www.tyco-fire.com
Contacts

Model WMA-1 Water Motor Alarm


Hydraulically Operated
Mechanical Sprinkler Alarm
General The owner is responsible for main-
taining their fire protection system
Description and devices in proper operating con-
dition. Contact the installing contrac-
The TYCO Model WMA-1 Water Motor tor or product manufacturer with any
Alarm is a hydraulically operated questions.
outdoor alarm designed for use with
fire protection system waterflow detec-
tion valves. It is lightweight yet rugged,
Technical
and it can be used in conjunction with
alarm check, dry pipe, deluge, and pre-
Data
action valves to sound a local alarm. Approvals
UL and ULC Listed
The Water Motor Alarm is suitable FM, LPCB and VdS Approved
for mounting to any type of rigid wall
and can accommodate a wall thick- Gong Finish
Red or Aluminum
ness range of 2 in. to 18 in. (50 mm
to 450 mm). It is provided with a listed Working Water Pressure Range
and approved TYCO Model WMA-1 7 to 300 psi (0,5 to 20,7 bar)
Y-Strainer for use in the alarm line. Nozzle K-factor
The Model WMA-1 utilizes a lightweight, 0.7 gpm/psi½ (10,1 Lpm/bar½)
impeller design that can produce a very Y-Strainer
high sound pressure level. The Gong, 3/4 in., cast iron, 20 mesh screen
Gong Mount, and Water Motor Housing
are fabricated from corrosion-resistant Trim Components
Galvanized steel nipples and cast iron
aluminum alloys. The polymer drive fittings
bearings do not require lubrication, and Item 5. The alarm line piping must be
the Gong is closely fitted to the Gong
Mount to eliminate the need for a sepa- Design positioned such that it can be drained
back to the waterflow detection valve
rate cover.
The Model WMA-1 Water Motor Alarm
Data trim.
Item 6. The Clean-Out Sump Plug is to
is a re-designation for the Central The TYCO Model WMA-1 Water Motor be located vertically below the Inlet to
Model F-2, Gem Model F630, and Star Alarm must be used in accordance with the Water Motor.
Model S450. the following design criteria: Item 7. Piping from the Water Motor
Item 1. The Y-Strainer is to be located Drain must be a minimum of 1 in.
NOTICE at the alarm outlet of the waterflow (DN25) in size throughout and directed
The TYCO Model WMA-1 Water Motor detection valve trim. to an open drain in order to ensure
Alarm described herein must be proper drainage for obtaining the
Item 2. The Water Motor Alarm maximum sound pressure level.
installed and maintained in compliance
must only be mounted to a rigid
with this document, as well as with the Note: The Water Motor Alarm Drain
wall surface that will not permit the
applicable standards of the NATIONAL may be connected to the main drain
Striker /Gong Mount to loosen and fall
FIRE PROTECTION ASSOCIATION of a waterflow detection valve if a non-
out of alignment.
(NFPA), in addition to the standards spring loaded swing-type check valve
of any authorities having jurisdiction. Item 3. In order to obtain the highest is installed in a horizontal portion of the
Failure to do so may impair the perfor- possible sound level, the Water Motor
water motor alarm drain piping (before
mance of this device. Alarm should be located as close as
possible to the waterflow detecting its connection to the main drain).
valve. For guidance, refer to NFPA 13. Item 8. In order to minimize any wall
Item 4. The alarm line piping from the staining that can be created by drain
alarm outlet of the waterflow detection water, it is recommended that the drain
valve trim to the Water Motor Alarm piping from the Water Motor be galva-
must be 3/4 in. (DN20) in size through- nized steel, brass, or other suitable cor-
out and it must be galvanized steel, rosion-resistant material.
IMPORTANT
Refer to Technical Data Sheet brass, or other suitable corrosion-resis-
TFP2300 for warnings pertaining to tant material.
regulatory and health information.

