Model K17-231 — 16.8 K-factor


Upright and Pendent Sprinklers
Standard Response, Standard Coverage
right and Pendent Sprinklers de-
General scribed herein must be installed and
maintained in compliance with this
Description document, as well as with the applica-
ble standards of the National Fire Pro-
The 16.8 K-factor, Model K17-231, tection Association, in addition to the
Standard Response, Standard Cover- standards of any other authorities hav-
age, Upright and Pendent Sprinklers ing jurisdiction. Failure to do so may
(Ref. Figure 1) are automatic sprin- impair the performance of these de-
klers of the frangible bulb type. They vices.
are “standard response - spray sprin-
klers” which produce a hemispherical The owner is responsible for maintain-
water distribution pattern below the de- ing their fire protection system and de-
flector. vices in proper operating condition.
The installing contractor or manufac-
The 16.8 K-factor, K17-231 Sprinklers turer should be contacted with any
were subjected to full scale, high-piled questions.
storage, fire tests to qualify their use in
lieu of 8.0 or 11.2 K-Factor standard
spray sprinklers for the protection of Sprinkler
high-piled storage.
Higher flow rates can be achieved at Identification
much lower pressures with the 16.8
K-factor, K17-231 Sprinklers — mak- Number
ing their use highly advantageous in TY7151 - Upright, 16.8K
high density applications, such as the TY7251 - Pendent, 16.8K
protection of high-piled storage.
TY7151 is a redesignation for C7151,
Applications for the 16.8 K-factor, G1888, and S8040.
Model K17-231 Pendent and Upright
Sprinklers are expanding beyond the TY7251 is a redesignation for C7251,
current listings/approvals. For informa- G1889, and S8041.
tion regarding research fire tests which
may be acceptable to an Authority
Having Jurisdiction, please contact the Technical Temperature Ratings
Technical Services Department.
Data Refer to Table A
WARNING Finish
The 16.8 K-factor, Model K17-231 Up- Approvals
UL and C-UL Listed. FM and NYC Ap- Natural Brass
proved. (Specific details for laboratory
listings and approvals given in Table A. Physical Characteristics
IMPORTANT The approvals apply to the service Frame . . . . . . . . . . . . Bronze
Always refer to Technical Data conditions indicated in the Design Cri- Button . . . . . . . . . . . . Bronze
Sheet TFP700 for the “INSTALLER teria section.) Sealing Assembly . . . . . . . . . .
WARNING” that provides cautions . . . . . . Beryllium Nickel w/Teflon†
with respect to handling and instal- Maximum Working Pressure Bulb . . . . . . . Glass (5 mm dia.)
lation of sprinkler systems and com- 175 psi (12,1 bar) Compression Screw . . . . . . . . .
ponents. Improper handling and in- Pipe Thread Connection . . . . . . . . . . . . . . . . . Brass
stallation can permanently damage 3/4 inch NPT or ISO 7-R3/4 Deflector . . . . . . . . . . . . Brass
a sprinkler system or its compo-
nents and cause the sprinkler to fail Discharge Coefficients †Registered trademark of DuPont.
to operate in a fire situation or cause K = 16.8 GPM/psi1/2
it to operate prematurely. (241,9 LPM/bar1/2)

Page 1 of 4 JANUARY, 2005 TFP332


Page 2 of 4 TFP332

SPRINKLER FINISH
TYPE TEMP. BULB NATURAL
LIQUID BRASS

155°F/68°C Red
UPRIGHT 1, 2, 3, 4
200°F/93°C Green
K=16.8 (TY7151)
286°F/141°C Blue
155°F/68°C Red
PENDENT 1, 2, 4
200°F/93°C Green
K=16.8 (TY7251)
286°F/141°C Blue
NOTES:

