You are on page 1of 6

Worldwide

www.tyco-fire.com
Contacts

Model CV-1FR Grooved-End


Riser Check Valves
2 Inch to 12 Inch (DN50 to DN300)
General NOTICE
The Model CV-1FR Riser Check Valve
Description described herein must be installed
and maintained in compliance with
The TYCO Model CV-1FR Grooved- this document and with the applicable
End Riser Check Valve is a compact standards of the NATIONAL FIRE PRO-
and rugged swing-type unit that allows TECTION ASSOCIATION, in addition to
water flow in one direction and pre- the standards of any authorities having
vents flow in the opposite direction. jurisdiction. Failure to do so may impair
A resilient elastomer seal facing on the performance of this device.
the spring-loaded clapper ensures a
leak-tight seal and non-sticking opera- Never remove any piping component
tion. The Model CV-1FR Riser Check nor correct or modify any piping defi-
Valves are designed to minimize water ciencies without first de-pressurizing
hammer caused by flow reversal. and draining the system. Failure to do
so may result in serious personal injury,
The Model CV-1FR Riser Check Valve property damage, and/or impaired
is furnished with grooved ends and device performance.
can be installed using GRINNELL
The owner is responsible for maintain-
Installation
Grooved Couplings or GRINNELL
Figure 71 Flange Adapters. The Model ing their fire protection system and
CV-1FR Riser Check Valves have been devices in proper operating condition.
designed with a removable cover for Contact the installing contractor or The Model CV-1FR Riser Check Valves
ease of field maintenance. These valves manufacturer with any questions. are to be installed in accordance with
can be installed horizontally (with cover this section:
in the upward position) or vertically with Technical 1. The arrow cast on the Body must
the flow in the upward direction. Refer
Data
point in the direction of the flow.
to Figure 6.
2. Valves installed vertically must
To facilitate their use in wet-type auto- Approvals be positioned with the flow in the
matic sprinkler system risers, the UL, C-UL Listed upward direction.
Model CV-1FR Riser Check Valves are FM Approved
provided with threaded outlets for pres- Sizes 3. Valves installed horizontally must be
sure gauges and a drain connection. 2 in. to 12 in. (DN50 to DN300) positioned with the Cover facing up.
They provide a more compact and eco- Maximum Working Pressure Refer to Figure 6.
nomical alternative to an alarm check 300 psi (20,7 bar) 4. Grooved-end pipe couplings used
valve where a water motor alarm is not Valve Assembly Finish with the Model CV-1FR Riser Check
required. Provisions must be made for Red, non-lead paint Valve must be installed in accordance
a local alarm using an approved flow with manufacturer’s instructions.
switch (not included).
NOTE: Valves should be installed a
The Model CV-1FR Riser Check Valve reasonable distance downstream from
is also Listed for use in conjunction pumps, elbows, expanders, reducers,
with the TYCO DV-5 Deluge Valve in or other similar devices to extend the
Preaction Systems under air pressure valve life. Standard piping practices
without the use of prime water. call for a minimum of five times the pipe
The Model CV-1FR Riser Check Valves diameter for general use.
are a redesign for the Central Figure
590FR and GRINNELL Figure 590FR.

IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 4 AUGUST 2018 TFP950


TFP950
Page 2 of 6

A B
1/4"
1/4" NPT
NPT

O.D.

J K

Nominal Dimensions
Nominal Pipe Size Inches Cover
(mm) Approx.
Bolt Weight
Torque
ANSI O.D. K lb
ft-lb
Inches Inches A B C D E F J Inches (kg)
(Nm)
DN (mm) NPT