Page 1 of 4 AUGUST 2018 TFP921


TFP921
Page 2 of 4

NO. DESCRIPTION QTY. REF. STRIKER ARM


1 Water Motor . . . . . . 1 92-630-1-012
COUPLING
2 Support Washer . . . 1 NR
SPACER
3 Drive Shaft Sleeve . 1 NR
4 Drive Shaft . . . . . . . 1 NR COUPLING
5 Gong Mount . . . . . . 1 NR 3/4" NPS
6 Striker . . . . . . . . . . . 1 See (a)
7 Gong . . . . . . . . . . . . 1 See (a) STRIKER
8 Cap Nut . . . . . . . . . 1 See (a) SHAFT
(a) Red Gong Repair STRIKER BEARING
Kit includes items: RING 2
6, 7 (red), and 8 . . . 1 92-630-1-025
CROSS-SECTION VIEW
(a) Aluminum Gong Repair OF STRIKER (ITEM 6)
Kit includes items:
6, 7 (alum.), and 8 . . 1 92-630-2-025

NR: Not Replaceable

3
6

7
4
IMPELLER

NOZZLE

INLET
DRAIN
5

INTERNAL VIEW OF
WATER MOTOR (ITEM 1)
8

FIGURE 1
MODEL WMA-1 WATER MOTOR ALARM
ASSEMBLY

Item 9. Drain water must be directed to • 3/4 in. Check Valve with 3/32 in. the Inlet Nozzle, a high velocity jet is
prevent accidental damage to property orifice (P/N 52-403-1-005) formed that impinges on the Impeller,
or danger to persons when the alarm is causing the Impeller and the Striker
Strainers must be located at the alarm
operating or thereafter. to rotate. With each rotation, the free
outlet in the trim of each of the water-
Item 10. The alarm line drain, at the flow detection valves. Check valves swinging Striker Ring hits the Gong and
waterflow detection valve, must be must be located between each strainer sounds the alarm. The spent water is
maintained at a minimum temperature and the interconnection with the alarm then drained through the 1 in. outlet.
of 40°F (4°C). line from another system. The alarm will sound as long as water
Item 11. A single Water Motor Alarm is flowing into the system and flowing
may be connected to the alarm lines Operation to the Water Motor Alarm. Water in the
alarm line will automatically drain back
from a maximum of three separate fire
protection systems. However, when Upon operation of the alarm check, through the orifice, which is also pro-
two or three alarm lines are intercon- dry pipe, deluge, or preaction valve to vided in the trim of the waterflow detec-
nected, each alarm line must be pro- which the TYCO Model WMA-1 Water tion valve.
vided with the following: Motor Alarm is connected, water will The Water Motor Alarm does not have
flow to the Water Motor and through to be reset after an operation. However,
• 3/4 in. Model WM-1 Y-Strainer the Inlet Nozzle. As water flows through
(P/N 52-271-1001) if the alarm was silenced during oper-
TFP921
Page 3 of 4

2"
(50,8 mm)
7/8" 3/4" NPS
(22,2 mm) 2-3/4" 2-7/16"
1-3/8" (69,9 mm) (61,9 mm)
(34,2 mm)
WATER
MOTOR 8-1/2" DIA.
SLEEVE END (215,9 mm)
2-9/16" T/O 2-1/2" T/O 3/4" NPT
(65,0 mm) (63,5 mm) THREADED
BY INSTALLER

1-13/16"
(46,0 mm) 10"
(254,0 mm)
DRAIN CL
3/4" NPT 1" NPT MINIMUM
INLET DRAIN
A

3/4" (DN20) NPS 1" (DN25) NPS 2-1/16"


