You are on page 1of 4

Worldwide

www.tyco-fire.com
Contacts

Model WMA-1 Water Motor Alarm


Hydraulically-Operated Mechanical Sprinkler Alarm
European Conformity, 16 bar
General Technical
Description Data
The TYCO Model WMA-1 Water Motor Approvals
Alarm is a hydraulically-operated FM and VdS Approved
outdoor alarm designed for use with CE Certified
fire protection system waterflow detec- Gong Finish
tion valves. It is lightweight yet rugged, Red or Aluminum
and can be used in conjunction with
alarm check, dry pipe, deluge, and pre- Working Water Pressure Range
action valves to sound a local alarm. 0,5 to 16,0 bar
The Water Motor Alarm is suitable Nozzle K-factor
for mounting to any type of rigid wall 10,1 Lpm/bar½
and can accommodate a wall thick- Y-Strainer
ness range of 50 mm to 450 mm. It is DN20, bronze, 0,65 mm mesh screen
provided with a Listed and Approved
Model 74A Y-Strainer (P/N 305004) for Trim Components
use in the alarm line. DN20 galvanized steel nipples and cast
iron fittings
The WMA-1 utilizes a lightweight,
impeller design that can produce a very
high sound pressure level. The Gong, Design
Gong Mount, and Water Motor Housing
are fabricated from corrosion-resistant Criteria
aluminum alloys with a brass nozzle
The TYCO Model WMA-1 Water Motor Item 6. The Clean-out Sump Plug is to
insert. The polymer drive bearings do
Alarm must be used in accordance with be located vertically below the Inlet to
not require lubrication, and the Gong
the following design criteria: the Water Motor.
is closely fitted to the Gong Mount to
eliminate the need for a separate cover. Item 1. The Y-strainer is to be located Item 7. Piping from the Water Motor
at the inlet to the Water Motor Alarm Drain must be a minimum DN25 in.
NOTICE (Ref. Figure 2). in size throughout and directed to an
The Model WMA-1 Water Motor Alarm Item 2. The Water Motor Alarm open drain in order to ensure proper
described herein must be installed and must only be mounted to a rigid wall drainage for obtaining the maximum
maintained in compliance with this surface which will not permit the sound pressure level.
document, as well as with the applica- Striker / Gong Mount to loosen and fall Note: The Water Motor Alarm Drain
ble standards of the NATIONAL FIRE out of alignment. may be connected to the main drain
PROTECTION ASSOCIATION (NFPA), Item 3. In order to obtain the highest of a waterflow detection valve if a non-
in addition to the standards of any other possible sound level, the Water Motor spring loaded swing-type check valve
authorities having jurisdiction. Failure Alarm should be located as close as is installed in a horizontal portion of the
to do so may impair the performance possible to the waterflow detecting water motor alarm drain piping (before
of these devices. valve. its connection to the main drain).
The owner is responsible for main- Item 4. The alarm line piping from the Item 8. In order to minimize any wall
taining their fire protection system alarm outlet of the waterflow detection staining that can be created by drain
and devices in proper operating con- valve trim to the Water Motor Alarm water, it is recommended that the drain
dition. Contact the installing contrac- must be DN20 in. in size throughout piping from the Water Motor be galva-
tor or product manufacturer with any and it must be galvanized steel, brass, nized steel, brass, or other suitable cor-
questions. or other suitable corrosion-resistant rosion-resistant material.
material. Item 9. Drain water must be directed to
Item 5. The alarm line piping must be prevent accidental damage to property
positioned such that it can be drained or danger to persons when the alarm is
back to the waterflow detection valve operating or thereafter.
IMPORTANT trim.
Refer to Technical Data Sheet Item 10. The alarm line drain at the
TFP2300 for warnings pertaining to waterflow detection valve must be
regulatory and health information. maintained at a minimum temperature
of 4°C.
Page 1 of 4 AUGUST 2018 TFP922
TFP922
Page 2 of 4

NO. DESCRIPTION QTY. REF. STRIKER ARM


1 Water Motor . . . . . . 1 92-630-1-021
COUPLING
2 Support Washer . . . 1 NR
SPACER
3 Drive Shaft Sleeve . 1 NR
4 Drive Shaft . . . . . . . 1 NR COUPLING
5 Gong Mount . . . . . . 1 NR 3/4" NPS
6 Striker . . . . . . . . . . . 1 See (a)
7 Gong . . . . . . . . . . . . 1 See (a) STRIKER
8 Cap Nut . . . . . . . . . 1 See (a) SHAFT
(a) Red Gong Repair STRIKER BEARING
Kit includes items: RING 2
6, 7 (red), and 8 . . . 1 92-630-1-025
CROSS-SECTION VIEW
(a) Aluminum Gong Repair OF STRIKER (ITEM 6)
Kit includes items:
6, 7 (alum.), and 8 . . 1 92-630-2-025