2 2.375 6.75 4.38 1.96 2.57 3.25 4.37 1.56 18 9.0


(60,3) (171,5) (111,3) (49,8) (65,3) (82,3) (111,0) (39,6) 1 (25) (4,5)
DN50
2-1/2 2.875 8.00 5.38 2.63 3.09 3.87 5.12 1.73 39 10.0
(73,0) (203,2) (78,5) 1-1/4 (54) (4,5)
DN65 (136,7) (66,8) (98,3) (130,0) (43,9)
76,1 - 8.00 5.38 2.63 3.09 3.87 5.12 1.72 39 10.0
(76,1) (203,2) (78,5) 1-1/4 (54) (4,5)
DN65 (136,7) (66,8) (98,3) (130,0) (43,7)
3 3.500 8.37 5.72 2.81 3.31 3.87 5.12 1.72 39 11.0
(88,9) (212,6) (84,1) 1-1/4 (54) (5,0)
DN80 (145,3) (71,4) (98,3) (130,0) (43,7)
4 4.500 9.63 6.68 3.80 3.63 4.53 5.78 2.12 50 25.0
(114,3) (245,6) (92,2) (115,4) 2 (69) (11,3)
DN100 (169,7) (96,5) (146,8) (53,8)
139.7 - 10.50 7.40 4.46 4.13 4.90 7.00 2.09 39 29.0
(139,7) (266,7) (104,9) (124,5) 2 (54) (13,2)
DN125 (188,0) (113,2) (177,8) (53,1)
5 5.563 10.50 7.40 4.46 4.13 4.90 7.00 2.09 39 29.0
(141,3) (266,7) (104,9) (124,5) 2 (54) (13,2)
DN125 (188,0) (113,2) (177,8) (53,1)
165.1 - 11.50 8.00 4.62 4.50 5.00 7.25 2.00 60 47.0
(165,1) (292,1) (114,3) (127,0) 2 (82) (21,3)
DN150 (203,2) (117,4) (184,2) (50,8)
6 6.625 11.50 8.00 4.62 4.50 5.00 7.25 2.00 60 47.0
(168,3) (292,1) (114,3) (127,0) 2 (82) (21,3)
DN150 (203,2) (117,4) (184,2) (50,8)
8 8.625 14.00 10.14 6.67 5.52 5.46 10.50 2.43 120 66.0
(219,1) (355,6) (140,2) 2 (164) (30,0)
DN200 (257,6) (169,4) (138,7) (266,7) (61,7)
10 10.750 18.00 12.38 8.62 6.41 7.50 10.75 3.38 130 109.7
(273,1) (457,2) (162,8) (190,5) 2 (178) (49,4)
DN250 (314,5) (218,9) (273,1) (85,9)
12 12.750 21.0 14.28 9.93 7.27 7.62 10.00 3.13 130 151.0
(323,9) (533,4) (362,7) (184,7) (193,5) 2 (178) (68,0)
DN300 (252,2) (254,0) (79,5)

FIGURE 1
MODEL CV-1FR RISER CHECK VALVES
NOMINAL DIMENSIONS
TFP950
Page 3 of 6

8 8
4,15 17 16
9 5
2 SEE
2 7 9
VIEW A 2 7 5
3 2" - 8" 10" - 12"
(DN50-DN200) (DN250 - DN300)
VIEW A
13
5 13
11,15
11 14,15
18
SEE
6
DETAIL B 5 6
2" - 8" 10" - 12"
1 (DN50-DN200) (DN250 - DN300)
DETAIL B

Detail Part Material Qty. Detail Part Material Qty. Detail Part Material Qty.
Clapper EPDM Stainless
1 Body Ductile Iron 1 6 Facing Grade “E” 1 14 Locknut Steel 1

Stainless Thread
2 Cover Ductile Iron 1 7 Spring 1 15 Adhesive AR
Steel Sealer
Cover Hinge Stainless
3 Nitrile Rubber 1 8 1 16 Nameplate Aluminum 1
Gasket Shaft Steel
Hex Cap Steel, Zinc Retaining Stainless
4 AR 9 AR 17 Rivet Steel 2
Screw Plated Ring Steel
Clapper Stainless Retention Stainless Stainless
2˝ - 8˝ 11 1 18 Spacer 1
Steel Bolt Steel Steel
(DN50-200)
5 1
Clapper Retaining Stainless
10˝ - 12˝ Ductile Iron 13 1
Disc Steel
(DN250-300)
FIGURE 2
MODEL CV-1FR RISER CHECK VALVES
ASSEMBLY

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
500 700 1000 2000 3000 5000 7000 10000 20000 30000 50000
5.0
0,30
65)

4.0
50)
DN
(DN

80)
IN POUNDS PER SQUARE INCH (PSI)

NOMINAL PRESSURE DROP IN BAR


H(

(DN

3.0
100
CH

0,20
INC
NOMINAL PRESSURE DROP

)
2 IN

CH

(DN

125
/2

(1 PSI = 0,06895 BAR)