GALVANIZED GALVANIZED (52,4 mm) B
STEEL OR 4 STEEL OR INLET CL
BRASS PIPE BRASS PIPE C
1 1
D
3
RIGID WALL
2 STRUCTURE
3/4"
Y-STRAINER 16" (457,2 mm)
LOCATION FOR CLEAN-OUT
OPTIONAL ELECTRICALLY MAXIMUM
STRAINER SUMP PLUG
SUPERVISED N.O. 2" (50,8 mm)
CLEAN-OUT ALARM CONTROL VALVE MINIMUM
CAP (SEE NOTE 4)
NOTES: STANDARD INLET TRIM OPTIONAL DRAIN TRIM
1. All installation dimensions are shown at nominal value. NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.
2. All dimensions are in inches and (mm).
1 3/4" x 3" Nipple . . . . . 2 A 1" 90° Elbow . . . . . . . 1
3. Items shown in dotted lines are not included with the WMA-1. 2 3/4" 90° Elbow . . . . . . 1 B 1" 45° Elbow . . . . . . . 1
4. Consult local Authority Having Jurisdiction for mechanical 3 3/4" x 1/4" x 3/4" Tee C Wall Plate . . . . . . . . . 1
alarm isolating control valve requirements. with 1/4" Plug. . . . . . . 1 D 1" x 1'-6" Pipe,
5. All included trim components are galvanized. 4 3/4" Union . . . . . . . . . 1 T.O.E. . . . . . . . . . . . . 1
FIGURE 2
MODEL WMA-1 WATER MOTOR ALARM
TYPICAL INSTALLATION

ation by closing an alarm control (0 mm to 3 mm). Thread the cut end to Step 8. Tighten the 3/4 in. Union.
valve, the alarm control valve must 3/4 in. NPT per ANSI B1.20.1. Install the Wall Plate and tighten the
be reopened after the fire protection 45° Elbow.
Step 4. Install the alarm line piping up
system is restored to service. to and including the Union half per Item Note: Apply pressure against the
4, Figure 2. outside edge of the Water Motor Body
Installation Note: Use thread sealant sparingly on and verify that the Body and Support
Washer sit squarely against the wall. If
The TYCO Model WMA-1 Water Motor male threads only.
not, adjust the alarm line and/or drain
Alarm must be installed in accordance Step 5. Prior to initiating installation piping to suit.
with this section. of the Water Motor Alarm, mount the
Step 9. From the outside wall, insert
Step 1. Mark the through-wall locations Drain Trim (less the Wall Plate and 45°
the Drive Shaft through the Sleeve and
for the centerlines of the Sleeve and Elbow) as well as the balance of alarm
fully insert it into the Impeller.
Drain Outlet. The Drain Outlet must be line piping, including the other Union
located at least 10 in. (250 mm) below half, to the Water Motor. Note: When fully inserted, the Shaft
the Sleeve per Figure 2. should protrude beyond the face of
Step 6. Tighten the NPT threaded end
the wall by approximately 20 minus 2 in.
Step 2. Make 1-1/2 in. (38 mm) diam- of the Sleeve into the Body, hand-tight
(508,0 minus 50,8 mm) wall thickness.
eter holes straight through the wall at plus 1/8 turn.
both locations. Mark the Drive Shaft at a point of
Step 7. Slip the Support Washer over
approximately 1/8 in. to 1/4 in. (3,2 mm
Step 3. Cut the non-threaded end of the Sleeve and place the assembly in
to 6,4 mm) inside the face of the wall.
the Sleeve to a length equal to that of position against the wall.
Remove the Shaft and cut it where pre-
the wall thickness plus 0 in. to 1/8 in.
TFP921
Page 4 of 4