1. Listed by Underwriters Laboratories, Inc. (UL Listed).


2. Listed by by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM Approved).
4. Approved by the City of New York under MEA 177-03-E.
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)

toned expanded Group A or B plastics, • a minimum design area” of 2000 ft2


Design Criteria with: (186 m2) for wet systems or 4500 ft 2
(418 m2) for dry pipe systems
UL and C-UL Listing • a storage height of up to 20 feet (6,1
Requirements m); FM Approval
The 16.8 K-factor, Model K17-231 • a maximum ceiling height of 27 feet Requirements
(TY7151 & TY7251) Sprinklers may be (8,2 m); The 16.8 K-factor, Model K17-231
installed in accordance with NFPA 13 • a minimum deflector to top of stor- (TY7151) Upright Sprinklers may be
standard sprinkler position and age clearance of 18 inches (457 installed in accordance with the appli-
area/density flow calculation require- mm); cable “control mode density/area”
ments for light, ordinary, or extra haz- guidelines provided by Factory Mutual.
ard occupancies with a minimum re- • a minimum design density of 0.60 (FM guidelines may differ from UL and
sidual (flowing) pressure of 7 psi (0,5 gpm/ft2 (24,4 mm/min); C-UL Listing criteria.)
bar) in wet or dry pipe sprinkler sys- • a minimum residual (flowing) pres-
tems, or they may be installed in ac- sure of 7 psi (0,5 bar);
cordance with NFPA 13 standard
• a minimum design area of 2000 ft2
Operation
sprinkler position and area/density
flow calculation requirements for high (186 m2) for wet systems or 2600 ft 2 The glass bulb contains a fluid that
piled storage occupancies (solid piled, (242 m2) for dry pipe systems expands when exposed to heat. When
palletized, rack storage, bin box, and Example 2: NFPA 13 provides ceiling the rated temperature is reached, the
shelf storage including but not limited only protection (i.e., no in-rack sprin- fluid expands sufficiently to shatter the
to Class I-IV and Group A plastics) with klers) criteria using open frame (i.e. no glass bulb, allowing the sprinkler to
a minimum residual (flowing) pressure solid shelves) single, double, multiple- activate and flow water.
of 7 psi (0,5 bar) for wet or dry pipe row, or portable rack storage (without
systems. the need for in-rack sprinkler protec-
The following two examples are typical tion) of cartoned or uncartoned unex-
of the types of arrangements permitted panded Group A or B plastics, or, car-
by NFPA 13. For all combinations of toned expanded Group A or B plastics,
lesser and greater building heights, with:
lesser and greater storage heights, • a storage height of up to 25 feet (7,6
storage arrangements, commodity m);
classifications, and lesser or greater
required design densities, refer to • a maximum ceiling height of 30 feet
NFPA 13 for specifics. (9,1 m);
Example 1: NFPA 13 provides ceiling • a minimum deflector to top of stor-
only protection (i.e., no in-rack sprin- age clearance of 18 inches (457
klers) criteria using open frame (i.e. no mm);
solid shelves) single, double, multiple- • a minimum design density of 0.80
row, or portable rack storage (without gpm/ft2 (32,6 mm/min);
the need for in-rack sprinkler protec-
tion) of cartoned or uncartoned unex- • a minimum residual (flowing) pres-
panded Group A or B plastics, or, car- sure of 7 psi (0,5 bar);
TFP332 Page 3 of 4

1 - Frame 4 - Bulb * Temperature rating is ** Pipe thread


2 - Button 5 - Compression Screw indicated on deflector. connections per ISO
3 - Sealing Assembly 6 - Deflector* 7/1 can be provided
on special request.