150
3 IN

(DN
2-1

CH

2.0
DN

)
4 IN

200
CH

(
CH
5 IN

(DN

)
250

)
6 IN

300

0,10
CH

DN

0,09
DN
8 IN

H(

0,08
H(
INC

1.0 0,07
INC
10

0.9 0,06
12

0.8
0.7 0,05
0.6 0,04
0.5
100 200 300 400 600 1000 2000 3000 4000 6000 10000 15000
FLOW RATE IN GALLONS PER MINUTE (GPM)
FIGURE 3
MODEL CV-1FR RISER CHECK VALVES
PRESSURE LOSS DATA
TFP950
Page 4 of 6

Nominal Dimensions
Nominal Pipe Size Inches
(mm)

ANSI O.D. E
Inches Inches A B C D Inches
DN (mm) NPT

2 2.375 6.75 5.87 3.25 9.52 1


DN50 (60,3) (171,5) (149,1) (82,6) (241,9)
2-1/2 2.875 8.00 6.66 3.87 10.80 1-1/4
DN65 (73,0) (203,2) (169,2) (98,3) (274,3)
76,1 – 8.00 6.66 3.87 10.80 1-1/4
DN65 (76,1) (203,2) (169,2) (98,3) (274,3)
3 3.500 8.37 6.88 3.87 11.02 1-1/4
DN80 (88,9) (212,6) (174,8) (98,3) (279,9)
4 4.500 9.63 7.63 4.53 11.92 2
DN100 (114,3) (244,6) (193,7) (115,1) (302,7)
139,7 – 10.50 8.13 4.90 12.42 2
DN125 (139,7) (266,7) (206,4) (124,5) (315,4)
5 5.563 10.50 8.13 4.90 12.42 2
DN125 (141,3) (266,7) (206,4) (124,5) (315,4)
165,1 – 11.50 8.50 5.00 12.79 2
DN150 (165,1) (292,1) (215,8) (127,0) (324,8)
6 6.625 11.50 8.50 5.00 12.79 2
DN150 (168,3) (292,1) (215,8) (127,0) (324,8)
8 8.625 14.00 9.52 5.46 13.81 2
DN200 (219,1) (355,6) (241,7) (138,7) (350,7)
10 10.750 18.00 10.41 7.50 14.70 2
DN250 (273,1) (457,2) (264,3) (190,5) (373,3)
12 12.750 21.00 11.27 7.62 15.56 2
DN300 (323,9) (533,4) (286,1) (193,5) (395,2)

FIGURE 4
MODEL CV-1FR RISER CHECK VALVE WITH TRIM COMPONENTS
NOMINAL DIMENSIONS
TFP950
Page 5 of 6

P/N 59-591-1-020
2 Inch (DN50)
NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa NOTES: MAIN
Water Pressure Gauge . . 2 92-343-1-005 1. All Fittings and Nipples are DRAIN VALVE
2 1/4" Gauge Test Valve . . 2 46-005-1-002 galvanized (Standard Order). (NORMALLY
3 1/4" Plug . . . . . . . . . . . . . 2 CH CLOSED)
2. CH: Common Hardware.
4 1" Angle Valve . . . . . . . . . 1 46-048-1-006
5 1/4" x 2" Nipple . . . . . . . . 1 CH
6 1/4" x 5" Nipple . . . . . . . . 1 CH
7 1" x 3" Nipple. . . . . . . . . . 1 CH 7
4

P/N 59-591-1-030
2-1/2 Inch (DN65) through 3 Inch (DN80)
NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa SYSTEM
Water Pressure Gauge . . 2 92-343-1-005 PRESSURE
2 1/4" Gauge Test Valve . . 2 46-005-1-002 GAUGE
3 1/4" Plug . . . . . . . . . . . . . 2 CH
1 SUPPLY
4 1-1/4" Angle Valve . . . . . . 1 46-048-1-007
5 1/4" x 2" Nipple . . . . . . . . 1 CH PRESSURE
2
6 1/4" x 5" Nipple . . . . . . . . 1 CH GAUGE
7 1-1/4" x 3" Nipple. . . . . . . 1 CH 5 3