NR: Not Replaceable

3
6

7
4
IMPELLER

NOZZLE

INLET
DRAIN
5

INTERNAL VIEW OF
WATER MOTOR (ITEM 1)
8

FIGURE 1
MODEL WMA-1 WATER ALARM
ASSEMBLY

Operation The alarm will sound as long as water


is flowing into the system and flowing Installation
Upon operation of the alarm check, to the Water Motor Alarm. Water in the The TYCO Model WMA-1 Water Motor
dry pipe, deluge, or preaction valve to alarm line will automatically drain back Alarm must be installed in accordance
which the Model WMA-1 Water Motor through the orifice which is also pro- with this section:
Alarm is connected, water will flow vided in the trim of the waterflow detec-
tion valve. Step 1. Mark the through-wall loca-
to the Water Motor and through the tions for the centerlines of the Sleeve
Inlet Nozzle. As water flows through The Water Motor Alarm does not have and Drain Outlet. The Drain Outlet must
the Inlet Nozzle, a high velocity jet is to be reset after an operation. However, be located at least 250 mm below the
formed which impinges on the Impel- if the alarm was silenced during oper- Sleeve per Figure 2.
ler, causing the Impeller and the Striker ation by closing an alarm control
to rotate. With each rotation, the free valve, the alarm control valve must Step 2. Make 38 mm diameter holes
swinging Striker Ring hits the Gong and be reopened after the fire protection straight through the wall at both
sounds the alarm. The spent water is system is restored to service. locations.
then drained through the 1 inch outlet.
TFP922
Page 3 of 4

50,8 mm

22,2 mm 3/4" NPS


69,9 mm (61,9 mm)
34,2 mm
WATER
MOTOR 215,9 mm
SLEEVE END
DIA.
65,0 mm 63,5 mm ISO 7-R 3/4
T/O T/O THREADED
BY INSTALLER

46,0 mm
254,0 mm
DRAIN CL
MINIMUM
ISO 7-R 3/4 ISO 7-R 1
DN20 INLET DRAIN
Y-STRAINER A
1
2 DN25
GALVANIZED B
3
STEEL OR
1 BRASS PIPE C
4 STRAINER
RIGID WALL D
CLEAN-OUT
CAP STRUCTURE

LOCATION FOR
OPTIONAL ELECTRICALLY 457,2 mm
SUPERVISED N.O. MAXIMUM
ALARM CONTROL VALVE 50,8 mm
(SEE NOTE 5) MINIMUM
NOTES:
1. All installation dimensions are shown at nominal value. STANDARD INLET TRIM OPTIONAL DRAIN TRIM
2. All included trim components are galvanized. NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.
3. With the exception of the DN20 Strainer, all included trim 1 3/4" x 3" Nipple . . . . . 2 A 1" 90° Elbow . . . . . . . 1
components are common hardware. 2 3/4" 90° Elbow . . . . . . 1 B 1" 45° Elbow . . . . . . . 1
4. Material shown in dotted lines is not included with Model WMA-1. 3 3/4" x 1/4" x 3/4" Tee C Wall Plate . . . . . . . . . 1
5. Consult local Authority Having Jurisdiction for mechanical with 1/4" Plug. . . . . . . 1 D 1" x 1'-6" Pipe,
alarm isolating control valve requirements. 4 3/4" Union . . . . . . . . . 1 T.O.E. . . . . . . . . . . . . 1
FIGURE 2
MODEL WMA-1 WATER MOTOR ALARM
TYPICAL INSTALLATION

Step 3. Cut the non-threaded end of Step 7. Slip the Support Washer over Mark the Drive Shaft at a point of
the Sleeve to a length equal to that the Sleeve and place the assembly in approximately 3 to 6 mm inside the
of the wall thickness plus 0 to 3 mm. position against the wall. face of the wall. Remove the Shaft and
Thread the cut end to ISO 7-R 3/4 per cut it where previously marked. File off
Step 8. Tighten the DN20 in. Union.
ISO 7-1. the burrs from the cut end of the Drive
Install the Wall Plate and tighten the
Shaft. Re-insert the Drive Shaft through
Step 4. Install the alarm line piping up 45° Elbow.
the Sleeve and fully insert it into the
to and including the union half per Item Note: Apply pressure against the Impeller.
4, Figure 2. outside edge of the Water Motor body
Step 10. Hold the Gong Mount in
Note: Use thread sealant sparingly and and verify that the body and Support
position against the wall, engage the
on male threads only. Washer sit square against the wall. If
Coupling with the Drive Shaft and
not, adjust the alarm line and/or drain
Step 5. Prior to initiating installation then carefully thread the Striker Shaft
piping to suit.
of the Water Motor Alarm, mount the Bearing onto the Sleeve. Securely
Drain Trim (less the Wall Plate and 45° Step 9. From the outside wall, insert tighten the Striker Shaft Bearing using
Elbow), as well as the balance of alarm the Drive Shaft through the Sleeve and a pair of channel locks on the 38 mm
line piping including the other union half fully insert it into the Impeller. hex end.
to the Water Motor. Note: When fully inserted, the Shaft Step 11. Spin the Striker by hand and
Step 6. Tighten the ISO-threaded end should protrude beyond the face of the verify that it spins freely, without any
of the Sleeve into the Body, hand-tight wall by approximately 500 mm minus sign of binding. If it does not, make the
plus 1/8 turn. 50 mm minus wall thickness. necessary adjustments.
TFP922
Page 4 of 4