FIGURE 1
MODEL K17-231 UPRIGHT (TY7151) AND PENDENT (TY7251) SPRINKLERS

Installation Care and


NOTE Maintenance
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of The Model K17-231 Sprinklers must
liquid from the bulb. With the sprinkler be maintained and serviced in accord-
held horizontal, a small air bubble ance with the following instructions:
should be present. The diameter of the
air bubble is approximately 1/16 inch NOTE
(1,6 mm) for the 155°F/68°C to 3/32 Before closing a fire protection system
inch (2,4 mm) for the 286°F/141°C rat- main control valve for maintenance
ing. work on the fire protection system that
it controls, permission to shut down the
The Model K17-231 Sprinklers must affected fire protection systems must
be installed in accordance with the fol- be obtained from the proper authori-
lowing instructions. ties and all personnel who may be FIGURE 2
affected by this action must be notified. W-TYPE 8 SPRINKLER
1. With pipe thread sealant applied to
the pipe threads, hand tighten the Sprinklers that are found to be leaking WRENCH
Model K17-231 Sprinkler into the or exhibiting visible signs of corrosion
sprinkler fitting. must be replaced.
The owner is responsible for the in-
Automatic sprinklers must never be spection, testing, and maintenance of
2. Using the W-Type 8 Sprinkler painted, plated, coated, or otherwise their fire protection system and de-
Wrench (Ref. Fig. 2) applied to the altered after leaving the factory. Modi- vices in compliance with this docu-
sprinkler Wrench Flats (Ref. Fig. 1), fied sprinklers must be replaced. ment, as well as with the applicable
tighten the Model K17-231 Sprinkler Sprinklers that have been exposed to standards of the National Fire Protec-
into the sprinkler fitting. corrosive products of combustion, but tion Association (e.g., NFPA 25), in
have not operated, should be replaced addition to the standards of any other
NOTE if they cannot be completely cleaned authorities having jurisdiction. The in-
A leak tight 3/4 inch NPT sprinkler joint by wiping the sprinkler with a cloth or stalling contractor or sprinkler manu-
should be obtained with a torque of 10 by brushing it with a soft bristle brush. facturer should be contacted relative to
to 20 ft.lbs. (13,4 to 26,8 Nm). Higher
Care must be exercised to avoid dam- any questions.
levels of torque may distort the sprin-
kler inlet with consequent leakage or age to the sprinklers - before, during, It is recommended that automatic
impairment of the sprinkler. and after installation. Sprinklers dam- sprinkler systems be inspected,
aged by dropping, striking, wrench tested, and maintained by a qualified
twist/slippage, or the like, must be re- Inspection Service in accordance with
placed. Also, replace any sprinkler that local requirements and/or national
has a cracked bulb or that has lost codes.
liquid from its bulb. (Ref. Installation
Section).
Page 4 of 4 TFP332

Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire When placing an order, indicate the full
Products are warranted solely to the product name. Please specify the
original Buyer for ten (10) years Sprinkler Identification Number (SIN),
against defects in material and work- quantity, and temperature rating. Refer
manship when paid for and properly to the Price List for complete listing of
installed and maintained under normal Part Numbers.
use and service. This warranty will ex-
Contact your local distributor for avail-
pire ten (10) years from date of ship-
ability.
ment by Tyco Fire Products. No war-
ranty is given for products or
Sprinkler Assemblies with NPT
components manufactured by compa-
Thread Connections:
nies not affiliated by ownership with
Specify: (specify SIN), 16.8 K-factor,
Tyco Fire Products or for products and
Model K17-231,(specify temperature
components which have been subject
rating), (specify Pendent or Upright)
to misuse, improper installation, corro-
Sprinkler, P/N (specify).
sion, or which have not been installed,
maintained, modified or repaired in ac- Upright (SIN TY7151)
cordance with applicable Standards of 155°F/68°C . . . . . . . . . . . . . . PSN 51-888-1-155
the National Fire Protection Associa- 200°F/93°C . . . . . . . . . . . . . . PSN 51-888-1-200
tion, and/or the standards of any other 286°F/141°C . . . . . . . . . . . . . PSN 51-888-1-286
Authorities Having Jurisdiction. Mate-
Pendent (SIN TY7251)
rials found by Tyco Fire Products to be 155°F/68°C . . . . . . . . . . . . . . PSN 51-889-1-155
defective shall be either repaired or 200°F/93°C . . . . . . . . . . . . . . PSN 51-889-1-200
replaced, at Tyco Fire Products’ sole 286°F/141°C . . . . . . . . . . . . . PSN 51-889-1-286
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to Sprinkler Wrench:
assume for it, any other obligation in Specify: W-Type 8 Sprinkler Wrench,
connection with the sale of products or P/N 56-892-1-001.
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.