprinkler system or its compo- Temperature Ratings TYCO Ultra Low Flow AQUAMIST
nents and cause the sprinkler to fail Refer to Table A Nozzles Type ULF AM30 from the Tech-
to operate in a fire situation or cause nical Services department.
it to operate prematurely.

Page 1 of 2 AUGUST 2018 TFP2201


TFP2201
Page 2 of 2

DIFFUSER
SHAPE
WRENCH RECESS
(USE ONLY
END "A")
1.22"
(31,0 mm)
FIGURE 2
W-TYPE 6 WRENCH
7 Components:
8
1 - Strainer Frequent visual inspections are recom­
1-11/16" 6 2 - Orifice Insert mended to be initially performed for
(42,9 mm) 9
3 - Frame nozzles installed in potentially corro­
WRENCH 5 4 - Button sive atmospheres to verify the integ­
2-3/8" FLATS 5 - Sealing rity of the materials of construction
(60,3 mm) 4 Assembly and finish as they may be affected by
6 - Bulb the corrosive conditions present for a
11/16"
3 7 - Loading given installation. Thereafter, annual
(17,5 mm)
Screw inspections per applicable standards
2 8 - Diffuser are required, in addition to inspec­
11/16" 9 - Ejection
(17,5 mm)
1/2" NPT tions required by the authority having
7/16" (11,1 mm) Spring
NOMINAL 1 jurisdiction.
MAKE-IN The owner is responsible for the
inspection, testing, and maintenance of
FIGURE 1
their fire protection system and devices
TYPE ULF AM30 AQUAMIST NOZZLE
in compliance with this document, as
NOMINAL DIMENSIONS
well as with the applicable standards
of any other authorities having juris­
Installation Care and diction. Contact the installing contrac­
tor or product manufacturer with any
TYCO Ultra Low Flow AQUAMIST
Nozzles Type ULF AM30 must be
Maintenance questions.
Water mist systems should be in­
installed in accordance with this TYCO Ultra Low Flow AQUAMIST spected, tested, and maintained by a
section. Nozzles Type ULF AM30 must be main­ qualified Inspection Service in accor­
Do not install any bulb type nozzle if tained and serviced in accordance with dance with local requirements and/or
the bulb is cracked or there is a loss this section. national codes.
of liquid from the bulb. With the nozzle Before closing a fire protection system
held horizontally, a small air bubble
should be present. The diameter of
main control valve for maintenance
work on the fire protection system
Limited
the air bubble is approximately 1,6 mm
(1/16 in.) for the 57°C (135°F) to 2,4 mm
that it controls, obtain permission to
shut down the affected fire protection
Warranty
(3/32 in.) for the 182°C (360°F) temper­ system from the proper authorities For warranty terms and conditions, visit
ature ratings. and notify all personnel who may be www.tyco-fire.com.
A leak-tight 1/2 inch NPT nozzle joint affected by this action.
should be obtained by applying a min­
imum-to-maximum torque of 9,5 to
Nozzles which are found to be leaking
or exhibiting visible signs of corrosion
Ordering
19,0 Nm (7 to 14 lb-ft). Higher levels
of torque can distort the nozzle inlet
must be replaced. Procedure
Automatic nozzles must never be Contact your local distributor for avail­
and cause leakage or impairment of
painted, plated, coated, or other­ ability. When placing an order, indicate
the nozzle.
wise altered after leaving the factory. the full product name and part number
Type ULF AM30 Modified nozzles must be replaced. (P/N).
The Type ULF AM30 AQUAMIST Nozzles that have been exposed to
Nozzles must be installed in accor­ corrosive products of combustion, but Type ULF AM30 AQUAMIST Nozzles
dance with the following instructions: have not operated, should be replaced Specify: Type ULF AM30 AQUA­
if they cannot be completely cleaned MIST Nozzle with Natural Brass finish,
Step 1. Install the Type ULF AM30 in the (specify) temperature rating, P/N
by wiping the nozzle with a cloth or by
upright position as shown in Figure 1. (specify):
brushing it with a soft bristle brush.
Step 2. With pipe thread sealant 57°C (135°F) . . . . . . . . . . . . . . . . . 49-230-1-135
Care must be exercised to avoid
ap­p lied to the pipe threads, hand- 68°C (155°F) . . . . . . . . . . . . . . . . . 49-230-1-155
damage to the nozzles before, during,
tighten the nozzle into the nozzle fitting. 79°C (175°F) . . . . . . . . . . . . . . . . . . 49-230-1-175
and after installation. Nozzles damaged 93°C (200°F) . . . . . . . . . . . . . . . . . 49-230-1-200
Step 3. Tighten the nozzle into the by dropping, striking, wrench twist/ 141°C (286°F) . . . . . . . . . . . . . . . . 49-230-1-286
nozzle fitting using only the W-Type 6 slippage, or the like, must be replaced. 182°C (360°F) . . . . . . . . . . . . . . . . 49-230-1-360
Wrench (Ref. to Figure 2). With refer­ Also, replace any nozzle that has a Wrench
ence to Figure 1, apply the W-Type 6 cracked bulb or that has lost liquid from Specify: W-Type 6 Sprinkler Wrench,
Wrench to the wrench flats. its bulb (Ref. Installation section). P/N 56-000-6-387