viously marked. File off burrs from the


cut end of the Drive Shaft. Re-insert the
If the alarm was silenced during opera-
tion, the alarm control valve must be Limited
Drive Shaft through the Sleeve and fully
insert it into the Impeller.
reopened immediately after the fire pro-
tection system is restored to service. Warranty
Step 10. Hold the Gong Mount in The owner is responsible for the inspec- For warranty terms and conditions, visit
position against the wall, engage the tion, testing, and maintenance of their www.tyco-fire.com.
Coupling with the Drive Shaft, and fire protection system and devices in
then carefully thread the Striker Shaft
Bearing onto the Sleeve. Securely
compliance with this document, as well
as with the applicable standards of the
Ordering
tighten the Striker Shaft Bearing using
a pair of tongue-and-groove pliers on
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
Procedure
the 1-1/2 in. (38 mm) hex end. the standards of any other authorities Orders for the WMA-1 Water Motor
having jurisdiction. Contact the install- Alarm Assembly, Optional Drain Trim,
Step 11. Spin the Striker by hand and
ing contractor or product manufacturer and replacement parts must include
verify that it spins freely, without any
regarding any questions. the description and Part Number (P/N).
sign of binding. If it does not, make the
necessary adjustments. Automatic sprinkler systems are rec- The complete Model WMA-1 Alarm
ommended to be inspected, tested, Assembly includes the Model WMA-1
Step 12. Install the Gong and securely
and maintained by a qualified Inspec- Water Motor Alarm, Model WM-1
tighten the Cap Nut. The identifica-
tion Service in accordance with local Strainer, and Standard Inlet Trim.
tion sign lettering must be orientated
requirements and/or national codes.
horizontally. WMA-1 Water Motor Alarm
The following procedures and inspec- Assembly
Step 13. Test the Water Motor Alarm by
tions should be performed as indicated, Specify: Model WMA-1 Water Motor
opening the alarm test valve in the trim
in addition to any specific requirements Alarm, (specify) Finish, P/N (specify):
of the waterflow detection valve. The
of the NFPA, and any impairment must
alarm must be clear and steady. If it is Red Finish Gong . . . . . . . . . . P/N 52-630-1-001P
be immediately corrected:
not, make the necessary adjustments. Aluminum Finish Gong �������� P/N 52-630-2-001P
Step 1. The Model WMA-1 Water Motor Optional Drain Trim
NOTICE Alarm does not require any regularly Specify: Optional Drain Trim for
scheduled maintenance. Rotating parts Model WMA-1 Water Motor Alarm,
Testing of the Water Motor Alarm may do not require lubrication. It is recom-
result in operation of other associated P/N 52-630-2-002
mended, however, that fire alarms be
alarms. Consequently, notification periodically operated (inspected) to Separately Ordered Parts for
must be given to the owner and the fire verify that they generate a clear and Multiple Systems
department, central control station, or steady sound. Correct any impairment Specify: Model WM-1 Y-Strainer,
other signal station to which the alarms immediately. P/N 52-271-1-001
are connected.
Step 2. The inspection should be made Note: One Y-Strainer is required for
Care and quarterly or more frequently, as may
be necessary for locations subject to
two systems; two Y-Strainers are
required for three systems.
Maintenance vandalism.
The Y-Strainer and Sump are to be
Specify: 3/4 in. Check Valve with 3/32
in. Orifice, P/N 52-403-1-005
The TYCO Model WMA-1 Water Motor cleaned out after each operation of the
Alarm must be maintained and ser- Note: Two Check Valves are required
Water Motor Alarm and after the alarm
viced in accordance with this section. for two systems; three Check Valves
line piping has been drained.
are required for three systems.
Before closing a fire protection system
main control valve for maintenance NOTICE Replacement Parts for
work on the fire protection system Water Motor Alarm
With reference to Figure 2, in the event
that it controls, obtain permission to Specify: (description) for use with
of a WMA-1 malfunction, inspect and
shut down the affected fire protection Model WMA-1 Water Motor Alarm,
clean the Y-Strainer of obstruction prior
system from the proper authorities P/N (see Figure 1)
to removing the Water Motor.
and notify all personnel who may be
affected by this decision. Make no attempt to disassemble,
repair, or internally clean the Water
Testing of the Water Motor Alarm may Motor. The Water Motor is not a field
result in operation of other associated serviceable part and must be replaced
alarms. Consequently, notification if malfunction is determined.
must be given to the owner and the fire
department, central control station, or
other signal station to which the alarms
are connected.

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;