P/N 59-591-1-080
4 Inch (DN100) through 12 Inch (DN300)
MODEL CV-1FR 1
NO. DESCRIPTION QTY. P/N
RISER CHECK
1 300 psi/ 2000 kPa VALVE 2
Water Pressure Gauge . . 2 92-343-1-005 6
2 1/4" Gauge Test Valve . . 2 46-005-1-002 3
3 1/4" Plug . . . . . . . . . . . . . 2 CH
4 2" Angle Valve . . . . . . . . . 1 46-048-1-009
5 1/4" x 2" Nipple . . . . . . . . 1 CH
6 1/4" x 5" Nipple . . . . . . . . 1 CH
7 2" x 3" Nipple. . . . . . . . . . 1 CH

FIGURE 5
MODEL CV-1FR RISER CHECK VALVES
TRIM PARTS LIST

COVER

OUTLET
INLET OUTLET
FLOW

COVER
FLOW

INLET

VERTICAL ORIENTATION HORIZONTAL ORIENTATION


FIGURE 6
MODEL CV-1FR RISER CHECK VALVES
INSTALLATION
TFP950 TFP950
Page 6 of 6 Page 6 of 6

Care and Limited


Maintenance Warranty
Before closing a fire protection system For warranty terms and conditions, visit
main control valve for maintenance www.tyco-fire.com.
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
Ordering
system from the proper authorities
and notify all personnel who may be Procedure
affected by this decision. Contact your local distributor for avail-
After placing a fire protection system ability. When placing an order, indicate
in service, notify the proper authorities the full product name and Part Number
and advise those responsible for moni- (P/N).
toring proprietary and/or central station Model CV-1FR Check Valves
alarms. Specify: Size and P/N (below):
The owner is responsible for the 2 in. (DN50). . . . . . . . . . . . . . P/N 59-590-1-020
inspection, testing, and maintenance of 2-1/2 in. (DN65). . . . . . . . . . . P/N 59-590-1-025
their fire protection system and devices 76,1 mm (DN65) . . . . . . . . . . P/N 59-590-1-076
in compliance with this document, as 3 in. (DN80). . . . . . . . . . . . . . P/N 59-590-1-030
well as with the applicable standards 4 in. (DN100). . . . . . . . . . . . . P/N 59-590-1-040
of the NATIONAL FIRE PROTECTION 139,7 mm (DN125) . . . . . . . . P/N 59-590-1-139
ASSOCIATION (e.g., NFPA 25), in addi- 5 in. (DN125). . . . . . . . . . . . . P/N 59-590-1-050
tion to the standards of any authority 165,1 mm (DN150) . . . . . . . . P/N 59-590-1-165
having jurisdiction. Contact the install- 6 in. (DN150). . . . . . . . . . . . . P/N 59-590-1-060
ing contractor or product manufacturer 8 in. (DN200). . . . . . . . . . . . . P/N 59-590-1-080
with any questions. Any impairments 10 in. (DN250). . . . . . . . . . . . P/N 59-590-1-100
must be immediately corrected. 12 in. (DN300). . . . . . . . . . . . P/N 59-590-1-120

Automatic sprinkler systems are rec- Model CV-1FR


ommended to be inspected, tested, Riser Check Valve Trim Assembly
and maintained by a qualified Inspec- Specify: Size and P/N (below).
tion Service in accordance with local 2 in. (DN50). . . . . . . . . . . . . . P/N 59-591-1-020
requirements and/or national codes. 2-1/2 in. (DN65). . . . . . . . . . . P/N 59-591-1-030
76,1 mm (DN65) . . . . . . . . . . P/N 59-591-1-030
3 in. (DN80). . . . . . . . . . . . . . P/N 59-591-1-030
4 in. (DN100). . . . . . . . . . . . . P/N 59-591-1-080
139,7 mm (DN125) . . . . . . . . P/N 59-591-1-080
5 in. (DN125). . . . . . . . . . . . . P/N 59-591-1-080
165,1 mm (DN150) . . . . . . . . P/N 59-591-1-080
6 in. (DN150). . . . . . . . . . . . . P/N 59-591-1-080
8 in. (DN200). . . . . . . . . . . . . P/N 59-591-1-080
10 in. (DN250). . . . . . . . . . . . P/N 59-591-1-080
12 in. (DN300). . . . . . . . . . . . P/N 59-591-1-080

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;