Step 12. Install the Gong and securely


tighten the Cap Nut. The identifica-
It is recommended that automatic
sprinkler systems be inspected, tested, Limited
tion sign lettering must be orientated
horizontally.
and maintained by a qualified Inspec-
tion Service in accordance with local Warranty
requirements and/or national codes. For warranty terms and conditions, visit
Step 13. Test the Water Motor Alarm
by opening the alarm test valve in the Testing of the Water Motor Alarm may www.tyco-fire.com.
trim of the waterflow detection valve. result in operation of other associated
The alarm must be clear and steady. If
not, make the necessary adjustments.
alarms. Consequently, notification
must be given to the owner and the fire
Ordering
NOTICE
department.
Procedure
If the alarm was silenced during opera-
Testing of the Water Motor Alarm may tion, the alarm control valve must be Contact your local distributor for avail-
result in operation of other associated reopened immediately after the fire pro- ability. When placing an order, indi-
alarms. Consequently, notification tection system is restored to service. cate the full product name, including
must be given to the owner and the fire description and part number (P/N).
The Model WMA-1 Water Motor
department, central control station, or Alarm must be maintained and ser- The complete Model WMA-1 Alarm
other signal station to which the alarms viced in accordance with the following Assembly includes the Model WMA-1
are connected. instructions: Water Motor Alarm, Model 74A Strainer,
and Standard Inlet Trim.
Care and Step 1. The Model WMA-1 Water Motor
Alarm does not require any regularly WMA-1 Water Motor Alarm

Maintenance scheduled maintenance. Rotating parts


do not require lubrication. It is recom-
Assemblies (select one)
Specif y: Model WMA-1 Alarm
mended, however, that fire alarms be Assembly with Red Finish Gong,
The TYCO Model WMA-1 Water Motor P/N 52-630-1-021R
Alarm must be serviced and main- periodically operated, i.e., inspected,
tained in accordance with this section. to verify that they generate a clear and Specify: Model WMA-1 Alarm Assem-
steady sound. Any impairment must be bly with Aluminum Finish Gong,
Before closing a fire protection system immediately corrected. P/N 52-630-2-021
main control valve for maintenance
work on the fire protection system that Step 2. The inspection should be made Optional Drain Trim
it controls, permission to shut down periodically in accordance with the Specify: Optional Drain Trim for
the affected fire protection systems requirements of the authority having Model WMA-1 Water Motor Alarm,
must first be obtained from the proper jurisdiction, or more frequently as may P/N 52-630-2-002E
authorities and all personnel who may be necessary in the case of locations
subject to vandalism. The Y-Strainer Replacement Parts for
be affected by this decision must be
notified. and the Reducing Tee at the WMA-1 WMA-1 Water Motor Alarm
inlet are to be cleaned out after each Specify: (specify product descrip-
The following procedures and inspec- operation of the Water Motor Alarm tion from Figure 1) for use with
tions should be performed as indicated, and after the alarm line piping has been Model WMA-1 Water Motor Alarm,
in addition to any specific requirements drained. P/N (specify from Figure 1)
of the authority having jurisdiction, and
any impairment must be immediately Replacement Trim Parts for
NOTICE WMA-1 Water Motor Alarm
corrected.
With reference to Figure 2, in the event Specify: Model 74A Y-Strainer,
The owner is responsible for the inspec- of a WMA-1 malfunction, inspect and P/N 305004
tion, testing, and maintenance of their clean the Y-strainer of obstruction prior
fire protection system and de-vices in to removing the Water Motor.
compliance with this document, as well
as in addition to the standards of any Make no attempt to disassemble,
authority having jurisdiction. Contact repair, or internally clean the Water
the installing contractor or product Motor. The Water Motor is not a field
manufacturer with any questions. serviceable part and must be replaced
if malfunction is determined.

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;

You might also like